CONTENTS
RATINGS GUIDE
Caterpillar Diesel Ratings 4
Caterpillar Diesel Rental Ratings 9
Caterpillar Diesel Ratings Definitions 10
Caterpillar Gas Ratings 14
Caterpillar Gas Ratings Definitions 19
Conversion Tables 22
Note Pages 33
1
DIESEL
RATINGS
CAT 50 Hz DIESEL RATINGS
kV A Genel'lltllrSet
Standby 1 Prime 1 Conlinuoua Modal
11
'
300 275 - 3406C
350 320 - 3406C
400 365 - 3406C
400 365 - C15 ACERT'"
450 410 - C15 ACERT
500 455 - C15 ACERT
550 500 - C15 ACERT
550 500 - C18 ACERT
600 545 - C18 ACERT
605 550 - C18 ACERT
650 591 - C18 ACERT
700 635 - C18 ACERT
750 680 - 3412C
800 725 - 3412C
900 810 - 3412C
1000 910 830 C32 ACERT
- 1000 906 35088
1100 1000 910 C32 ACERT
1250 1150 1000 3512
1400 1275 1206 3512
1500 1360 1320 35128
1600 1500 - 35128
1750 1600 1500 35128-HD
1875 1700 - 35128-HO
2000 1825 1600 3516
2250 2000 1750 35168
2500 2275 2000 35168- HD
3000 2725 2500 C175-16
3100* 2825* 2600* C175-16
*Rating does not include package mounted radiator
4
Conliguration
Low 8SFC
-
Low 8SFC
Low 8SFC
EU Stage 11 , Low 8SFC,
Low Emi ssions
EU Stage 11, Low 8SFC,
Low Emi ssions
EU Stage 11 , Low 8SFC,
Low Emissions
EU Stage 11, Low 8SFC,
Low Emi ssi ons
Low 8SFC, Low Emissions
Low 8SFC, Low Emi ssions
EU Stage 11
EU Stage 11 , Low 8SFC,
Low Emi ssions
Low 8SFC
-
Low 8SFC
-
Low 8SFC
Low 8SFC
Low 8SFC, Low Emissions
Low 8SFC, Low Emi ssions
Low 8SFC, Low Emissions
Low 8SFC
Low 8SFC
Low 8SFC, Low Emissions
Low 8SFC, Low Emissions
Low 8SFC, Low Emissions
Low 8SFC, Low Emissions
Low 8SFC
Low 8SFC, Low Emissions
Low 8SFC, Low Emissions
Low 8SFC
Low 8SFC
DIESEL
CONTINUED
CAT 50 Hz DIESEL RATINGS (CONT.)
Stendby 1 Pri:A 1 Contln1ous
-
1 ~ - - - 1 -
2688
3575
5375
7150
2163
2863
4325
5725
2425
3250
48:&---
6500
1963
2600
3925
5200
1 - - - : : - - 1 ~
1- 1-
1--1-
1-----=------ 1-----=---
1 ~ 1 - - : - - - -
1- 1-
-
----1-
1368
1825
2025
2200
2938
4400
5875
1775
2225
2875
2363
3238
3550
4725
6988
9313
3456
4656
5238
6550
7638
8725
9825
13094
17463
Gene111tor Set
Modal
111 1
,_
1 '
, ,, 1
11 '
6CM20
8CM20
9CM20
3606
3608
3612
3616
3606
6CM25
8CM25
3608
9CM25
3612
3616
12CM32
16CM32
6CM32
8CM32
9CM32
6CM43
7CM43
8CM43
9CM43
12CM43
16CM43
Conllgurllion
5
DIESEL
DIESEL
CONTINUED
CONTINUED
CAT 60 Hz DIESEL RATINGS CAT 60 Hz DIESEL RATINGS (CONT.)
Available only for North Ameri ca
ekW
GeumorSet
Stal dby 1 Prill8 1 Cond- Model Conligui'IIIIOI
: 11 1
300 275 - C9 ACERfT" EPA Ti er 3
17 16 017-4S EPA Tier 4 300 275 - 3406C - Low 8SFC
-
20 18 020-6S EPA Tier 4 350 320 - 3406C Low 8SFC
25 22 025-8S EPA Tier 4 350 320 - C15 ACERT EPA Tier 3, Low 8SFC,
30 27 030-8S EPA Tier 4 Low Emissions
40 36 040-6S EPA Tier 3 400 365 - 3406C Low 8SFC
50 45 050-6S EPA Ti er 3 400 365 - C15 ACERT EPA Tier 3, Low 8SFC,
60 54 060-8S EPA Tier 3
80 72 080-6S EPA Tier 3
1-
Low Emi ssions
450 410 - C15 ACERT EPA Tier 3, Low 8SFC,
100 90 0100-6S EPA Tier 3 Low Emi ssions
3-Phase tput 1800 rpm
500 455 - - C15 ACERT EPA Tier 2, Low 8SFC,
13 12 01 3-4 EPA Ti er 4 Low Emissions
18 16 018-4 EPA Tier 4 550 - - C15 ACERT EPA Ti er 2, Low 8SFC,
20 18 020-6 EPA Ti er 4 (ESP) ' Low Emi ssions
25 22 025-8 EPA Tier 4 550 500 - C18 ACERT EPA Ti er 2, Low 8SFC
30 27 030-10 EPA Ti er 4 600 545 - C18 ACERT EPA Ti er 2, Low 8SFC
40 36 040-6 EPA Tier 3 650 591 - C27 ACERT EPA Tier 2, Low 8SFC
50 45 050-6 EPA Ti er 3 700 635 - C27 ACERT EPA Tier 2, Low 8SFC
60 54 060-6 EPA Ti er 3 750 680 - C27 ACERT EPA Tier 2, Low 8SFC
80 72 080-6 EPA Ti er 3 800 725 - C27 ACERT EPA Ti er 2, Low 8SFC
100 90 0100-6 EPA Tier 3 900 810 740 C32 ACERT EPA Tier 2, Low 8SFC
125 114 0125-6 EPA Ti er 3 - 910 832 35088 Low 8SFC, Low Emi ssions
150 136 0150-8 EPA Tier 3 1000 910 830 C32 ACERT EPA Tier 2, Low 8SFC
175 158 0175-2 EPA Tier 3 1100 1000 890 3512 Low 8SFC
*AII ratings at t.O pf **AII ratings at 0.8 pf
..
1250 1135 1010 3512 Low 8SFC
1400 1275 1230 35128 Low 8SFC, Low Emi ssions
1500 1360 - 1230 35128 Low 8SFC, Low Emissions
CAT 60 Hz DIESEL RATINGS (CONT.)
1500 1360 1230 3512C EPA Ti er 2
1750 1600
-
1450 3516 Low 8SFC
2000 1825 1640 35168 Low 8SFC, Low Emi ssions
2000 - 1825 1650 3516C EPA Tier 2
Collllgul'lllion 2250 - - 35168 EPA Tier 1, Low 8SFC
2500 2250 2050 3516C-HO EPA Tier 2
Low 8SFC
Low 8 S F ~ C ---l
3000 2725 2500 C175-16 Low 8SFC, EPA Tier 2
3100* 2825* 2600* C175-16 Low 8SFC, EPA Tier 2
EPA Tier 3
Note': (ESP) Emergency Standby Rating
6
*Rating does not include package mounted radiator
7
DIESEL
DIESEL
CONTINUED
RENTAL UNIT RATINGS
CAT 60 Hz DIESEL RATINGS (CONT.) CAT 60 Hz RENTAL UNIT RATINGS
elcW Generetor Set ekW
Renllll Gene111tor
S111ndby 1 Prime 1 Conlinuoaa Modal Configuretion Standby 1 Prime 1 Contii UOUS Model Configuration
' 11
'
:11 1
980 6CM20 -
----=--
1----:--
1300
1-
8CM20 -
- - 1470 9CM20 -
2000 1820 1650 3606 -
20 18 XQ20 EPA Ti er 4
30 27
1-
XQ30
1- -
-
1-
EPA Tier 4
45 41 - XQ45 EPA Ti er 3
-
60 54 XQ60
1- -
-
1-
EPA Ti er 3
-
2660 2420 2200 3608
,
4000 3640
3300- l -
3612
80 70 - XQ80 EPA Ti er 3
100 90 XQ100
!-
EPA Tier 3
-
-
1-
-
5320 4840 4400 3616 -
1
'
230* 210 - XQ230 EPA Ti er 3
300* 275 - XQ300
1 ~
EPA Tier 3
-
1-
-
1680 1525 1375 3606 -
- - 1730 6CM25 -
400* 365 - XQ400 EPA Tier 3
600 545 XQ600
:- -
- ,_ EPA Tier 2
-
2200 2020 1830 3608 -
- - 2230 8CM25 -
1000* 910 - XQ1 000 EPA Tier 2
2000 182s- - XQ2000 EPA Tier 2
- - 2500 9CM25 -
3360 3050 2750 3612
*Avai lable at 50Hz
4400 4040 3660 3616 -
- - 5590 12CM32 -
- - 7450 16CM32 -
"'
'
- - 2765 6CM32 -
-
- 3725 8CM32 -
- - 4190 9CM32 -
..
'
-
--=--
5240 6CM43 -
- - 6110 7CM43
- -
69-ao- 8CM43
____:_ __;;__ -
7860 9CM43 -
------::----
~
10475 12CM43 -
- - 13970 16CM43 -
8 9
DIESEL
RATINGS DEFINITIONS
CAT DIESEL RATING DEFINITIONS:
Emergencv Stand by Power (ES PI
Output available with varyi ng load for the duration of an emergency
outage. Average power output is 70% of the stand by power rating.
Typical operation is 50 hours per year with maximum expected usage
of 200 hours per year. Stand by power in accordance with IS08528.
Fuel stop power in accordance with IS03046.
Standby Power
Output available with varying load for the duration of the interruption
of the normal source power. Average power output is 70% of the
stand by power rating. Typical operation is 200 hours per year, with
maximum expected usage ol 500 hours per year. Fuel stop power in
accordance with IS03046.
10
DI ESEL
RATINGS DEFINITIONS
Prime Power
Output available with varying load for an unlimited time. Average
power output is 70% of the prime power rating. Typical peak demand
of 100% al prime-rated ekW with 10% of overload capability lar
emergency use lora maximum al 1 hour in 12. Overload operation
cannot exceed 25 hours per year. Prime power in accordance with
IS08528. Fuel stop power in accordance with IS03046.
Continuous Power
Output available without varying load lor an unlimited time. Average
power output is 70 - 100% of the continuous power rating. Typical
peak demand is 100% ol conti nuous rated ekW lar 100% of operating
hours. Continuous power in accordance with IS08528. Fu el stop
power in accordance with IS03046.
11
GAS
RATINGS
CAT 50 Hz CONTINUOUS
GAS RATINGS
kV A kV A Nlllllral
1000[11m 1500[11m Gas
- 80 -
87 G3306 NA
1----=---
106 G3306 NA
1-
129
1----=---
-
- 138 G3306 TA
1--::---
156 G3306 TA
1-
156 G3406 NA --
1-
200 G3406 TA
1---=--
350 G3412 TA
1----::--
450 G3412C LE
1-
600 G3508 LE
1-
619 G3508 LE
1-----=--
631 G3508 LE
1--=--
1---=--
638 G3508 LE
906 G3512LE
1-
931 G3512LE
1---=--
956 G3512LE
1-
963 G3512 LE
1-
1094 - -
1----::--
1156 -
1-
1219 G3516 TA
1----=----
1219 G3516 LE
1-
1256 G3516 TA
1-
1256 G3516 LE
1-
1288 G3516 TA
1-
1288 G3516 LE
l.___..;;__
1356 G3516B
1-
1388 G3516B
- 1431 G3516B
low Energy
Gas
- G3306NA
1-
- -
1-
-
-
1-
! -
G3406NA
- -
1-
-
-
-
-
- -
- -
- -
-
-
-
-
- -
-
-
;_
- -
!-
-
i-
G3512 LE
- -
G3516 LE
1-
-
G3516 LE -
- -
-
-
- -
- -
1-
- -
1-
G3516 LE -
1-
- -
1-
-
-
-
-
Note
1
: A factory supplied generator by OTO ora customer supplied generator needed.
14
-
-
-
-
-
-
-
-
kV A kV A Natural
1000rJ1m 1500 rJim Gas
1606 - G3606
1712 - G3606
- 1944 G3516C IM*
- 1944 G3516C
- 1986 G3516C
2143 - G3608
2281 - G3608
- 2438 G3520C
- 2458 G3520C !M*
3212 - G3612
3425 G3612
-
3593
--=---
G3612
3625
___;:__
G3612
4281
---=--
G3616
4562 G3616
-
4825 - G3616
*IM lsland Mode
kV A kV A Natural
1000_rpm 1500!'Pm Gas
-

G3516B
G3516B - 1456
2000 G3516E
,_
2500 G3520C
- 2500 G3520E
GAS
CONTINUED
CAT 50 Hz CONTINUOUS
GAS RATINGS (CONT.)
low Energy
Propane Gas
- -
1- -
-
-
-
-
- -
- -
-
-
-
1-
-
-
1-
-
-
- G3520C
1- -
-
-
1- -
-
1-
G3520C
-
-
-
1- -
-
-
- -
-
-
-
-
CAT 50 Hz CONTINUOUS CHP
GAS RATINGS
low Energy
Propane Gas
-
-
1- -
-
-
- -
- -
- , -
15
GAS
CONTINUED
CAT 60 Hz STANDBY
GAS RATINGS
kW kW Natural
1000 rpm 11100 rpm Gas
150 G3406 NA
1-
240 G3406 TA
1__,;:.._
- 260 G3406 TA
1-
275 G3406 TA
1__,;:.._
- 350 G3412TA
1-
375 G3412C LE
1__,;:.._
410 -
1-
435 G3412 TA
1__,;:.._
- 445 -
1-
450 G3412 TA
1-
460 G3412TA
1-
1-=--
470 G3412 TA
480 G3412 TA
1-
495 G3412 TA
1__,;:.._
- 515 G3412 TA
- 1040 G3516 LE
CAT 60 Hz CONTINUOUS
GAS RATINGS
kW kW Natural
1201!. !Pm 11100_rpm Gas
- 72 -
~
85 G3306 NA
100 G3306 NA
-
~
132 -
- 135 G3306 TA
~
140 G3306 TA
- 150 G3306 TA
16
lowEnergy
Pro pana Gas
- -
, ~
- -
- -
- -
- -
-
G3412TA -
- -
G3412TA -
- -
1-
-
- -
- -
- -
- -
- -
- -
low Energy
Propane Gas
- G3306NA
1-
- -
1-
- -
-
1-
G3406NA
1-
- -
1-
-
- -
j
-
-
-
-
-
kW kW Natural
J2!Jll. rpm J80Q_rpm Gas
- 150 G3406 NA
- 190 G3406 TA
- 350 G3412TA
360 - G3508 LE
370 - G3508 LE
370 - - G3508 TA
- 375 G3412TA
- 375 G3412C LE
375 - G3508 LE
380 G3508 TA
385
! -
G3508 LE
,_
390 G3508 LE
1-
400 - G3508 LE
555
! -
G3512 TA
1--=--
560 G3512 TA
570
! -
G3512 TA
--=--
570 - G3512 LE
585
! -
G3512 LE
--=--
600 G3512 LE
695
1---:--
-
735
1-
-
750
1-
G3516 TA
755
1-
G3516 TA -
770
1-
G3516 TA
1-
770 - G3516 LE
795
' ---:--
G3516 LE
815
1-
-
820 - G3516 LE
GAS
CONTINUED
CAT 60 Hz CONTINUOUS
GAS RATINGS (CONT.)
lowEnergy
Propane Gas
-
-
1-
-
-
G3412TA -
- -
G3412TA -
-
G3412TA -
- -
-
-
- -
-
-
-
-
-
-
- -
- -
- -
- -
- -
-
-
G3516 LE
G3516 LE -
-
-
- -
-
-
- -
1-
-
1-
G3516 LE
-
-
-
-
Note
1
: A factory suppl ied generator by OTO ora customer supplied generator needed.
17
GAS
CONTINUED
CAT 60 Hz CONTINUOUS
GAS RATINGS (CONT.)
kW kW kW
900111m 1200111m 1800_rpm
1155 - -
1235
__::.._
1 ~ 0 -
-
----:--
f-
1400
1540 -
-
- 1600 -
- - 1635
1640
~
-
-
- 1660
1-
1900
__::__ , ~
2055
1-
2055 -
____;;,__
2310 -
-
2315
__::.._ -
2335
---=--
-
2465
__::.._ -
2595 -
-
2615 -
-
3080 - -
3105
-
___._::_____
-
3285 -
3480
----:--
-
*IM lsla nd Mode
18
Natural
Ges
G3606
G3606
1-
G3516B
G3516B
1-
G3608
G3520C
1-
G3516C
G3608
f -
G3516C
G3520C
G3520C
G3520C IM*
G3612
G3612
G361 2
~ 3 6 1 2
G3612
G3612
G3616
G3616
G3616
GJ616
Low Energy
Ges
-
-
-
-
-
-
G3520C
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
GAS
RATINGS DEFINITIONS
CAT GAS RATING DEFINITIONS:
Stand by Power
These ratings are applicable for supplying continuous electrical
power (at variable load) in the event of a util ity power failure. No
overload is permitted on these ratings. Natural gas ratings have been
established on natural gas with net calorific Low Heat Value (LHV) of
approximately 35.6 MJ/m3 (905 Btu/ft3) and 80 methane number (MN).
Continuous Power
Output avai lable without varying load for an unlimited time.
Continuous power in accordance with IS08528, AS2789, and BS5514.
Natural gas ratings have been establi shed on natural gas with net
calorific Low Heat Val u e (LHV) of approximately 35.6 MJ/m3 (905
Btu/ft3) and 80 methane number (MN).
ekW- Generator output at 0.8 pf
kV A- Generator output
19
CONVERSIONS
RATINGS GUIDE
FUEL SYSTEM - DIESEL
Day Tan k Si zing
Tank Size lgal) = Rated BSEC llb/hphrl x Rated HP x Load Factor
7.076ilb/gal)
x Hours Between Refilling
+ Reserve Requirement
OR
Rule of Thumb for tan k size with 25% reserve
0.056 x Ave. BHP demand x Hours between refills x 1.25 = ___ gal.
0.27 x Ave. BKW demand x Hours between refills x 1.25 = ___ liters.
Note: Additional tank capacity required for cooling of recirculated fuel in unit-injected
engines. Tank should be located below leve! of injectors or nozzles.
On-Site Power Requirements
Based on 100,000 sq ft. of offi ce bldg., etc and 40N. Latitudes
Electric Requi rements
600 kW continuous load
IAir conditioning is absorption)
Use three - 300kW units
12 prime and 1 stand by)
Refri geration
Air Conditioning and Compressor
400 tons prime load
Use two- 200 hp engines
!No Standby)
One ton refrigeration = 200 Btu/min = 12,000 Btu/h
One Boi ler hp = 33,475 Btu/h
One ton compressor rating = One engine hp
Auxi li ary a ir conditioning equipment requires 1/4 hp/ton of compressor rating
Ice Plant
Complete power requires 4-5 hp per dai ly ton capacity
Air Compressor
hp = 1/4 x cu ft m/min at 100 psi
lncrease bhp 10% for 125 psi
Oecrease bhp 10% for 80 psi
22
CONVERSIONS
CONTINUED
ELECTRICAL TABLES
Altemating Current
To Obtain Single-Phase
Ki lowatts V x 1 x P.E.
1000
1-
KVA 'l..x.l
1000
Horsepower
K'I'J.
required when KW .746 x EFF.I Gen)
known IGenerator)
KW input when .I::!..E.x.l.4Q
HP known !Motor) EEE.IMot.)
Ampheres when HP x .746
HP known V x P.E. x EFF.
Ampheres when

KW known V x P.E.
Ampheres when .!S'I.8..x..l.Q
KVA known V
Frequency Poles x RPM
lc.p.s) 120
Reactive V x 1 x11-IP.f.l'
kV A IKVAR) 1000
% Voltage
100 IVNt..:lf.FJ
Regulation
v"
ELECTRI CAL TABLE ABBREVIATIONS:
V- voltage in volts
1 - current in ampheres
KW- power in kilowatts !actual power)
KVA- kilovolt-ampheres lapparent power)
HP - horsepower
RPM - revolutions per minute
Three-Phase Oiract Currant
1.732 '1. X 1 P.E. 'l..x.l
1000 1000
t -
-
1Illii.'Lxl
1000
KW KW
.746 x EFE.IGen) .746 x EFE. (Gen)
HP x .746 HP x .746
EEE.IMot.) EEE.IMot.)
.I::!..E.x.l.4Q .I::!..E.x.l.4Q
1.732 x V x EFE. x P.E. V x EFE.

1.732 x V x P.E. V
K'I.Ax.l.QOO
1.732 x V
x BPM
120
'
1000
.lO.OJ\j_NL.:.'&d .lO.OJ'I..t..:lf.FL)
v" v"
KVAR - reactive kilovolt-ampheres
EFF. - efficiency as a decimal factor
NL- no load
FL - fullload
P.E. - power factor
Note: OC KW = OC KVA
23
CONVERSIONS
CONTINUED
THREE-PHASE CONNECTION SYSTEMS
24
THREE PHASE, THREE-WIRE IWYEJ
A
240 VOLTS
THREE-PHASE, THREE-WIRE (DELTA)
B
THREE- PHASE, FOUR-WIRE IWYEJ
e
THREE-PHASE, FOUR WIRE (DELTA)
D
!
Type of Starter
Full Voltage Starter
Auto Transfor mar
80% Tap
65% Tap
50% Tap
-
Resistor Starter
Single Step
(adjusted for motor
voltage to be 80%
of line voltage)
-
Reactor
50% Tap
45% Tap
37.5% Tap
Part Winding (low-
speed motors only)
75% Winding
80% Winding
CONVERSIONS
CONTINUED
REDUCED VOLTAGE STARTERS
Line Current Starting Torque
Motor Voltage (% Full Voltagel (% of Full Voltagel
(% Une Voltagel Starting Current Starting Torque
100 100 100
- 1- - 1- -
80 68 64
65 46 42
50 30 25
:- - 1- - :- -
80 80 64
- 1-- -
1-
-
50 50 25
45 45 20
37.5 37.5 14
- 1-
~
:-
100 75 75
100 50 50
25
CONVERSIONS
CONTINUED
COMPARISON OF REDUCED VOLTAGE STARTING METHODS
Two-Step
Characteristlc Autotransfonner Primary Reaistor Reactor PartWinding
Starting Line Curren!
at Same Motor Leas! - More than autotransformer type -
Terminal Voltage
-
1-
1 1
-
Starting Power
Low High* Low Low
Factor
- r--
u
Power Draw from
Low - More than autotransformer type -
Line During Starting
Torque
In creases slightly
lncreases rapidly with speed
lncreases slightly
with speed with speed
Smoothness
Motor momentarily Smooth. Transfer made
of Acceleration
disconnected from with little change in Smooth
line from start to run motor terminal voltage
Relativa Cost Average
Lower in small size-
Average Less than others
otherwise equal
-
No provision
Ea se of Control S ame S ame S ame for adjustment of
starting curren!
-
1-
Maintenance S ame S ame S ame Less than others
Line Disturbance - Varies with conditions and type of load - More than others
*Resi stor starting adds considerable kW load to generator set. Total power
required includes the motor kW and the kW which is lost as heat in the resistor.
The series resistors account for a higher than normal starting power factor.
26
CONVERSIONS
CONTINUED
ENGI NE ROOM VENTILATI ON
Engine room venti lation can be estimated by the following formulas,
assuming 1ooF IJsc ambienta ir temperatura:
V lcfm) ;
0
_
070
x H
0
_
24
x Al + Engine Combustion A ir
V 1m3/mini; + Engine Combustion Ai r
1.099 x 0.017 xAT
V; Ventilation a ir lcfm) lm3/min).
H ; Heat radiation IBtu/min)(kW).
Al ; Permissible temperatura ri se in engine room (F)(C).
Density of a ir at 100F; 0.070 lb/ cu ft (1.099 kg/m3 _
Specific heat of a ir; 0.24 Btu/F (0.017 kWJC).
27
CONVERSIONS
CONTINUED
CONVERSION FACTORS
1
25.4
304.8
914.4
1000
100 0000
160 9340
.03937
1
12
36
39.3701
39 370.1
63 360
.003281
0.083 33
1
3
3.280 84
3208.84
5280
Langth
0.027 78
0.333 33
1
1.093 61
1093.61
1760
0.0254
0.3048
0.9144
1
1000
1609.34
0.000 03
0.000 30
0.000 91
0.001
1
1.609 34
0.000 645 16 0.006 944
1 10.764
0.0929
0.000 62
0.621 37
1
1 sq mil e= 640 acres
1 acre = 4840 yd2
1 cir mil = 7.854 x 1Q7in2
1 cir mil = .7854 x mils2
1 cir mil= 5.067 x 1QScm2
1
0.4536 16
907.2 32,000 0.9072
1,016 35,840 1 1.016
1,000 35,300 1.102 0.9842
1 grain = 0.064799 gram
28
CONVERSIONS
CONTINUED
CONVERSION FACTORS
1 1.547
448.8 0.0646 101 .9
4.403 0.006 34 0.009 81 1 0.2778
15.85 0.0228 0.0353 3.60
MCFD = 1000 ft3fday MMCFD = 1,000,000 ftlf day lb/bhp-hr x 607.73 = g/kW-hr
0.252 0.00001
3.08866 4.187 0.001
0.323765 1 1.356 0.003089
0.23895 0.73745 0.000239
1000 3089 4185 1 2.519
396.8254 128.5347 94.78169 0.39682
1 Therm = 1,000,000 Btu Bt ufft3 = 8.899 kg-calfm3
Btu!ft2/min = 0.1220 Watts/in2 Btu/lb = .5556 kg-cal/kg
29
CONVERSIONS
CONTINUED
CONVERSION FACTORS
30
Capacity
1728
46656
6.1 X 1Q-5
61 023.7
231
277.419
61.023 7
1 board-foot = 144 in3
51.7149
735.559
750.062
7.500 62
0.000 58
27
4.0 X J0-8
35.3147
0.13368
0.160 54
0.035 31
43 560
1 bushel = 1.244 ft3
1
0.00128
42.456
0.00095
41.827
59
0.05687
0.07 355
0.882 65
2.036 02
28.959
29.530
0.295 30
1
0.000 02 16387.1
0.037 04 28 320 000
764 554 858
1
1.307 95 1,000,000,000
0.004 95 3785420
0.005 95 4540090
0.001 31 1000 000
1613.33
1 bushe1 = 4 pecks
778.2
1
33000
0.7405
32550
44250
44.25
13.61
12
27.70 2.309
395 32.84
401.8 33.49
4.01835 0.33486
CONVERSIONS
CONTINUED
CONVERSION FACTORS
'
', ,
0.000 02 0.004 32 0.003 61 0.01639
0.028 32 7.480 52 5.228 83 28.3169
0.76455 201.974 168.178 764.555
- 2.6 X J0-7 2.2 X JOl 1.0 X J06
1 264.192 219.969 1000
0.003 78 1 - 3.785 41
0.004 55 1.200 95 1 4.546 09
0.001 0.264 17 0.219 97 1
1233.48 325 851 271 335 -
J/min Metroc hp kW W
1055.000 0.02391 0.0175843 17.5843
1.3504 0.00003 0.0000226 0.0226
44791 1.014 0.74570 745.7
1 0.0000226 0.0000166 0.016668
44127 1 0.73549 735.498
59997 1.35962 1 1000
59.9968 0.00136 0.001 1
0.491 15 0.034 53
0.036 13 0.002 54 0.002 49 0.002 46 0.249
0.433 52 0.030 479 0.029 89 0.029 50 2.989
1 0.070 31 0.068 95 0.068 05 6.895
14.2257 0.980 67 0.967 84 98.067
14.504 1.019 72 1 0.98692 101 .325
0.145038 0.010 1972 O.DIO 000 0.009 869 20
31
CONVERSIONS
CONTINUED
CONVERSION FACTORS
32
Temperature Conversion
' F = 11.8 X ' C) + 32
' C = 0.5555I' F - 32)
Angle
1 quadrant = 90 degrees
1 quadrant = 1.57 radians
1 radian = 57.3 degrees
1 degree = 60 minutes
1 minute = 2.9 x 10 radians
ldentifying Code Letters on AC Motors
0.00 . 3. 14
3. 15 . 3.54
3.55. 3.99
4.00. 4.49
4.50 . 4.99
5.00 . 5.59
5.60 . 6.29
6.30 . 7.09
7.10-7.99
8.00. 8.99
9.00. 9.99
10.00-11 .19
11.20 . 12.49
12.50. 13.99
14.00 . 15.99
16. 00. 17.99
18.00 . 19.99
20.00 . 22.39
22.40
Note: Code letters apply to motors up to 200 HP.
NOTES
RATINGS GUIDE
33
NOTES