ARDEBIL GAS TURBINE POWER PLANT

Client Doc. No.: GT3-AD-29EE-08-YBQ-001

CALCULATION OF CABLE CROSS SECTION

Rev.: 0

LENGTH

CURRENT
CAPACITY OF
CABLES

(A)

SELECTED
CROSS
SECTION

(A)

APPARENT
CURRENT

START UP
CURRENT

(V)

(A)

(mm2)

(m)

(A)

8.71

0.80

0.75

14.52

4x4

30

36

4.610

0.107

0.42

0.42

6.11

36.66

0.80

0.75

10.18

4x2.5

10

27

7.410

0.110

0.16

0.96

P03

MCC

AIR BLOWER # 2

0.81

0.59

87.5

400

6.11

36.66

0.80

0.75

10.18

4x2.5

10

27

7.410

0.110

0.16

0.96

P04

MCC

SEWAGE LIFTING PUMP # 1

1.5

0.79

0.61

85

400

3.22

19.35

0.80

0.75

5.37

4x2.5

10

27

7.410

0.110

0.08

0.50

P05

MCC

SEWAGE LIFTING PUMP # 2

1.5

0.79

0.61

85

400

3.22

19.35

0.80

0.75

5.37

4x2.5

10

27

7.410

0.110

0.08

0.50

P06

MCC

CHLOR. DOSING UNIT # 1

0.08

0.75

0.66

71

400

0.22

1.30

0.80

0.75

0.36

4x2.5

10

27

7.410

0.110

0.01

0.03

P07

MCC

CHLOR. DOSING UNIT # 2

0.08

0.75

0.66

71

400

0.22

1.30

0.80

0.75

0.36

4x2.5

10

27

7.410

0.110

0.01

0.03

P08

MCC

CHLOR. SOLUTION STIRRER

0.25

0.78

0.63

77

400

0.60

3.60

0.80

0.75

1.00

4x2.5

10

27

7.410

0.110

0.02

0.09

8
9
10
11
12
13
14
15
16
17
18

NOTE:
PERMISIBLE VOLTAGE DROP BETWEEN MAIN DISTRIBUTION PANEL(MDP) AND MCC'S OR LIGHTING PANELS IS EQUAL TO 3%
PERMISIBLE VOLTAGE DROP BETWEEN MAIN MCC'S & MOTORS IS EQUAL TO 2%

ATTACHMENT
CABLE CALCULATION

1 of 1

START UP
VOLTAGE
DROP

8.71

400

(/Km) (/Km)

VOLTAGE
DROP

400

87.5

XL

100

0.59

(KW)

RW

0.60

0.81

SIN ()

0.80

COS ()

4.83

AIR BLOWER # 1

POWER

MCC

MCC

TO

00BHC

P02

FROM

P01

CODE

ITEM

GROUPING
FACTOR

CURRENT

(%)

CONVERSION
FACTOR

VOLTAGE

ATTACHMENT
EFFICIENCY

Date: 06-04-2008

(%)

(%)