International Journal of Mechanical and Production Engineering Research and Development (IJMPERD ) ISSN 2249-6890 Vol.

2, Issue 4 Dec 2012 89-97 TJPRC Pvt. Ltd.,

CONFIGURATION OF A 2 kW CAPACITY ABSORPTION REFRIGERATION SYSTEM DRIVEN BY LOW GRADE ENERGY SOURCE
1 1

ANIL SHARMA, 2BIMAL KUMAR MISHRA, 3ABHINAV DINESH & 4ASHOK MISRA
2

Department of Production Engineering, Birla Institute of Technology- Extension Centre, Deoghar, India Department of Applied Mathematics Birla Institute of Technology- Mesra, Ranchi, India

Department of Electronics & Communication Engineering, Birla Institute of Technology- Extension Centre, Jaipur, India
4

Department of Mechanical Engineering, Birla Institute of Technology- Mesra, Ranchi, India

ABSTRACT
Consistently increasing CO2 emission and ozone depletion from CFCs are serious environmental issues challenging scientific community. The dependence on fossil fuels has to be reduced and alternative environmental friendly options need to be explored. In this aspect, vapor absorption system gives scope of utilizing low grade energy source i.e. solar panel for generating cooling effect which is dominated by high grade energy driven compression technology. The LiBr aqueous solution based absorption cycle consists of four stages: generation, condensation, evaporation and absorption with ideally no moving part. In this paper, a configuration of 2kW capacity LiBr-Water based absorption refrigeration system is presented. The selection of evaporator capacity i.e. 2kW guides the operating conditions of other component in the cycle. Empirical correlations had been used to determine heat transfer rate. Based on these results specification for heat exchangers are established. This configuration serves as a platform to design for manufacturing of such systems.

KEY WORDS: Absorption Cycle, Low Grade Energy, Overall Heat Transfer Coefficient, System Configuration INTRODUCTION
In a basic absorption cycle, low pressure refrigerant vapor is converted to a liquid phase (solution) at same pressure. This conversion is made possible by the vapor being absorbed by a secondary fluid called absorbent. Absorbent absorbs refrigerant because of the mixing tendency of miscible substances, and an affinity between absorbent and refrigerant molecules. Thermal energy is released during this absorption process and should be transferred to a sink. Among various absorbent and refrigerant pair, LiBr- Water is most promising in chiller application due to high safety, high volatility ratio, high affinity, high stability and high latent heat. The working temperature for this pair should be above 00C, because the refrigerant turns to ice at this temperature. The properties of this pair are vastly documented in literature, in this paper, the properties of LiBr aqueous solutions are referred from the reference [3]. In the cycle shown in figure 1, water vapor evaporate and separates from aqueous LiBr solution in generator, and increases the concentration of LiBr in solution. For this process heat is supplied from external source. At the same pressure, the water vapors from generator are condensed in condenser and this condensed water is throttled to the evaporator at low pressure. Due to reduced pressure, the water change phase and evaporate by taking latent heat of vaporization in the evaporator at chiller temperature and generates the cooling effect. At same pressure, the vapors from evaporator are absorbed by LiBr-aqueous solution supplied form generator having higher concentration of LiBr. The absorption of water vapor reduces the concentration of LiBr in aqueous solution, this solution is then passed to generator

90

Anil Sharma, Bimal Kumar Mishra, Abhinav Dinesh & Ashok Misra

through pump at higher pressure. A solution heat exchanger is used between absorber and generator to increase the efficiency of system. In this paper, the source of heat in generator is low grade energy i.e. hot water at 900C. This low grade energy can be obtained from solar panel, cooling of automobile engine, hot water release in several industries and other source of waste heat. The cooling water is circulated in absorber to release the heat of absorption at 280C and after exit from absorber at 330C, it is passed in the condenser to change the phase of water from vapor to liquid.

NOMENCLATURE
A Cp g h k m P Q r Re T U X area (m2) specific heat (J/kg-K) gravitational acceleration(m/s2) heat transfer coefficient (W/m2-K) thermal conductivity (W/m-K) mass flow rate (kg/sec) pressure (Pa) Heat transfer rate (W) radius (m) Reynolds number Temperature (K) overall heat transfer coefficient (W/m2-K) LiBr mass fraction (%) thermal diffusivity (m2/s) specific film flow rate (kg/m-s) dynamic viscosity (kg/m-s) kinematic viscosity (m2/s) density (kg/m3) D Nu Pr Gr surface tension diameter (m) Nusselt Number Prandtl Number Grasfhoff Number Subscript: i o s h a g e c C l f D 1 -10 inside outside Solution side hot absorber generator evaporator condensor cold liquid film Diameter Position as mentioned in figure.

Configuration of a 2 kW Capacity Absorption Refrigeration System Driven by Low Grade Energy Source

91

Figure 1: Flow Diagram

MASS FLOW RATE AND HEAT TRANSFER


Assumptions Following assumption had been made to model the system. 1. 2. 3. 4. 5. 6. 7. 8. 9. Generator and condenser as well as evaporator and absorber are under same pressure. There are no pressure changes except through the flow restrictors and the pump. Refrigerant vapor leaving the evaporator is saturated pure water. Liquid refrigerant leaving the condenser is saturated. Strong solution leaving the generator is boiling. Weak solution leaving the absorber is saturated. No liquid carryover from evaporator. Flow restrictors are adiabatic. Pump is isentropic.

10. No jacket heat losses.

92

Anil Sharma, Bimal Kumar Mishra, Abhinav Dinesh & Ashok Misra

Selection of Operating Parameters Table 1: Operating Parameters for Cycle Pressure in generator and condenser Pressure in absorber and evaporator Saturation temperature in generator Saturation temperature in condensor Saturation temperature in evaporator Solution Temperature in absorber Solution Concentration at 3 Solution Concentration at 5 Mass Flow Rate Calculations for 2kW Capacity Mass flow rate in evaporator (m9) = Load / (Change in enthalpy) = 2 kW / (2514.2-163.4) = 0.0008507742 kg/sec Mass flow rate for weak and strong solution m4 X 0.60 = m3 X 0.55 also, m3 = m4 + m7 m4 = 0.0093585162 kg/sec m3 = 0.01020929 kg/sec m1 = m2 = m3 ; m4 = m5 = m6 ; and m7 = m8 = m9 = m10 7 kPa 1 kPa 82.863 0 c 38.199 0 c 6.3150 c 36 0 c 55 % 60%

HEAT TRANSFER RATE


Heat transfer rate in evaporator is 2 kW, base on this selected parameter heat transfer rate at other components are calculated as follows. At Condenser (Qc) = m7 (h7 h8) h7 = Enthalpy of super heated steam at 70 0 C and 7 kPa = 2611.98 kJ/kg h8 = Enthalpy of water (saturated liquid) at 7 kPa and 38.199 0C = 163.4 kJ/kg Qc = 2.083188 KW. At Generator (Qg) = m4h4 + m7h7 m3h3 h4 = Enthalpy of solution at 82 0 C and 60 % Concentration = 196.7447 kJ/kg h3 = Enthalpy of solution at 62 0 C and 55 % concentration.

Configuration of a 2 kW Capacity Absorption Refrigeration System Driven by Low Grade Energy Source

93

= 139.1669 k J/kg h7 = Enthalpy of super heated steam at 70 0 C and 7 kPa. = 2611.98 k J/kg Qg = 2.727202777 kW At Absorber (Qa) = m6h6 + m10h10 m1h1 h6 = Enthalpy of solution at 50 0 C and 60 % concentration = 134.9947 k J/kg h10 = Enthalpy of saturated water vapor at 1 kpa and 6.315 0 C. = 2514.4 kJ/kg h1 = Enthalpy of solution at 35 0 C and 55 % concentration. = 83.3824 kJ/kg Qa = 2.657201466kW

EMPIRICAL CORRELATIONS
Inside Tube Heat Transfer Coefficient (hi) Petukhov-Popov Equation for condenser, generator, evaporator and absorber. In all these heat exchangers water flow inside tube without phase change.

Here,

Outside Tube Heat Transfer Coefficient (Ho) For Condensor

For Generator

Roshenow Correlation

94

Anil Sharma, Bimal Kumar Mishra, Abhinav Dinesh & Ashok Misra

For Absorber Wilkes Correlation

Film thickness For Evaporator


1

2 g 3600 2 k l3 3 h o = 1 . 1006 Re f 1 / 3 l l2
Log Mean Temperature Difference (LMTD)

Over all Heat Transfer Coefficient (U)

Heat Transfer Rate (Q)

CONFIGURATION OF HEAT EXCHANGERS


Standard dimensions of copper tubes had been selected from manufacturers guide. Shell and tube type heat exchangers are been analysed due to their efficiency and ease in manufacturing.

CONDENSOR
Table 2: Specifications for Condenser Inner diameter of tube Outer diameter of tube Number of tubes Tube orientation Length of tubes Overall heat transfer coefficient Cooling water in temperature Cooling water out temperature Mass flow rate of refrigerant - water Log mean temperature difference (LMTD) 0.43 inch 0.5 inch 1 (6-tube pass) Horizontal 2m 2467.165 W/m2 oC 330C 370C 0.12477168 kg/sec 14.89

Configuration of a 2 kW Capacity Absorption Refrigeration System Driven by Low Grade Energy Source

95

GENERATOR
Table 3: Specifications for Generator Inner diameter of tube Outer diameter of tube Number of tubes Tube Orientation Length of tubes Overall heat transfer coefficient Heating water in temperature Heating water out temperature Log mean temperature difference (LMTD) 0.545 inch 0.625 inch 1 (twelve tube pass) Horizontal 4.8 m 829.9376 W/m2 oC 900C 840C 13.84

EVAPORATOR
Table 4: Specifications for Evaporator Inner diameter of tube Outer diameter of tube Number of tubes Tube orientation Length of tubes Overall heat transfer coefficient Chilling water in temperature Chilling water out temperature Mass flow rate of refrigerant - water Log mean temperature difference (LMTD) 0.315 inch 0.375 inch 1 (8-tube pass) Horizontal 3m 2077.68 W/m2 oC 120C 80C 0.119189511 kg/sec 11

ABSORBER
Table 5: Specifications for Absorber Inner diameter of tube Outer diameter of tube Number of tubes Tube orientation Length of tubes Overall heat transfer coefficient Cooling water in temperature Cooling water out temperature Log mean temperature difference (LMTD) 0.545 inch 0.625 inch 1 (12-tube pass) Horizontal 5m 975.9336 W/m2 oC 280C 330C 11.27

CONCLUSIONS
Above calculated specification gives a platform to design for manufacturing of a 2 kW absorption system, driven by low grade energy source i.e. solar panel. Shell and tube type heat exchangers are analyzed due to their efficiency and ease in manufacturing. Among the components, absorber dimensions are highest and required further design modifications to make the system more compact. The design procedure used can be applied to scale up the capacity. This paper assists the economic analysis for manufacturing of absorption chillers. The current calculations has used some assumptions which need more analysis i.e. no jacket heat loss. In the analysis of absorber, empirical correlation for outside heat transfer coefficient ignores the fact of simultaneous mass transfer. Other fields of investigation are creating and sustaining vacuum, throttling process and optimum size of pump.

96

Anil Sharma, Bimal Kumar Mishra, Abhinav Dinesh & Ashok Misra

REFERENCES
1. Arzoz, D., Rodriguez, P., Izquierdo, M. Experimental study on the adiabatic absorption of water vapor in to LiBrH2O solutions, Applied Thermal Engineering 25 (2005) 797-811. 2. Asdrubali, F. and Grignaffini, S. Experimental evaluation of the performances of a H2O-LiBr absorption refrigerator under different service conditions, International Journal of Refrigeration, 28, (2005), pp. 489-497. 3. 4. 5. ASHRAE Fundamental Handbook (SI): 2001, Atlanta, USA. ASHRAE Handbook of fundamentals, 1997. Bourouis, M., Valles, M., Medrano, M., Coronas, A. Absorption of Water vapour in the falling film of water(LiBr+ LiI+LiNO3+LiCl) in a vertical tube at air-cooling thermal conditions, Internatinal Journal of Thermal Scineces 44 (2005)491-498. 6. Bredow, D., Jain, P., Wohlfeil, A., Ziegler, F. Heat and mass transfer characteristics of a horizontal tube absorber in a semi-commercial absorption chiller. International Journal of Refrigeration 31 (2008) 1273-1281. 7. Castro, J., Oliva, A., Segarra, C.D. and Oliet, C. Modeling of the heat exchangers of a small capacity, hot water driven, air-cooled H2O-LiBr absorption cooling machine, International Journal of Refrigeration, 31, (2008), pp. 75-86. 8. Florides, G.A., Kalogirou, S.A., Tassou, S.A., Wrobel, L.C. Design and construction of a LiBrwater absorption machine, Energy Conversion and Management 44 (2003) 24832508. 9. Goodheart, K.A. Low firing temperature absorption chiller system, Thesis submitted for Master of Science, University of Wisconsin-Madison, (2000). 10. Islam, M.R. Absorption process of a falling film on a tubular absorber: An experimental and numerical study, Applied Thermal Engineering, Elsevier, 28 (2008), pp. 1386-1394. 11. Islam, M.R., Wijeysundera, N.E., Ho, J.C. Evaluation of heat and mass transfer coefficients for falling-films on tubular absorbers, International Journal of Refrigeration 26 (2003) 197-204. 12. Kaynakli, O. and Horuz, I. Comparison of parallel and counter flow coil absorber performance, International Communications in Heat and Mass Transfer, 33 (2006), pp. 211-223. 13. Killion, J.D., Garimella, S. A critical review of models of coupled heat and mass transfer in falling film absorption, International Journal of Refrigeration, 24 (2001) 755-797. 14. Kohlenbach, P. and Ziegler, F. A dynamic simulation model for transient absorption chiller performance. Part-I: The Model, Part-II: Numerical results and experimental verification, International Journal of Refrigeration, 31 (2008), pp. 217-233. 15. Kyung, I., Herold, K.E. and Kang, Y.T. Experimental verification of H2O/LiBr absorber bundle performance with smooth horizontal tubes, International Journal of Refrigeration, 30, (2007), pp. 582-590. 16. Martineza, P.J., Pinazo, J.M. A method for design analysis of absorption machines, International Journal of Refrigeration 25 (2002) 634639.

Configuration of a 2 kW Capacity Absorption Refrigeration System Driven by Low Grade Energy Source

97

17. Medrano, M., Bourouis, M., Coronas, A. Absorption of water vapour in the falling film of water-lithium bromide inside a vertical tube at air-copoling thermal conditins, Internatinal Journal of Thermal Sciences 41 (2002) 891898. 18. Misra, R.D., Sahoo, P.K., Sahoo, S. and Gupta, A. Thermo economic optimization of a single effect water/LiBr vapour absorption refrigeration system, International Journal of Refrigeration, 26 (2003), pp. 158-169. 19. Nosoko, T., Miyara, A., Nagata, T. Characteristics of falling film flow on completely wetted horizontal tubes and the associated gas absorption, International Journal of Heat and Mass Transfer 45 (2002) 2729-2738. 20. Papaefthimiou, V.D., Karampinos, D.C., Rogdakis, E.D. A detailed analysis of water-vapour absorption in LiBrH2O solution on a cooled horizontal tube, Applied Thermal Engineering 26 (2006) 2095-2102. 21. Patnaik, V., Perez-Blanco, H. A study of absorption enhancement by wavy film flows, International Journal of Heat and Fluid Flow 17 (1996) 71-77. 22. Sencan, A., Yakut, K.A. and Kalogirou, S.A. Exergy analysis of lithium bromide/water absorption systems, Renewable Energy, Elsevier, 30 (2005), p.p. 645-657. 23. Sharma, A., Mishra, B.K., Dinesh, A., Misra, A. Theoretical investigation and parametric study of a solar driven absorption refrigeration system, Renewable Energy Asia 2008 An International Conference & 4th SEE Forum Meeting, Center for Rural Development and Technology, Indian Institute of Technology Delhi, Hauz Khas, New Delhi- India. 24. Srikhirin, P., Aphornratana, S., Chungpaibulpatana, S. A review of absorption refrigeration technologies, Renewable and Sustainable Energy Reviews, 5 (2001) 343372. 25. Subramaniam, V., Garimella, S. From measurements of hydrodynamics to computation of species transport in falling films, International Journal of Refrigeration 32 (2009) 607-626. 26. Wassenaar, R.H. Measured and predicted effect of flowrate and tube spacing on horizontal tube absorber performance, International Journal of Refrigeration 19 (1996) 347-355. 27. Xie, G., Sheng, G., Bansal, P.K., Li, G. Absorber performance of a water/lithium-bromide absorption chiller, Applied Thermal Engineering 28 (2008) 1557-1562. 28. Xu, Z.F., Khoo, B.C., Wijeysundera, N.E. Mass transfer across the falling film: Simulations and experiments, Chemical Engineering Science 63 (2008) 2559-2575. 29. Yoon, J., Phan, T., Moon, C., Bansal, P. Numerical study of heat and mass transfer characteristic of plate absorber, Applied Thermal Engineering 25 (2005) 2219-2235.