INSTRUCTION MANUAL UG30 CONTROL

Uniguard BASE UG30 and mP30 CONTROL FOR PRECISION AIR CONDITIONERS - CHILLED WATER (CW/S-CW) - DIRECT EXPANSION (DX/S-DX)

INSTRUCTION MANUAL

UNIFLAIR 2004

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

1 (44)

INSTRUCTION MANUAL UG30 CONTROL

UNIFLAIR ITALIA S.p.A.


Via dellIndustria, 10 35020 BRUGINE (Padova) Italy Tel. +39 (0)49 9713211 Fax. +39 (0)49 5806906 Internet: www.UNIFLAIR.com E-Mail: info@UNIFLAIR.com

Release:

1.5

Date:

18 03 - 2004

Checked by:

2 (48

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

INSTRUCTION MANUAL UG30 CONTROL

CONTENTS
Page 4 4 5 6 7 8 8 9 16 17 18 19 19 20 20 21 22 27 28 29 30 30 31 32 33 34 34 35 38 38 38 39 40 43 44 44

Program identification Warnings General characteristics Lay-out of Uniguard Base UG30/mP30 circuit Inputs and outputs Optional sensors Optional circuits Lay-out of CP1 circuit Display Keyboard Information on display when unit is OFF Unit start-up conditions Switching the unit ON and OFF STATUS MASK Information on display when unit is ON Unit status display Access to parameters when consulting or programming Changing the Password Hardware configuration Operation hour-counter Exceeding hour-counter threshold Maintaining the humidifier cylinder Remote control of unit Connecting more than one unit Temperature set points Humidity set points Calibration and setting Clock/dater Time-bands Delays due to alarm signals Serious alarms Active alarms Reading the alarms historic record Alarm codes description Default values Memory reset Appendix: Flowchart for UG30/mP30 masks Access with USER password Flowchart for UG30/mP30 masks Access with FACTORY password

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

3 (44)

INSTRUCTION MANUAL UG30 CONTROL

PROGRAM IDENTIFICATION
This manual describes the characteristics of the standard UG30 and mP30 control for conditioners. until your reach the "Hr" parameter; this The software version can be read by repeatedly pressing key information must be supplied to the technical service centres when they are called in for a job.
Version Parameter

1.6

Hr

The setting of some parameters on a special unit version may differ from those described in this manual.

WARNINGS
Do not install the controls in places with the following characteristics: - relative humidity above 80%; - exposed to aggressive and polluting atmospheres (e.g.: sulphur or ammonia gasses, salt mists, fumes) to avoid corrosion and/or oxidation; - high magnetic and/or radio frequency interference (therefore, avoid installing units near transmitter aerials); Cut power before beginning work on the circuit in the case of assembly, maintenance or replacement jobs. In general, all the instructions found in the units Installation, Use and Maintenance Manual apply. WARNING: In direct expansion air-conditioners with a three-phase power supply, the controller's power may be cut if the phase sequence relay (RSF) is tripped.

4 (48

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

INSTRUCTION MANUAL UG30 CONTROL

CHARACTERISTICS
UG30/mP30 is an electronic control for full management of precision air conditioners, for both chilled water (CWCW/S) and direct expansion (DX-DX/S) versions with 1 or 2 compressors. The control consists of a user interface and a power circuit, both fitted inside a single container. The display shows the units operating status and main parameters by means of symbols and alphanumeric codes consisting of one letter and one number: 1, 2: r1, r2 : c9, CA: F9, FA: P1, P2: H1, H2: probe parameters; adjustment parameters (e.g. r1 = cooling set-point); compressor management parameters; fan management parameters; alarm management parameters; general configuration parameters.

All control parameters are set in the factory according to the type of unit and configuration; programming is effected by a hardware key or via a serial line. To change parameters, the operator may use the keyboard on the front panel. USER or FACTORY parameters are available depending on whether they are accessible to the user or reserved for authorised personnel. TECHNICAL SPECIFICATIONS Power supply : Maximum absorbed current: Transformer power for UG30/mP30 and digital inputs: Operating conditions: Storage conditions: 24 Vac 15% 50/60 Hz 200 mA with 800 mA T (delayed) internal fuse 10 VA -10 +54C with 20-80 non condensating R.H. -10 +70C with 0-80 non condensating R.H.

Alarms are active when the relevant input is open (not powered) Input ID1, for remote ON/OFF, powers up the unit when it is itself powered.

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

5 (44)

INSTRUCTION MANUAL UG30 CONTROL

LAY-OUT OF UNIGUARD BASE UG30/mP30 CIRCUIT


The figure shows the rear of the UG30/mP30 control, with input and output terminals. The following are shown in the figure: - low down: connectors ("1" - "2" - "3"), with the analogue and digital inputs and outputs; - lay-out for the clock circuit (optional); - lay-out for the RS485 serial circuit (optional);

C5

C3/4

OUT3

C1/2

Y1

Y2

OUT5 OUT4 OUT2 OUT1

GND

GND

G0

B4

B2

B3

ID2

ID4

ID6

ID8

ID10

B1

GND

+V

ID1

ID3

ID5

ID7

ID9

C6

NO6

C7

NC6

NO7

6 (48

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

INSTRUCTION MANUAL UG30 CONTROL

INPUTS AND OUTPUTS


The following tables shows information on inputs and outputs according to the type of selected unit. CW = 'LEONARDO' chilled water air conditioner; CW/S = 'AMICO' chilled water air conditioner; DX = 'LEONARDO' direct expansion air conditioner with 1 or 2 compressors. DX/S = 'AMICO' direct expansion air conditioner. DIGITAL INPUTS Connector 2 Equipped with 10 24Vac digital inputs.
CW - CW/S DX - DX/S Remote ON/OFF Remote ON/OFF Air flowswitch Air flowswitch Dirty filters flowswitch Dirty filters flowswitch (standard issue on CW/S unit, optional extra on CW unit) Safety thermostat for heating elements Safety thermostat for electrical resistors ID4 Alarm from temperature and humidity external sensors, and from Alarm from temperature and humidity external sensors, and from ID5 flooding sensor (optional) flooding sensor (optional) Humidifier alarm from circuit CDA303 Humidifier alarm from circuit CDA303 ID6 -Circuit 1 high pressure ID7 -Circuit 1 low pressure ID8 -Circuit 2 high pressure ID9 Compressor thermal breaker Circuit 2 low pressure ID10 -Common for inputs 1 10 GO ID1 ID2 ID3

ANALOGUE INPUTS Connector 2 Equipped with 3 analogue inputs for NTC sensors and 1 active probe 0-1Vdc / 4-20mA.
B1 B2 B3 B4 GND +V CW - CW/S Room temperature External air temperature for summer/winter changeover Room relative humidity STM delivery temperature Common for analogue inputs Power supply for active sensors 14Vdc (max.30mA) DX - DX/S Room temperature External air temperature for summer/winter changeover Room relative humidity STM delivery temperature

DIGITAL OUTPUTS The card is equipped with 7 outputs including: 1 200 Vac relay, with exchange contact; 1 200 Vac relay, with normally opened contact. Digital outputs Connector 1
DO1 DO2 DO3 DO4 DO5 C1/2 OUT1 C1/2 OUT2 C3/4 OUT3 C3/4 OUT4 C5 OUT5 CW - CW/S Cold water valve + (opens) Cold water valve - (closes) 1st stage for heating elements/ Hot water valve + (opens) 2nd stage for heating elements/ Hot water valve - (closes) Fan Triggering by fire-smoke sensor DX - DX/S Compressor circuit 1 Compressor circuit 2 1st stage for heating elements/ Hot water valve + (opens) 2nd stage for heating elements/ Hot water valve - (closes) Fan Triggering by fire-smoke sensor

Digital outputs with relays Connector 3


DO6 DO7 CW - CW/S C6-NO6-NC6 Serious alarm Dehumidifying solenoid-valve (CW) C7-NO7 Available for non-serious alarm warning (on CW/S) DX - DX/S Serious alarm Dehumidifying solenoid-valve (DX) Available for non-serious alarm warning (on DX/S)

ANALOGUE OUTPUTS Connector 1 Equipped with a 0-10Vdc analogue output and 1 phase cut-out output.
Y1 Y2 Y1 GND CW - CW/S Humidifier control DX - DX/S Humidifier control

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

7 (44)

INSTRUCTION MANUAL UG30 CONTROL

OPTIONAL SENSORS
The presence of sensors depends on the units configuration and version.. If a sensor is connected to a pre-installed conditioner, one of the FACTORY parameters described below must be modified. Prob 1 2 3 SENSORS
B2 sensor present (external air temperature) 0 = absent 1 = NTC Sensor B3 present (room humidity) 0 = absent 2 = 4-20 mA Sensor B4 present (delivery temperature) 0 = absent 1 = NTC Default 0 0 0

OPTIONAL CIRCUITS
UG30/mP30 is designed to be use with the following optional circuits: - RS485 serial circuit making it possible to connect the control to a supervision or remote assistance network; - Clock circuit, allows the user to see date and time, indispensable for operating programmes linked to time (time bands and memorising of the time and date of an alarm event). RS485 SERIAL CIRCUIT To use UG30/mP30 in an RS485 supervision system or remote assistance network, the optional RS485 circuit must be fitted as follows: - cut power to the unit - disconnect the connectors from terminal boards "1", "2" and "3"; - unscrew the rear cover of the control; - fit the RS485 circuit on the connector at the rear of the control; - break the plastic protection to allow access to terminals GND, RX/TX+, RX/TX-; - re-position the cover and connectors; - make the serial line connection observing the indicated polarities; - power up. Set the UG30/mP30s address in the network with parameter Ho and the speed with parameter HP (see paragraph REMOTE CONTROL OF UNIT . Consult manual for Supervision Systems. CLOCK CIRCUIT To enable the clock, time bands and the alarm historic record function, fit the optional circuit and follow the procedure below: - cut power to the unit - disconnect the connectors from terminal boards "1", "2" and "3"; - unscrew the rear cover of the control; - fit the clock circuit on the connector at the rear of the control; - re-position the cover and connectors; - power up. - set date and time and delete the alarms historic record. HUMIDIFIER INTERFACE CIRCUIT CP1 The CP1 electronic circuit is fitted on the electrical panel of the unit. It enables the management of the humidifier and signals any alarm statuses. The circuit is not provided with a display, and, therefore, signals are produced by lighting of coloured LEDs.

8 (48

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

INSTRUCTION MANUAL UG30 CONTROL

LAY-OUT OF CP1 CIRCUIT

The CP******** electronic card has been designed to control the immersed-electrodes OEM KUE* humidifiers. Since the CP********* card is uncovered, it must be installed so as to avoid any accidental contact with people during normal operating conditions and to prevent the danger of possible high tension or high temperature points. As to installation refer to the user manual of the immersed-electrodes OEM series.

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

9 (44)

INSTRUCTION MANUAL UG30 CONTROL


TECHNICAL SPECIFICATIONS Power supply:24Vac, from -15% to +10%, 50/60Hz Consumption:9VA (solenoid valves not included) - 35VA max (valves included) Operating conditions: 0T60C; <90%r.H. non condensing Storage conditions: -10T70C; <90%r.H. non condensing Environmental pollution: normal Digital outputs (relays: micro-interruption 1C type): - electrode power supply (cards CP1* and CP2*): 2 relays SPST, 250Vac 20A resistive (12A inductive cos = 0,4); min. number of commutations: 100.000 -electrode power supply (cards CP3* and CP4*): 1 relay SPST, 250Vac 5A (2A); min. number of commutat.: 100.000 - cumulative alarm relay: 1 relay SPST, 250Vac 5A (2A) Digital inputs: - AB-AB (remote ON/OFF start consent): external potential-free contact: ON= closed contact (Rmax of closed contact= 50, Imax through closed contact= 10mA); OFF= open contact (Vmax across open contact= 32Vdc) - VR-SET (humidistat): external potential-free contact for the production on/off control. Used as an alternative to SET-GND connection (read below under Analogue input). START OF PRODUCTION= closed contact (Rmax of closed contact= 50, Imax through closed contact= 10mA); STOP OF PRODUCTION= open contact (Vmax across open contact= 10Vdc) - Manual drainage: 2 external complementary potential-free contacts: ON-GND: closed= control enabled (drainage OFF), Rmax of closed contact= 50, Imax through closed contact= 5mA open= control disabled (drainage ON), Vmax across open contact= 5Vdc DR-GND: closed= drainage ON (disabled control), Rmax of closed contact= 1, Imax through closed contact= 0.5A open= drainage OFF (enabled control), Vmax across open contact= 24Vac Analogue input: - SET-GND (steam production request from ext. regulator; input impedance 15k): 0/10V (default), 2/10V, 0/1V. Used as an alternative to VR-SET (read above under Digital inputs) Protection index: IP00 Maximum cable length (TAM inputs, level, conductivity): shorter than 10m

NEW UE HUMIDIFIERS CP1 CARD HARDWARE CONFIGURATION (EXTERNAL TAM)


CP1 card used in single-phase OEM (AMICO unit): 2 relays (2x250V AC) to break phase and neutral (no external contactor needed). CP1 card used in three-phase OEM (Leonardo, Big units): 1 relay (1x250V AC) used to supply power to electrode supply contactor's coil. MEANING WHEN LED FLASHES Steam production: YELLOW LED (transitory production short flashes - steady-state production long flashes). AMICO UNIT CP1 CONFIGURATION (SD/SU 0151 0251 0331..)

AMICO unit (single-phase OEMs): For all sizes, the Cp1 card must be configured for a nominal steam flow of 3 kg/h

10 (48

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

INSTRUCTION MANUAL UG30 CONTROL

FACTORY SETTINGS . Dip switches type A (alarm relay and maximum production settings) A1 ON OFF A2 A3 A4

X X

Dip switch 1-not used Dip switch 2 set to ON: Relay not energized (contact open) with at least one alarm active, otherwise energized (contact closed)

Dip switches 3-4 set to OFF: 100% of nominal steam flow ( 3 kg/h)

Dip switches type B (auxiliary functions and automatic draining time) B1 B2 B3 B4 B5 B6 B7 B8

ON OFF Dip switch 1 set to OFF: complete draining after 7 days without production being requested (function enabled) Dip switch 2 set to OFF: automatic draining with or without electrode power supply (electrodes not supplied) Dip switch 3 set to OFF: the new production setpoint is reached by means of evaporation cycles when demand is reduced by less than 25%. Draining is achieved by means of evaporation cycles. Dip switch 4 set to OFF: cylinder exhaustion advance warnings (alarms are displayed when the cylinder is approaching exhaustion). Dip switches 5-6 set to OFF: automatic draining time (default setting) Dip switches 7-8 set to OFF: Evaporation time threshold (default setting) The TA RATE dip switches are left in their default positions since an external TAM is being used
Jumper setting on external TAM

In the AMICO models used, the jumper must be placed in position 100 (end of scale is quantified in amperes 100=10 amperes)
LEONARDO/BIG UNIT CP1 CONFIGURATION (MD/MU ._ D.G. _ 3 )

LEONARDO/BIG unit (three-phase OEM): Nominal steam flow will be reduced by 50% (4 kg/h) for Leonardo 1-2 frame and by 75% (6 kg/h) for Leonardo 3-4 frame and Big units.

Dip switches type A (alarm relay and maximum production settings) A1 ON OFF A2 A3 A4

X X

Dip switch 1-not used


mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

11 (44)

INSTRUCTION MANUAL UG30 CONTROL Dip switch 2 set to ON: Relay not energized (contact open) with at least one alarm active, otherwise energized
(contact closed)

Dip switch 3 set to ON Dip switch 4 set to OFF

50% of nominal steam flow FRAME 1-2 BIG

. Dip switches type A (alarm relay and maximum production settings) A1 ON OFF A2 A3 A4

X X

Dip switch 1-not used Dip switch 2 set to ON: Relay not energized (contact open) with at least one alarm active, otherwise energized (contact closed)

Dip switch 3 set to OFF Dip switch 4 set to ON

75% of nominal steam flow FRAME 3-4 & BIG

Dip switches type B (auxiliary functions and automatic draining time) B1 ON OFF Dip switch 1 set to OFF: complete draining after 7 days without production being requested (function enabled) Dip switch 2 set to OFF: automatic draining with or without electrode power supply (electrodes not supplied) Dip switch 3 set to OFF: the new production setpoint is reached by means of evaporation cycles when demand is reduced by less than 25%. Draining is achieved by means of evaporation cycles. Dip switch 4 set to OFF: cylinder exhaustion advance warnings (alarms are displayed when the cylinder is approaching exhaustion). Dip switches 5-6 set to OFF: automatic draining time (default setting) Dip switches 7-8 set to OFF: Evaporation time threshold (default setting) The TA RATE dip switches are left in their default positions since an external TAM is being used
Jumper setting on external TAM

B2

B3

B4

B5

B6

B7

B8

IN LEONARDO/BIG MODELS, THE JUMPER MUST BE PLACED IN POSITION 100 (END OF SCALE IS QUANTIFIED IN AMPERES 100=10 AMPERES)

12 (48

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

INSTRUCTION MANUAL UG30 CONTROL


LIST OF ALARMS Alarm state is active when the LEDs flash, and their type is described in the following tables.

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

13 (44)

INSTRUCTION MANUAL UG30 CONTROL

14 (48

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

INSTRUCTION MANUAL UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

15 (44)

INSTRUCTION MANUAL UG30 CONTROL

DISPLAY
The display shows the main controlled quantities and the operating status of the unit and its components. Below are the symbols on the display, and their meanings.

The symbol indicates that the display is showing the temperature and relative humidity values instantaneously measured in the environment, plus the relevant measurement units. Temperature may be in Centigrade of Fahrenheit (see paragraph DISPLAY OF UNIT STATUS. When you access the parameter programming mode (providing the the value and code of the parameters are shown (set-point,.). Programming (reading and modification of parameters). If flashing, the value of a parameter is being modified. Always lighted: operating mode automatic or manual. Unit status (from outside contact): - ON : unit enabled; - OFF : unit on stand-by. OFF status from remote command Display of operating hours of devices and clock functions. symbol is absent)

OFF status from hour bands. Activation or disabling of the unit is obtained through a remote command (with parameter HE=1) only.

Day of the week (1 = Monday,.7 = Sunday)

An alarm status is present. If P40 (see paragraph READING OF ALARMS HISTORIC RECORD) is selected, the buzzer is active. Dehumidification activated. Heating activated. Indicates heating power as the opening % of the hot water valve ( ) or as the number of activated heating elements. Ventilation activated. Cooling activated. Indicates cooling power as the opening % of the cooled water valve ( ) or as the number of activated compressors. All keys locked. To unlock the keyboard, access with the USER password and reset the USER Hi parameter to 0 value (see paragraph THE KEYBOARD). PASSWORD input requested. Humidifier activated; indicates the steam production percentage. Indicates the compressor operation hourcounter.

16 (48

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

INSTRUCTION MANUAL UG30 CONTROL

KEYBOARD
The main control statuses (power ON, alarm active, and unit ON) are shown to the user by the lighting of keys on the front panel
ON OFF

(green light) (red light) (yellow light)

The unit is ON. Machine in alarm status. Power ON: the control is powered.

Display information:
ON OFF

Changes unit status: if ON, pressing the key puts the unit on Stand-by; vice-versa, if the unit is on stand-by, pressing the key will turn ON the unit. In case of an alarm (the symbol will appear on the display ), it enables the alarm to be shut off. The alarm sound is heard only when the parameter P4 is other than zero (see ACTIVE ALARMS). When the power is returned ti the unit press the button in order to reset default values. When programming, parameter values can be increased When programming, parameter values can be reduced. When programming, you can select the value of a parameter, modify it, and confirm its value after modification. Takes you back to the STATUS MASK to display the units operating status. Used to scroll through the list of menus in sequence: "Prob", "SetP", "Com", "FAn", "ALAr", "GLb", "Cloc", "AlPG". If this key is pressed repeatedly, the following are shown cycle-wise: current time, date, room air temperature, operation hour-counters, and the software version. Functions as an Exit key to return to the previous mask. For scrolling parameters in sequence in the following menus: "Prob", "SetP", "Com", "FAn", "ALAr", "GLb", "Cloc", "AlPG".

2 sec
( + ) 5 sec

5 sec ( ( + + ) )

If held down for 2 seconds, it resets the alarm provided the alarm cause was eliminated. If pressed down together for 5 seconds (as from the STATUS MASK) you can access the programming mode for reading and modifying FACTORY parameters. If pressed down together for 5 seconds the hour-counters can be reset (but only if the display shows the hour-counter parameter in the USER parameters programming mode). If pressed for 5 seconds, you can access the programming mode for reading and modifying USER parameters. Used for adjusting the contrast of the LCD display according to the visual angle being used (starting with the STATUS MASK) If the keys shown here are pressed simultaneously, contrast is increased or reduced.

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

17 (44)

INSTRUCTION MANUAL UG30 CONTROL


The functions associated with the keys can be disabled by setting the USER Hi=1 parameter (see paragraph ACCESS TO PARAMETERS WHILE CONSULTING OR PROGRAMMING). MENU GLb
Hi

DESCRIPTION
Minimum 0 Maximum 1 Measurement unit flag Default 0

GENERAL INFORMATION
Prevents unauthorised operators from modifying parameters (the padlock symbol is shown). 0 = no lock 1= lock out of all functions for modifying parameters, and resetting alarms and hour-counters (except access to the USER password and keyboard power down) the padlock symbol is shown on the display).

PARAMETER

INFORMATION ON DISPLAY WHEN UNIT IS OFF


STATUS MASK When the unit is powered up but not running, the STATUS MASK is shown on the display indicating the following active fields: A. Room temperature, room relative humidity (with humidity sensor only);

B. The indication: and " Supervisor; " ": unit turned OFF from a remote contact or a

unit turned OFF according to set hour bands.

C. Unit turned OFF due to alarm status:

18 (48

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

INSTRUCTION MANUAL UG30 CONTROL

UNIT START-UP CONDITIONS


In order for the unit to be Started-up it is necessary that there are no active alarms, that the control programme receives power and that one of the following conditions is verified:

Check that the yellow light of key Check if the red light of key

is lighted (control powered up); is OFF (no alarm activated);


ON

The operator must have pressed key OFF so that the green light on the key is lighted and the fan symbol appears on the display; if the remote input was selected (USER parameter HE=1), digital input ID1 must be in the closed contact on the display refer to the status of the conditioner. position. The words if the supervisor is connected and the unit is configured (see USER parameters Ho and HP), the unit must be enabled by the supervisor; If using daily or weekly hour bands, they must enable power up of the control;

SWITCHING THE UNIT ON AND OFF


The unit can be switched ON in one of the following modes:
ON

Local MODE from keyboard: the unit is commanded by the OFF push-button (when first pressed, the unit starts, and when pressed again, it stops. Start-up can be delayed by a time period equal to the value of the USER HG parameter. In Direct expansion units, the control commands the compressor to start so that the starting and stopping cycles are not too close. Compressor start-up can be delayed with respect to pressure of the ON/OFF key (also see parameter FACTORY c7). The units current status is stored in the memory; when power is restored, the unit returns to its status before power failure, and restarts if it had been running. GLb
HG

GENERAL INFORMATION
Delayed start up. During this phase all unit components remain off.

Minimum 0 Minimum 0

Maximum 300 Maximum 300

Measurement unit sec Measurement unit sec

Default 0 Default 60

Com
C7

COMPRESSOR
Compressor start-up delayed by start-up of fan.

The stop of the units fan is delayed with respect to pressure of the ON/OFF push-button by a time period equal to FACTORY parameter Fd (default = 10 seconds). While the unit is OFF, the Fan
Fd FANS Fan switch-off delay (FACTORY). Minimum 0

symbol flashes on the display.


Maximum 900 Measurement unit sec Default 10

Automatic MODE: the control is configured so that the unit is started and stopped as follows: 1. a remote ON/OFF contact (the symbol appears on the display); 2. a supervision system (possible only in units equipped with a serial circuit); 3. programmable hour bands (only in units equipped with a clock circuit).

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

19 (44)

INSTRUCTION MANUAL UG30 CONTROL

STATUS MASK
The units function parameters (temperature, humidity, .) can be read by pressing key

INFORMATION ON DISPLAY WHEN UNIT IS ON


STATUS MASK When the unit is running, the STATUS MASK is shown on the display, with the following active fields: B. Room temperature, room humidity (with humidity sensor only); If the measured temperature and humidity values are incorrect, the sensors can be calibrated as described in paragraph SENSOR CALIBRATION.

C. Currently operating functions: the following symbols are lighted according to work conditions: D. Unit commanded from a remote contact or a Supervisor. E. Fans operating automatically. On standard units (with F1=0 parameter) the fans always run at 100% therefore, the symbol displayed on the right is always OFF. F. Abnormal status: " : turns on during alarm event; ": flashes if the threshold of a work hour-counter was exceeded.

20 (48

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

INSTRUCTION MANUAL UG30 CONTROL

UNIT STATUS DISPLAY


The units function parameters (temperature, humidity, .) can be read by repeatedly pressing key of the reading cycle, you return to the initial STATUS MASK. If you press key you immediately return to the STATUS MASK. At the end

The display shows only information and data concerning the selected configuration (e.g. time and date appear only in controls equipped with a clock card). is pressed, the following are shown in sequence: Whenever key - FA: fan hour-counter; - Fc: air filter hour-counter; - c9: compressor 1 hour-counter (for DX-DX/S units only) - cA: compressor 2 hour-counter (for DX units only) - ro: external air temperature (from SE sensor) - rP: relative humidity (from STU sensor) - rr: delivery temperature (from STM sensor) - hours: minutes (with optional clock card only) -year (with optional clock card only) - day-month - Hr: software version.

0 23.9

FA

Fc

0 17.2

c9

cA

ro

53.0 1.6

rP

rr

10:54

3 - 4 - 01

Hr

By using parameter C, you can select a temperature measurement unit. As this parameter varies, the UG30/mP30 control automatically converts all the configuration parameters (set-point, differentials, etc.). The measurement unit being used is constantly shown on the display. Note: If the Centigrade to Fahrenheit (and vice-versa) changeover is effected by the supervisor, the parameters are not converted (all that changes is the value read by the temperature sensors and the symbol on the display). Prob
/C SENSORS Measurement unit 0= Centigrade (C) is used 1= Fahrenheit (F) is used Minimum 0 Maximum 1
Measurement unit

Default 0

SEtP
ro rP rr

ADJUSTMENT
B2 sensor reading (external air temperature) Only shown if sensor installed. B3 sensor reading (humidity percentage). Only if sensor installed. B4 sensor reading (delivery air temperature) Only shown if sensor installed.

C %R.H. C

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

21 (44)

INSTRUCTION MANUAL UG30 CONTROL

ACCESS TO PARAMETERS WHEN CONSULTING OR PROGRAMMING


Control parameters are read and programmed on the control keyboard: 1. ACCESS IN READ ONLY MODE : data can be consulted but cannot be changed; 1.a. press key to go to the STATUS MASK. to scroll the following menus in sequence: "Prob", "SetP", "Com", "FAn", again after

1.b. repeatedly press key

"ALAr", "GLb", "Cloc", "AlPG". The menus are presented cycle-wise: if you press key AIPG, you return to the Prob menu. The

symbol appears in the bottom left corner of the display.

1.c. press key to access the first parameter of each menu and key to scroll through the successive menus in sequence (see the masks flowchart in the APPENDIX ). The value of the parameter is shown at the centre of the display, while the parameter code is shown at top right. The parameters are grouped in menus as shown in the following table: MENU PARAMETERS sensor parameters r c F P H adjustment parameters (e.g. r1 = cooling set-point) compressor management parameters fan management parameters alarm management parameters general configuration parameters clock function parameters alarms historic record

1.d. press key 1.a. press key

once to return to the initial menu selection mask (see point 1.b.). again to return to the STATUS MASK.

22 (48

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

INSTRUCTION MANUAL UG30 CONTROL


EXAMPLE: humidity set-point reading (parameter r5).

23.9

53 %rH

Prob

SetP

23.0

r1

50.0
(*)

r5

SetP

23.9

53 %rH

(*)

Parameter r5 (= Humidity set-point); Value = 50.0%.

2. ACCESS IN PROGRAMMING MODE (READING AND WRITING) with USER password: USER parameters can be modified:

2.a. press key

to go to the STATUS MASK.

for 5 seconds to view the USER password request mask. Symbol appears in 2.b. press key the bottom left corner of the display; the abbreviation "uP" (="USER PASSWORD") is shown in the top right corner and value 0 flashes at the centre of the display. 2.c. Input the USER password (see envelope enclosed with the manual) with keys and .

to confirm the value. If the password is incorrect, you automatically return to the status mask 2.d. Press (see point 3.a.). If the password is correct Prob is shown on the display. 2.e. repeatedly press key to scroll the following menus in sequence: "Prob", "SetP", "Com", "FAn", again after

"ALAr", "GLb", "Cloc", "AlPG". The menus are presented cycle-wise: if you press key AIPG, you return to the Prob menu. The symbol appears at bottom left of the display.

to access the first parameter of each menu and key to scroll through the menus in 2.f. press key sequence (see the masks flowchart in the APPENDIX ). The value of the parameter is shown at the centre of the display, while the parameter code is shown at top right.

2.g. press key

to modify the displayed parameter. Symbol and .

will start to flash.

2.h. Input the value of the parameter with keys 2.i. Press key

to confirm the value of the parameter. The symbol will stop flashing. to go back by one mask or press key to return to the STATUS

You can, from any point, press key MASK.

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

23 (44)

INSTRUCTION MANUAL UG30 CONTROL


EXAMPLE: modifying the humidity set-point (parameter r5).

23.9

53 %rH

(press for 5 seconds)

uP

**

uP

**: input the USER password contained in


the envelope enclosed with the manual.

Prob

SetP

23.0

r1

50.0

r5

50.0

r5

55.0

r5

55.0

r5

23.9

53 %rH

shown on the display: This is the meaning of symbol - on with steady light: access to masks is in read only mode; on and flashing : access to masks is in programming mode;

24 (48

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

INSTRUCTION MANUAL UG30 CONTROL


3. ACCESS IN PROGRAMMING MODE (READING AND WRITING) with FACTORY password: FACTORY parameters can be modified:

3.a. press key

to go back to the STATUS MASK. and for 5 seconds to view the FACTORY password request

3.b. simultaneously press keys

appears in the bottom left corner of the display; the abbreviation "FP" (="FACTORY mask. Symbol PASSWORD") is shown in the top right corner and value 0 flashes at the centre of the display. 3.c. Input the FACTORY password (contact the technical service centre) with keys and .

to confirm the value. If the password is incorrect, you automatically return to the status mask 3.d. Press (see point 3.a.). If the password is correct Prob is shown on the display. 3.e. repeatedly press key to scroll the following menus in sequence: "Prob", "SetP", "Com", "FAn", again after

"ALAr", "GLb", "Cloc", "AlPG". The menus are presented cycle-wise: if you press key AIPG, you return to the Prob menu. The

symbol appears in bottom left corner of the display.

to access the first parameter of each menu and key to scroll through the menus in 3.f. press key sequence (see the masks flowchart in the APPENDIX ). The value of the parameter is shown at the centre of the display, while the parameter code is shown in the top right corner.

3.g. press key

to modify the displayed parameter. Symbol and .

will start to flash.

3.h. Input the value of the parameter with keys 3.i. Press key

to confirm the value of the parameter. The symbol will stop flashing. to go back by one mask or press key to return to the STATUS

You can, from any point, press key MASK.

After you have modified the machine configuration parameters, to ensure correct operation right away, we advise you to reset the control by turning off power.

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

25 (44)

INSTRUCTION MANUAL UG30 CONTROL


EXAMPLE: modification of parameter 3 (delivery air presence "B4").

23.9
.

53 %rH

(press simultaneously for 5 seconds)

FP

**

FP

**: ask your nearest technical service centre for the FACTORY password

Prob

23.9

53 %rH

Meaning of symbol shown on the display: - on with steady light: access to masks is in read only mode; on and flashing : access to masks is in programming mode;

CHANGING THE PASSWORD


The password for all FACTORY parameters can not be modified; the password of the USER parameters can be modified through parameter HH. GLb
HH (**)

GENERAL
USER Password

Minimum 0

Maximum 200

Default (**)

the USER password is contained in the sealed envelop enclosed with the Instruction Manual.

26 (48

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

INSTRUCTION MANUAL UG30 CONTROL

HARDWARE CONFIGURATION
The units control programme must be adapted to the unit in which it is installed and therefore it must be configured. During this phase it is important to define all the elements that are part of the unit and that the Microprocessor will have to control. Normally this operation is performed when the Control programme is installed on the unit, this operation is performed in the FACTORY during final commissioning. It may however be necessary to modify the Control programme due to variations carried out on the unit.

GLb
H1 H5

GENERAL
Unit model: 0 = DX-DX/S unit 1 = CW-CW/S unit Functioning mode of cooling out puts OUT1 and OUT2: 1 = one compressor 2 = two compressors on two circuits 3 = valve (three points) 5 = two compressors in TANDEM on one circuit Functioning mode of heating out puts OUT3 and OUT4: 0 = no heating elements 1 = one heating phases (**) 3 = hot water valve (three points ) 4 = three heating phases Humidifier present: 0 = no 1 = si Type of dehumidification: 0 = start up of compressor n.1 (for DX units with 1 compressor on each refrigerant circuit) 2 = start up of all compressors (for DX single circuit units fitted with a TANDEM compressor) 3 = override the opening of the chilled water valve (for CW units) 5 = fan speed reduced with compressor n1 switched on (for DX/S units) 8 = overriding cold ramp and reducing fan speed (for CW/S units)

Min. 0 1

Max 2 5

Default (*) (*)

H6

0/3/4 (on CW) 0/1/3 (on CW/S)

(*)

H8 H9

0 0

1 8

(*) (*)

(*) DEFAULT values depend on the type of unit (DX-DX/S-CW-CW/S), the number of compressors and the construction version of the unit (C, T, D, H). (**) in T-version AMICO units with standard heating elements, parameter H6 always has the value 1. In units with more powerful heating elements (models 0331-0601 and 0200-0600), it has the value 3.

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

27 (44)

INSTRUCTION MANUAL UG30 CONTROL

OPERATING HOUR-COUNTER
The UG30/mP30 control displays the operating hours of the units main components. By using the hour-counter threshold parameters, the maintenance intervals for each component can be established. When the device in question exceeds the indicated value, the processor signals the maintenance request by activating an alarm signal symbol in the top right corner of the display. and showing the To modify the hour-counter thresholds, first have access the parameters in the programming mode (USER password ). Com
c8

COMPRESSOR
Hour-counter threshold for compressors operation. It establishes the number of compressor operating hours beyond which the maintenance request is signalled. If c8 = 0 is selected, the function is disabled.

Minimum 0

Maximum 30000

Measurement unit Hours

Default 0

FAn
F9 Fb

FANS
Hour-counter threshold for fan (0=hour-counter disabled) Hour-counter threshold for filter (0=hour-counter disabled)

Minimum 0 0

Maximum 30000 30000

Measurement unit Hours Hours

Default 0 1000

With the hour-counter parameter, the number of hours accumulated by the units component can be read. If you press keys and for a few seconds, the hour-counter is reset. This operation is executed in programming symbol flashes.
Minimum 0 Maximum 30000 Measurement unit hours Default 0

mode only, when the Com


c9 cA

COMPRESSOR
Compressor 1 hour-counter Compressor 1 hour-counter Indicates number of operating hours of compressor 1 and/or 2

FAn
FA Fc

FANS
Fan hour-counter. Indicates number of fan operating hours. Filter hour-counter. Indicates number of filter operating hours. This hour-counter is increased only if the fan is running.

Minimum 0 0

Maximum 30000 30000

Measurement unit hours hours

Default 0 0

EXAMPLE: resetting the filter hour-counter (FC parameter).

23.9

53 %rH

(press for 5 seconds)

uP

**

uP

**: input the "USER" password contained in


the envelope enclosed with the manual.

Prob

FAn

F9

1001

Fc

1001

Fc

(press keys Simultaneously for at least 5 seconds)

Fc

28 (48

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

INSTRUCTION MANUAL UG30 CONTROL

EXCEEDED HOUR-COUNTER THRESHOLDS


If the hour-counter threshold is exceeded, the only response is a signal by the control, however, this is not a true alarm status and does not shut down the unit. hc:C1 hc:C2 hc:Fi hc:uF Alarm: Compressor 1 hour-counter exceeded Alarm: Compressor 2 hour-counter exceeded Alarm: air filter hour-counter exceeded Alarm: re-circulation fan hour-counter exceeded

MAINTENANCE OF HUMIDIFIER CYLINDER


The control does not measure the humidifier operating hours, however, lime scales must be periodically cleaned off the steam cylinder. Excessive lime scales can cause malfunctions or an alarm signal by the humidifier interface circuit. Before the cylinder is removed for replacement or cleaning, water must be thoroughly drained from the boiler. This command is not given directly by the UG30/mP30 control, but by the CDA303 circuit.
Note: To prevent tripping of the differential on the distribution panel, dip-switch N7 is turned ON: In this way, the CU contactor is de-energised during discharge and, as a result, there is no current dispersion.

To open the solenoid discharge valve and empty the cylinder, you must switch the MANUAL DRAINING jumper contacts on the CP1 card from GND-ON (automatic) to GND-DR (manual). Attention: electronic components are sensitive to static charges emitted by the human body. Touch a grounding facility before handling any electronic component. - Open the humidifier thermal breaker; - Clean or replace the cylinder; - After cleaning or replacing the cylinder, re-position the component and restore normal humidifier operation.

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

29 (44)

INSTRUCTION MANUAL UG30 CONTROL

REMOTE CONTROL OF UNIT


The unit can be started and stopped alternatively by : 1. a remote contact (or remote control); 2. a supervision system connected to the microprocessor by a serial cable. ON/OFF FROM REMOTE CONTACT: the unit is started via the ID1 digital input. When the input is open, the unit is on stand-by signalled by the OFF symbol on the display. If, instead, 24V is supplied, the unit is powered up (signalled by the ON symbol on the display). GLb
HE

GENERAL
ON/OFF digital input: enables the ID1 digital input as a remote ON/OFF. 0= absent 1= present, disables ON/OFF switching from the keyboard. 2= absent, disables ON/OFF switching from the keyboard (only in the case of supervision systems)

Minimum 0

Maximum 2

Default 0

SUPERVISION SYSTEM A supervision system exchanges data via serial cable with the units basic circuit which is remotely commanded and controlled: to this end, the RS485 Serial Circuit (optional) must be present. GLb
Ho HP

GENERAL
Serial address in the RS485 supervision network. Supervisor serial Baudrate. It sets the line speed on the RS485 supervision network. 1= 1200 Baud 2= 2400 Baud 3= 4800 Baud 4= 9600 Baud 5= 19200 Baud

Minimum 1 1

Maximum 200 5

Default 1 5

30 (48

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

INSTRUCTION MANUAL UG30 CONTROL

CONNECTING MORE THAN ONE UNIT


It is possible to electronically connect up to 6 units on the same local network connection, where 5 units run in normal operation and 1 unit in stand-by. In order to distribute the work load an automatic unit rotation is managed, it works on a temporal base at programmable time intervals (FACTORY H4 parameter). When necessary 1 of the units is turned off and the unit in stand-by is activated. The rotation follows the progressive order of the addresses set (FACTORY H3 parameter). If an Alarm event occurs on one of the units connected the control automatically activates the unit in Stand-by (serious alarms are specified in the section entitled "DESCRIPTION OF ALARM CODES"). IMPORTANT: the Units are electrically connected using digital output DO7 and digital input ID5 (see electric drawings), therefore the connection can not be made in the following cases: - for units that are already using the digital output DO7 for the dehumidification electrovalve(CW-DX airconditioners) or for reporting of a non-serious alarm status (CW/S-DX/S air-conditioners). - for units that are already using the digital in put ID5 for the connection of optional digital sensors (high/low temperature/humidity sensors, water leak detector). After having performed the electrical connection between the units , it is necessary to modify the parameters "GLb": H2, H3, H4 ed HA. GLb
H2 H3 H4 HA

GENERAL
Number of units connected: 0 = stand-alone unit; 26 = total number of units connected. Address for unit connected for rotation. Each unit must have a different address between 1 and 6. If two units have the same address then they will be placed in stand-by. Rotation time between the units in hours. If H4 = 0 the control will perform a test, the units will rotate at intervals of 2 minutes. Digital output configuration DO7: 0 = excited relay in dehumidification (CW unit) 1 = de-energize in dehumidification (DX unit) 2 = alarm relay for non-serious alarms (CW/S-DX/S only) 3 = output for rotation control

Min. 0 1 0 0

Max 6 6 250 3

Measurement unit hours -

Default 0 0 168 3

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

31 (44)

INSTRUCTION MANUAL UG30 CONTROL

TEMPERATURE SET-POINTS
To change set-points, you have to input the USER password to access the SetP menu in programming mode. SEtP
r1 r2 r3 r4

SETTING
Temperature (summer) set-point. Used for setting the cooling set-point. Cooling differential. Heating differential. Temperature neutral zone. When the temperature measured by sensor B1 is within the neutral temperature zone, all actuators are OFF, except in the following cases: Minimum ON time or the switch-off delay between the two compressors has not elapsed yet; the compressors (or the valve) are operating following a dehumidification request. Delivery temperature lower limit. When the temperature read by delivery sensor B4 drops by 3C below the set limit (default = 15C), the cold actuators (compressors or refrigerated water valve) are switched off. The actuators are automatically restored when temperature rises back to rn value.

Minimum 0 0.1 0.1 0.1

Maximum Measurement unit 50 C 11.0 C 11.0 C 20.0 C

Default 23 1.5 1.5 0.2

rn

-20

30

15

VALVOLA ACQUA CALDA

SET POINT DI TEMP.

VALVOLA ACQUA FREDDA

r1
(Default 23C) 100% 100%

r4
(Default 0.2C)
Zona neutra per la temp.

temperatura ambiente da sonda B1

r3
(Default 1.5C)

r2
(Default 1.5C)

RESISTENZE

SET POINT DI TEMP.

COMPRESSORI

R1+R2 R2 R1

r1
(Default 23C)

C2

C1

r4
(Default 0.2C)
Zona neutra per la temp.

temperatura ambiente da sonda B1

r3
(Default 1.5C)

r2
(Default 1.5C)

32 (48

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

INSTRUCTION MANUAL UG30 CONTROL

HUMIDITY SET-POINT
SEtP
r5 r6 r7 r8

SETTING
Humidity set-point Humidification differential. Dehumidification differential. Humidity neutral zone. When the temperature measured by sensor B3 is within the neutral temperature zone, the 0-10V output, which activates the humidifier, equals 0 and dehumidification is not active.

Minimum 20 1 1 0

Maximum Measurement unit 90 %R.H. 20 %R.H. 20 %R.H. 20 %R.H.

Default 50 5 5 10

UMIDIFICA

SET POINT DI UMIDIT

DEUMIDIFICA

r5
(40%) 10Vdc (Default 50%) (60%) ON

r8
(Default 10%)
Zona neutra di umidit

OFF

umidit ambiente da sonda B3

r6
(Default 5%)

r7
(Default 5%)

CALIBRATION AND SETTINGS


By using parameters 6, 7, 8, 9 the measurement of the sensors can be corrected if a difference is noted between the value measured by the sensor and the effective value measured by a precision instrument. Prob
6 7 8 9

SENSORS
B1 sensor calibration. Room temperature. B2 sensor calibration. External air temperature. B3 sensor calibration. Room relative humidity. B4 sensor calibration. Delivery temperature.

Minimum -6.0 -6.0 -10 -6.0

Maximum Measurement unit 6.0 C 6.0 10 6.0 C %R.H. C

Default 0 0 0 0

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

33 (44)

INSTRUCTION MANUAL UG30 CONTROL

CLOCK/DATER TIME BANDS (with optional clock circuit only)


SETTING THE DATE AND TIME To modify date and time, you have to input the USER password to access the parameters of the Clock menu in programming mode.

23.9

53 %rH

(press for 5 seconds)

uP

**

uP

**: input the USER password contained in the envelope enclosed with the manual.

Prob

Cloc

10:39

10:39

10:54

SETTING THE TIME-BANDS If using controls with an optional clock circuit fitted, you can set the automatic start-up and stop of the unit on a time basis (time-bands) obtaining up to 2 daily ON-OFF cycles. N.B.: The ON status from time-bands operates only if the unit is activated from the keyboard and from a remote input. Enabling of time-bands is through the following parameter: Cloc
rt 0= time-band disabled 2= ON/OFF from time-bands Minimum 0 Maximum 2 Default 0

34 (48

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

INSTRUCTION MANUAL UG30 CONTROL


To enable the time-bands, enter the Cloc menu and select the rt=2 parameter.

Cloc

10:39

rt

rt

rt

rt

.
(*) (*) if you press key (Tuesday), 7 (Sunday). Keys and you can view the time-bands in sequence for every day of the week: 1 (Monday), 2 on

can be used to modify the starting time of the selected band in 10-minute steps. indicates switch OFF time.
rt
ON

the display indicates unit switch ON time, and


rt
ON

8:30

8:30

8:40

rt
ON

19:00 rt

OFF

If the hours of the time-bands of a given day are valid for the following days too, they can be copied by holding down for 3 seconds. key On completion of copying, symbol automatically stops flashing and the next day is displayed. If the next day and then press it again for another 3 seconds.

has to be copied as well, release key MANUAL OVERRIDE START OR STOP

OFF status from time-bands can be viewed by means of the symbol on the display; the unit is put on stand-by as if the ON/OFF key had been pressed. However, the unit can be manually forced to start.
ON

Access the Cloc menu, view the hour-band that caused the OFF status, and then press the the unit,

OFF

key to restart

23.9
..

53 %rH

..

Cloc

..

19:00 rt

OFF

19:00 rt

OFF

ON OFF

19:00 rt

ON

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

35 (44)

INSTRUCTION MANUAL UG30 CONTROL

DELAYS DUE TO ALARM SIGNALS


Some alarm signals can be delayed with respect to the activation of a component to allow stable operating conditions to be reached for example: Alarm A:FL (airflow absent or presence of fire-smoke) is not read during the first 30 seconds after fan start; this value is linked to the FACTORY P1 parameter. Alarms LO:C1 and LO:C2 (1/2 circuit low pressure) are not read during the first 180 seconds after start-up of the relevant compressor. This value is linked to the FACTORY parameter P3. ALAR
PA

ALARM
Delay of low/high temperature/humidity alarm at start-up. This establishes the delay in recognising low/high temperature and humidity alarms at UNIT start-up. N.B.: The low humidity alarm is delayed at humidifier start-up. This is to avoid a low humidity alarm when a possible humidifier alarm is reset. General alarm delay. This establishes the activation delay of the ID5 general alarm. This establishes the delay in recognising the flow alarm from start of fan. This establishes the delay in recognising the flow alarm while the fan is operating. This establishes the delay in recognising the low pressure alarm at compressor start-up to allow reaching a stable situation.

Minimu m 0

Maximum 150

Measurement unit min

Default 15

PC P1 P2 P3

0 0 0 0

250 250 90 250

sec sec sec sec

0 30 3 180

SERIOUS ALARMS
Two different types of alarm warnings are available: "serious " and "non-serious" alarms (see section "DESCRIPTION OF ALARM CODES "). In a configuration with more than one unit connected, serious alarms trigger the activation of the DO7 relay and therefore the activation of the unit in stand-by. In a configuration with no unit rotation, the FACTORY parameters HA and HF can be changed, in such a way as to have two different alarm signals: - "serious alarms" through the general alarm relay DO6; - "non-serious alarms" through the dehumidification relay DO7 (CW/S and DX/S only). GLb
HA

GENERAL
Configuration of digital output DO7:

Min 0

Max 3

Default 3

Setting to manage 2 alarms 2

2 = alarm relay for not critical alarms (follows the logic set through the parameter HF)
HF 3 = output for rotation control Alarm relay logic: 0 = de-energise in alarm for all the alarms 2 = de-energise in alarm only for the serious alarms 0 3 0 2

ACTIVE ALARMS
When an alarm occurs, the control performs the following actions: displays the symbol and the alarm code; de-energize the DO6 relay (general alarm); the relays functioning logic, normally energised or de-energised, and the alarm category that activates this relay is set by the HF parameter (default equals 0); (in AMICO CW/S and DX/S units, if HA is set to 2) relay D07 de-energised (non-serious alarm); relay logic, normally energised or de-energised, is defined by parameter HF (default setting is 0); ; lights up the red light of key activates the buzzer (if the USER P4 parameter is set at a value other than zero).

36 (48

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

INSTRUCTION MANUAL UG30 CONTROL


ALAR
P4

ALARM
Establishes buzzer activation time in case of an alarm: 0 = OFF (buzzer always disabled) 1-14 = the buzzer is automatically silenced after P4 minutes have elapsed. 15 = continuous. The buzzer remains active until the alarm situation ceases (on automatic reset) or for as long as the Alarm push-button is pressed.

Minimu m 0

Maximum 15

Measurement unit min

Default 1

All alarms are manually resettable; to reset an alarm press key cause.

for about 2 seconds after eliminating the

READING OF THE ALARMS HISTORIC RECORD (with optional clock card only)
When an alarm occurs, the following are automatically stored in the memory: alarm code, hour, minute and date on which alarm occurred, up to a maximum of 300 signalling operations. To view the list of stored alarms, enter the AIPG menu: the code of the last alarm occurring is shown and, if you press repeatedly the hour, minute and date.
2 2 01

LP:C1

10:29

3-4

, the list of all the alarms is displayed; when you reach the first position in which no alarm is If you press key stored, "- - - - dashes are shown instead to the code. The display includes an incrementing index on the right-hand field, which identifies the current position; the 55 hundreds are shown in the left-hand field (E.g.: 1 ---- , indicate the alarm code stored in position 155).
1 2 3

rES

LP:C1

----

----

55

DELETION OF ALARMS HISTORIC RECORD If you access programming mode with the USER password and reach the AIPG menu, you can delete the entire alarms historic record by simultaneously pressing keys and for 5 seconds. This operation re-initialises the clock card EEprom and must be performed when installing the card itself. When you have cleaned the alarms page, the "- - - - dashes are shown. The displayed alarm codes are those shown in the following chapter; some special codes are also included to report the following events: Code PrOn RES Meaning UNIT started after power failure Manual reset of alarms by Alarm key.

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

37 (44)

INSTRUCTION MANUAL UG30 CONTROL

ALARM CODES DESCRIPTION


All possible alarm codes are listed below. All alarms, except the clock alarm, are read only with the UNIT ON. Code CLoC SP:A Description Clock alarm. External general alarm. Restart Manual Alarm type Non-serious Serious

CLoC: clock alarm faulty An alarm generated by a malfunctioning clock card. It causes an interruption of the hour-bands and the regulator goes into ON status even if it is commanded to OFF by the current band. This event does not shut down the alarms historic record function, which continues recording the signals, but with incorrect time values. SP:A external general alarm Alarm configurable with parameters Pb and PC. TEMPERATURE AND HUMIDITY LIMITS EXCEEDED These are signal-only alarms linked to an excess in the set temperature and humidity levels. Restart Code Description High room humidity alarm. Automatic HI:RH Low room humidity alarm. Automatic LO:RH High room temperature alarm. Automatic HI:Rt Low room temperature alarm. Automatic LO:Rt

Alarm type Non-serious Non-serious Serious Non-serious

The thresholds are defined by FACTORY parameters P6, P7, P8, P9 according to the following diagrams. They are ignored during UNIT start-up for a time period equal to the PA parameter (see paragraph DELAYS DUE TO ALARM SIGNALLING). The alarm is tripped if the set threshold is exceeded for at least one minute.
SET POINT DI TEMPERATURA

r1
10C (Default 23C) 30C
SOGLIA DI INTERVENTO DELL'ALLARME SEGNALAZIONE DI ALLARME

LO:Rt P6
(Default 13C)

HI:Rt P7
(Default 7C)

T ambiente da sonda B1

If the high temperature threshold is exceeded, this causes immediate start-up of the compressors without respecting the relevant times.
SET POINT DI UMIDIT

r5
30% (Default 50%) 80%
SOGLIA DI INTERVENTO DELL'ALLARME SEGNALAZIONE DI ALLARME

LO:RH P8 P9

HI:RH

(Default 20%) (Default 30%)

rH umidit ambiente da sonda B3

38 (48

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

INSTRUCTION MANUAL UG30 CONTROL


FUNCTIONAL ALARMS Code A:FL CL:Fi Co:FA Ct:H Ft:H HE:OH HP:C1-HP:C2 HU:FA LP:C1-LP:C2 Description Airflow alarm or Fire /smoke detector alarm Air filter obstructed. Cooling function alarm. Compressor/s thermal breaker alarm. Fan/s thermal breaker alarm. Restart Manual Manual Manual Manual Manual Manual Manual
(***)

Electrical heating elements overheating.


Compressor 1./2. high pressure. Humidifier alarm. Compressor 1./2. low pressure.

Alarm type Serious Serious Serious Serious Serious Non-serious Serious Serious

A:FL Airflow alarm or optional Fire/smoke detector alarm The alarm can be delayed by parameters P1 and P2 and causes all devices to switch off immediately. CI:F1 dirty filter Signal only alarm. To reset it, reset the filter hour-counter (USER parameter Fc). CO:FA: delivery (or cooling function) high temperature alarm It is read by the B4 delivery temperature sensor when the cooling function is active, but the difference between the delivery air temperature and room temperature is lower than the value defined by the Pd parameter (default 3C). The alarm has a fixed delay set at 4 minutes and is tripped only if the cold actuators are ON (at least one compressor ON or refrigerated water valve open by more than 50%) and the hot actuators are OFF. When this alarm is noted, it shuts down only the compressor that is ON (running at that moment) , while the second compressor remains enabled. Ct:H compressor thermal breaker alarm Causes instantaneous shut-down of the compressor. Ff:H fan thermal breaker alarm Causes instantaneous shut-down of all devices. HE:OH heating elements thermal breaker alarm Causes instantaneous shut-down of the heating elements. HP:C1-HP:C2 circuit 1 or 2 high pressure Causes immediate shut-down of the compressor without respecting the relevant times. HU:FA humidifier alarm Alarm delayed by 30 seconds. This is detected by the CDA3403 card and is transmitted to the UG30 control which disables the U1 humidifier output. LP:C1-LP:C2 circuit 1 or 2 low pressure This alarm is detected only if the compressor is ON and is ignored during the first 180 seconds from compressors start. It causes immediate shut-down of the compressor without respecting the relevant times.

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

39 (44)

INSTRUCTION MANUAL UG30 CONTROL


SENSOR INDUCED ALARMS These alarms are generated for open or short-circuited sensors. Code Description Sensor B1 fault. SE:1F Sensor B2 fault. SE:2F Sensor B3 fault. SE:3F SE:4F Restart Automatic Automatic Automatic Automatic Alarm type Serious Non-serious Non-serious Non-serious

Sensor B4 fault.

SE:1F room temperature sensor fault. Alarm delayed by 1 minute from the moment when the UNIT is turned ON and from when the error is detected. When the error is detected, all components, except the fan, are turned OFF, respecting the configured times with the exception of fan time. SE:2F external air sensor fault. Alarm delayed by 1 minute from the moment when the UNIT is turned ON and from when the error is detected. When the error is detected, all functions (summer/winter switch-over) associated with the sensor are disabled. SE:3F humidity sensor. Alarm activates when the sensor is disconnected (if the input is configured as 420mA) and for currents that are lower than 3 mA or above 23 mA. Alarm delayed by 1 minute from the moment when the UNIT is turned ON and from when the error is detected. When the error is detected, all functions associated with the sensor (humidification, dehumidification) are disabled SE:4F delivery air temperature sensor. Alarm delayed by 1 minute from the moment when the UNIT is turned ON and from when the error is detected. When the error is detected, all functions associated with the sensor (CO:FA alarm management) are disabled.

40 (48

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

INSTRUCTION MANUAL UG30 CONTROL

DEFAULT VALUES
Prob
/1 /2 /3 /4 /5 /6 /7 /8 /9 /C

SENSORS
Sensor B2 presence (external air temperature) Sensor B3 presence (room relative humidity) Sensor B4 presence (delivery temperature) Humidity value at 4mA Humidity value at 20mA Sensor B1 calibration (room temperature) Sensor B2 calibration (external air temperature) Sensor B3 calibration (room relative humidity) Sensor B4 calibration (delivery temperature) Measurement unit (0=C,1=F)

Type FACTORY FACTORY FACTORY FACTORY FACTORY FACTORY FACTORY FACTORY FACTORY USER Type USER USER USER USER USER USER USER USER FACTORY FACTORY FACTORY FACTORY FACTORY FACTORY FACTORY FACTORY Type FACTORY FACTORY FACTORY USER USER USER Type FACTORY USER USER USER USER FACTORY Type FACTORY FACTORY FACTORY USER FACTORY FACTORY FACTORY FACTORY FACTORY USER FACTORY USER

Minimu m 0 0 0 0 /4 -6.0 -6.0 -10 -6.0 0 Minimu m rA 0.1 0.1 0.1 rC 1 1 0 -20 rA 0 rC 0 10 -2.0 -20 Minimu m 0 0 0 0 0 0 Minimu m 0 0 0 0 0 0 Minimu m 0 0 0 0 1 0 0 0 0 0 0 0

maximum Measurement unit 1 flag 2 flag 1 flag /5 %R.H. 100 %R.H. 6.0 C 6.0 C 10 %R.H. 6.0 C 1 flag maximum Measurement unit rb C 11.0 C 11.0 C 20.0 C rd %R.H 20 %R.H. 20 %R.H. 20 %R.H. rb C 60 C rd %R.H. 100 %R.H. 1 flag 3600 sec 2.0 30 C

Default 0,1 0,2 0,1 0.0 100.0 0 0 0 0 0 Default 23 1.5 1.5 0.2 50 5 5 10 0.0 35.0 20 90 1 600 0.0 15

SEtP
r1 r2 r3 r4 r5 r6 r7 r8 rA rb rC rd rE rF rG rn

REGULATOR
Temperature (summer) set-point. Cooling differential. Heating differential. Temperature neutral zone. Humidity set-point Humidification differential Dehumidification differential Humidity neutral zone. Minimum temperature set point Maximum temperature set point Minimum humidity set point Maximum humidity set point Adjustment type Integration time for P+I Enable compensation Minimum delivery temperature set point

Com
c4 c6 c7 c8 c9 cA

COMPRESSOR
Delayed start-up between two compressors Compressor rotation Delayed compressor start from fan start-up. Hour-counter threshold for compressor (0=disabled hour-counter) Compressor 1 hour-counter Compressor 2 hour-counter FANS Fan mode functioning Hour-counter threshold for fan (0=disabled hour-counter) Delivery fan hour-counter Hour-counter threshold for filter (0=disabled hour-counter) Filter hour-counter Fan delayed switch-off

maximum Measurement Default unit 300 sec 90 (DX-DX/S) 1 flag 1 (DX-DX/S) 300 sec 60 (DX-DX/S) 30000 hours 0 (DX-DX/S) 30000 hours 0 (DX-DX/S) 30000 hours 0 (DX-DX/S) maximum Measurement unit 1 flags 30000 30000 30000 30000 900 hours hours hours hours sec Default 0= no RV 1= con RV 0 0 1000 0 10 Default 30 3 180 (DX-DX/S) 1 3 13.0 7.0 20.0 30.0 15 2 0

FAn
F1 F9 FA Fb Fc Fd

ALAR ALARM
P1 P2 P3 P4 P5 P6 P7 P8 P9 PA Pb PC Delayed flow alarm at start Delayed flow alarm during operation Delayed low pressure alarm at compressor start-up Buzzer activation Reset alarms Delta from set for low temperature alarm Delta from set for high temperature alarm Delta from set for low humidity alarm Delta from set high humidity alarm Alarm start delay high/low temperature /humidity Management type general alarm input ID5 General alarm delay

maximum Measurement unit 250 sec 90 sec 500 sec 15 5 50 50 50 50 150 6 250 min flag C C %R.H. %R.H. min flag sec

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

41 (44)

INSTRUCTION MANUAL UG30 CONTROL


GLb
H1 H2 H3 H4 H5 H6

GENERAL
Unit model Number of connected units Address of connected unit Rotation time between all connected units Functioning mode of chilled water outputs OUT1-OUT2 Functioning mode of hot water outputs OUT3-OUT4

Type FACTORY FACTORY FACTORY FACTORY FACTORY FACTORY

Minimu m 0 0 1 0 1 0

maximum Measurement unit 2 flag

Default

H7 H8 H9

3 point valve excursion time end dumper FC Humidifier present Dehumidification present

FACTORY FACTORY FACTORY

0 0 0

HA

Digital output function DO7

FACTORY

Hb HC Hd HE HG HH Hi HL Ho HP

Cloc
rt

Output function Y2 Functioning of B2 sensor Functioning of B3 sensor Digital input ON/OFF Delay at power up USER Password Keyboard lock-out Parameters setting Serial address for supervision network Serial baud rate for supervisor CLOCK Hour-bands setting

FACTORY FACTORY FACTORY USER USER USER USER FACTORY USER USER Type USER

0 0 0 0 0 0 0 0 1 1 Minimu m 0

0 (DX-DX/S) 1,2 (CWCW/S) 6 flag 0 16 6 flag 16 250 ore 168 5 flag 3 (CW) 1 (DX/S) 1 / 2 / 5 (DX) 4 flag 0/3/4 (CW-DX) 0/1/3 (CW/S-DX/S) 600 sec 150 1 flag 0/1 8 flag 3 (CW) 8 (CW/S) 0 / 2 (DX) 5 (DX/S) 3 flag 0 (CW) / 3 2 (CW/S) / 3 1 (DX) / 3 2 (DX/S) / 3 2 flag 0 3 flag 0 1 flag 0 2 flag 0/1/2 300 sec 0 200 22 (**) 1 flag 0 3 flag 1 200 1 5 flag 5 maximum Measurement Default unit 2 flag 0

(**): "USER" password contained in envelope enclosed with manual

MEMORY RESET
in order to reset the parameter values. With the control programme on, press the button After having performed this first step: - Set the default values, see above paragraph Default Values; - Configure the devices and the sensors fitted according to the type of unit, adjust the set-points that needed to be different from the default values.

APPENDIX mask flowcharts

42 (48

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

INSTRUCTION MANUAL UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

43 (44)

UG30 Screen Flow Chart - Access password "USER"

(press button for 5 seconds)

00

uP

(insert password "USER")

**

uP

(press button to confirm)

(reading only) (reading and programming ) (*)

Prob

SetP

r1

r2

r3

r4

r5

r6

r7

r8

r9

ro

rP

rr

Con

c8

c9

cA

FAn

F9

FA

Fb

FC

ALAr

P4

PA

PC

GLb

H2

H3

H4

HE

HF

HG

HH

Hi

Ho

HP

Hr

Cloc

11:54

3 - 4 - 01

rt

AlPG

rES

10:37

3 - 4 - 01

(alarm history)

LP:C1

10:29

3 - 4 - 01

return to PROB screen by pressing again on the button:

Prob
(*)

UG30 Screen Flow Chart Access password FACTORY

(press on both buttons at the same time for 5 seconds )

00

FP

(insert password "FACTORY")

***

FP

(press button to confirm)

(reading and programming) (**)

Prob

SetP

r1

r2

r3

r4

r5

r6

r7

r8

r9

rA

rb

rC

Con

c1

c2

c3

c4

c5

c6

c7

c8

c9

cA

FAn

F1

F2

F3

F4

F5

F6

F7

ALAr

P1

P2

P3

P4

P5

P6

P7

GLb

H1

H2

H3

H4

H5

H6

H7

H8

H9

HA

Hb

Cloc

11:54

3 - 4 - 01

rt

AlPG

rES

10:37

3 - 4 - 01

(alarm history) return to PROB screen by pressing again on the button:

LP:C1

10:29

3 - 4 - 01

Prob
(**)

INSTRUCTION MANUAL UG30 CONTROL

UNIFLAIR ITALIA S.p.A.


Via dellindustria, 10 35020 BRUGINE (Padova) - Italy Tel. +39 (0)49 9713211 Fax +39 (0)49 5806906 Internet: www.UNIFLAIR.com E-mail: INFO@UNIFLAIR.com

44 (48