technical data

air conditioning systems


FTKS/FTXS-C FTKS/FTXS-B Wall Mounted, Inverter Controlled Unit

Split Sky Air

Split - Sky Air

ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment

Daikin units comply with the European regulations that guarantee the safety of the product.

Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.

Daikin Europe N.V. is participating in the EUROVENT Certification Programme. Products are as listed in the EUROVENT Directory of Certified Products.

Specifications are subject to change without prior notice.

Zandvoordestraat 300 B - 8400 Ostend Belgium www.daikineurope.com

EEDE04-1/3 10/2004 Prepared in Belgium by Goekint Graphics

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

TABLE OF CONTENTS FTKS/FTXS-C/B


1 2 Features 2 3

.................................................................................

Specifications

.......................................................................

Nominal capacity, capacity steps and nominal input

Technical specifications

3 4 5 6

Dimensional drawings Piping diagrams Wiring diagrams Sound level

.....................................................

13 15 17 19

..................................................................

.................................................................

..........................................................................

Sound level data Sound pressure spectrum

Accessories

..........................................................................

24

Standard accessories Optional accessories

8 9 10

Control systems Center of gravity Installation

..................................................................

25 27 28

................................................................

............................................................................

For capacity tables, please refer to part II: outdoor units

Split - Sky Air Indoor units

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

Features
+ Up to 4 indoor units can be connected to 1 Multi outdoor unit. All indoor units are individually controllable with remote control and do not need to be installed in the same room. They operate simultaneously within the same cooling or heating mode. + The outdoor unit can easily be mounted on a roof, a terrace or placed against an outside wall. + Outdoor units are fitted with a swing compressor, renowned for its low noise and energy efficiency. + The remote control has a 24 hour timer + The indoor model also has a start/stop button mounted on the front panel + Up to 5 indoor units can be operated from a single centralised control + Purpose designed holder provided for your remote control

1
1

+ Flat front panel: its stylish appearance fits easily within any interior dcor and is more easy to clean. + Lightweight and compact + The movement sensor saves power consumption in unoccupied rooms. + The home leave operation saves energy during absence. + Automatic horizontal and vertical auto-swing ensures uniform air flow and temperature distribution. + 3D-air flow (50,60,71 class only) + Powerful mode can be selected for rapid cooling or heating. + Air purification filter with photocatalytic deodorising function - deodorises the air - powerful decomposes cigarette and pet odours - removes house dust and pollen - deactivates bacteria and viruses + Indoor / outdoor unit silent operation Silent buttons on the remote control lower the operating sound of the indoor and/or outdoor unit by 3dB(A) each. + Night quiet mode automatically reduces the operating sound of the outdoor unit by 3dB(A) at night. multi outdoors in cooling mode only

2 3 r 0
Standard Optional 5 steps

q 7 x 8 6 0 6 4
MKS/MXS (cooling appl. only)

FTXS

FTKS

z !
Split - Sky Air Indoor units

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

Specifications

1
NOMINAL CAPACITY and NOMINAL INPUT
For indoor units only: INDOOR UNITS NOMINAL INPUT Cooling nominal kW FTKS20CVMB 0.04 FTKS25CVMB 0.04 FTKS35CVMB 0.04

For combination indoor + outdoor units (air cooled): INDOOR UNITS OUTDOOR UNITS - PAIR APPLICATION NOMINAL CAPACITY (2-3) Cooling (1) min.nom.max. NOMINAL INPUT Cooling min.nom.max. EER ENERGY LABEL Cooling ANNUAL ENERGY Cooling CONSUMPTION OUTDOOR UNITS - PAIR APPLICATION NOMINAL CAPACITY (2-3) Cooling (1) min.nom.max. NOMINAL INPUT Cooling min.nom.max. EER ENERGY LABEL Cooling ANNUAL ENERGY Cooling CONSUMPTION OUTDOOR UNITS - MULTI APPLICATION

kW kW

kWh kW kW

FTKS20CVMB RKS20CVMB 1.32.03.0 0.300.500.98 4.00 A 250 RKH20CVMB 1.32.02.6 0.430.620.945 3.23 A 310

FTKS25CVMB RKS25CVMB 1.32.53.0 0.300.6950.98 3.60 A 347.5 RKH25CVMB 1.32.253.0 0.430.701.20 3.21 A 350

FTKS35CVMB RKS35CVMB 1.43.43.8 0.301.061.30 3.21 A 530 RKH35CVMB 1.43.153.8 0.461.0451.425 3.01 B 522.5 4MKS58,75,90B

kWh

2MKS40/3MKS50/4MKS58,75,90B For more information, see chapter MKS-B

TECHNICAL SPECIFICATIONS
For indoor units only: INDOOR UNITS DIMENSIONS Unit H W D mm mm mm kg dB(A) dB(A) dB(A) dB(A) m3/min m3/min m3/min rpm rpm rpm W mm FTKS20CVMB FTKS25CVMB 273 784 195 7.5 White 38 25 22 56 7.7 4.2 3.6 5 steps, silent and auto 1,340 1,090 840 Cross flow fan 18 ML fin - J7Hi - XA tube 2 x 12 x 1.4 Removable/washable/mildew proof Microcomputer control J 6.4 J 9.5 J 18.0 Both liquid and gas pipes See chapter RKS-C/RKH-C See chapter MKS-B
3D044242B 3D044243B 3D044244B

FTKS35CVMB

WEIGHT COLOUR SOUND LEVEL

Unit Unit Sound pressure (cooling) (4)

FAN

Sound power (cooling) (5) Air flow rate (cooling)

high low super low high low super low steps high medium low

Speed

38 25 22 56 7.7 4.2 3.6 1,340 1,090 840 18 2 x 12 x 1.4

39 26 23 57 7.7 4.4 3.8 1,340 1,100 870 18 2 x 12 x 1.4

HEAT EXCHANGER AIR FILTER TEMPERATURE CONTROL PIPING CONNECTIONS

Type Motor output Type Rows x stages x fin pitch

INSULATION MATERIAL For outdoor units

Heat insulation tape Pair application Multi application

liquid gas drain

mm mm mm

Split - Sky Air Indoor units

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

Specifications

1
2
NOMINAL CAPACITY and NOMINAL INPUT
For indoor units only: INDOOR UNITS NOMINAL INPUT Cooling nominal kW FTKS50BVMB 0.04 FTKS60BVMB 0.04 FTKS71BVMB 0.045

For combination indoor + outdoor units (air cooled): INDOOR UNITS OUTDOOR UNITS - PAIR APPLICATION NOMINAL CAPACITY (2-3) Cooling (1) min.nom.max. NOMINAL INPUT Cooling min.nom.max. EER ENERGY LABEL Cooling ANNUAL ENERGY Cooling CONSUMPTION OUTDOOR UNITS - MULTI APPLICATION

kW kW

kWh

FTKS50BVMB RKS50BVMB9 0.905.005.80 0.451.662.30 3.01 B 830 4MKS58,75,90B

FTKS60BVMB RKS60BVMB9 0.906.006.70 0.452.122.45 2.83 C 1,060 4MKS75,90B For more information, see chapter MKS-B

FTKS71BVMB RKS71BVMB9 0.907.108.00 0.452.533.07 2.81 C 1,265 4MKS90B

TECHNICAL SPECIFICATIONS
For indoor units only: INDOOR UNITS DIMENSIONS Unit H W D mm mm mm kg dB(A) dB(A) dB(A) dB(A) m3/min m3/min m3/min rpm rpm rpm W mm FTKS50BVMB 290 795 238 9 44 35 32 63 11.4 8.0 7.1 1,340 1,180 1,010 40 2 x 16 x 1.4 FTKS60BVMB 290 1,050 238 12 FTKS71BVMB

WEIGHT COLOUR SOUND LEVEL

Unit Unit Sound pressure (cooling) (4)

FAN

Sound power (cooling) (5) Air flow rate (cooling)

high low super low high low super low steps high medium low

Speed

HEAT EXCHANGER AIR FILTER TEMPERATURE CONTROL PIPING CONNECTIONS

Type Motor output Type Rows x stages x fin pitch

White 45 36 33 63 16.2 11.4 10.2 5 steps, silent and auto 1,330 1,170 1,010 Cross flow fan ML fin - J8Hi - XA tube 2 x 16 x 1.4 Removable/washable/mildew proof Microcomputer control J 6.4 J 18.0 Both liquid and gas pipes See chapter RKS-B See chapter MKS-B

46 37 34 63 16.7 11.6 10.6 1,370 1,210 1,040 43 2 x 16 x 1.4

INSULATION MATERIAL For outdoor units

Heat insulation tape Pair application Multi application

liquid gas drain

mm mm mm

J 12.7

J 15.9

3D040781A 3D040782A 3D040783A

Split - Sky Air Indoor units

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

Specifications

1
ELECTRICAL SPECIFICATIONS

For indoor units only: CURRENT Nominal running current Maximum running current For combination indoor units + outdoor units:

cooling cooling

A A

FTKS20CVMB 0.18

FTKS25CVMB 0.18 See chapter RKS-C: electrical data FTKS25CVMB RKS25CVMB 3.9 See chapter RKS-C: electrical data

FTKS35CVMB 0.18

Nominal running current cooling cooling Maximum running current Starting current cooling For combination indoor units + outdoor units: CURRENT Nominal running current Maximum running current Starting current cooling cooling cooling

CURRENT

A A A

FTKS20CVMB RKS20CVMB 2.8

FTKS35CVMB RKS35CVMB 4.9

A A A

FTKS20CVMB RKH20CVMB 3.3

FTKS25CVMB RKH25CVMB 3.7 See chapter RKH-C: electrical data

FTKS35CVMB RKH35CVMB 4.9

For combination indoor units + outdoor units: CURRENT Nominal running current Maximum running current Starting current cooling cooling cooling A A A

FTKS20CVMB

FTKS25CVMB 2MKS40/3MKS50/4MKS58,75,90B See chapter MKS-B: electrical data

FTKS35CVMB

For indoor units only: POWER SUPPLY NOMINAL DISTRIBUTION SYSTEM Phase VOLTAGE Frequency Voltage

Hz V

FTKS20CVMB VM 1 50 230

FTKS25CVMB VM 1 50 230

FTKS35CVMB VM 1 50 230
3D044242B 3D044243B 3D044244B

NOTES
1 2 3 4 5 6 7 8 Nominal cooling capacities are based on: indoor temperature 27CDB/19CWB * outdoor temperature 35CDB * refrigerant piping length: 7.5m * level difference: 0m. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Units should be selected on nominal capacity. Maximum capacity is limited to peak periods. The sound pressure level is measured via a microphone at a certain distance from the unit. For measuring conditions: please refer to item 6 of this chapter. The sound power level is an absolute value indicating the power which a sound source generates. Energy label: scale from A (most efficient) to G (less efficient). The Energy Label Directive 2002/31/EC will enter into force once the relevant measurement standard will be published in the European Official Standard. Annual energy consumption: based on average use of 500 running hours per year at full load (= nominal conditions)

Split - Sky Air Indoor units

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

Specifications

1
2
ELECTRICAL SPECIFICATIONS
For indoor units only: CURRENT Nominal running current Maximum running current For combination indoor units + outdoor units: CURRENT Nominal running current Maximum running current Starting current cooling cooling cooling A A A cooling cooling A A FTKS50BVMB 0.18 FTKS60BVMB 0.18 See chapter RKS-B: electrical data FTKS60BVMB RKS60BVMB9 9.3 See chapter RKS-B: electrical data FTKS50BVMB 4MKS58,75,90B FTKS60BVMB 4MKS75,90B See chapter MKS-B: electrical data FTKS71BVMB 4MKS90B FTKS71BVMB 0.20

FTKS50BVMB RKS50BVMB9 7.3

FTKS71BVMB RKS71BVMB9 11.1

For combination indoor units + outdoor units: CURRENT Nominal running current Maximum running current Starting current cooling cooling cooling A A A

For indoor units only: POWER SUPPLY NOMINAL DISTRIBUTION SYSTEM Phase VOLTAGE Frequency Voltage

Hz V

FTKS50BVMB VM 1 50 230

FTKS60BVMB VM 1 50 230

FTKS71BVMB VM 1 50 230
3D040781A 3D040782A 3D040783A

NOTES
1 2 3 4 5 6 7 8 Nominal cooling capacities are based on: indoor temperature 27CDB/19CWB * outdoor temperature 35CDB * refrigerant piping length: 7.5m * level difference: 0m. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Units should be selected on nominal capacity. Maximum capacity is limited to peak periods. The sound pressure level is measured via a microphone at a certain distance from the unit. For measuring conditions: please refer to item 6 of this chapter. The sound power level is an absolute value indicating the power which a sound source generates. Energy label: scale from A (most efficient) to G (less efficient). The Energy Label Directive 2002/31/EC will enter into force once the relevant measurement standard will be published in the European Official Standard. Annual energy consumption: based on average use of 500 running hours per year at full load (= nominal conditions)

Split - Sky Air Indoor units

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

Specifications

1
NOMINAL CAPACITY and NOMINAL INPUT
For indoor units only: INDOOR UNITS NOMINAL INPUT Cooling Heating nominal nominal kW kW FTXS20CVMB 0.04 0.04 FTXS25CVMB 0.04 0.04 FTXS35CVMB 0.04 0.04

For combination indoor + outdoor units (air cooled): INDOOR UNITS OUTDOOR UNITS - PAIR APPLICATION NOMINAL CAPACITY (3-4) Cooling (1) min.nom.max. Heating (2) min.nom.max. NOMINAL INPUT Cooling min.nom.max. Heating min.nom.max. EER Cooling COP Heating ENERGY LABEL Cooling Heating ANNUAL ENERGY Cooling CONSUMPTION INDOOR UNITS OUTDOOR UNITS - PAIR APPLICATION NOMINAL CAPACITY (3-4) Cooling (1) min.nom.max. Heating (2) min.nom.max. NOMINAL INPUT Cooling min.nom.max. Heating min.nom.max. EER Cooling COP Heating ENERGY LABEL Cooling Heating ANNUAL ENERGY Cooling CONSUMPTION OUTDOOR UNITS - MULTI APPLICATION

kW kW kW kW

kWh

FTXS20CVMB RXS20CVMB 1.32.02.6 1.32.74.5 0.300.500.98 0.290.6751.46 4.00 4.00 A A 250 FTXS20CVMB RXH20CVMB 1.32.02.6 1.32.64.0 0.430.620.945 0.350.761.31 3.23 3.42 A B 310

FTXS25CVMB RXS25CVMB 1.32.53.0 1.33.44.5 0.300.6950.98 0.290.9351.46 3.60 3.64 A A 347.5 FTXS25CVMB RXH25CVMB 1.32.53.0 1.32.854.5 0.430.701.20 0.350.8351.61 3.21 3.41 A B 350 2MXS40/3MXS52/4MXS68/80B For more information, see chapter MXS-B

FTXS35CVMB RXS35CVMB 1.43.43.8 1.44.05.0 0.301.061.30 0.311.171.59 3.21 3.42 A B 530 FTXS35CVMB RXH35CVMB 1.43.153.8 1.43.65.0 0.461.0451.425 0.4051.0551.90 3.01 3.41 B B 522.5

kW kW kW kW

kWh

3D044245B 3D044246B 3D044247B

Split - Sky Air Indoor units

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

Specifications

1
2
NOMINAL CAPACITY and NOMINAL INPUT
For indoor units only: INDOOR UNITS NOMINAL INPUT Cooling Heating nominal nominal kW kW FTXS50BVMB 0.04 0.045 FTXS60BVMB 0.04 0.045 FTXS71BVMB 0.045 0.050

For combination indoor + outdoor units (air cooled): INDOOR UNITS OUTDOOR UNITS - PAIR APPLICATION NOMINAL CAPACITY (3-4) Cooling (1) min.nom.max. Heating (2) min.nom.max. NOMINAL INPUT Cooling min.nom.max. Heating min.nom.max. EER Cooling COP Heating ENERGY LABEL Cooling Heating ANNUAL ENERGY Cooling CONSUMPTION OUTDOOR UNITS - MULTI APPLICATION

kW kW kW kW

kWh

FTXS50BVMB RXS50BVMB 0.905.005.80 0.905.807.50 0.451.662.30 0.451.702.58 3.01 3.41 B B 830 3MXS52/ 4MXS68,80B

FTXS60BVMB RXS60BVMB 0.906.006.70 0.907.008.00 0.452.122.45 0.452.093.10 2.83 3.35 C C 1,060 4MXS68,80B For more information, see chapter MXS-B

FTXS71BVMB RXS71BVMB 0.907.108.00 0.908.509.50 0.452.533.07 0.452.633.80 2.81 3.23 C C 1,265 4MXS80B

3D040778A 3D040779 3D040780A

Split - Sky Air Indoor units

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

Specifications

1
TECHNICAL SPECIFICATIONS
For indoor units only: INDOOR UNITS DIMENSIONS Unit H W D mm mm mm kg dB(A) dB(A) dB(A) dB(A) m3/min m3/min m3/min rpm rpm rpm W mm FTXS20CVMB FTXS25CVMB 273 784 195 7.5 White 38/38 25/28 22/25 56/56 7.7/7.8 4.2/5.3 3.6/4.6 5 steps, silent and auto 1,340/1,300 1,090/1,130 840/960 Cross flow fan 18 ML fin - J7Hi - XA tube 2 x 12 x 1.4 Removable/washable/mildew proof Microcomputer control 6.4 9.5 18.0 Both liquid and gas pipes See chapter RXS-C/RXH-C See chapter MXS-B
3D044245B 3D044246B 3D044247B

FTXS35CVMB

WEIGHT COLOUR SOUND LEVEL

FAN

HEAT EXCHANGER AIR FILTER TEMPERATURE CONTROL PIPING CONNECTIONS

high low super low Sound power (cooling/heating) high (6) Air flow rate high (cooling/heating) low super low Speed (cooling/heating) steps high medium low Type Motor output Type Rows x stages x fin pitch

Unit Unit Sound pressure (cooling/heating) (5)

38/38 25/28 22/25 56/56 7.7/7.8 4.2/5.3 3.6/4.6 1,340/1,300 1,090/1,130 840/960 18 2 x 12 x 1.4

39/39 26/29 23/26 57/57 7.7/8.1 4.4/5.3 3.8/4.6 1,340/1,340 1,100/1,150 870/960 18 2 x 12 x 1.4

INSULATION MATERIAL For outdoor units

Heat insulation tape Pair application Multi application

liquid gas drain

mm mm mm

Split - Sky Air Indoor units

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

Specifications

1
2
TECHNICAL SPECIFICATIONS
For indoor units only: INDOOR UNITS DIMENSIONS Unit H W D mm mm mm kg dB(A) dB(A) dB(A) dB(A) m3/min m3/min m3/min rpm rpm rpm W mm FTXS50BVMB 290 795 238 9 44/42 35/33 32/30 63/60 11.4/12.6 8.0/8.9 7.1/7.7 1,340/1,370 1,180/1,200 1,010/1,030 40 2 x 16 x 1.4 FTXS60BVMB 290 1,050 238 12 FTXS71BVMB

WEIGHT COLOUR SOUND LEVEL

FAN

HEAT EXCHANGER AIR FILTER TEMPERATURE CONTROL PIPING CONNECTIONS

high low super low Sound power (cooling/heating) high (6) Air flow rate high (cooling/heating) low super low Speed (cooling/heating) steps high medium low Type Motor output Type Rows x stages x fin pitch

Unit Unit Sound pressure (cooling/heating) (5)

White 45/44 36/35 33/32 63/62 16.2/17.4 11.4/12.7 10.2/11.4 5 steps, silent and auto 1,330/1,360 1,170/1,200 1,010/1,040 Cross flow fan ML fin - J8Hi - XA tube 2 x 16 x 1.4 Removable/washable/mildew proof Microcomputer control 6.4 12.7 18.0 Both liquid and gas pipes See chapter RXS-B See chapter MXS-B

46/46 37/37 34/34 63/63 16.7/18.5 11.6/13.5 10.6/12.1 1,370/1,440 1,210/1,270 1,040/1,100 43 2 x 16 x 1.4

INSULATION MATERIAL For outdoor units

Heat insulation tape Pair application Multi application

liquid gas drain

mm mm mm

15.9

3D040778A 3D040779 3D040780A

10

Split - Sky Air Indoor units

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

Specifications

1
ELECTRICAL SPECIFICATIONS

For indoor units only: CURRENT Nominal running current Maximum running current

cooling heating cooling heating

A A A A

FTXS20CVMB 0.18 0.18

FTXS25CVMB 0.18 0.18 See chapter RXS-C: electrical data

FTXS35CVMB 0.18 0.18

For combination indoor units + outdoor units: CURRENT Nominal running current Maximum running current Starting current For combination indoor units + outdoor units: CURRENT Nominal running current Maximum running current Starting current cooling heating cooling heating cooling heating A A A A A A cooling heating cooling heating cooling heating A A A A A A

FTXS20CVMB RXS20CVMB 2.8 3.5

FTXS25CVMB RXS25CVMB 3.9 4.4 See chapter RXS-C: electrical data

FTXS35CVMB RXS35CVMB 4.9 5.4

FTXS20CVMB RXH20CVMB 3.3 4.0

FTXS25CVMB RXH25CVMB 3.7 4.4 See chapter RXH-C: electrical data

FTXS35CVMB RXH35CVMB 4.9 4.9

For combination indoor units + outdoor units: CURRENT Nominal running current Maximum running current Starting current cooling heating cooling heating cooling heating A A A A A A

FTXS20CVMB

FTXS25CVMB 2MXS40/3MXS52/4MXS68,80B

FTXS35CVMB

See chapter MXS-B: electrical data

For indoor units only: POWER SUPPLY NOMINAL DISTRIBUTION SYSTEM Phase VOLTAGE Frequency Voltage

Hz V

FTXS20CVMB VM 1 50 230

FTXS25CVMB VM 1 50 230

FTXS35CVMB VM 1 50 230
3D044245B 3D044246B 3D044247B

NOTES
1 2 3 4 5 6 7 8 9 Nominal cooling capacities are based on: indoor temperature 27CDB/19CWB * outdoor temperature 35CDB * refrigerant piping length: 7.5m * level difference: 0m. Nominal heating capacities are based on: indoor temperature 20CDB * outdoor temperature 7CDB/6CWB * refrigerant piping length 7.5m (horizontal) * level difference 0m. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Units should be selected on nominal capacity. Maximum capacity is limited to peak periods. The sound pressure level is measured via a microphone at a certain distance from the unit. For measuring conditions: please refer to item 6 of this chapter. The sound power level is an absolute value indicating the power which a sound source generates. Energy label: scale from A (most efficient) to G (less efficient). The Energy Label Directive 2002/31/EC will enter into force once the relevant measurement standard will be published in the European Official Standard. Annual energy consumption: based on average use of 500 running hours per year at full load (= nominal conditions)

Split - Sky Air Indoor units

11

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

Specifications

1
2
ELECTRICAL SPECIFICATIONS
For indoor units only: CURRENT Nominal running current Maximum running current cooling heating cooling heating A A A A FTXS50BVMB 0.18 0.20 FTXS60BVMB 0.18 0.20 See chapter RXS-B: electrical data FTXS50BVMB RXS50BVMB 7.3 7.5 FTXS60BVMB RXS60BVMB 9.3 9.2 See chapter RXS-B: electrical data FTXS71BVMB RXS71BVMB 11.1 11.6 FTXS71BVMB 0.20 0.22

For combination indoor units + outdoor units: CURRENT Nominal running current Maximum running current Starting current cooling heating cooling heating cooling heating A A A A A A

For combination indoor units + outdoor units: CURRENT Nominal running current Maximum running current Starting current cooling heating cooling heating cooling heating A A A A A A

FTXS50BVMB 3MXS52/ 4MXS68,80B

FTXS60BVMB 4MXS68,80B

FTXS71BVMB 4MXS80B

See chapter MXS-B: electrical data

For indoor units only: POWER SUPPLY NOMINAL DISTRIBUTION SYSTEM Phase VOLTAGE Frequency Voltage

Hz V

FTXS50BVMB VM 1 50 230

FTXS60BVMB VM 1 50 230

FTXS71BVMB VM 1 50 230
3D040778A 3D040779 3D040780A

NOTES
1 2 3 4 5 6 7 8 9 Nominal cooling capacities are based on: indoor temperature 27CDB/19CWB * outdoor temperature 35CDB * refrigerant piping length: 7.5m * level difference: 0m. Nominal heating capacities are based on: indoor temperature 20CDB * outdoor temperature 7CDB/6CWB * refrigerant piping length 7.5m (horizontal) * level difference 0m. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Units should be selected on nominal capacity. Maximum capacity is limited to peak periods. The sound pressure level is measured via a microphone at a certain distance from the unit. For measuring conditions: please refer to item 6 of this chapter. The sound power level is an absolute value indicating the power which a sound source generates. Energy label: scale from A (most efficient) to G (less efficient). The Energy Label Directive 2002/31/EC will enter into force once the relevant measurement standard will be published in the European Official Standard. Annual energy consumption: based on average use of 500 running hours per year at full load (= nominal conditions)

12

Split - Sky Air Indoor units

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

Dimensional drawings

1
FTK/XS20-25-35C
The mark (Y) shows piping direction
Rear Left Right Air flow (indoor) required space (for performance and maintenance)
(including installation plate)

unit (mm)

(space for maintenance)


Home leave lamp

(space for maintenance)

Name plate
Signal receiver Room temp. thermistor

Terminal block with earth terminal Gas pipe 9.5Cut (The length of pipe outside the unit: about 300) Liquid pipe J6.4 CuT (the length of pipe outside the unit: about 350) Drain hose (connecting part I.D. J 14.0, O.D. J 18.0) (The hose length on the outside of the unit is approx. 410)

Bottom Flaps Front grille fixing screws (Inside)

Intelligent movement sensor Timer lamp Operation lamp Indoor unit ON/OFF switch

Signal transmitter

Blade angle
Up/down (automatic) Cooling, dry Heating

Infrared remote control


FTXS--: (ARC433A1) FTKS--: (ARC433A2)

Right/left (manual)

Wall hole for embedded piping J 65 hole

Standard locations of wall holes

Wall hole J 65 hole

3D044026

FTK/XS50B
The mark (Y) shows piping direction
Left Right (including installation plate)
50 MIN

Air flow (indoor) required space (for performance and maintenance)

50 MIN

(space for maintenance) Name plate


Operation lamp Signal receiver Indoor unit ON/OFF switch Intelligent movement sensor Room temp. thermistor Timer lamp Home leave lamp

Required space

(space for maintenance)

Terminal block with earth terminal (Inside) Gas pipe 12.7Cut (The length of pipe outside the unit: about 340) Liquid pipe J6.4 CuT (the length of pipe outside the unit: about 350) Drain hose (connecting part I.D. J 14.0, O.D. J 18.0) (The hose length on the outside of the unit is approx. 440)

Bottom

Front grille fixing screws (Inside) Flaps Signal transmitter

Blade angles
Horizontal blade (Automatic) Cooling

Heating (FTX -- only)

Dry

Fan only Vertical blade (Automatic) Wall hole J 65 hole

Infrared remote control


FTX---: (ARC433A21) FTK---: (ARC433A22)

Wall hole for embedded piping J 65 hole

Standard locations of wall holes

3D040071

(space for performance)

Rear

Rear

30 MIN

(space for performance)

unit (mm)

Split - Sky Air Indoor units

13

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

Dimensional drawings

1
3
FTK/XS60-71B
The mark (Y) shows piping direction
Left Right (space for maintenance)
50 MIN (including installation plate) 30 MIN 50 MIN

Air flow (indoor) required space (for performance and maintenance)

unit (mm)
(space for performance)

Rear

Rear

Required space
Name plate Terminal block with earth terminal Gas pipe J B Cut (The length of pipe outside the unit: about 340)

(space for maintenance)

Operation lamp Signal receiver Indoor unit ON/OFF switch Room temp. thermistor

Bottom Flaps Front grille fixing screws (Inside)

Intelligent movement sensor Timer lamp Home leave lamp

FTX(K)S6071--

A 6.4

FTX(K)S60-FTX(K)S71--

B 12.7

Drain hose (connecting part I.D. J 14.0, O.D. J 18.0) (The hose length on the Liquid pipe J A Cut (The length of pipe outside of the unit is outside the unit: about 390) approx. 440)

Signal transmitter Horizontal blade (Automatic) Cooling

Blade angle
Heating (FTX -- only) Dry

Fan Vertical blade (Automatic) Infrared remote control FTX---: (ARC433A2133) FTK---: (ARC433A22) Wall hole for embedded piping J 80 hole Wall hole J 80 hole

Standard locations of wall holes

3D040073A

14

Split - Sky Air Indoor units

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

Piping diagrams

1
FTK/XS20-25-35C
Indoor unit
Heat exchanger

Thermistor on heat exchanger

Field piping

Cross flow fan

Fan motor Field piping

Refrigerant flow Cooling Heating 4D033698B

FTK/XS50-60B
Indoor unit

Heat exchanger

Thermistor on heat exchanger Cross flow fan

Field piping

Field piping

Fan motor

Refrigerant flow Cooling Heating 4D040081

Split - Sky Air Indoor units

15

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

Piping diagrams

1
4
FTK/XS71B
Indoor unit

Heat exchanger

Thermistor on heat exchanger Cross flow fan

Field piping

Field piping

Fan motor

Refrigerant flow Cooling Heating 4D040082

16

Split - Sky Air Indoor units

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

Wiring diagrams

1
FTK/XS20-25-35C

Intelligent movement sensor

(Terminal for centralised control) Transmission circuit

Outdoor

g Field wiring
CAUTION

Signal receiver

Note that operation will restart automatically if the main power supply is turned off and then back on again.

R
Infrared remote control

Indoor

C70 FU H1PH3P M1F M1S PCB1PCB3 R1T, R2T S1S36 S1W X1M

: Protective earth : Running capacitor : Fuse : Pilot lamp : Fan motor : Swing motor : Printed circuit board : Thermistor : Connector : Operation switch : Terminal strip

3D033599C

FTK/XS50B

g Field wiring
Rectifier

Outdoor

Transmission circuit

CAUTION
Note that operation will restart automatically if the main power supply is turned off and then back on again.

R
FG FU H1H3 H1PH3P M1F M1S, M2S PCB1PCB5 R1T, R2T S1S38 S1W X1M

Intelligent movement sensor

Signal receiver Infrared remote control

Indoor

: Protective earth : Frame ground : Fuse : Harness : Pilot lamp : Fan motor : Swing motor : Printed circuit board : Thermistor : Connector : Operation switch : Terminal strip

3D038065A

Split - Sky Air Indoor units

17

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

Wiring diagrams

1
5
FTK/XS60-71B
g Field wiring
Rectifier

Outdoor

Transmission circuit

CAUTION
Note that operation will restart automatically if the main power supply is turned off and then back on again.

R
FG FU H1H3 H1PH3P M1F M1S, M2S PCB1PCB5 R1T, R2T S1S38 S1W X1M

Intelligent movement sensor

Signal receiver Infrared remote control

Indoor

: Protective earth : Frame ground : Fuse : Harness : Pilot lamp : Fan motor : Swing motor : Printed circuit board : Thermistor : Connector : Operation switch : Terminal strip

3D038530B

18

Split - Sky Air Indoor units

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

6 6-1
Cooling only

Sound level
Sound level data
Sound pressure level

1
6
230V, 50Hz Cooling Measuring location SL 22 22 23 32 33 34
Location of microphone

Model H FTKS20C FTKS25C FTKS35C FTKS50B FTKS60B FTKS71B 38 38 39 44 45 46

Sound power level (Cooling) 56 56 57 63 63 63

6-1

L 25 25 26 35 36 37

Heat pump
Sound pressure level Model H FTXS20C FTXS25C FTXS35C FTXS50B FTXS60B FTXS71B 38/38 38/38 39/39 44/42 45/44 46/46 230V, 50Hz Cooling/Heating L 25/28 25/28 26/29 35/33 36/35 37/37 SL 22/25 22/25 23/26 32/30 33/32 34/34
Location of microphone

Measuring location

Sound power level (Cooling/Heating) 56/56 56/56 57/57 63/60 63/62 63/63

6-2
Cooling only

Sound pressure spectrum

FTKS20-25C

FTKS35C

Octave band sound pressure level dB:(0dB = 0.0002 bar)

Octave band sound pressure level dB:(0dB = 0.0002 bar)

approximate threshold hearing for continuous noise

approximate threshold hearing for continuous noise

4D035255B Octave band center frequency (Hz)

4D035256B Octave band center frequency (Hz)

Split - Sky Air Indoor units

19

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

1
6
6-2

6 6-2
FTKS50B

Sound level
Sound pressure spectrum

FTKS60B

Octave band sound pressure level dB:(0dB = 0.0002 bar)

Octave band sound pressure level dB:(0dB = 0.0002 bar)


approximate threshold hearing for continuous noise approximate threshold hearing for continuous noise

4D040303 Octave band center frequency (Hz)

4D040304 Octave band center frequency (Hz)

FTKS71B

Octave band sound pressure level dB:(0dB = 0.0002 bar)


approximate threshold hearing for continuous noise

4D040305 Octave band center frequency (Hz)

NOTE
1 Operation noise differs with operation and ambient conditions.

Legend 50/60Hz 220-240/220-230V(H) 50/60Hz 220-240/220-230V(L)

20

Split - Sky Air Indoor units

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

6 6-2
Heat pump

Sound level
Sound pressure spectrum

1
6
FTXS20-25C (Heating)

FTXS20-25C (Cooling)

6-2

Octave band sound pressure level dB:(0dB = 0.0002 bar)

approximate threshold hearing for continuous noise

Octave band sound pressure level dB:(0dB = 0.0002 bar)


approximate threshold hearing for continuous noise

3D035240B Octave band center frequency (Hz)

3D035240B Octave band center frequency (Hz)

FTXS35C (Cooling)

FTXS35C (Heating)

Octave band sound pressure level dB:(0dB = 0.0002 bar)

approximate threshold hearing for continuous noise

Octave band sound pressure level dB:(0dB = 0.0002 bar)


approximate threshold hearing for continuous noise

3D035241B Octave band center frequency (Hz)

3D035241B Octave band center frequency (Hz)

NOTE
1 Operation noise differs with operation and ambient conditions.

Legend 50/60Hz 220-240/220-230V(H) 50/60Hz 220-240/220-230V(L)

Split - Sky Air Indoor units

21

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

1
6
6-2

6 6-2

Sound level
Sound pressure spectrum

FTXS50B (Cooling)

FTXS50B (Heating)

Octave band sound pressure level dB:(0dB = 0.0002 bar)

approximate threshold hearing for continuous noise

Octave band sound pressure level dB:(0dB = 0.0002 bar)


approximate threshold hearing for continuous noise

3D040299 Octave band center frequency (Hz)

3D040299 Octave band center frequency (Hz)

FTXS60B (Cooling)

FTXS60B (Heating)

Octave band sound pressure level dB:(0dB = 0.0002 bar)

approximate threshold hearing for continuous noise

Octave band sound pressure level dB:(0dB = 0.0002 bar)


approximate threshold hearing for continuous noise

3D040300 Octave band center frequency (Hz)

3D040300 Octave band center frequency (Hz)

NOTE
1 Operation noise differs with operation and ambient conditions.

Legend 50/60Hz 220-240/220-230V(H) 50/60Hz 220-240/220-230V(L)

22

Split - Sky Air Indoor units

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

6 6-2

Sound level
Sound pressure spectrum

1
6
FTXS71B (Heating)

FTXS71B (Cooling)

6-2

Octave band sound pressure level dB:(0dB = 0.0002 bar)

Octave band sound pressure level dB:(0dB = 0.0002 bar)

approximate threshold hearing for continuous noise

approximate threshold hearing for continuous noise

3D040301 Octave band center frequency (Hz)

3D040301 Octave band center frequency (Hz)

NOTE
1 Operation noise differs with operation and ambient conditions.

Legend 50/60Hz 220-240/220-230V(H) 50/60Hz 220-240/220-230V(L)

Split - Sky Air Indoor units

23

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

1
7
7-1

7 7-1
j Mounting plate A

Accessories
Standard accessories
1 2 1 j Remote control holder E j AAA dry-cell G batteries j Indoor unit fixing screws M4x12L H 1 2 2 j Operation manual K j Installation manual L 1 1

FTK/XS20-25-35C

j Air purification filter with photocatalytic deodorising B function j Infrared remote control D

FTK/XS50-60-71B

j Mounting plate A j Air purification filter with photocatalytic deodorising B function j Infrared remote control D

1 2 1

j Remote control holder E j AAA dry-cell G batteries j Indoor unit fixing screws M4x12L H

1 1 2

j Operation manual K j Installation manual L

2 1

7-2
FTK/XS-C/B

Optional accessories
20 Normal open contact Normal open pulse contact 1 up to 5 rooms (2) 25 35 KRP413A1S KRP413A1S KRC72 DCS302C51 DCS301B51 DST301B51 KRP928A2S KAF918A43 KAF918A44 KKF917A4 50 60 71

Option name Wiring adapter for time clock / remote control (1) Centralised control board Central remote control Unified ON/OFF control Schedule timer Interface adapter (3) Air purification filter with photocatalytic deodorising function (with frame) Air purification filter with photocatalytic deodorising function (without frame) Anti-theft protection for remote control

(1) Wiring adapter is also required for each indoor unit. (2) Wiring adapter supplied by Daikin. Time clock and other devices: field supply. (3) Interface adapter for room air conditioners (DIII-NET)

24

Split - Sky Air Indoor units

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

8 8-1

Control systems
Infrared remote control

1
8
8-1

FTK/XS20-25-35C

<ARC433A1, A2>

1 2

3 4 5 6 7

Signal transmitter: It sends signals to the indoor unit. Display: It displays the current settings. (In this illustration, each section is shown with all its displays ON for the purpose of explanation.) HOME LEAVE button: for HOME LEAVE operation POWERFUL button: for POWERFUL operation TEMPERATURE adjustment buttons: It changes the temperature setting ON/OFF button: Press this button once to start operation. Press once again to stop it. MODE selector button: It selects the operation mode (Auto , / Dry I / Cool u / Heat w / Fan B)

8 9 10 11 12 13 14 15 16

OUTDOOR UNIT SILENT button: SILENT operation FAN setting button: It selects the air flow rate setting. SWING button SENSOR button: for INTELLIGENT EYE Operation ON TIMER button OFF TIMER button TIMER setting button: It changes the time setting TIMER CANCEL button: It cancels the timer setting. CLOCK button

Split - Sky Air Indoor units

25

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

1
8
8-1

8 8-1

Control systems
Infrared remote control

FTK/XS50-60-71B

<ARC433A21, A22>

1 2

3 4 5 6 7

Signal transmitter: It sends signals to the indoor unit. Display: It displays the current settings. (In this illustration, each section is shown with all its displays ON for the purpose of explanation.) HOME LEAVE button: for HOME LEAVE operation POWERFUL button: for POWERFUL operation TEMPERATURE adjustment buttons: It changes the temperature setting ON/OFF button: Press this button once to start operation. Press once again to stop it. MODE selector button: It selects the operation mode (Auto , / Dry I / Cool u / Heat w / Fan B)

8 9 10 11 12 13 14 15 16 17

OUTDOOR UNIT SILENT button: SILENT operation FAN setting button: It selects the air flow rate setting. SENSOR button: for INTELLIGENT EYE Operation SWING button Flap (horizontal blade) SWING button Louver (Vertical blades) ON TIMER button OFF TIMER button TIMER setting button: It changes the time setting TIMER CANCEL button: It cancels the timer setting. CLOCK button

26

Split - Sky Air Indoor units

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

Center of gravity

FTK/XS20-25-35C

1
9

4D020686H

FTK/XS50B

4D040311

FTK/XS60-71B

4D040313

Split - Sky Air Indoor units

27

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

10
10

Installation

FTK/XS20-25-35C

Indoor unit installation drawings

How to attach the indoor unit. Hook the claws of the bottom frame to the mounting plate. If the claws are difficult to hook, remove the front panel. How to remove the indoor unit. Push up the marked area (at the lower part of the front panel) to release the claws. If it is difficult to release, remove the front panel. Front panel

j Mounting A plate Clip

j Mounting plate A

Bottom frame Mark (rear side)

The mounting plate should be installed on a wall which can support the weight of the indoor unit.

30mm or more from ceiling

Caulk pipe hole gap with putty.

Front grille Cut thermal insulation pipe to an appropriate length and wrap it with tape, making sure that no gap is left in the insulation pipes cut line.

50 mm or more from walls (on both side) (on both side) Air filters Appearance of the indoor unit may differ from some models.

Service lid This service lid is an open/close type.

j Air purification filter with photocatalytic B deodorising function Tabs (upper 3 locations)

+ Remove the screws on the service lid. + Slide the service lid leftward. + Rotate the service lid upward.

Tabs (lower 2 locations)


B Insert the upper side of the j Air purification filter with photocatalytic deodorising function into the tabs (upper 3 locations), push the lower side of the filters up a little and into the tabs (lower 2 locations).

Before screwing the remote control holder to the wall, make sure that control signals are properly received by indoor unit. j Infrared remote control D

j Remote control E holder

28

Split - Sky Air Indoor units

Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB

10

Installation
10
Indoor unit installation drawings
j Mounting plate A

FTK/XS50-60-71B

The mounting plate should be installed on a wall which can support the weight of the indoor unit. The figure shows a 50 class unit. (See Indoor Unit Installation 1. Installing the mounting plate for details regarding 60 and 71 class units.)
Cut thermal insulation pipe to an appropriate length and wrap it with tape, making sure that no gap is left in the insulation pipes cut line.

30mm or more from ceiling Front grille

Caulk pipe hole gap with putty.

50 mm or more from walls (on both side) (on both side) Air filters Intelligent movement sensor Only for 60 and 70 class units.

Wrap the installation pipe with the finishing tape from bottom to top

Service lid Opening service lid Service lid is opening/closing type. Opening method 1) Remove the service lid screws. 2) Lift the service lid upward.

j Air purifying filter with photocatalytic B deodorizing function. 50 class Tabs (upper 3 locations)

Tabs (lower 2 locations) 60, 71 class Tabs (upper 3 locations)

Tabs (lower 3 locations)


B Insert the upper side of the j Air purification filter with photocatalytic deodorising function into the tabs (upper 3 locations), push the lower side of the filters up a little and into the tabs (lower 2 locations).

Movement sensor
Caution
1) Do not hit or violently push the movement sensor. This can lead to damage and malfunction. 2) Do not place large objects near the sensor. Also keep heating units or humidifiers outside the sensors detection area.

Split - Sky Air Indoor units

29