Relay type Overcurrent-time and motor protection 7SJ511, 512, 531 7SJ45, 46, 60 7SJ61, 62, 63, 64 7SJ80, 7SK80
Min. required sym. shortcircuit current factor Kssc IHigh set point Kssc Ipn at least: 20 Iscc max (ext. fault) Kssc Ipn
Min. required knee-point voltage Uk IHigh set point Uk (Rct + Rb) Isn 1.3 Ipn 20 at least: (Rct + Rb) Isn 1.3 Iscc max (ext. fault) Uk (Rct + Rb) Isn 1.3 Ipn and: 3 (Uk / (Rct + Rb) Ipn / Isn)end1 4 4 (Uk / (Rct + Rb) Ipn / Isn)end2 3 UK Iscc max (ext. fault) Ktd (Rct + Rb) Isn 1.3 Ipn and (only for 7SS): Iscc max (ext. fault) 100 Ipn (measuring range)
Line differential protection (without distance function) 7SD52x, 53x, 610 (50 / 60 Hz) Tranformer / generator differential protection
Transformer 1.2
Kssc Iscc max (ext. fault) Ktd Ipn and (only for 7SS): Iscc max (ext. fault) 100 Ipn (measuring range)
Transformer
7UT612, 7UT612 V4.0 4 7UT613, 633, 635, 7UT612 V4.6 3 7UM62 4 Busbar protection 7SS52, 7SS60 Distance protection 7SA522, 7SA6, 7SD5xx (with distance function) Ktd (a) Ktd (b)
for stabilizing factors k 0.5 0.5 primary DC time constant Tp [ms] 30 1 4 50 2 5 100 4 5 200 4 5 Kssc Iscc max (close in fault) Ktd (a) Ipn and: Iscc max (zone 1 end fault) Ktd (b) Ipn UK Iscc max (close in fault) Ktd (a) (Rct + Rb) Isn 1.3 Ipn and:
Iscc max (zone 1 end fault) Ktd (b) (Rct + Rb) Isn Ipn
132 kV, 50 Hz -T (G S2) 6,000/1 A 5P20 20 VA Rct = 18 -G1 120 MVA 13.8 kV, 50 Hz xd = 0.16 G 3~ 35.8 kA I = 60 m A = 4 mm2 7UM62 CB xd uk 1-2 Rrelay I = 40 m A = 4 mm2 34.5 kA -T (T LV1)) 6,000/1 A 5P20 20 VA Rct = 18 1)
3
-T (L end 2) 1,500/1 A
-G2 7UT633
l = 100 m A = 4 mm2
17 kA (given)
arrangement inside power plant is not shown = Generator direct axis subtransient reactance in p.u. = Transformer impedance voltage HV side LV side in % = Assumed with 0.1 , (power consumption for above relays is below 0.1 VA)
Fig. 6.2-125: Example 1 CT verication for 7UM62, 7UT6, 7SD52 (7SD53, 7SD610)