You are on page 1of 7

Sensible

load
AHU ROOM
Area of north side wall excluding glass area (22' x 16')
U= 0.39
Temperature difference 95-71.6=23.4
Conduction Heat transfer = A*U*TD
Area of East wall excluding glass area (22' x 16') - (4'x20') =
272 ft2
U= 0.39
Temperature difference 95-71.6=23.4
Conduction Heat transfer = A*U*TD
Conduction heat gain thru glass area =(4'x20)
Glass U
Temperature difference =23.4 deg
Conduction Heat transfer = A*U*TD

Area of West wall excluding glass area (22' x 16') - (5'x8') =


312 ft2
U= 0.39
Temperature difference 95-71.6=23.4
Conduction Heat transfer = A*U*TD

352
0.39
23.4
3212.352

272
0.39
23.4
2482.272
80
1.06
23.4
1984.32

312
0.39
23.4
2847.312

Ceiling area 22'x22' = 484 ft2


U=0.27
Temperature difference =23.4
Conduction Heat transfer = A*U*TD

484
0.27
23.4

Floor area 22'x22' = 484 ft2


U=0.27
Temperature difference =18
Conduction Heat transfer = A*U*TD

484
0.27
18

Latent heat due to occupancy


No of occupants = 484/5115*30 = 3 persons
Sensible heat due to occupancy
Latent heat due to occupancy
Total
Heat load due to equipments
Heat load due to new panels
Lighting load @ 1.5W/ft2 484x1.5x3.4
Ventilation load
Fresh air introduced for 3 air changes/hr 22x22x12x3=
17424 ft3
sensible heat 1.08*17424*(95-71)/60=7527
Latent heat 0.7*17424*(140-63)/60 = 15653

Latent
load

3057.912

2352.24

3
250
200
750

600

14638.28
21511.8
2468.4

7527
15653

62831.89
SHR

0.794487

16253 79084.89

6.590407

CPP CONTROL ROOM EXISTING


Area of east side wall excluding
glass area (114' x 16') -(114x4)
U= 0.39
Temperature difference 9571.6=23.4
Conduction Heat transfer =
A*U*TD
Glass area on east side (114'x4')
Glass U
Temp difference
Heat transfer
Area of West wall excluding glass
area (116' x 16') - (4'x116') = 1392
ft2
U= 0.39
Temperature difference 9571.6=23.4
Conduction Heat transfer =
A*U*TD
Conduction heat gain thru west
glass area =(4'x116')
Glass U
Temperature difference =23.4 deg
Conduction Heat transfer =
A*U*TD

Area of North wall excluding glass


area (40' x 16') = 640 ft2
Area of North wall excluding glass
area (9' x 16') - 48 = 96 ft2
Area of North wall excluding glass
area (7' x 16') = 112 ft2
U= 0.39
Temperature difference 9571.6=23.4
Conduction Heat transfer =
A*U*TD
Glass area on north wall = 48 ft2
Glass U
Temperature difference 9571.6=23.4
Heat transfer thru glass

1368
0.39
23.4
12484.37
456
1.06
23.4
11310.62

1392
0.39
23.4
12703.39
464
1.06
23.4
11509.06

640
96
112
0.39
23.4
7738.848
48
1.06
23.4
1190.592

Area of South wall excluding glass


area (12' x 16') = 192 ft2

192

Area of South wall excluding glass


area (34' x 16') - (5x16) = 464 ft2

464

U= 0.39
Temperature difference 9571.6=23.4
Conduction Heat transfer =
A*U*TD
Area of South wall excluding glass
area (7' x 16') for partition = 112 ft2
Partition U
Temperature difference 9571.6=23.4
Heat transfer

0.39
23.4
5986.656

112
0.5
23.4
1310.4

Glass area on south wall = 80 ft2


Glass U
Temperature difference 9571.6=23.4
Heat transfer thru glass

80
1.06

Ceiling area 5115 ft2


U=0.27
Temperature difference =23.4
Conduction Heat transfer =
A*U*TD

5115
0.27
23.4

Floor area 5115 ft2


U=0.27
Temperature difference =18
Conduction Heat transfer =
A*U*TD

5115
0.27
18

Latent heat due to occupancy


No of occupants = 25 nos
Sensible heat due to occupancy
Latent heat due to occupancy
Total
Heat load due to equipments

23.4
1984.32

32316.57

24858.9

25
250
200

6250
5000

154700

Heat load due to new panels


Lighting load @ 1.5W/ft2
5115x1.5x3.4

26086.5

Ventilation load
Fresh air introduced for 3 air
changes/hr 5115x12x3= 184140 ft3
sensible heat 1.08*184140*(9571)/60=7527
Latent heat 0.7*184140*(14063)/60 = 15653
Glass area

184140
79548.48
165427.2
1128

Total

Total heat load due to equipments


Instrument panels old
Instrument panels new
Load due to UPS & elec panels
PC with monitors
Printers
Photocopiers
Total
Heat load (Btu/hr)

389978.7 170427.2 560405.9 46.70049

1
1
1
10
10
1

15000
6327
20000
500
450
1000

15000
6327
20000
5000
4500
1000
51827
176211.8
45500
154700

You might also like