Standard Engine(CCEC Cummins NTA855-G1A) Radiator 40 max, fans are driven by belt, with safety guard 24V charge alternator Alternator(STAMFORD HCI444ES), single bearing alternator, Protection Class IP22, insulation class H/H Dry Type air filter, fuel filter, oil filter, pre-filter, absorber Main line circuit breaker Standard control panel Two12V batteries, rack and cable Ripple flex exhaust pipe, Exhaust siphon, flange, muffler Operation manual
Features
Ratings Standby Amps 413 431 451 477 Standby Ratings (KW/KVA) 275/344 275/344 275/344 275/344 Prime Ratings (KW/KVA) 250/313 250/313 250/313 250/313
Voltage
Frequency
Phase
60 60 60 60
3 3 3 3
Prime Power(PRP):Prime power is available for an unlimited number of annual hours in variable load application, in accordance with GB/T2820-97(eqvlSO8528);A10%voerload capability is available for a period of 1 hour within a 12-hour period of operation. Standby Power Rating (ESP):The standby power rating is applicable for supplying emergency Copyright By GB POWER
1/4
Dimension Of Dimension(L*W*H)/CM For Open Type Net Weight/KG For Open Type
Dimension(L*W*H)/CM For Sound Proof Type Net Weight/KG For Sound Proof Type
Dimension (L*W*H)/MM For Trailer Type Net Weight/KG For Trailer Type
Specification Of Engine Model Manufacturer Prime Power Standby Power Engine Configuration Gas Feeding Model BoreStroke Displacement Engine Rated Speed Speed Governor Starter Model Fuel Consumption Standby Power (100% load) Fuel Consumption Power (75% load) Oil Consumption Cooling System Compression Ratio Max Back Pressure Max Intake Restriction Exhaust Temperature Prime
Engine
NTA855-G1 CCEC Cummins 288KW/386HP 317KW/425HP 6Cylinder In Line, 4Stroke Turbocharged 140152(MM) 14L 1800RPM Electronic 24V DC Start 219 g/Kw.h 221 g/Kw.h 4 g/kw.h Water Cool 14.5:1 10KPA 6.25KPA 543
Copyright By GB POWER
2/4
Specification Of Alternator Model Manufacturer Prime Output Standby Output Excitation Model Cooling Method Connection Type Power Factor Protection Class Insulation Class Altitude Voltage Regulation, Steady State Alternator Telephone Influence Factor Sudden Voltage Warp (100% Sudden Reduce) Sudden Voltage Warp (Sudden Increase) Voltage Stable Time (100% Sudden Reduce) Voltage Stable Time (Sudden Increase) Frequency Reduce Frequency Regulation, Stead State Frequency Waving Sudden Frequency Warp (100% Sudden Reduce) Sudden Frequency Warp (100% Sudden Increase) Frequency Recovery Time (100% Sudden Reduce) Frequency Recovery Time (Sudden Increase) Compliance
Alternator HCI444ES STAMFORD company 260KW/325KVA 286KW/357.5KVA Brushless, Self-Exciting Air Cooling 3 Phase and 12 Wires 0.8 IP22 H 1000m 1% 50 1% 25% 6S 6S 0-5% adjustable 1.5% 0.8% +12% -10% 5S 5S Star Connection