3 PHASE SURGE ARRESTER

3 PHASE PTs ES (3GD-2) DS (3G) ES(3GD-1) CT

DS (2G)

DS (1G)

CB (11DL)

ES (1GD)

CT

Bus Bar 2

Bus Bar 1

1 Oil pump motor - charging overtime alarm 2 Oil pump motor starting signal of CB 3 Low Gas pressure of CB 4 Low Gas pressure of Compartment 2~8 5 Low Gas Pressure Lockout 6 Closing Low Oil pressure lock out 7 Main Opening Low Oil pressure lock out 8 Auxiliary Opening low oil pressure lock out

1. CB Motor 2. Auxiliary Circuit 3. Moisture Dispelling & Heating Circuit 4. DS/ES Mechanism Moisture Dispelling Circuit 5. DS Motor 6. ES Motor 7. DS Control 8. ES Control

1 2 3 4 5 6

Motor Counting of Pole R Motor Counting of Pole S Motor Counting of Pole T Oil Pump Motor Starting Count of R Oil Pump Motor Starting Count of S Oil Pump Motor Starting Count of T

1 2 3 4 5 6 7 8

CB Motor Auxiliary Switch DS Motor ES Motor DS Control ES Control Moisture Dispelling & Heating ES/DS Moisture Dispelling & Heating

Mechanism interface to the 1 high voltage circuit breaker with position indicator Auxiliary Switch Assembly for 2 signaling of the switching State Control Module with Individual 3 adjustable switching speed & reaction time Spring limit switch to monitor 4 the charging level 5 Disc spring column

TECHNICAL PARAMETERS : EARTH SWITCH Rated Voltage: 252KV Rated Current: 3150A Rated Short Circuit Withstand Current: 50KA Rated Short Circuit Duration: 2~3s Electrostatically induced Switching Current: 10A/15KV Electromagnetically induced Switching Current: 160A, 15KV Opening time: <6s Closing time: <6s Rated SF6 Pressure (at 20C) : 0.45/0.5MPa Mechanical Duration: 3000 times

TECHNICAL PARAMETERS : DISCONNECTOR Rated Voltage: 252KV Rated Current: 3150A Rated Short Circuit Withstand Current: 50KA Rated Short Circuit Duration: 3s Opening time: <6s Closing time: <6s Rated SF6 Pressure (at 20C) : 0.45/0.5MPa Mechanical Duration: 3000 times MOTOR OPERATING MECHANISM Output Torque: 150N.m Output Angle: 80 SPRING OPERATING MECHANISM Output Torque: 140N.m Output Angle: 80 Energy Stored Time: <6s

CB Chamber Rated Alarm Min Pressure All Other Chambers Rated Min Pressure Unit of Pressure : Bar

6 5.2 5 5 4.4

CB Chamber Rated 6 Alarm 5.2 Min Pressure 5 All Other Chambers Rated 5 Min Pressure 4.4 Unit of Pressure : Bar

GT

STG

NAME: GT-1/2/3 & STG RED670


1 DIFFERENTIAL TRIP 2 TRIP LINE 1 3 TRIP LINE 2 4 TRIP LINE 3 5 BREAKER FAILURE TRIP 6 BREAKER FLASHOVER 7 COMMUNICATION FAILURE 8 Id ALARM

9 CT OPEN ALARM
10 RECEIVE TRIP OF 220KV CB 11 RECEIVE TRIP BUS COUPLER 12 RECEIVE PANC TRIP 220KV CB 13 RECEIVE GEEPE TRIP 220KV CB

GT-1,2&3 CT CT1 CT2 CT3 CT4 CT5 CT6 CT7 CT8 KKS 11LH 12LH 13LH 14LH 15LH 16LH 17LH 18LH RATIO ACCURACY VA(Burden) Primary Sec 20 600-1200 1 0.2S 20 600-1200 1 5P40 20 600-1200 1 5P40 20 600-1200 1 5P40 20 600-1200 1 5P40 20 600-1200 1 5P40 20 600-1200 1 5P40 20 600-1200 1 0.2S STG CT CT1 CT2 CT3 CT4 CT5 CT6 CT7 CT8 KKS 11LH 12LH 13LH 14LH 15LH 16LH 17LH 18LH RATIO ACCURACY VA(Burden) Primary Sec 20 900-1800 1 0.2S 20 900-1800 1 5P40 20 900-1800 1 5P40 20 900-1800 1 5P40 20 900-1800 1 5P40 20 900-1800 1 5P40 20 900-1800 1 5P40 20 900-1800 1 0.2S

3 PHASE S.A

ES (3GD-2)

DS (3G)

ES(3GD-1

CB(11DL) DS (2G) DS(1G)

ES (1GD)

Bus Bar 2

Bus Bar 1

NAME: KCR-1/2 REL670


1 DISTANCE- TRIP 2 CARRIER- TRIP 3 TEF -TRIP 4 TOC -TRIP 5 TRIP LOCK OUT- B 6 SOFT -TRIP 7 COMMUNICATION- FAULT 8 ZCOM-CRL 9 ZCOM- CS 10 DISTANCE -START 11 PSD -SATART 12 TEF START 13 RE-CLOSE- OPERATE

14 SUPERVISION- ALARM

ONE PHASE PT 7YH RATIO ACCURACY VA(Burden) Primary Sec 150 220/1.732 0.11/1.732 0.2(3P) 150 220/1.732 0.11/1.732 0.2 200 220/1.732 0.11/1.732 3P

KCR-1&2

CT KKS CT1 CT2 CT3 CT4 CT5 CT6 CT7 CT8 11LH 12LH 13LH 14LH 15LH 16LH 17LH 18LH

RATIO Primary 1500-3000 1200-2400 1200-2400 1200-2400 1200-2400 1200-2400 1200-2400 1500-3000

VA(Burden ACCURACY ) Sec 1 1 1 1 1 1 1 1

0.2S 5P20 5P20 5P20 5P20 5P20 5P20 0.2S

30 30 30 30 30 30 30 30

NAME: SHT-LINE-1/2 REB670

1 2 3 4 5 6 7 8

Diff-protection trip Trip A Trip B Trip C TOC1- Trip OCT-alarm ID>-Alarm Lin>-alarm

SHORT LINES 1&2 CT KKS RATIO Primary CT1 CT2 CT3 CT4 CT5 CT6 CT7 CT8 11LH 12LH 13LH 14LH 15LH 16LH 17LH 18LH 1500-3000 1200-2400 1200-2400 1200-2400 1200-2400 1200-2400 1200-2400 1500-3000 Sec 1 1 1 1 1 1 1 1 0.2S 5P20 5P20 5P20 5P20 5P20 5P20 0.2S 30 30 30 30 30 30 30 30 ACCURACY VA(Burden)

THREE PHASE PT IYH/IIYH RATIO ACCURACY VA(Burden) Primary Sec 150 220/1.732 0.11/1.732 0.2(3P) 100 220/1.732 0.11/1.732 0.2 150 220/1.732 0.11/1.732 3P 200 220/1.732 0.11 3P

BUS COUPLER CT CT1 CT2 CT3 CT4 CT5 CT6 CT7 CT8 KKS 11LH 12LH 13LH 14LH 15LH 16LH 17LH 18LH RATIO ACCURACY VA(Burden) Primary Sec 20 1200-2400 1 0.2S 20 1200-2400 1 5P40 20 1200-2400 1 5P40 20 1200-2400 1 5P40 20 1200-2400 1 5P40 20 1200-2400 1 5P40 20 1200-2400 1 5P40 20 1200-2400 1 0.2S

NAME: BUSBAR REB670 1 ZA-TRIP 2 ZA-BFP 3 ZA-EXT-TRIP 4 ZB-TRIP 5 ZB-BFP 6 ZB-EXT-TRIP 7 ZA-OCT-ALARM 8 ZA-Id>-ALARM 9 ZALINE>-ALARM 10 ZB-OCT-ALARM 11 ZB-Id>-ALARM 12 ZB-Lin>-ALARM 13 SWITCH-ALARM 14 15 ZA-BLOCKED ZB-BLOCKED

THREE PHASE PT IYH/IIYH RATIO ACCURACY VA(Burden) Primary Sec 150 220/1.732 0.11/1.732 0.2(3P) 100 220/1.732 0.11/1.732 0.2 150 220/1.732 0.11/1.732 3P 200 220/1.732 0.11 3P

NO

YES

NO
NOT OK

YES

LOW

HIGH

LOW

HIGH

FAIL

PASS

FAIL

PASS

X X

GT

X X

X X

X X

GT

X X

GT

X X

GT

X X

GT

X X

X X

X X

X X

X X

X X