You are on page 1of 12

Introducing Failures- Transformers Do Fail

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

FAILURE ANALYSIS FOR POWER TRANSFORMERS


Presentation P 6 Doble 2005 Regional seminars
Doble 2005 regional seminar
2

Transformer failures

Doble 2005 regional Seminar

Introducing Failures There are three categories of Transformer Failure 1. Unexpected ones leading to Forced outage 2. Managed failures in a Scheduled outage 3. Removals at end of useful life- rare for
transformers- more for switchgear

Transformer failures

Doble 2005 regional Seminar

Transformer failures

Doble 2005 regional Seminar

Introducing Failures But there are several definitions and no consensus of Failure across plant groups 1. Failure to perform ie a trip, causing an outage but only minor and easily re-instated- more
typical for switchgear

Introducing Failures

WE MUST LEARN
How to avoid unexpected failures
By understanding failure history By linking failures to some indicator By using the indicators to detect potential problems Condition assessment By tracking a worsening condition= asset health review Removing the Transformer just prior to failure = effective asset management =

2. End of useful life failures leading to removal, from plinth for repair at works or scrap

Transformer failures

Doble 2005 regional Seminar

Transformer failures

Doble 2005 regional Seminar

Failure costs

This Presentation

Cost of losses Maintenance cost index Third party costs at failure Cost of constraints Cost of clean-up Cost of secondary damage Cost of replacement Current net worth Bushings and Tap changers

1. Introduction to Failure
2. Asset Life Concepts- what causes physical failure 3. Defining Failure Modes 4. Understand your design groups and their failure modes 5. Distribution and generation/ transmission units 6. Leading to other presentations: -Defining the indicators of those modes -Ranking of your fleet -Managing the risk
8

Transformer failures

Doble 2005 regional Seminar

Transformer failures

Doble 2005 regional Seminar

2 The technical Asset life At specification stage Most utilities expect 35-40 years for static plant, although generator transformers were given 25y in UK in 1960s. Experience Now Some transformer design groups, in some applications will last 50-80 years.

2 - Failure rate with age

Hazard Rate %
9

Transformer failures

Doble 2005 regional Seminar

10

Transformer failures

Doble 2005 regional Seminar

2 - Technical Life

2 - The Asset life assigned values When the 400 kV system was built most transformer experts thought their specs were wonderful and their transformers would fail at old age- when the winding paper fell apart. If a unit was held at rated maximum hot spot temperature IEC thought it would last 40y (test tube R&D) IEEE testing on models and distribution units indicated 19y life- but thought it should last 40y since rating not maintained.
12

When the condition of any integral part of the unit is beyond both acceptable risk for further service and economic refurbishment.

11

Transformer failures

Doble 2005 regional Seminar

Transformer failures

Doble 2005 regional Seminar

2 - The Asset life Realities Experience Now Most transformer failures are not old age mechanisms- except in some 3rd W areas Most failures are due to some limitation in specification/ application/ design/ manufacture/ care, ave age 16-19y. But in some applications some design groups will last 50-80 years.
13

2 - Failures Variety of modes and causes Design weaknesses Abnormal system conditions - trigger Aged condition / service loading Pre-existing faults Timescales
14

Transformer failures

Doble 2005 regional Seminar

Transformer failures

Doble 2005 regional Seminar

Failure Model

3 - Failure Modes
Reducing Strength with time and after incidents

Insulation Strength Insulation Spare Margin

Thermal Dielectric

Failure Insulation Stress Incidents

Mechanical
Old
16

New
15

Increasing Age

Transformer failures

Doble 2005 regional Seminar

Transformer failures

Doble 2005 regional Seminar

3 And Three types of Thermal Failure

3 Winding Thermal Failure

1. The so called long term Intrinsic Ageing of winding paper 2. But also early life failures from accelerated local ageing =Same process just different causes 3. Core bolt insulation/ leads/ connections

End of Life of the winding insulationis when the paper is too brittle to withstand mechanical and electrical stresses and shorted turns occur. Transformers are designed to operate under rated conditions of ambient temperatures and load for an acceptable life duration

17

Transformer failures

Doble 2005 regional Seminar

18

Transformer failures

Doble 2005 regional Seminar

3 - Rated temperatures IEEE C57.91-1995 The thermal rating is the steady state current that produces a temperature rise of 650 C under the following conditions. It is a normal test during factory acceptance- although not always done for every transformer. A starting oil temperature of 300 C A final top oil temperature of (30 + 65) = 950 C A presumed hottest spot conductor temperature of 95+ 15 = 1100 C
19

3 - Thermal Failure

Most assessments looking at time -at -temperature support the view that lives 60+ years are reasonable. But: Localised hot spots can lead to accelerated
ageing

Transformer failures

Doble 2005 regional Seminar

20

Transformer failures

Doble 2005 regional Seminar

3 - Thermal Failure- winding paper

Premature Ageing

Causes of Localised hot spots


Poor design of conductor sizing/ transpositions Joints defective Leakage flux heating due to poor stress shield/ shunts Blocked cooling ducts

21

Transformer failures

Doble 2005 regional Seminar

22

Transformer failures

Doble 2005 regional Seminar

Localised overheating

3 - Thermal Failure elsewhere

Causes of Localised hot spots


Joints defective Defective earth insulation leading to Circulating currents- frame or core and tank Eddy currents from Defective core bolt insulation

23

Transformer failures

Doble 2005 regional Seminar

24

Transformer failures

Doble 2005 regional Seminar

Core bolt insulation

Frame- Earth Fault Overheating Frame-

25

Transformer failures

Doble 2005 regional Seminar

26

Transformer failures

Doble 2005 regional Seminar

3 - Dielectric failures
A properly designed transformer should withstand normal and transient voltages Causes of dielectric failure

Inter Phase Barrier Board Failure

Incorrect stress distribution calculation and turn over-stresses with impulse ( a factory test) Inadequate phase to phase insulation,(winding or bushing to tank, tap changer clearance) Moisture leading to tracking in phase-to-phase barrier boards and flashover Bubble formation at overloading a wet unit Static electrification at high flow rates Debris from sludge and carbon due to degraded oil, paper fibres and metal from pumps Turn faults following mechanical and thermal ageing
Doble 2005 regional Seminar
28

27

Transformer failures

Transformer failures

Doble 2005 regional Seminar

3 - Inter-winding insulation

Note the insulation in the 2 previous slides


Inter phase boards

Interwinding wrap
29

Transformer failures

Doble 2005 regional Seminar

30

Transformer failures

Doble 2005 regional Seminar

Inter-turn failure

Sparking at clamping bolt


Not all arcing leads to a failure

31

Transformer failures

Doble 2005 regional Seminar

32

Transformer failures

Doble 2005 regional Seminar

3 - Mechanical Failure A Properly specified and designed unit should withstand system fault levels and frequency Causes of mechanical failure 1. Poor design tools used for older units 2. Design not proven by test or service 3. Clamping pressure deterioration 4. Fault levels higher and/ or frequency higher than specified

3 Mechanical Failure Ageing Effects As a transformer ages the insulation shrinks and clamping pressure is lost.-reduces strength. Any minor winding deformation usually results in electromagnetic imbalance increases stresses during subsequent faults.

33

Transformer failures

Doble 2005 regional Seminar

34

Transformer failures

Doble 2005 regional Seminar

3 - Mechanical Failure Service Issues The number and severity of short-circuit events suffered are important. Close-up short circuits are a common cause of winding movement failures. Tap-changer faults can cause tap winding failures. Faulty synchronisations can cause winding damage and failures.
35

3 - Mechanical Failure Detection Problems DGA will only indicate a problem when the insulation has been damaged ( usually too late to repair ). Internal visual inspections often inconclusive Winding failures can usually be diagnosed by various electrical tests ( but not always ). But interim damage is much harder to detect. Your transformer may be critically damaged without you being aware of it !
36

Transformer failures

Doble 2005 regional Seminar

Transformer failures

Doble 2005 regional Seminar

3 - Mechanical Failure Modes Hoop buckling of inner winding Conductor tipping Conductor telescoping Coil clamping failure End insulation collapse Spiral tightening Lead displacement

Buckled windings

Capacitance detected movement and deformation of transformer windings.

37

Transformer failures

Doble 2005 regional Seminar

38

Transformer failures

Doble 2005 regional Seminar

Twisted Winding- not much seen externally

3 - Mechanical Failure Winding damage seen now

39

Transformer failures

Doble 2005 regional Seminar

40

Transformer failures

Doble 2005 regional Seminar

3 - Mechanical Failure -Core Frame

Part 4

Understanding your design families

41

Transformer failures

Doble 2005 regional Seminar

42

Transformer failures

Doble 2005 regional Seminar

Understanding your design families Your company data National Associations, eg CEA, EA Collaborative Groups, eg Doble International surveys, eg CIGRE

Understanding your design families

Two questions 1. What are the failure rates for your design groups? 2. What aspects cause troubles and failures for each family

43

Transformer failures

Doble 2005 regional Seminar

44

Transformer failures

Doble 2005 regional Seminar

4 - Hazard Rates Where mathematical techniques have been applied to failure and population statistics identify future hazardrates and modes. Examples are shown for two design families of transformer, A & B in the next two slides.

4- Company A- Two design families

45

Transformer failures

Doble 2005 regional Seminar

46

Transformer failures

Doble 2005 regional Seminar

4 - Failure Probability density function

4 - Company A - Hazard Rates Type B has a high random failure rate and a very ill defined end of life for this poor design family. Type A has a very low failure rate until true ageing effects begin after 30+ years, so allowing effective asset life planning.

47

Transformer failures

Doble 2005 regional Seminar

48

Transformer failures

Doble 2005 regional Seminar

Understanding your design families

THE SUMMARIES OF ASK DOBLE

Company X had plenty of data of its own Company Y didnt, and so they filed a question on the Ask Doble forum about failures of one type of design. They got 10 replies and a data set from someone who did have data- company X.

49

Transformer failures

Doble 2005 regional Seminar

50

Transformer failures

Doble 2005 regional Seminar

Substation Distribution Transformer Failure Rate

Understanding your design families

Distribution Transformer Failure Rates


1 9 98

1
Failure Rate

.90 .88 .84 .75

1 9 99
.71

0.8 0.6 0.4 0.2


1998 1999 1998 1999 2000 2001 2002

2 0 00 2 0 01 2 0 02

The best international survey is that by Cigre done in the 1970s and published in 1983 But that was a long time ago

.24 .24

. 2 2 . 2 0 . 18

. 18

. 18

. 16 . 14

. 12 .023 .022 . 0 19 . 0 2 2 .020

2000

2001

2002

1998

1999

2000

2001

2002

1998

1999

2000

2001

3ph

w/ o FP E X

FP E only X

1ph

0.13 = Industry Avg.

51

Transformer failures

2002

Doble 2005 regional Seminar

52

Transformer failures

Doble 2005 regional Seminar

Dobles Trouble and Failure Reporting System


Features Web-Based Access Who has access to the reports Simplified Data-entry Form Pick Lists for Standardized Info Monthly Reports Containing Anonymous Details Reports are clearly understandable Partnering With Other Organizations = more involvement, more entries = more knowledge for you!

Dobles Trouble and Failure Reporting System

53

Transformer failures

Doble 2005 regional Seminar

54

Transformer failures

Doble 2005 regional Seminar

Fault & Defects for Transformers


CIGRE Substation WINDINGS CORE TANK& OIL TAP CHANGER BUSHINGS OTHER
Period Number of failures

Visual Inspection at tear down


DOBLE
ONE

DOBLE
ALL DESIGN

19% 3 13 41 12 12
1968-78 1000

43% 4 8 16 19 10
1993-8 1500

47% 7 12 8 8
1980-2000 100

55

Transformer failures

Doble 2005 regional Seminar

56

Transformer failures

Doble 2005 regional Seminar

Understanding your design families

Fault and defects - LTCs


1993-98 analysis of 300 failures Opinions of two experts

Simple stats can confuse

CONTACTS MECHANISM INSULATION LEADS REACTOR OTHER

44% 18% 12% 7% 4% 15%

80% 20%

25% 75%

57

Transformer failures

Doble 2005 regional Seminar

58

Transformer failures

Doble 2005 regional Seminar

Understanding your design families


Distribution of Power Transformer Failures Per Year of Manufacture 9 8 7 6
Percentage

Understanding your design families


Failures Versus Age, Adjusted for Quantities in the Database Manufactured in the Year.
6

% of Failures
5

Percentage

5 4 3 2 1 0

4 3 2 1

All Major

10

12

14

16

18

20

22

24

26

28

30

32

34

36

38

YEAR
59

AGE
60

Transformer failures

Doble 2005 regional Seminar

Transformer failures

Doble 2005 regional Seminar

40

1910

1920

1930

1940

1950

1960

1970

1980

1990

2000

2010

10

5 What about Distribution units?

What is the age of Distribution Units in USA?


Ave age oldest 47y 53y 77y 60-70y (25% >50y) 65-70y (5 units) 51y 77y 62y 34% >40y 77y 45-50y replace on failure
Doble 2005 regional Seminar

Comment

69kV and Below

30y 29y 36y 42y 30y 23y 36y 32y 35y 38y 30y

replace on failure ave age at fail= 14y Evaluation prog replace on failure replace on failure replace on failure replace on failure Health index

61

Transformer failures

Doble 2005 regional Seminar

62

Transformer failures

Where is the site of the fault?


CIGRE Substation WINDINGS CORE TANK& OIL LTC BUSHINGS OTHER UNKNOWN Period Number of failures
63

Distribution Transformers
DOBLE ALL 43% 4 8 16 19 10 DOBLE 69 kV 47% 6 3 11 3 4 28

Email forum and Doble data indicatesThere are a lot of old units out there working well at 40+ years Failures tend to be at 15-20y and main initiating causes are lightning and through faults But are failure rates higher?

19% 3 13 41 12 12

1968-78 1000

1993-8 1500
Doble 2005 regional Seminar

1955-85 955
64

Transformer failures

Transformer failures

Doble 2005 regional Seminar

Causes of thru-faults
-

Thermal Overload

65

Transformer failures

Doble 2005 regional Seminar

66

Transformer failures

Doble 2005 regional Seminar

11

Distribution Transformers 2003 Doble conference paper- Prout & Wilson Have more but lower intensity through faults More tolerant to poorer dielectric Have poorer preservation systems Flush bushing flanges can allow water ingress Failure of fans/ gauges more consequential Fewer LTCs below 69 kV/ NLTCs reliable Old fleet well designed >1970s units more unreliable
67

Moving forward

Looking at Failures is all very interesting but we need to move forward

1. Assess the Risk 2. Create a failure tree 3. Link an assessment program to tree

Transformer failures

Doble 2005 regional Seminar

68

Transformer failures

Doble 2005 regional Seminar

12

You might also like