You are on page 1of 4

RTU560

Data Sheet Analog Input 23AE23


Analog Input 23AE23

Characteristics
Basic checks and computing intensive, cyclical processing functions will already be done on the board and remove therefore the burden from the central unit. Relevant changes transmits the board as event via the peripheral bus. The 8 differential inputs are not potentially isolated against the RTU560 power supply. Unipolar or bipolar values resolves the 23AE23 into 4096 steps (12 bit plus sign) for 100 % of the measuring signal. The differential inputs are protected against static and dynamic over-voltages by a protection circuit. A low-pass filter suppresses non line frequency ac disturbance.

Application
The 23AE23 board records up to eight analog measured values. The 23AE23 board allows it to connect all typical measured value ranges It can be configured for the following measurement ranges by simple switches and jumpers: 2 mA 5 mA 10 mA 20 mA 40 mA 2 V DC 0 ... + 20 V DC Other effective ranges and live zero signals become generated out of these ranges through conversion of the communication unit CMU. The 23AE23 is functional- and pin-compatible to the 23AE21 board.

Doc-No.: 1KGT 150 573 V003 1

RTU560
Data Sheet Analog Input 23AE23
Zero point monitoring Switch-over recognition Smoothing Threshold value monitoring on absolute value or with accumulation and periodic background transmission. Measuring range and line frequency are easily to configure by switch registers respectively jumpers. The micro controller needs these configurations parameters to setup the AD-converter.

The AD-converter, operating with the sigma-delta method scans with a higher resolution and has additional algorithms for a high suppression of line frequency and line harmonics interference voltages. Even for a deviation of 10 % of the line frequency there is still given a suppression of > 45 dB. The internal high resolution allows it to scan all measuring ranges (exception: 2 V DC (11 bit +sign)) with the same resolution (12 bit + sign) on one board. A 9th channel is used for automatic zero calibration.

Line frequency [Hz]

Conversion period per channel [ms] 62,5 72,5 202,5

Scan cycle per board [ms] 500 580 1620

A/D-converter Multiplexer Connection: +


60 50 16,6

Resistor network

EA11

BUS MODULE

EA10

Input circuit

The micro controller controls the A/D converter and executes all of the processing functions of the configured measured values within the conversion time. Furthermore the micro controller is responsible for interactive communication with the RTU560 system bus. All configuration characteristics and processing parameters are downloaded from the CMU via the RTU system bus. During initialization and operation the board carries out a number of tests. If a fault occurs it is reported to the CMU. All fault conditions impairing the function of the board are displayed as common fault signal with a light emitting diode (ST) on the front panel. A failure of the board is detected by the CMU. The board has a serial connection to the RTU560 peripheral bus. It cant be used in a basic subrack of a RTU232 (parallel bus).

Protection circuit

A Input circuit

+ -

EA81 EA80

Fig. 1:

Block diagram Analog input board 23AE23

The analog input board 23AE23 can carry out the following processing functions on the measured values:

Doc.No.: 1KGT 150 573 V003 1

RTU560
Data Sheet Analog Input 23AE23 Technical Data
In addition to the RTU560 general technical data, the following applies:

Power Supply
Supply: 5V / 190 mA

Input channels
Inputs Measuring ranges 8 differential inputs 2 mA 5 mA 10 mA 20 mA 40 mA 2 V DC / 0 20 V DC 50 at 40 and 20 mA 150 at 10 to 2 mA 110 k at 2 V and 20 V DC max. 80 mA for ranges 40 and 20 mA, max. 40 mA for ranges 10/5 to 2 mA, max. 38 V / max. 0.5 mA for ranges 2 and 20 V DC 24 bit

Mechanical Layout
Printed circuit board Front panel: Weight: 3HE, Euro-card format (160 x 100 mm) 4R, 1 slot (20 mm) approx. 0.3 kg

Connection Type
Connector: indirect 48 pole, F DIN 41612

Shunt / impedance

Electromagnetic Compatibility
Electrostatic discharge Immunity IEC 61000-4-2 (level 3) Radiated RadioFrequency Electromagnetic Field Immunity Test IEC 61000-4-3 (level 3) Immunity to Electrical Fast Transient IEC 61000-4-4 (level 3) 6 kV Contact 8 kV Air Performance criteria A 10 V/m Performance criteria A

Continuous load without destruction

AD converter resolution: Resolution:

12 bit + sign = 100%, all ranges except 2 V DC: 11 bit + sign for 2 V DC Function limit typ. 8 V DC Absolute maximum rating 150 V DC. Common mode rejection at 0 ... 50 Hz > 70 dB at +25 C > 60 dB at 0 ... +25 C > 100 dB for f N 2% > 45 dB for fN 10%

2 kV Performance criteria A

Common mode voltage

Surge Immunity Test 2 kV IEC 61000-4-5 Performance criteria A (level 3) Immunity to Conducted Disturbances, induced by Radio-Frequency IEC 61000-4-6 (level 3) 10 V Performance criteria A

Line frequency interference suppression Line frequency Error on delivery:

(f N): 16.6, 50 or 60 Hz 0.1 % 0.2 % for 2 V DC 0.1 % 100 ppm/K (0...70 C)

Environmental Conditions
Temperature: Relative humidity: -10 ... 70 C 5 ... 95 % (non condensing)

Linearity error: Temperature drift:

Doc.-No. 1KGT 150 573 V003 1

RTU560
Data Sheet Analog Input 23AE23
Ordering Information
Front plate: 23AE23 R5001 Plastic light beige 1KGT 012 200 R5001

Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents - in whole or in parts is forbidden without prior written consent of ABB AG. Copyright 2011 ABB All rights reserved

Doc.No.: 1KGT 150 573 V003 1