TAMIL NADU ELECTRICITY BOARD

TENDER SPECIFICATION FOR SUPPLY OF Control and Relay Panels For various Substations

TNEB SPECIFICATION NO.P&C-782

Office of the Superintending Engineer/Design, Protection & Communication, MLDC Block, 2nd Floor, 802, Anna Salai, Chennai-600 002. TAMIL NADU.

TECHNICAL DETAILED TECHNICAL SPECIFICATION : TECHNICAL SPECIFICATION FOR CONTROL & RELAY PANELS: This specification provides for the design, fabrication, manufacturing of panels with relays, meters and other associated equipments with provision for wiring of all equipments. The equipments shall be capable of working satisfactorily in the environmental conditions: 1. GENERAL: The manufacturer, whose C&R panels and protective relays are offered, should have a minimum of three years experience for having designed, manufactured, tested, supplied and commissioned C&R panels and protective relays upto 230 KV Feeders and 230KV Autotransformers. The panels are to be of simplex type; shall be independent and totally closed having wiring access from rear for control panels and either front or rear for relay panels. The equipments are to be mounted on the front side of the panel. The control panels shall be provided with rear doors and doors shall have handles with built-in facility. The relay panel shall be provided with swing door on front side and transparent protective door covering the front swing door on which the relays and associate equipments shall be mounted. The panels shall be completely metal enclosed and shall be dust, moisture and vermin proof. The enclosure shall provide a degree of protection not less than IP-31 in accordance with IS:2147.Panels shall have base-frame with smooth bearing surface, antivibration strips / pad made of shock absorbing materials shall be placed between panel and base frame. All doors, removable covers and panels shall be gasketted all around with neoprene gaskets. Ventilating louvre shall have screens and filters. Cable entries to the panels shall be from the bottom. Necessary cable gland should fitted. Cable gland plates fitted on the bottom shall be connected to earthing of panel/station through a flexible braided copper conductor rigidly. Each panel shall be provided with space heater rated for 240V single phase AC supply with controlling thermostat. All equipments on and in panels shall be mounted and completely wired to the terminal blocks ready for external connections. The spare contacts shall also be wired upto the terminal box. Each panel shall be provided with the interior lights (40W, fluorescent) controlled by door switch. A 230V singlephase, 3-pin AC socket 15/5A with switch shall be provided in each panel for connection of hand lamps. Accessories required for fixing the panel such as foundation bolts and nuts shall be provided along with the panel.

1.

DIMENSION: Height:2312 mm (The Height includes 10mm base frame and 12mm vibration pad), Depth: 600 mm. Width:720mm

Thickness of sheet: Front and near side not less than 10 SWG and top not less than 14 SWG. For Vembadithalam SS Size of control panel Size of relay panel 3. :-720x650x2250 mm :-720x650x2312 mm

NAME PLATE & MARKINGS: All equipment mounted on front and rear side as well as equipment mounted inside the panels shall be provided with individual nameplates with equipment designation engraved. Also on the top of each panel on front as well as rear side, large and bold name plates shall be provided for circuit/feeder designation. Name plate shall be made of non-rusting metal or 3 ply lamicoid. Nameplates shall be black with white engraving lettering. Each instrument and meter shall be prominently marked with quantity measured e.g. KVA, MW etc., All relays and other devices shall be clearly marked. Each switch shall bear clear inscription identifying its function. Coloured mimic diagram and symbols showing the exact representation of the system shall be provided in the front of control panel. Mimic diagram shall be made preferably of anodized aluminium or plastic material, which shall be screwed on to panel and can be easily cleaned. Painted overlaid mimic is also accepted. The mimic bus shall be 2 mm thick. The width of mimic bus shall be 10mm for busbars and 7 mm for other connections. The colour of the mimic may be as follows: 230 KV Signal red.110 KV Brilliant green.

3.

PAINTING: i) ii) iii) All sheet steel work shall be phosphated in accordance with IS:6005. Oil, grease, dirt, swart, rust and scale etc., shall be removed by adapting to proper cleansing procedure. After phosphating and thorough rinsing, the phosphate coating shall be sealed with application of two coats of ready mixed stoved type zinc chromate primer. The first coat may be `flash dried' while the second coat shall be stoved. After application of the primer, two coats of finishing synthetic enamel paint shall be applied, each coat followed by stoving. The colour of the panel shall match the existing panel colour of the subject station and normally of the following choice for new stations. Exterior Interior Bus frame Finish : : : : stoved enamel grey stoved enamel white stoved enamel black glossy surface treatment shall be done as per ISS.

iv) v)

5.

INDICATING INSTRUMENTS AND METERS: shall be of Size Scale Accuracy : 144 Sq.mm outer size with circular dials. : 90 degrees. : +/-1.0% uniform deflection.

Wattmeter / VAR meter shall be of three phase two element type suitable for measurement of unbalanced load in 3 phase 3 wire circuit and shall be flush mounting type. The instrument dial shall be parallax free with white scale and black knife-edge pointer and with black numerals and lettering. Import (+) and Export (-) in MW / MVAR meters shall be marked to indicate the direction of active and reactive power flow towards and away from the substation bus bar. Digital bus voltage and frequency meters shall be of class: 0.5 and shall have digital display of five (5) and four (4) digits respectively with display size, not less than 50 mm (height). All indicating instruments, meters, recorders etc., shall be enclosed in dust proof moisture restraint cases and shall be suitable for tropical use. Electronic Trivector Meters shall be with facility for separate registering of KWH, KVAH and KVARH consumption and also to record export/import and demands and their input quantities. The accuracy of meters shall be 0.5 clause. The meter shall have communication facility with open protocol. It shall record and indicate the measured parameters for frequency variations of 15% and for AC auxiliary variation from -40% to +10% and shall have facility to communicate on line parameters as well as down load stored data. The connectivity to the computer shall be of RS485 and necessary connectors shall be supplied. 6. INDICATING LAMPS: i) Indicating lamps shall be panel mounting with rear terminal connections. Lamps shall be provided with series connected resistors preferably built in the lamp assembly. ii) Lamps shall have translucent covers to diffuse lights. The lamp cover shall be preferably of screwed type, unbreakable and moulded from heat resisting material. iii) The wattage and resistance of the lamps shall be as follows: a) b) iv) 220/250V DC : 5 to 10 Watts; 4 to 8 Kilo ohms. 110V DC : 5 to 10 Watts; 1 to 2 Kilo ohms.

Bulbs/LEDs etc., shall be interchangeable and easily replaceable from the front of the panel. Tools if required for replacing the bulbs and LEDs shall be included in the scope of supply.

v) vi)

The indicating lamps shall withstand 120% of rated voltage on a continuous basis. Colour of the indicating lamps may be as follows: a) P.T. Supply : Red, yellow and Blue for the three phases. b) Breaker position : ON-Red. OFF-Green. c) Air pressure : White. normal d) Gas pressure : White. normal e) Line P.T. Supply : Yellow / Amber f) Isolator Position : ON-Red. OFF-Green.

7.

SWITCHES: Control and instrument switches shall be rotary operated type with escutcheon plates clearly marked to show operating position and circuit designation plates and suitable to flush mounting with only switch front plate and operating handle projecting out. a) Control switches for Breakers/Isolators shall be of two position spring return to neutral type with pistol grip black handle. The control springs shall be strong and robust enough to prevent inadvertent operation due to light touch. Instrument selection switches shall be of maintained contact (stay put) type. Ammeter selector switch shall have six position stayput type and shall have make-before-break type contacts so as to prevent open circuiting of CT secondaries when changing position of the switch. Voltmeter transfer switches for AC shall be suitable for reading all line-to-line voltages. Synchronising switches shall be of stay put type having a common removable key for a group of switches. The key shall be removable only in OFF position. Push Buttons shall be of momentary contact type with rear terminal connections. They shall be provided with functional indication engraved in an inscription plate. The contacts of the push button switch shall be capable of carrying 5 Amps. at 250V DC and shall be cable of breaking lamp inductive load at 250V DC. General: Lockable type of switches which can be locked in particular position shall be provided when specified. The contacts of the switches shall be open and close with snap action

b)

c)

d)

e)

to minimise arcing. Contacts of switches shall be spring assisted and contact faces shall be with rivets of pure silver or sliver alloy. The springs shall not be used as current carrying parts. The contacts shall be of the rating of not less than 10 amps. for make and carry continuously and 30 amps for short time rated for 0.5 sec. And 3 amps for breaking resistive loads and 0.2 amps for breaking inductive load with L/R = 40 m sec. 8. PANEL WIRING: i) All wiring shall be provided with minimum 650V Grade single core multistrand copper conductor wires with PVC insulation and shall be flame, vermin and rodent proof. The minimum size of the stranded copper wire shall be: a) b) for all circuits except C.T. circuits. 1.5 sq.mm. for C.T. circuits 2.5 sq.mm. All wiring shall be in accordance with the wiring for functioning of connected equipment.

diagram

ii) iii)

Flexible wires shall be used for wiring of devices on moving parts such as swinging panels or panel door. Panel wiring shall be securely supported, neatly arranged, readily accessible and connected to equipment terminals and terminal blocks. Wiring gutters and troughs shall be used for this purpose. Cables/wires shall be uniformly bunched and tied by means of PVC belts and carried in PVC carrying troughs. The position of PVC carrying troughs and hanging bunch of wires shall not give any hindrance for fixing or removing relay casing, switches etc., Wire termination shall be made with solderless crimping type and tinned copper lugs, which firmly grip the conductor. Insulated sleeves shall be provided at all the wire terminations. Engraved core identification plastic ferrules marked to correspond with panel wiring diagram shall be fitted at both ends of each wire. The wire number shown on the wiring shall be in accordance with the I.S. 375.

(iv)

v)

vi)

vii)

viii) ix)

All wires directly connected to trip circuit breaker or device shall be distinguished by addition of red colour unlettered ferrule. Inter connections to adjacent panels shall be brought out to a separate set of terminal blocks located near the slots or holes to be provided at the top portion of the panel. Arrangements shall be made for easy connections to adjacent panels at site and wires for this purpose shall be provided and bunched inside the panel. Bus wire shall run at the top of the panel. bus wire shall be with isolating links. The terminal block for

x) xi)

The terminal block used shall be minimum 650V grade and have 10 amps continuous rating, moulded piece, complete with insulated barriers, stud type terminals, washers, nuts and locknuts suitable for operation with a tubular box spanner or screw driver. Terminal block shall be arranged in vertical formation at an inclined angle with sufficient space between terminal blocks with a minimum of150 mm for easy wiring. Terminal block shall include a white fibre marking strip with clear plastic, slip on/clip on terminal covers. Markings on the terminal strips shall correspond to wire number and terminal number on the wiring diagrams. There shall be a minimum clearance of 250 mm between the first row of terminal blocks and the associated cable and plate or panel sidewall. At least 20% of total terminals shall be provided as spare for further connections and these spare terminals shall be uniformly distributed on all terminal blocks. Wiring is preferable with the following colour code.

xii)

xiii)

xiv)

xv)

xvi)

PT supply : Red, Yellow, Blue for phase and Black for neutral. CT circuits : Similar to the above. DC circuit : Gray for both Positive and Negative. 230V AC circuits: Black for both Phase and Neutral. Earthing : Green.

9.

EARTHING: i) All panels shall be equipped with an earth bus securely fixed along the inside base of the panels. When several panels are mounted adjoining to each other, the earth bus shall be made continuous and necessary connectors and clamps for this purpose shall be included in the scope of supply. The size of the earth bus shall be made of 25mm x 6mm tinned copper flat. The earth of the substation will be 40mm diameter M.S. rods, Provision shall be made on the earth bus bars of the end panels for connecting to the earth grid. Necessary terminal clamps and connectors shall be included in the scope of supply. All metallic cases of the relays, instruments and other panel mounted equipments shall be connected to the earth bus by independent copper wires of size not less than 2.5 sq.mm. The colour code of earthing wire shall be green. Earthing wires shall be connected on the terminals with suitable clamp connectors and soldering shall not be permitted.

ii) iii)

iv)

10.

CIRCUIT DISTRIBUTION AND ISOLATION: i) Each control and relay panel shall be provided with necessary arrangements for receiving, isolating and fusing of AC and DC supplies for various control of signaling, lighting and space heaters. The incoming and sub-circuits shall be separately provided with switch fuse units, selection of the main and sub-circuit fuse rating shall be such as to ensure selective clearance of sub-circuit faults. Potential circuits for relaying and metering shall be protected by fuses. All fuses shall be of HRC cartridge type conforming to IS 2203 mounted on plug-in type fuse bases. All accessible live connection of fuse bases shall be adequately shrouded. Fuses shall have operation fuse' condition. indicators for indicating `blown-

ii)

iii) iv)

v)

vi)

Fuses carrier base shall have imprints of fuse rating and voltage.

vii)

Removable links should be provided at the output of each relay for trip output and reclose output. Adequate space shall be left between fuse units when arranged adjacently.

11.

LABELS: All front mounted equipment as well as equipment mounted inside the panel shall be provided with individual labels with equipment designation engraved. Labels shall be made of non rusting metals or 3 ply lanced. Label shall have white letters on black or dark back-ground. The size of the label shall be ; width-1.5 cms; length-as per length of inscription; the letter size-0.75cm.

12.

SYNCHRONISING EQUIPMENT: i) The synchronizing panel shall be mounted with double voltmeter, double frequency meter, synchroscope and lamps fully wired. ii) Suitable auxiliary voltage transformers wherever necessary shall be provided for synchronizing condition. ANNUNCIATORS: i) The annunciations fascia shall be provided with flasher, hooters and bell for separate indication of tripping alarm/non-tripping alarms. All the panels shall have the inter connection for accepting the alarm but the reset shall be from the individual panel. ii) Each annunciations fascia/window shall be provided with LED. iii) Trip and non-trip discrimination shall be made in the fascia. For example all trip fascia shall have red colour and non trip fascia white colour. RELAYS: i) ii) iii) All relays shall confirm to IS: 3231 and IS: 8686 and or other relevant standards in vogue. Descriptive details of the relays are furnished and specified in separate heads. Testing facility provided on the relay shall be detailed.

13.

14.

iv)

Necessary test plugs, test blocks and switches shall be provided.

v) vi)

Unless otherwise specified all auxiliary relays and timers shall be supplied in non-drawout cases / plug in type modular cases. Relays shall have the rating for 110V VT secondaries and 1 amp CT s secondaries. D.C.Auxiliaries and timers shall be designed for the DC Voltage specified. Provision shall be made for isolation of trip circuits of each relay for the purpose of testing and maintenance. All relays / wiring shall withstand a test voltage of 2.5 KV, 50 Hz r.m.s. voltage for 1 minute. The relays shall be able to be tested with universally acceptable testing kit.

vii) viii) ix)

All the relays offered shall have to be type tested. Necessary bill of materials in each case has been enclosed in the appendix. 15. GENERAL:For each type of Numerical relay offered in the tender, necessary software capable of interacting with the realy for performing following complete functions: i) Input/Output relay assignment ii) LED configuration iii) Setting & Modification of relay parameters iv) Analysis of disturbance recording v) Tools to download details of relay shall be supplied . No Laptop/Desktop computer is required. 16. RELEVANT REFERENCE STANDARDS: IS IS IS IS IS IS IS IS 3231 8686 2147 1248 6236 2705 3156 4237 Electrical relays for power system protection. Static protective relays. Degree of protection of cubicles. and IS - 2419 indicating instruments. Recorders. Current Transformers. Voltage Transformers. General requirements for switches and control gear for voltages not exceeding 1 KV.

x)

IS - 0722 Energy meters, control switches (LV switching devices for control and auxiliary circuits). IS - 0337, 0337-1 -doIS - 0297 (Part 1-3) Dimensions for mechanical structures of the

482.6 mm (19") Series. IS - 0375 Marketing and arrangement for switch gear, busbars main connection and auxiliary wiring. IS - 6875 Control Switches (CLV switching devices for control and aux. circuits) IS - 0005 Colour for ready mix paints. IS - 1554 (Part-I) PVC insulated cables upto and including 1000 Volts. IS - 3842 (Part I - VII) Application guide for protection. IS - 9224 (Part-II) HRC cartridge fuse links. IS - 6005 Code of practice for phosphating iron and steel. IES- 2555-1-0 Electrical relays -All-or-nothing elec. relays. ICE- 255-3,5,6,7,8,10,11,12,13,16 Electrical relays for various specifications. ICE- 255-21-2,3 ICE- 255-22-1,2,3,4 Electrical relays - vibration & disturbance etc., test. ICE- 255-23 Electrical relays - contact performance.

TRANSFORMER PROTECTION:
A.
1.

Biased Differential Protection Relay for Two Winding Transformers.

Shall be Numerical Type.

2. 3. 4.

Three phase with faulty phase identification. Shall have continuous self monitoring and Diagnostic features. Shall have instantaneous High set feature with facility to adjust 5 to 20 times normal current. Shall have second harmonic restraint content in the range of 15 to 25 %. feature with second harmonic

5.

6.

The disturbance recording functions should be Integrated in the relay module. The disturbance recorder shall have facility to record at least 4 Nos. external digital signals apart from digital signals from relay and currents in HV & LV windings.

7.

Facility to set transformer Vector group and CT ratio selection/correction through software.
8. 9. 10. 11 . 12 . 13 . 14 . 15 . 16 . 17.

Rated current 1 amp. Thermal withstand current. Continuous 2 amps and for 1 sec-70Amps Rated Voltage : 110/220 V DC Basic bias setting 20 to 40% in steps of 10%or15% to 45% in steps of 15%. Operating current setting range 15 to 30% Have an operating time not greater than 35 ms at 3 times normal current. maximum operating time for instantaneous operation:25 ms +/-4% of set value Recording memory capacity : 5 Sec. Shall have restricted earth fault protection. Have front or back RS232 port for connecting Lap Top (Suitable connecting cards/converter to be supplied) and rear RS485 or Fibre optic port for local and remote communications. However for uniformity all the relays shall be provided either with RS 485 port or Fibre optic port at the rear. The communication shall be through IEC-60870-5-103 or DNP3.0. or IEC 61850 protocols. Have time synchronisation facility.

18 .

B.

Back up non-directional overcurrent protection instantaneous for HV.

with high set

1.

Shall be of Numerical Type.

2.

IDMT Characteristic with a definite minimum time of 3.0 sec. at 10 times current and with a variable setting range of 50 to 200% of rated current of one ampere in steps of 10%. Time multiplier range 0.05 - 1.0 in steps of 0.05. Provided with Hand reset flags/LED Indicators. High set feature 500 - 2000% of rated current. Have front or back RS232 port for connecting Lap Top ( Suitable connecting cards/converter to be supplied) and rear RS485 or Fibre optic port for local and remote communications. However for uniformity all the relays shall be provided either with RS 485 port or Fibre optic port at the rear. The communication shall be through IEC-60870-5-103 or DNP3.0. or IEC 61850 protocols.
Back up Non Directional Over Current Relay for LV side.

3. 4. 5.

C.
1. 2.

Shall be of Numerical Type. IDMT Characteristic with a definite minimum time of 3.0 sec. at 10 times current and with a variable setting range of 50 to 200% of rated current of one ampere in steps of 10% Time multiplier range 0.05 - 1.0 in steps of 0.05 Provided with Hand reset flags/LED Indicators. Have front or back RS232 port for connecting Lap Top ( Suitable connecting cards/converter to be supplied) and rear RS485 or Fibre optic port for local and remote communications. However for uniformity all the relays shall be provided either with RS 485 port or Fibre optic port at the rear. The communication shall be through IEC-60870-5-103 or DNP3.0. or IEC 61850 protocols. MISCELLANEOUS PROTECTIONS: Breaker Failure Relay (Stuck Breaker Protection Relay) LBB:The relay shall be triple pole type, be suitable for station DC supply. have an operating time of less than 15 millisecs. have a resetting time of less than 15 millisecs. have three over current elements, each element, shall be arranged to get individual initiation from the corresponding phase of line protection.

3. 4.

V. 1. -

be of solid-state type. have a setting range of 10 - 80% of rated current of one ampere. have a continuous thermal withstand of two times rated current irrespective of the setting.

have timer with continuously adjustable setting range of 0.1 - 1 Sec. suitable for 110/220V DC operation. No separate LBB is required under the following condition: For Transformers: If biased differential and back up over current relays for HV and LV do have in built feature.

2.

DC Supervision Relay: The relay shall monitor continuously DC supply to protection system. The de-energisation of this relay will indicate the DC supply failure. Auxiliary supply for the relay is 110/220V DC. The relay shall have a time delay on drop-off' of not less than 100 millisec. The relay shall be provided with operation indicators (reverse flag) - self reset. Sufficient number of contacts, potential free, may be provided. Separate relays for dual source are to be provided. Trip Circuit Supervision Relays: The relay shall supervise the healthiness of trip circuit continuously (both pre-closing and post closing conditions of the circuit breakers).The relay shall be capable of monitoring the healthiness of each `phase' tripcoil and associated circuit of the circuit breaker during "ON" and "OFF" conditions. The relay shall work on 110V or 220V DC with allowable margin as the case may be. The relay shall have adequate contacts for providing connection to alarm and event logger, self-reset. The relay shall have a `time delay on drop-off of not less than 200 millisecs., and provided with operation indicators. The short circuiting of any series resistance provided in this relay or short circuiting the coil of the relay should not energize the trip coil of the breaker. Tripping (Master) Relay: For tripping of feeder / transformer breakers in a station on operation of protective relays and for interlock purposes. The relay shall be voltage rated for 110V or 220V DC with allowable margin of variation, be instantaneous (operating time not to exceed 10 milliseconds). Reset within 20 milliseconds. have adequate contacts to meet the requirement of scheme, other functions like auto-reclose relay, LBB relay as well as to cater to associated equipments like SER, DR, etc., be provided with operation element / coil.

3.

4. -

BILL OF MATERIALS
3. 132/11 KV TRANSFORMER CONTROL PANEL:

1. 2. 3. 4. 5. 6.

Circuit label in front and rear Mimic diagram Ammeter - 144 sqmm, 90 degree scale (0.300A)CTR 300/1 MW meter - 144 sqmm, 90 degree scale (100-0-100MW, 110V,1A) MVAR meter-144 sqmm, 90degree scale(60-0-60MVAR),110V,1A. Electronic Trivector meter for import and export with RS485 port for communication alongwith necessary software (110 V, 1A, 0.5 class). 6 position Ammeter selector switch Control switch for HV/LV Breakers and HV Isolators. Trip Transfer Switch. Synchronizing switch lockable type for 230 KV side Indication lamps for ON-OFF position for breaker & isolators 1 No.

2 Nos.

2 Nos. 1 No. 1 No.

1 No. 2 Nos. 5 Nos. 1 No.

7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17.

10 Nos.

Indication lamps for HV/LV breaker air/gas pressure indication4 Nos. Indication lamp for 132 KV Bus PT supply and DC fail Micro processor based Annunciation system suitable for 20 windows. Test/Accept/Reset Push button for annunciation Test/Accept Push button for DC fail test for source 1 & 2. Test terminal block 5 Nos. 1 set 3 Nos. 3 Nos. 1 No.

BILL OF MATERIALS
4. 132/ 11 KV TRANSFORMER RELAY PANEL:

1. 2. 1 No. 3. 1 No. 4. 5. 6. 7. 8.

Circuit label Numerical, biased Differential protection relay for 2 winding Transformer with REF features. Numerical, non-directional Over Current protection relay with High set for HV side. Numerical, non-directional Over Current protection relay without High set for LV side. Local Breaker Back up Relay with Timer for HV & LV side. Trip circuit supervision relay for HV & LV DC supply supervision relay for HV & LV 8 Nos.

1 No.

1 No. 2 Nos.

3 Nos.

5 element High burden Hand Reset with Flag Indication Relay for HV/LV breaker annunciation and transformer function annunciation with a minimum of 3 sets of N/O contacts and 1 set of N/O contact. 4 Nos. Three phase Master Trip relay (Hand reset relay and Flag). DC fail alarm accept Relay 4 position PT selector switch lockable type (for HV side) 2 Nos. 1 No. 1 No.

9. 10. 11.

GUARANTEED TECHNICAL PARTICULARS

1.

Transformer Biased Differential Relay: Make & Type : Numerical : Rated DC Voltage : Current Rated : Continuous : For 1 Sec. : Two Winding Relay : Operating time at 3 times normal current: Operating time for instantaneous operation: Bias setting range with steps : Availability of faulty phase identification : Availability of instantaneous High set feature with current setting range: Range of second harmonic restrain feature available. :

Availability of continuous self monitoring and diagnostic features. : Transformer vector group and CT ratio selection/corrections through software. Disturbance recorder: a) b) No. of external digital signal that can be recorded. Facility to record currents in HV & LV Winding. : :

Memory Capacity of D.R: Fault records : No. of fault records that can be stored :

Details of ports available with protocol :

GUARANTEED TECHNICAL PARTICUALRS FOR DIRECTIONAL AND NON DIRECTIONAL OVER CURRENT AND EARTH FAULT RELAYS: 1. 2. 3. 4. Description Model No. & Make DC Operating Voltage & its Range Selectability between definite time & IDMT O/C function. Over current setting range Phase fault Earth fault Time setting range and steps High set Over current setting range Phase fault. Earth fault Time setting range and steps IDMT characteristics P.T. Voltage Relay characteristic angle settable for Phase fault and Earth fault. Operating time for instantaneous element. Indications provided Communication ports provided Protocols supported Disturbance Recorder Details a. No. of analog input. b. No. of digital input. c. Sampling rate. d. Maximum storage capacity Event Recorder Details a. Maximum no. of events. b. Resolution. Sampling rate & frequency Self diagnostic feature provided Availability of Time Synchronisation facility Reset ratio Resetting time Other features available : : : : : : : : : (Not applicable for non : directional over current relays : for LV side of transformer) : : : : : : : : :

5.

6. 7. 8. 9. 10. 11. 12. 13.

14. 15. 16. 17. 18. 19. 20.

: : : : : : :