Professional Documents
Culture Documents
Verification of Overcurrent and Earth Fault Coordination Setting in Kuala Lumpur Distribution Network
Ab Halim Abu Bakar , Muhammad Hafizuddin Mohammad , Hazlie Mokhlis , Hazlee Azil Illias
1
2,3
1,3
1,3
University of Malaya Power Energy Dedicated Advanced Center (UMPEDAC),Level 4,Wisma R&D, University of Malaya, Jalan Pantai Baharu, 59990 Kuala Lumpur, Malaysia 2 Tenaga National Berhad (TNB) 3 Department of electrical Engineering, Faculty of Engineering, University of Malaya, 50603 Kuala Lumpur, Malaysia
Abstract
In modern power system protections, reliable protective systems are important to ensure the system operation stability and the reliability of the supply. When a fault occurs, it is important that the protection system in a network isolates the faulted section in the shortest time. One of the most common methods for protection in a distribution system is Over Current and Earth Fault (OCEF) protections. The standard type of over current relay is the Inverse Definite Minimum Time (IDMT) relay. This paper focuses on the relay setting and coordination in a power distribution system. A program was developed using Microsoft Excel Visual Basic to study the effect of different grading margins on relay coordination. Studies on characteristics of the relay, scheme and function of the relay in power distribution system were performed. Keywords: Over Current and Earth Fault relays, grading margin, relay coordination
I. Introduction
The main reason of power system protection is to minimize the damage and to ensure reliable supply and in a safe condition. One of the most important components in protection system is relay. A protection relay detects defective lines and apparatus and any intolerable conditions. A protection system includes circuit breakers and relays [1]. A reliable protective system is important to ensure the operation of the system stability. When a fault occurs, it is important that the protection system in a network isolates the faulted section in the shortest time. The coordination and grading of different types of protection devices require different requirements. One of the most common methods for backup protection in a distribution system is OCEF protection. This type of protection is suitable for backup protection because of the robust operating time and versatility of the over current relay. A standard type of over current relay is the Inverse Definite Minimum Time (IDMT) relay. The operating principle of IDMT is, the greater the magnitude of a fault current, the faster the relay
operates, thus creating an inverted operating characteristic. Although IDMT over current relays is a form of non-unit protection, discrimination between two adjacent protection zones can be achieved by an appropriate selection of each relay setting [2]. In a radial distribution network, it is common to have one to two substations located in series, which a normal grading margin of 0.4s is applicable. Sometime, there are also three to five substations located in series, which is impossible to use normal grading margin of 0.4s. Therefore, in this paper, a grading margin for over current and earth fault coordination setting in Kuala Lumpur distribution network with five substations in series was verified. The study concentrated on the relay setting and coordination in a power distribution system. A program was developed using to Microsoft Excel Visual Basic study the effect of different grading margins on relay coordination. The analyses involve three phase fault current and single phase to ground fault current, characteristic of the relay, scheme and function of the relay in power distribution system. In the simulation, single line diagram was used to analyse a real distribution network system. From the analysis, the optimum grading margin of OCEF relay in distribution system was obtained. A site testing was conducted to test and verify the grading margin.
OMICRON electronics Asia Limited 2012 Asia-Pacific Protection & Testing Conference
Presentation 1.2
setting range of 50-200% of 5 A is set at 100%. It would not represent a "full load" setting, where the actual setting is 125% of full load current. Therefore, the choice of the current setting depends on the load current and the CT ratio. It is normally near to but above the maximum load current (typically 10%), by assuming the circuit is capable of carrying the maximum load. It is also important to consider the resetting of the relay. The relay will reset when the current is reduced to 90%95% of the setting, depending on the relay design. If the normal load current is higher than this value, the relay will not reset after operating under through fault conditions, which are cleared by other switchgear.
Fig. 1 Over current inverse time relay curves associated with two breakers on the same feeder
OMICRON electronics Asia Limited 2012 Asia-Pacific Protection & Testing Conference
Presentation 1.3
The procedures mentioned are appropriate if it is assumed that the relays have their characteristic curves scaled in seconds. For relays where the time adjustment is given as a percentage of the operating curve for one second, the time multiplier setting can be determined from the fastest multiplier applied to the curve for time multiplier l. Modern relays the time settings are from 0.1s and in steps of 0.05s.
X 11P5
10P5 X
X 9P5
CB4
OMICRON electronics Asia Limited 2012 Asia-Pacific Protection & Testing Conference
Presentation 1.4
OMICRON electronics Asia Limited 2012 Asia-Pacific Protection & Testing Conference
Presentation 1.5
side of the third level substation (i.e. CB3) will have the ROT of -0.138s for the circuit breaker which is not possible. When the grading margin was set at 0.2s, there was no relay in the system that has the ROT of less than 0s. All LV outgoing feeders have some margins to coordinate with its respective first leg substation. Therefore, the grading margin of 0.2s is the optimum grading for five radial substations in Kuala Lumpur distribution network.
OMICRON electronics Asia Limited 2012 Asia-Pacific Protection & Testing Conference
Presentation 1.6
simulated because of its low current magnitude, whereas over current can be up to few thousand fault current. A 300A earth fault current is selected instead than the nominal earth fault current of 1600A due to the hardware limitation to create a fault current larger than 800A. A 600A earth fault current has been tested, which is tenth time of the earth fault pickup current. This shows that this testing does not depend on the magnitude of the fault current. The equipment used for the testing is OMICRON CMC secondary injection and OMICRON CPC primary injection. OMICRON CMC test set initiated a fault current injection and capture relay and circuit breaker activities. The sampling rate for OMICRON CMC is 10 kHz. Two samples of switchgears have been tested, which was manufactured and installed in year 2010 (PPU A), and the other switchgear was manufactured and installed in year 1998 (PPU B). Both switchgears were made by the same manufacturer, Tamco. This is to ensure that the wear and tear of the old circuit breaker does not affect its timing operation. In this testing, the incoming and outgoing circuit breakers were initially given a 0.4s margin. The margin is then decreased until both circuit breakers trip simultaneously, which confirm the minimum required margin.
Control signal
Incomin g
CPC
CMC
OCEF relay
Outgoin g
OMICRON electronics Asia Limited 2012 Asia-Pacific Protection & Testing Conference
Presentation 1.7
Incoming Incoming Earth fault setting: 300/5A, 5P20 PSM = 20% (60A) TMS = 0.280 ROT = 1.198s Curve = IDMT (IEC) Outgoing Earth fault setting: 300/5A, 5P20 PSM = 20% (60A) TMS = 0.187 ROT = 0.798s Curve = IDMT (IEC) Outgoing
OCEF relay OCEF relay
Fig. 8. Relay setting for the site testing purpose, with grading margin of 0.4s
Conclusion
An analysis of over current and earth fault relay in Kuala Lumpur distribution network with a maximum of five radial substations in series has been performed. Satisfactory results between simulation results and site testing have been obtained. From the simulation and testing conducted, the standard grading margin of 0.4s can be reduced to 0.2s to cater for a maximum of five substations in series.
OMICRON electronics Asia Limited 2012 Asia-Pacific Protection & Testing Conference
Presentation 1.8
References
[1] C37.010-1999, IEEE Application Guide for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis, 1999. Davies, T., Protection of Industrial Power Systems, Second Edition, Newnes, 1996 International Standard IEC 60909: Shortcircuit currents in three-phase A.C. systems, 2001. Massimo Mitolo, Ph.D., Chu & Gassman Consulting Engineers, Short-Circuit Calculation Methods, Electrical Construction & Maintenance (EC&M) Magazine, October 2004. International Standard IEC 60255151:Measuring relays and protection equipment Part 151: Functional requirements for over/under current protection, 2009 Whiting, J.P., Lidgate, D., Computer prediction of IDMT relay setting and performance for interconnected power system, IEE Proc, Vol. 130, Pt C, No.3, May 1983 TNBD Maintenance Standards, TNB Distribution Division Maintenance Manual: Switchgear 2007, Revision: Section 11.5.14, 30th July 2007
World Best Paper Award in the Conference on the Application of Fault and Disturbance Recorders in 1999 and also won the Outstanding Engineer 2008 Award of the IEEE PES Malaysian Chapter.
[2] [3]
[4]
[5]
[6]
[7]
OMICRON electronics Asia Limited 2012 Asia-Pacific Protection & Testing Conference