Technical Clarifications BHEP/V-0230/HIP/SR-PM/TN/0070 dated 27.06.2012 BHEP/V-0230/HIP/SR-PM/TN/0076 dated 21.07.2012 M/s KARNATAKA POWER CORPORATION LIMITED Customer ref. BHADRA Project Code VAssembly 0230 Customer Observation
Date
05.08.2012
Sheet No. 1 of 6
LOT/BHADRA/RBU/R&M/1112 D&D Drawing No. E4 V-0230 511/512 Panels 01/02 Andritz Hydro Clarification
S No.
b)
Technical Clarifications BHEP/V-0230/HIP/SR-PM/TN/0070 dated 27.06.2012 BHEP/V-0230/HIP/SR-PM/TN/0076 dated 21.07.2012 M/s KARNATAKA POWER CORPORATION LIMITED Customer ref. BHADRA Project Code VAssembly 0230
Date
05.08.2012
Sheet No. 2 of 6
As per working of Timers, the timer contacts NO & NC shown in Rev-0 may please be retained. c)
d)
Technical Clarifications BHEP/V-0230/HIP/SR-PM/TN/0070 dated 27.06.2012 BHEP/V-0230/HIP/SR-PM/TN/0076 dated 21.07.2012 M/s KARNATAKA POWER CORPORATION LIMITED Customer ref. BHADRA Project Code VAssembly 0230
Date
05.08.2012
Sheet No. 3 of 6
S No.
Customer Observation The current rating of 3 pole power contactors provided is equal to the rated current of the corresponding motors. The power contactors of higher current rating considering 10% overload 5% tolerance shall be provided. At present, 2 Nos. of recently commissioned 50HP submersible pumps installed at power house are carrying/taking continuous load current of 85Amps. As per the manufacturer specifications, the rated full load current is 82Amps at 415Volts and 0.85 PF. Hence ratings of all the Power Contactors (Star-Delta) for all the Motors/submersible Pumps may be changed to 100Amps in order to have standardization and stock of minimum spares. Sht. No. 3: In the legend, description for V, A, VSS, ACK PB & ASS may be indicated Sht. No. 5: Refer grid reference A5, under the heading WIRING- Internal wiring will be done by Ring type and Pin type lugs shall be replaced by Internal wiring will be done by Ring type and Flat type lugs. Sht. No. 6: 1) The ammeter & voltmeter shall be provided with communication facilities/transducer 2) Ammeter shall be provided for each pump.
c)
d) e)
Agreed. Revised documents shall be provided to you. Agreed. Revised documents shall be provided to you.
f)
1) According to contract, no communication facilities will be provided. 2) Agreed. Single phase current measurement provision will be provided. We have already provided two protections. One MCCB in main incomer and MPCB for individual motors, so there is no need of HRC fuses.
g)
Sht. No. 8: HRC fuses for backup protection shall be provided for all pumps.
Technical Clarifications BHEP/V-0230/HIP/SR-PM/TN/0070 dated 27.06.2012 BHEP/V-0230/HIP/SR-PM/TN/0076 dated 21.07.2012 M/s KARNATAKA POWER CORPORATION LIMITED Customer ref. BHADRA Project Code VAssembly 0230
Date
05.08.2012
Sheet No. 4 of 6
LOT/BHADRA/RBU/R&M/1112 D&D Drawing No. E4 V-0230 511/512 Panels 01/02 1) Kindly clarify, In manual mode how many pumps will be ON at a time. If only one pump will be ON then Kaycee / Vaishno make 4 position with OFF switch will be provided. For more than one pump, no switch will be provided. 2) We will provide Star/Delta timer of EAPL make. Model : A1DS Contact Detail: 2NO 15,18 & 25,28 3) As per the working of timer, this contact will be NO only. 4) Agreed. Revised documents shall be provided to you. 1) We will provide Star/Delta timer of EAPL make. Model : A1DS Contact Detail: 2NO 15,18 & 25,28 2) As per the working of timer, this contact will be NO only. 3) Agreed. Revised documents shall be provided to you. Stud type Elmex make TBs For 6 to 35 sq. mm cable CBT M6S1 For 2.5 to 6 sq. mm cable CAT M4
Sht. No. 13, 14: 1) Details of Pump selection switch (SW1) shall be provided.
h)
2) Details of Timers - T1 & T2 shall be provided. 3) At grid reference G3, it is observed that the NO contact of timer is to be replaced by NC contact. The same may be reviewed and implemented. 4) At grid reference G5, it is observed that the NC contact of timer is to be replaced by NO contact. The same may be reviewed and implemented
i)
Sht. No. 15, 16: 1) Details of Timers- T3 & T4 shall be provided. 2) At grid reference G3, it is observed that the NO contact of timer is to be replaced by NC contact. The same may be reviewed and implemented. 3) At grid reference G5, it is observed that the NC contact of timer is to be replaced by NO contact. The same may be reviewed and implemented.
j)
Sht. No. 20: 1) TBs provided for AC circuits shall be matched for the cable sizes of the respective motors. Details of TBs provided shall be furnished.
Technical Clarifications BHEP/V-0230/HIP/SR-PM/TN/0070 dated 27.06.2012 BHEP/V-0230/HIP/SR-PM/TN/0076 dated 21.07.2012 M/s KARNATAKA POWER CORPORATION LIMITED Customer ref. BHADRA Project Code VAssembly 0230
Date
05.08.2012
Sheet No. 5 of 6
S No
Customer Observation
b)
Technical Clarifications BHEP/V-0230/HIP/SR-PM/TN/0070 dated 27.06.2012 BHEP/V-0230/HIP/SR-PM/TN/0076 dated 21.07.2012 M/s KARNATAKA POWER CORPORATION LIMITED Customer ref. BHADRA Project Code VAssembly 0230
Date
05.08.2012
Sheet No. 6 of 6
LOT/BHADRA/RBU/R&M/1112 D&D Drawing No. E4 V-0230 511/512 Panels 01/02 1) Provision has already been provided in the panel. Wiring from cubicle to control room is in customer scope.
d)
Sht. No. 9 & 10: 1) Alarm and indications for the maximum water Level may also be provided at Control Room.