CHAPTER 17

LIGHTNING PROTECTION OF DISTRIBUTION CABLE SYSTEMS


William A. Thue
1.

INTRODUCTION

Distribution cable systems have peak failure rates during the summer months throughout North America. Research work has shown that impulse surges to cables shortens their service life [17-11. It is also well documented that water trees reduce the i p l e level of extruded dielectric insulated cables. mus

M s of the effort that has been spent in the past on lightning protection of ot distribution system components has been on overhead transformers. This is
logical when you consider that the companies that build trandormers are also the ones that sell arresters. The older paper insulated cables were manufactured with an inherently high impulse level and that level was maintained Over the 40 @us years of life of the system. Today, the extruded dielectric insulated cables that are used so extensively in underground systems, exhibit a dramatic drop in electrical strength in just a few months of service. It is important to note that crosslinked polyethylene (XLPE) cables start with a much higher impulse level than ethylene propylene (EPR) or paper cables. EPR cables have initial impulse strengths less than the others, but their impulse level doesnt drop as quickly and levels out. With time, both XLPE and EPR have impulse levels that are much nearer the basic i p l e level (BIL) of the system than for paper cables. mus Because of this, lightning protection is a significant consideration for these newer cables.
2.

SURGE PROTECTION TERMINOLOGY

2.1 ProtectiveMargin

This is defined as being:

Insulation Withstand Level Arrester Protection Level

100

Copyright 1999 by Marcel Dekker, Inc.

245

Another form of this equation for protective margin is: Equipment BIL in kV Arrester Dischaige Voltage in kV + Discharge Voltage of Arrester Leads in kV

-j

x100

A minimum protection margin of 20% over BIL has usually been recommended for transformers.

2.2

Voltage Rating

Voltage rating of an MOV arrester is based on its duty-cycle test. The duty-cycle test defines the maximum permissible voltage that can be applied to an arrester and allow it to discharge its rated current. Another way to consider this is that it is the voltage level at which power follow current can be interrupted after a surge discharge has taken place. At voltage levels above this, power follow current interruption is doubtful. The safe arrester rating is usually determined by the highest power voltage that can appear from line to ground during unbalanced faults and shifting of the system ground.
2.3 Highest Power Voltage

The highest power voltage can be calculated by multiplying the maximum system line-to-line voltage by the coefficient of grounding at the point of arrester placement.
2.4 Coefficient of Grounding

This is defined as the ratio, expressed in percent, of the highest rms line-toground voltage on an unfaulted phase during a fault to ground. Systems have historically been referred to as being effectively grounded when the coefficient of grounding does not exceed 80%.
2.5. Sparkover

This refers to the initiation of the protective cycle that occurs when the surge voltage reaches the level at which an arc develops across the devices electrodes to complete the discharge circuit to ground. In terms of voltage across gapped arresters, this is somewhat indefinite since sparkover of a simple gap structure is a function of both the wave front and the voltage of the incoming surge.
The essential requirement of a proper sparkover level is the speed of response to steep fronts such as natural lightning yet give a consistent response to waves
Copyright 1999 by Marcel Dekker, Inc.

246

wt slower rates of rise which are typical of indirect strokes and system ih
generated surges. Sparkover of an arrester should not be confused with flashover. Flashover refers to the exterior arcing which can occur, for instance, when surfaces become contaminated.
2.6

Surge Discharge

Surge discharge refers to the situation where the arrester must handle t e power h frequency line current as well as the momentary surge current. This power follow current continues to flow until the arrester can extinguish the arc.
2.7

IR Dischaqe Voltage

The IR discharge voltage of an arrester is the product of the discharge current and the resistance or inductance of the discharge path. While the resistance may be very low, the discharge current can be very high and the R discharge voltage can reach levels that equal or exceed the arrester sparkover voltage. The inductance of the combined line and ground leads must be kept as short as possible. This is accomplishedby placing the arrester as close as practical to the cable termination and always connecting the arrester closer to the incoming line than the termination. See Fig. 17-5.
3.

WAVE SHAPE AND RATE OF RISE

Natural lightning must be simulated in the laboratory to test and evaluate lightmg protection devices and equipment. This is accomplished with a surge generator. A group of capacitors, spark gaps and resistors are connected $0 that the capacitors are charged in parallel from a relatively low voltage source and then discharged in a series arrangement though the device being tested. The terms used to describe both natural and artificial lightning are wave shape and rise time. The wave crest is the maximum value of voltage reached. Wave shape is expressed as a combination of the time &om zero to crest value for the front of the wave and the time from zero to one-half crest of the wave tail. Both values of time are expressed in microseconds. T e rate of rise is determined by h the slope of a line drawn through points of 10 and 90 percent of crest value. Testing of surge arresters has historically been done with an 8 x 20 microsecond wave, but more recent work has been done at 4 x 10 even though a direct stroke of natural lightning is more nearly 1 x 1000. See Figure 17-1 to see how these times are defined.

Copyright 1999 by Marcel Dekker, Inc.

247

Figure 17-1 Wave Sbape

20

Time to 112 Crest


Time to 112 Crest

Time to Crest

Figure 17-2 Rate of Rise

Time i Microseconds n
. I

4.

OPERATION OF A SURGE ARRESTER

4.1 AirGaps

The original surge arrester was a simple air gap. They were made of a simple rod or spheres installed between line and ground that were far enough apart to keep the line voltage from sparking over but close enough to discharge when a surge occurred. Air gaps have the disadvantage of allowing system short circuit current to continue to flow until the breaker, fuse or other backup device operates.
Air gaps have another disadvantage. Electrically spedung they are sluggish and their response varies as stated above. Sparkover may not occur until a considerable portion of a rapidly rising lightning surge has been impressed on the system. The short gap spacing necessary to pro\ide adequate protection against steep front lightning waves may result in frequent and unnecessary sparkovers on minor power frequency disturbances.

Copyright 1999 by Marcel Dekker, Inc.

248

Non-linear resistance can best be considered as resistance that varies inversely with applied voltage. Under normal voltage conditione, the resistance is high; under unusual voltages the resistance is low. Non-Linear Resistance

Resistam

[.

AppWVoltage

The material that, in the past, has been used so extensively in valve arresters is silicon carbide. It is blended with a ceramic binder, pressed into blocks under high pressure and fired in kilns at temperatures of over 2000 OF. This component is the valve block. The number of valve blocks used in an arrester is determined resistance requirement for the rating of the system.

For silicone carbide blocks, it is essential that an air gap be in series with the blocks. This gap must ionize the atmosphere in the arc chamber to break down that gap before the blocks encounter any voltage. After the air gap breaks down, the valve blocks begin to conduct the combination of surge current and power current. The high voltage of the lightning surge decreases the resistance of the valve blocks and the current flows to ground. The voltage now across the blocks is approximately the line-to-ground voltage of the system. The valve blocks hs revert to their normal high resistance. T i forces the power flow current to be reduced to a value that the series blocks can interrupt at the next system current
ZW.

Copyright 1999 by Marcel Dekker, Inc.

249

Figure 17-4 Schematic of a Silicone Carbide Arrester

Air Gap

Valve Block

Ground

4.3 Metal Oxide Arresters

Commonly known as MOVs, metal oxide varistors, became available for distribution systems in about 1978. Their first use on distribution systems were on terminal poles, hence the riser pole arrester term. Gaps are not required because the material is extremely non-linear. The lower half of the schematic shown in Figure 17-4 represents a MOV arrester. A voltage increase of just Over 50% results in a conduction current change of 1 to 100,000. The absence of gaps allows these devices to operate much faster than the older gapped silicone carbide arresters. The absence of gaps is a major factor in allowing MOVs to be used in load break elbow arresters. Grounding resistance / impedance must be treated more seriously now that the URD systems are using conduit and/or jacketed neutral wires. With bare neutral wires, the stroke energy was dissipated along the cable run. The insulation provided by the jacket or conduit makes low resistance grounds at the terminals an essential factor.
5.

NATURAL LIGHTNING STROKES

The understanding of natural lightning has increased tremendously since the early 1980s. EPRI efforts led to the construction of antennas throughout the United States to record lightning strokes. These systems are now capable of pinpointing the time, location, magnitude, and polarity of strokes that occu between clouds and ground. What has been determined is that the rate of rise and the current magnitudes of natural lightning is much more severe than previously assumed. From this information, we now have recorded strokes of over 500,000 amperes.
Copyright 1999 by Marcel Dekker, Inc.

250

Although these high stroke currents do occur,examination of arresters removed f o service do not show that they have discharged such high values of current. rm One possible explanation is the division of stroke currents into multiple paths. Another is that the majority of strokes terminate to buildings, trees, or the ground without directly striking the electrical system. Recent research indicates that indirect strokes may be the biggest cause of failures on todays distribution systetns. Rate of rise is extremely important because the faster the rate, the higher the discharge voltage will be for all types of arresters. Recorded data shows that natural lightning strokes have rise times between 0.1 and 30 ps with 17% of the recorded strokes having rise times of 1 ps or faster and 50% are less than 2.5 p. For the same wave shape, the average rate of rise increases with the crest magnitude. Using the standard 8 x 20 microsecond wave and a 9 kV gapped arrester, the discharge voltage is about 40 kV. For the same 20 kA stroke but rising to crest in one microsecond, the arrester would have a 54.4 kV discharge, or a 36% increase. Metal oxide arresters (without gaps, of course) commonly exhibit a 12 to 29% increase under similar circumstances. The inductance (hence length and shape) of the arrester leads becomes more pronounced with the faster rate of rise. Applying the generally used value of 0.4 microhenries per foot, the lead voltage is 8 kV per foot of total lead length at 20 kA per microsecond and 16 kV per foot at 4 kA. Assuming n w arresters and 0 e two feet of total lead length, the total voltage at 20 kA and 40 kA would be 70 and 96 kV respectively. Saying this in a different way, a stroke having a 40 kA per microsecond rate of rise would add 32 kV to the arrester discharge voltage given in a typical manufacturersliterature. Prudent engineering suggests that the level of protection should be calculated for a family of possible values of current and rates of rise for the anticipated lightning activity in the service area under study. This suggests currents such as 40 kA for parts of centrd Florida but only 10 kA or lower for California.Rates of rise of 1 to 3 microseconds are commonly used in calculations. For an interesting note, these systems are of use to many organizations. Lightning stroke information is used by the forest service to warn of fires. Antennas near Anchorage, Alaska, warn of volcano eruptions that produce lightning.
6.

TRAVELING WAVE PHENOMENA

Whenever a lightning stroke encounters an electric system, energy is propagated along the circuit from the point of origin in the form of a traveling wave. The
25 1

Copyright 1999 by Marcel Dekker, Inc.

current in the wave is equal to the voltage divided by the surge impedance of the circuit. Surge impedance is approximately equal to the square root of the ratio of the self inductance to the capacitance to ground of the circuit. Both the inductance and capacitance are values pcr given unit length making the surge impedance of a circuit independent of the actual length of the circuit.
A !ravelingwave will keep moving without change in a circuit of uniform surge impedance except for the effects of attenuation. As soon as the wave reaches a point of change in impedance, reflections occur.

A wave reaching an open circuit is reflected without change in shape or polarity. The resultant voltage at the open end will be the vector sum of the incident wave and the reflected wave. This is the source of the voltage doubling circumstance. If an arrester is located at the open point, this doubling does not occur after the arrester befins to discharge.

When a wave arrives at a ground or other value of impedance that is lower than the surge impedance of the circuit, the incident wave is reflected without change in shape but with a reversal in polarity.
No reflections will occur on a circuit that is connected to ground through a resistance / impedance that is equal to the surge impedance of the circuit since there is no change in impedance.

hn It is convenient to t i k of traveling waves as having square shapes to illustrate the points just mentioned, but since real surges have a finite time to crest, the results of the superposition of the actual wave shapes are quite Merent than the square waves, which are the worst case scenario.
7.

VELOCITY OF PROPAGATION

For practical purposes, a traveling wave on an overhead line travels at the speed of light -- 984 feet per microsecond. The velocity of propagation of a traveling wave in cables commonly used today is about half the speed of light, or 500 to 600 feet per microsecond. This can be derived from the fact that, in an insulated and shielded cable, the speed is reduced depending on the specific inductive capacity, or permativity, of the insulating material.
Y = l / p
=

984ftperpsec.

(17.1)

This calculates out to 659 ft/psec for TR-XLPE and 577 Wpsec for an EPR.

Velocity of propagation becomes important to the protection of distribution cables because the travel time from the junction arrester to the end of the cable
252

Copyright 1999 by Marcel Dekker, Inc.

run is very short as compared to the conduction time of the arrester. Consider a typical 5,000 foot long loop that is open at the midpoint. At 500 feet per microsecond, the travel time to the end is only 5 microsecondsto the end and 10 microseconds for the round trip. The arrester conduction time for an 8 x 20 microsecond wave is about 50 microseconds. This means that the junction arrester still has 90% of its conduction time left when the wave has traveled to the end of the cable. If the end does not have an arrester, the reflected wave will travel back towards the junction point and add to the incoming voltage wave throughout the length of the cable. Thus the entire cable is exposed to the "doubled" wave. The amount of time the incoming wave is maintained becomes an important considerationas to the exposure of the cable to this full doubling of voltage.
Attenuation has a negligible effect on the reflected voltage because the low loss insulations that are in use today do not attenuate the wave appreciably in the relatively short runs used for distribution systems.
8.

PROPER CONNECTION OF ARRESTERS

There are several extremely important installation rules for arresters:

0 Keep both the line and ground side leads as short and straight as possible. (It is the sum of the two lead lengths that must be used in the calculations). 0 The lead from the line should go to the arrester FIRST to the termination.

-- then

0 The ground resistance should be as low as practical. This means ten ohms if the cable has an insulatingjacket or is in a conduit.
8.1 Lead Lengths

The issue of lead length on the voltage that will be impressed on a cable has been discussed earlier in this chapter. All of that is correct. There is, however, one more issue here. Does that lead cany the lightning current? If the lightning current flows in that lead, its length is a factor. If, on the other hand, the lead does not carry lightning current its length and impedance are not factors. In the real world, the current generally flows through all the paths that are available. The amount of current times the length of each lead establishes the voltage that is impressed on the cable. The practical point is that the circuit must be analyzed in its entirety.

Copyright 1999 by Marcel Dekker, Inc.

253

8.2 Route of Current Flow

In the beginning of this section, it was stated that the lead from the incoming line should first be attached to the arrester -- then to the termination. Wait a minute. This isnt the way we have always done it! Are you certain of that? Yes. If we can visualize the flow of lightning current as a flood of water, we can easily recognize that we would be much better off if we could divert that flood around our house - not through it. That is why the arrester is the first connection point. The bulk of the current flows through the arrester and through its ground. The termination lead length is not very significant because it isnt carrying that much current.
8.3 Ground Resistance / Impedance

Why is the ground resistance / impedance important? We are concerned about voltage and voltage is the product of current and impedance (length). Almost all of the current that goes through the arrester m s flow to ground at the arrester ut location. Remember that the impedance of an overhead line (the neutral for our purposes) is about 50 to 60 ohms. If the ground at the arrester is very high, then all of that lightning current must flow along those neutrals. That means that the footing resistance is 60 ohms. The voltage that is developed is the current multiplied by 60 ohms. Even if there are t o directions for the ground current to w flow, this can be a very high voltage. The voltage build-up through the arrester is increased by the voltage build-up in the ground circuit.

Copyright 1999 by Marcel Dekker, Inc.

254

Figure 17-5 Correct Arrcstcr Connection Diagram

9.

REFERENCES

[ 17- 11. L'nakrground Distribution System &sign and Imdlafion Guide, NRECA 1993. Section 5.

[ 17-21. "Effect of Voltage Surges on Solid Dielectric Cables"EPRI RP 2284.


[ 17-31. "Surge Behavior of URD CabIe Systems" EPRI EL-720. [17J]. A. C Westrum, "State of the An in Distribution Arresters," Thirty. Second Annual Power Distriiution Coaference. University of Texas-Austin 1979. [ 17-51. Ralph H.Hopkinson, "Better Surge Rotection lncrmses Cable Me." Electric Forum, 1983.

[ 1 7 4 . E. C. Sakshaug, "Influence &Rate of& Pnrteaive Capability," Electric Forum. 1977.

on Distribution Amster

117-71. Lightning Protectionfor Rural Electric Systems, 1993, NRECA Pub. #92-12.