Gateway IntesisBox-BACnet-Lonworks V43

1. BACnet Protocol Implementation Conformance Statement (PICS) ......................... 2 1.1 BACnet Standardized Device Profile (Annex L): .............................................. 2 1.2 Segmentation Capability: ............................................................................ 2 1.3 Data Link Layer Options: ............................................................................. 3 1.4 Device Address Binding:.............................................................................. 3 1.5 Networking Options: ................................................................................... 3 1.6 Character Sets Supported ........................................................................... 3 1.7 Gateway ................................................................................................... 3 2. BACnet Interoperability Building Blocks Supported (BIBBs) .................................. 4 2.1 Data Sharing BIBBs .................................................................................... 4 2.2 Alarm and Event Management BIBBs ............................................................ 4 2.3 Scheduling BIBBs ....................................................................................... 5 2.4 Trending BIBBs .......................................................................................... 5 2.5 Network Management BIBBs ........................................................................ 5 2.6 Device Management BIBBs .......................................................................... 6 3. Objects .......................................................................................................... 7 3.1 Supported Object Types .............................................................................. 7 3.2 Device Object Type .................................................................................... 8 3.3 Analog Input Object Type ............................................................................ 9 3.4 Analog Output Object Type ........................................................................ 10 3.5 Analog Value Object Type.......................................................................... 10 3.6 Binary Input Object Type .......................................................................... 12 3.7 Binary Output Object Type ........................................................................ 13 3.8 Binary Value Object Type .......................................................................... 13 3.9 Multistate Input Object Type ...................................................................... 15 3.10 Multistate Output Object Type .................................................................. 16 3.11 Multistate Value Object Type .................................................................... 17

Intesis Software SL

1. BACnet Protocol Implementation Conformance Statement (PICS)

Date: 2011-02-07 Vendor Name: Intesis Software SL Product Name: IntesisBox-Bacnet-Lon Product Model Number: IntesisBox-Bacnet-Lon Application Software Version: 43.0.3 Firmware Revision: 43.0.3 BACnet Protocol Revision: 2

Product Description: Lonworks (FT-10) to BACnet/IP Gateway Mapping of network variables as Bacnet Objects to enable read and write Lonworks data points.

1.1 BACnet Standardized Device Profile (Annex L):

BACnet Operator Workstation (B-OWS) BACnet Building Controller (B-BC) BACnet Advanced Application Controller (B-AAC) BACnet Application Specific Controller (B-ASC) BACnet Smart Sensor (B-SS) BACnet Smart Actuator (B-SA)

Additional BACnet Interoperability Building Blocks Supported (Annex K): Reference of BIBBs List

. .

1.2 Segmentation Capability:


Segmented request supported Segmented responses supported No No Yes Yes Window Size Window Size

Intesis Software SL

1.3 Data Link Layer Options:


BACnet IP, (Annex J) BACnet IP, (Annex J), Foreign Device ISO 8802-3, Ethernet (Clause 7) ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8) ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s) ____ MS/TP master (Clause 9), baud rate(s): MS/TP slave (Clause 9), baud rate(s): Point-To-Point, EIA 232 (Clause 10), baud rate(s): Point-To-Point, modem, (Clause 10), baud rate(s): LonTalk, (Clause 11), medium: _____ Other:

1.4 Device Address Binding:


Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.) Yes No

1.5 Networking Options:


Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc. Annex H, BACnet Tunneling Router over IP BACnet/IP Broadcast Management Device (BBMD) Does the BBMD support registrations by Foreign Devices? Yes No

1.6 Character Sets Supported


Indicating support for multiple character sets does not imply that they can all be supported simultaneously. ANSI X3.4 IBM/Microsoft DBCS JIS C 6226 ISO 10646 (UCS-4) ISO 10646 (UCS-2) ISO 8859-1

1.7 Gateway
If this product is a communication gateway, describe the types of non-BACnet equipment/network(s) that the gateway supports: Cable pair Lonworks (FT-10) bus and all devices in the bus.

Intesis Software SL

2. BACnet Interoperability Building Blocks Supported (BIBBs)


2.1 Data Sharing BIBBs
BIBB Type DS-RP-A DS-RP-B DS-RPM-A DS-RPM-B DS-RPC-A DS-RPC-B DS-WP-A DS-WP-B DS-WPM-A DS-WPM-B DS-COV-A Active Data Sharing-ReadPropertyA Data Sharing-ReadPropertyB Data Sharing-ReadPropertyMultipleA Data Sharing-ReadPropertyMultipleB Data Sharing-ReadPropertyConditionaA Data Sharing-ReadPropertyConditionalB Data Sharing-WritePropertyA Data Sharing-WritePropertyB Data Sharing-WritePropertyMultipleA Data Sharing-WritePropertyMultipleB Data Sharing-COVA BACnet Service ReadProperty ReadProperty ReadPropertyMultiple ReadPropertyMultiple ReadPropertyConditional ReadPropertyConditional WriteProperty WriteProperty WritePropertyMultiple WritePropertyMultiple SubscribeCOV ConfirmedCOVNotification UnconfirmedCOVNotification SubscribeCOV ConfirmedCOVNotification UnconfirmedCOVNotification SubscribeCOV ConfirmedCOVNotification UnconfirmedCOVNotification SubscribeCOV ConfirmedCOVNotification UnconfirmedCOVNotification UncofirmedCOVNotification UncofirmedCOVNotification Initiate Execute

DS-COV-B

Data Sharing-COVB

DS-COVP-A DS-COVP-B

Data Sharing-COVPA Data Sharing-COVPB

DS-COVU-A DS-COVU-B

Data Sharing-COV-UnsolicitedA Data Sharing-COV-Unsolicited-B

2.2 Alarm and Event Management BIBBs


BIBB Type AE-N-A AE-N-I-B AE-N-E-B AE-ACK-A AE-ACK-B AE-ASUM-A AE-ASUM-B AE-ESUM-A AE-ESUM-B AE-INFO-A AE-INFO-B AE-LS-A AE-LS-B Alarm and Event-NotificationA Alarm and Event-Notification InternalB Alarm and Event-Notification ExternalB Alarm and Event-ACKA Alarm and Event-ACKB Alarm and Event-SummaryA Alarm and Event-SummaryB Event-SummaryA Event-SummaryB Alarm and Event-InformationA Alarm and Event-InformationB Alarm and Event-LifeSafetyA Alarm and Event-LifeSafetyB Active BACnet Service ConfirmedEventNotification UnconfirmedEventNotification ConfirmedEventNotification UnconfirmedEventNotification ConfirmedEventNotification UnconfirmedEventNotification AcknowledgeAlarm AcknowledgeAlarm GetAlarmSummary GetAlarmSummary GetEnrollmentSummary GetEnrollmentSummary GetEventInformation GetEventInformation LifeSafetyOperation LifeSafetyOperation Initiate Execute

Intesis Software SL

2.3 Scheduling BIBBs

BIBB Type SCHED-A SCHED-I-B SchedulingA (must support DS-RP-A and DS-WP-A) Scheduling-InternalB (shall support DS-RP-B and DS-WP-B) (shall also support ether DM-TS-B or DS-UTC-B) Scheduling-ExternalB (shall support SCHED-I-B and DS-WP-A) Trending - Viewing and Modifying TrendsA Trending - Viewing and Modifying Trends InernalB Trending - Viewing and Modifying Trends ExternalB Trending - Automated Trend RetrievalA Trending - Automated Trend RetrievalB

Active

BACnet Service

Initiate

Execute

SCHED-E-B T-VMT-A T-VMT-I-B T-VMT-E-B T-ATR-A T-ATR-B

ReadRange ReadRange ReadRange ConfirmedEventNotification ReadRange ConfirmedEventNotification ReadRange

2.4 Trending BIBBs


BIBB Type T-VMT-A T-VMT-I-B T-VMT-E-B T-ATR-A T-ATR-B Active Trending - Viewing and Modifying TrendsA Trending - Viewing and Modifying Trends InernalB Trending - Viewing and Modifying Trends ExternalB Trending - Automated Trend RetrievalA Trending - Automated Trend RetrievalB BACnet Service ReadRange ReadRange ReadRange ConfirmedEventNotification ReadRange ConfirmedEventNotification ReadRange Initiate Execute

2.5 Network Management BIBBs


BIBB Type NM-CE-A Network Management - Connection EstablishmentA Active BACnet Service Establish-Connection-ToNetwork Disconnect-Connection-ToNetwork Establish-Connection-ToNetwork Disconnect-Connection-ToNetwork Who-Is-Router-To-Network I-Am-Router-To-Network I-Could-Be-Router-ToNetwork Initialize-Routing-Table Initialize-Routing-Table-Ack Who-Is-Router-To-Network I-Am-Router-To-Network Initialize-Routing-Table Initialize-Routing-Table-Ack Initiate Execute

NM-CE-B

Network Management - Connection Establishment B

NM-RC-A

Network Management - Router ConfigurationA

NM-RC-B

Network Management - Router ConfigurationB

Intesis Software SL

2.6 Device Management BIBBs


BIBB Type DM-DDB-A DM-DDB-B DM-DOB-A DM-DOB-B DM-DCC-A DM-DCC-B DM-PT-A DM-PT-B DM-TM-A DM-TM-B DM-TS-A DM-TS-B DM-UTC-A DM-UTC-B DM-RD-A DM-RD-B Device Management - Dynamic Device BindingA Device Management - Dynamic Device BindingB Device Management - Dynamic Object BindingA Device Management - Dynamic Object BindingB Device Management - DeviceCommunicationControlA Device Management - DeviceCommunicationControlB Device Management - PrivateTransferA Device Management - PrivateTransferB Device Management - Text MessageA Device Management - Text MessageB Device Management - TimeSynchronizationA Device Management - TimeSynchronizationB Device Management - UTCTimeSynchronizationA Device Management - UTCTimeSynchronizationB Device Management - ReinitializeDeviceA Device Management - ReinitializeDeviceB Active BACnet Service Who-Is I-Am Who-Is I-Am Who-Has I-Have Who-Has I-Have DeviceCommunicationControl DeviceCommunicationControl ConfirmedPrivateTransfer UnconfirmedPrivateTransfer ConfirmedPrivateTransfer UnconfirmedPrivateTransfer ConfirmedTextMessage UnconfirmedTextMessage ConfirmedTextMessage UnconfirmedTextMessage TimeSynchronization TimeSynchronization UTCTimeSynchronization UTCTimeSynchronization ReinitializeDevice ReinitializeDevice AtomicReadFile AtomicWriteFile CreateObject ReinitializeDevice AtomicReadFile AtomicWriteFile ReinitializeDevice UnconfimedCOVNotification UnconfimedCOVNotification AddListElement RemoveListElement AddListElement RemoveListElement CreateObject DeleteObject CreateObject DeleteObject VT-Open VT-Close VT-Data VT-Open VT-Close VT-Data Initiate Execute

DM-BR-A

Device Management - Backup and RestoreA

DM-BR-B DM-R-A DM-R-B DM-LM-A DM-LM-B DM-OCD-A DM-OCD-B

Device Management - Backup and RestoreB Device Management - RestartA Device Management - RestartB Device Management - List ManipulationA Device Management - List ManipulationB Device Management - Object Creation and DeletionA Device Management - Object Creation and DeletionB

DM-VT-A

Device Management - Virtual TerminalA

DM-VT-B

Device Management - Virtual TerminalB

Intesis Software SL

3. Objects
3.1 Supported Object Types
To monitoring and controlling items of Lonworks networks variables, they are assigned with general object types specified by BACnet. The objects type supported is shown in the table below.
Object Type Analog-Input Analog-Output Analog-Value Averaging Binary-Input Binary-Output Binary-Value Calendar Command Device Event-Enrollment File Group Life-Safety-Point Life-Safety-Zone Loop Multistate-Input Multistate-Output Multistate-Value Notification-Class Program Schedule Trend-Log ID 0 1 2 18 3 4 5 6 7 8 9 10 11 21 22 12 13 14 19 15 16 17 20 User defined User defined User defined User defined User defined User defined Supported Management Point User defined User defined User defined

Intesis Software SL

3.2 Device Object Type


Property Identifier
Object_Identifier Object_Name Object_Type System_Status Vendor_Name Vendor_Identifier Model_Name Firmware_Revision Application_Software_Version Location Description Protocol_Version Protocol_Conformance_Class Protocol_Services_Supported Protocol_Object_Types_Supported Object_List Max_APDU_Length_Accepted Segmentation_Supported VT_Class_Supported Active_VT_Sessions Local_Time Local_Date UTC_Offset Daylight_Saving_Status APDU_Segment_Timeout APDU_Timeout Number_Of_APDU_Retries List_Of_Session_Keys Time_Synchronization_Recipients Max_Master Max_Info_Frames Device_Adress_Binding Database_Revision Configuration_Files Last_Restore_Time Backup_Failure_Timeout Active_COV_Subscriptions Profile_Name

Property Datatype
BACneObjectIdentifier CharacterString BACnetObjectType BACnetDeviceStatus CharacterString Unsigned CharacterString CharacterString CharacterString CharacterString CharacterString Unsigned Unsigned BACnetService Supported BACnetObjectTypes Supported BACnetARRAY[N] of BACnetObjectIdentifir Unsigned BACnetSegmentation List of ACnetVTClass List of BACnetVTSession Time Date Signed Boolean Unsigned Unsigned Unsigned List of BACnetSessionKey List of BACnetRecipient Unsigned Unsigned List of BACnetAddress Binding Unsigned BACnetARRAY[N] of BACnetObjectIdentifir BACnetDateTime Unsigned List of BACnetCOV Subscription CharacterString

BACnet
R R R R R R R R R O O R R R R R R R O1 O2 O3,4 O3,4 O4 O4 O1 R R O O5 O6 O6 R R O7 O7 O8 O9 O

IntesisBox
R R R R R R R R R R R R R R R R R R R -

Remarks
User defined User defined DEVICE

Intesis Software SL 246 IntesisBox_BACNET_LON 43.0.1 43.0.1

1 3

3000 3

. .

Intesis Software SL

3.3 Analog Input Object Type


Property Identifier
Object_Identifier Object_Name Object_Type Present_Value Description Device_Type Status_Flags Event_State Reliability Out_Of_Service Update_Interval Units Min_Pres_Value Max_Pres_Value Resolution COV_Increment Time_Delay Notification_Class High_Limit Low_Limit Deadband Limit_Enable Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Profile_Name

Property Datatype
BACneObjectIdentifier CharacterString BACnetObjectType Real CharacterString CharacterString BACnetStatusFlags BACnetEventState BACnetReliability Boolean Unsigned BACnetEngineeringUnits Real Real Real Real Unsigned Unsigned Real Real Real BACnetLimitEnable BACnetEventTransitionBits BACnetEventTransitionBits BACnetNotifyType BACnetARRAY[3] of BACnetTimeStamp CharacterString

BACnet
R R R R1 O O R R O R O R O O O O2 O3 O3 O3 O3 O3 O3 O3 O3 O3 O3 O

IntesisBox
R R R R R R R R R R -

Remarks
User defined User defined ANALOG INPUT

Same the object name

All bits: FALSE always. NORMAL: NORMAL (0) NO_FAULT_DETECTED always. Always FALSE.

NULL (no units)

Any change

Intesis Software SL

3.4 Analog Output Object Type


Property Identifier
Object_Identifier Object_Name Object_Type Present_Value Description Status_Flags Event_State Reliability Out_Of_Service Units Min_Pres_Value Max_Pres_Value Resolution Priority_Array Relinquish_Default COV_Increment Time_Delay Notification_Class High_Limit Low_Limit Deadband Limit_Enable Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Profile_Name

Property Datatype
BACneObjectIdentifier CharacterString BACnetObjectType Real CharacterString BACnetStatusFlags BACnetEventState BACnetReliability Boolean BACnetEngineeringUnits Real Real Real BACnetPriorityArray BACnetBinaryPV Real Unsigned Unsigned Real Real Real BACnetLimitEnable BACnetEventTransitionBits BACnetEventTransitionBits BACnetNotifyType BACnetARRAY[3] of BACnetTimeStamp CharacterString

BACnet
R R R R4 O R R O R R O O O R R O2 O3 O3 O3 O3 O3 O3 O3 O3 O3 O3 O

IntesisBox
R R R RW R R R R R R R R R -

Remarks

User defined ANALOG INPUT

Same the object name All bits: FALSE always. NORMAL: NORMAL (0) NO_FAULT_DETECTED always. Always FALSE. NULL (no units)

Accept all writes as Priority 16 Same Present_Value data Any change

3.5 Analog Value Object Type

Intesis Software SL

10

Property Identifier
Object_Identifier Object_Name Object_Type Present_Value Description Device_Type Status_Flags Event_State Reliability Out_Of_Service Units Priority_Array Relinquish_Default COV_Increment Time_Delay Notification_Class High_Limit Low_Limit Deadband Limit_Enable Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Profile_Name

Property Datatype
BACneObjectIdentifier CharacterString BACnetObjectType Real CharacterString CharacterString BACnetStatusFlags BACnetEventState BACnetReliability Boolean BACnetEngineeringUnits BACnetPriorityArray BACnetBinaryPV Real Unsigned Unsigned Real Real Real BACnetLimitEnable BACnetEventTransitionBits BACnetEventTransitionBits BACnetNotifyType BACnetARRAY[3] of BACnetTimeStamp CharacterString

BACnet
R R R R4 O O R R O R R R R O2 O3 O3 O3 O3 O3 O3 O3 O3 O3 O3 O

IntesisBox
R R R RW R R R R R R R R R -

Remarks

User defined ANALOG VALUE

Same the object name

All bits: FALSE always. NORMAL: NORMAL (0) NO_FAULT_DETECTED always. Always FALSE. NULL (no units) Accept all writes as Priority 16 Same Present_Value data Any change

Intesis Software SL

11

3.6 Binary Input Object Type


Property Identifier
Object_Identifier Object_Name Object_Type Present_Value Description Device_Type Status_Flags Event_State Reliability Out_Of_Service Polarity Inactive_Text Active_Text Change_Of_State_Time Change_Of_State_Count Elapsed_Active_Time Time_Of_Active_Time_Reset Time_Delay Notification_Class Alarm_Value Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Profile_Name

Property Datatype
BACneObjectIdentifier CharacterString BACnetObjectType BACnetBinaryPV CharacterString CharacterString BACnetStatusFlags BACnetEventState BACnetReliability Boolean BACnetPolarity CharacterString CharacterString BACnetDateTime Unsigned Unsigned BACnetDateTime Unsigned Unsigned BACnetBinaryPV BACnetEventTransitionBits BACnetEventTransitionBits BACnetNotifyType BACnetARRAY[3] of BACnetTimeStamp CharacterString

BACnet
R R R R1 O O R R O R R O2 O2 O3 O3 O4 O5 O5 O5 O5 O5 O5 O5 O5 O

IntesisBox
R R R R R R R R R R -

Remarks

User defined BINARY INPUT

Same the object name

All bits: FALSE always. Always NORMAL: NORMAL (0) NO_FAULT_DETECTED always. Always FALSE. NORMAL

Intesis Software SL

12

3.7 Binary Output Object Type


Property Identifier
Object_Identifier Object_Name Object_Type Present_Value Description Device_Type Status_Flags Event_State Reliability Out_Of_Service Polarity Inactive_Text Active_Text Change_Of_State_Time Change_Of_State_Count Time_Of_State_Count_Reset Elapsed_Active_Time Time_Of_Active_Time_Reset Minimum_Off_Time Minimum_On_Time Priority_Array Relinquish_Default Time_Delay Notification_Class Feedback_Value Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Profile_Name

Property Datatype
BACneObjectIdentifier CharacterString BACnetObjectType BACnetBinaryPV CharacterString CharacterString BACnetStatusFlags BACnetEventState BACnetReliability Boolean BACnetPolarity CharacterString CharacterString BACnetDateTime Unsigned BACnetDateTime Unsigned BACnetDateTime Unsigned Unsigned BACnetPriorityArray BACnetBinaryPV Unsigned Unsigned BACnetBinaryPV BACnetEventTransitionBits BACnetEventTransitionBits BACnetNotifyType BACnetARRAY[3] of BACnetTimeStamp CharacterString

BACnet
R R R W O O R R O R R O1 O1 O2 O2 O2 O3 O3 O O R

IntesisBox
R R R RW R R R R R R R

Remarks

User defined BINARY INPUT

Same the object name

All bits: FALSE always. Always NORMAL: NORMAL (0) NO_FAULT_DETECTED always. Always FALSE. NORMAL

Accept all writes as Priority 16 Same Present_Value data

O4 O4 O4 O4 O4 O4 O4 O

3.8 Binary Value Object Type

Intesis Software SL

13

Property Identifier
Object_Identifier Object_Name Object_Type Present_Value Description Status_Flags Event_State Reliability Out_Of_Service Inactive_Text Active_Text Change_Of_State_Time Change_Of_State_Count Time_Of_State_Count_Reset Elapsed_Active_Time Time_Of_Active_Time_Reset Minimum_Off_Time Minimum_On_Time Priority_Array Relinquish_Default Time_Delay Notification_Class Alarm_Value Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Profile_Name

Property Datatype
BACneObjectIdentifier CharacterString BACnetObjectType BACnetBinaryPV CharacterString BACnetStatusFlags BACnetEventState BACnetReliability Boolean CharacterString CharacterString BACnetDateTime Unsigned BACnetDateTime Unsigned BACnetDateTime Unsigned Unsigned BACnetPriorityArray BACnetBinaryPV Unsigned Unsigned BACnetBinaryPV BACnetEventTransitionBits BACnetEventTransitionBits BACnetNotifyType BACnetARRAY[3] of BACnetTimeStamp CharacterString

BACnet
R R R W O R R O R O1 O1 O2 O2 O2 O3 O3 O O R

IntesisBox
R R R RW R R R R R R

Remarks

User defined BINARY VALUE

Same the object name All bits: FALSE always. Always NORMAL: NORMAL (0) NO_FAULT_DETECTED always. Always FALSE.

Accept all writes as Priority 16 Same Present_Value data

O4 O4 O4 O4 O4 O4 O4 O

Intesis Software SL

14

3.9 Multistate Input Object Type


Property Identifier
Object_Identifier Object_Name Object_Type Present_Value Description Device_Type Status_Flags Event_State Reliability Out_Of_Service Number_Of_States State_Text Time_Delay Notification_Class Alarm_Values Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Profile_Name

Property Datatype
BACneObjectIdentifier CharacterString BACnetObjectType Unsigned CharacterString CharacterString BACnetStatusFlags BACnetEventState BACnetReliability Boolean Unsigned BACnetARRAY[N] of CharacterString Unsigned Unsigned List of Unsigned BACnetEventTransitionBits BACnetEventTransitionBits BACnetNotifyType BACnetARRAY[3] of BACnetTimeStamp CharacterString

BACnet
R R R R1 O O R R O2 R R O O3 O3 O3 O3 O3 O3 O3 O

IntesisBox
R R R R R R R R R -

Remarks

User defined MULTISTATE INPUT

Same the object name

All bits: FALSE always. Always NORMAL: NORMAL (0) NO_FAULT_DETECTED always. Always FALSE. Unreliable

Intesis Software SL

15

3.10 Multistate Output Object Type


Property Identifier
Object_Identifier Object_Name Object_Type Present_Value Description Device_Type Status_Flags Event_State Reliability Out_Of_Service Number_Of_States State_Text Priority_Array Relinquish_Default Time_Delay Notification_Class Feedback_Values Event_Enable Acked_Transitions Notify_Type Event_Time_Stamps Profile_Name

Property Datatype
BACneObjectIdentifier CharacterString BACnetObjectType Unsigned CharacterString CharacterString BACnetStatusFlags BACnetEventState BACnetReliability Boolean Unsigned BACnetARRAY[N] of CharacterString BACnetPriorityArray Unsigned Unsigned Unsigned Unsigned BACnetEventTransitionBits BACnetEventTransitionBits BACnetNotifyType BACnetARRAY[3] of BACnetTimeStamp CharacterString

BACnet
R R R R1 O O R R O2 R R O R R O1 O1 O1 O1 O1 O1 O1 O

IntesisBox
R R R RW R R R R R R R -

Remarks

User defined MULTISTATE OUTPUT

Same the object name

All bits: FALSE always. Always NORMAL: NORMAL (0) NO_FAULT_DETECTED always. Always FALSE. Unreliable

Accept all writes as Priority 16 Same Present_Value data

Intesis Software SL

16

3.11 Multistate Value Object Type


Property Identifier
Object_Identifier Object_Name Object_Type Present_Value Description Status_Flags Event_State Reliability Out_Of_Service Number_Of_States State_Text Priority_Array Relinquish_Default Time_Delay Notification_Class Alarm_Values Fault_Values Acked_Transitions Notify_Type Event_Time_Stamps Profile_Name

Property Datatype
BACneObjectIdentifier CharacterString BACnetObjectType Unsigned CharacterString BACnetStatusFlags BACnetEventState BACnetReliability Boolean Unsigned BACnetARRAY[N] of CharacterString BACnetPriorityArray Unsigned Unsigned Unsigned List of Unsignet List of Unsignet BACnetEventTransitionBits BACnetNotifyType BACnetARRAY[3] of BACnetTimeStamp CharacterString

BACnet
R R R R1 O R R O2 R R O O3 O3 O4 O4 O4 O4 O4 O4 O4 O

IntesisBox
R R R RW R R R R R R R -

Remarks

User defined MULTISTATE OUTPUT

Same the object name All bits: FALSE always. Always NORMAL: NORMAL (0) NO_FAULT_DETECTED always. Always FALSE. Unreliable

Accept all writes as Priority 16 Same Present_Value data

Intesis Software SL

17