You are on page 1of 5

IBETH15GB_0

page 1/5

TYPE MAS 12000-1140

OIL TREATMENT ARRAS MAXEI


TECHNICAL DESCRIPTION OF THE STANDARD OIL TREATMENT PLANTS

TYPE MAS 12000 140kW 1000m3/h


PREAMBLE The use with confidence of the dielectric fluids in the transformers, circuit breakers, and other types of electrical equipment depends upon some of their basic characteristics, which can affect the general operating efficiency of the electrical equipment. In order to ensure manifold functions such as an insulant, a coolant and an extinguishing medium, these dielectric fluids must have some basic properties, and especially a high dielectric strength. Now, in service, the dielectric fluids properties may be affected by the appearing of oxidation, condensation and other contaminants such as water, solid impurities and dissolved gases. Working on the principles of filtration, dehydration and vacuum degasification, MAXEI Industries Electriques oil treatment plants are particularly recommended to maintain, dry and fill your transformers and circuitbreakers. By removing the impurities, dissolved moisture and gases, they indeed enable to restore the oil dielectric properties and to extend the useful life of your electrical equipment. Used and well-known all over the world for their performance, reliability and ease of operation, our standard plants are now enriched with our latest technological achievements. Automated, fitted with remote control or telecontrol systems, our oil treatment plants are more and more autonomous, which insure you increased productivity.

SUMMARY:
Principle of operation Main characteristics Components of the plant Description of the plant Operating diagram Optional features

2 2 2 3 4 5

MAS 12000 on road trailer With metallic cover

Oil treatment
The oil treatment plants ARRAS MAXEI has been designed to treat dielectric oil having a 50 ppm moisture content and a dissolved gas content of approx. 10% by volume before being treated. After getting the optimal treatment conditions, the clean treated oil goes out after 1 pass at a maximum temperature of 70C with a moisture content below 5 ppm* and a dissolved gas content of approximately 0,1% by volume*. The breakdown voltage of the oil will be in excess of 75 kV after treatment. An oil at 20 ppm will go out at 3 ppm* after 1 pass. The above figures are reached with oils having a 10-2 mbar distillation curve at a temperature of 80 C.
Evolution of the moisture content and of the dielectric 100 80 60 40 20 0
Moisture content
1000

Comparison betwenn vapor and liquid phases of moisture and dielectric oil EAU Lliquid water Liquid oil Vapor water Vapor oil

100

HUILE

mbars

10

0,1

0,01

20

40

60

80

100

15 10 5 0

PPM of water

dilectric

20

T C

* : Theoretical values depending on the measuring device accuracy and ranging from 2 to 5 ppm

KV

120

IBETH15GB_0 page 2/5

OIL TREATMENT ARRAS MAXEI

TYPE MAS 12000-1140

Principle of operation
Options Road trailer Low speed trailer The dielectric fluid enters in the plant through an inlet strainer, and then passes through an inlet oil pump and into an oil heater, where it is heated by immersion heaters. After a fine filtration on cartridge, the dielectric fluid is sprayed into a vacuum chamber on a basket of Raschig rings. Finally, after the contaminants are eliminated, the clean treated fluid flows through the outlet oil pump.

Options Plant with metallic cover Plant with tarpaulin

Options Foam regulation system

Main characteristics
Nominal flow* during treatment in l/h Heating power in kW Total power in kW Filtration** by cartridges in nominal m Limit vacuum against closed suction in mbars Vacuum during treatment in mbars 12000 140 169 1 0,05 0,5 to 2

Options Transformer insulating system High level detection system

* : Approximate values. ** : Consumable cartridge with filtration expressed in m nominal. All our plants are equipped in standard with tropicalized electrical material, for a feeding tension 400 Volts 3 phases 50 Hz and auxiliary operation in 220 Volts by transformer.

Components of the plant


Options Voltmeter / Ampere meter 1 1 1 1 1 1 1 1 1 3 inlet oil motor-pump direct electrical heater with 3 working temperatures cartridge filter dehydration tank outlet oil vacuum motor-pump double-staged vacuum motor-pump set measuring, controlling, alarming, and regulating apparatus control panel set of pipes, valves and accessories lifting rings placed on upper part of the of the degasification unit

Options Telecontrol

The standard plant is installed on a section iron plate with retention tray and maintenance wheels.

IBETH15GB_0 page 3/5

OIL TREATMENT ARRAS MAXEI

TYPE MAS 12000-1140

Description of the plant


Heater and oil filtering system.
Maxi flow of the pump in l/h Pump type Height of discharge in mCE Motor power in kW Pump building Rotation speed in rpm Connection diameter in mm 15000 Centrifugal 40 7,5 Cast iron/steel 1500 65

1) Inlet oil motor-pump The oil inlet suction of the ARRAS MAXEI standard oil treatment plants are equipped with a symmetrical connection (like French fire system), a strainer filter, an insulation valve, an inlet oil motor-pump and an oil sampling valve also serving as an heater drain.

Total heating power in kW Number of thermodippers Power of an element kW Auxiliary heating connection

140 2 70 65

2) Heater The motor-pump outlet of the standard ARRAS MAXEI oil treatment plants are equipped with a heater made of pipe stub heating casing, equipped with flanged immersion heater. This heater has two working temperature. The heater outlet is equipped with a safety valve adjusted at 4 bars, an overheating safety thermostat, a temperature regulation probe PT100, a heater by-pass, a pressostat and a manometer -1 / +5 bars. 3) Filtering system The standard ARRAS MAXEI oil treatment plants are equipped with two consumable cartridge filter with 1 m nominal filtration. The filters, equipped of a clogging control, are connected to the dehydration tank.

Number of filters Number of cartridges Filter building Clogging control

2 12 Cast iron/steel Pressostat

Flow of primary pump in m3/h Limit vacuum in mbar Motor power in kW Rotation speed in rpm Oil capacity in litre Flow of roots pump in m /h Roots motor power in kW Rotation speed in rpm Oil capacity in litre Cooling system power in kW Condenser in m
2 3

240 0,08 5.5 1450 8,5 1000 4 3000 3,5 4 6 Pirani 80

Oil degazing under vacuum.


4) Dehydration tank The standard ARRAS MAXEI oil treatment plants are equipped with a cylindrical steel dehydration cell. It includes a spraying blockhead and a basket of dehydration rings. The upper part of the cell is equipped with an inlet oil connection, a connection to the vacuum pump, a vacuum indicator 1000 to 0 mbar and a vacuum regulation valve. The collar is equipped with a level sensor, a low tension headlight window to look at the lower part of the cell and a foam regulation system. The lower part is equipped with a flow regulation tube and a draining valve. 5) Vacuum motor-pump The standard ARRAS MAXEI oil treatment plants are equipped with a double-staged group composed of a pump with pales, greasing through oil circulation with filter, antireturn valve, air ballast and a roots pump. The group is connected to the dehydration cell by a pipe equipped with a safety valve, an insulating valve, a Pirani vacuum gauge with display and an exhaust electro-valve of the group. The pumping group is equipped of a condenser and a cooling system for an optimal protection of the primary pump.

Vacuum measure Auxiliary vacuum connection

Maxi flow of the pump in l/h Pump type Height of discharge in mCE Motor power in kW Rotation speed in rpm Pump building Connection diameter in mm

10000 Centrifugal 40 5,5 1500 Cast iron/bronze 65

Oil outlet.
6) Outlet oil vacuum motor-pump The outlet discharge of the standard oil treatment plants are equipped with an outlet oil vacuum motor-pump, a valve of oil sampling, a manometer, a pressostat, an anti-return valve, an insulation valve and a symmetrical connection (like French fire system).

IBETH15GB_0 page 4/5

OIL TREATMENT ARRAS MAXEI

TYPE MAS 12000-1140

7) Control panel The standard ARRAS MAXEI oil treatment plants are equipped with an industrial water proof type cabinet in painted steel, with contactors, relays, fuses, connectors and wires necessar for the equipment running. On the door, theres the buttons and warning lights of the different equipment components. 8) Finishing painting The standard oil treatment plants ARRAS MAXEI are painted in white (RAL9002) for the system and in blue (RAL 5012) for the platform. 9) Dimensions
Length in Width in High in mm mm mm Plant on platform Plant on skid Plant on cart Plant on cart with tarpaulin Plant on cart with metallic cover Plant on road trailer with tarpaulin Plant on road trailer with metallic cover 4500 4500** 4500** 4500** 4500** 4500** Not proposed 2100 2100 2100 2100 2100 2100 2580 2960 3210 3210 3480 3480 4500 5300 5500 6000 8000* 8000* * : The weight is not higher for the road trailers equipped with tarpaulin or metallic cover ** : The lengths are given without the draw bar Weight in kg

All characteristics may be modified without any prior notice.

IBETH15GB_0 page 5/5

OIL TREATMENT ARRAS MAXEI

TYPE MAS 12000-1140

Optional features
Process controls
1) INSULATING SYSTEM This option enables, in case of incident or any sudden treatment stopping (power cut), to insulate the plant from the electric appliance to be treated and thus to prevent from dangerous oil flowing into the oil treatment plant. 2) HIGH LEVEL DETECTION SYSTEM This option enables the automatic stop of the plant, when the valve, which protects the vacuum pump, is full. This reinforced safety and avoids the transfer of the condensates in the vacuum pump. 3) AUTOMATIC DRAINING OF THE VALVE This option enables an optimal protection of the vacuum network of the plant. 4) VOLTMETER / AMPERE METER This option will enable you to visualize the feeding tension of the plant as well as the developed intensity in order to protect the network and the equipment. 5) RECORDER This option ables to record the physical dimensions, characterizing the degazing process, like the temperature and the vacuum. 6) QUALITY CONTROL OF OILS

The presentations

1) CART The oil treatment can be installed on a cart with full tyres (maxi speed : 20 km/h). 2) ROAD TRAILER The oil treatment plant can be installed on a road trailer. The trailer can be equipped with rear lights in accordance with the EU regulations of road code. The whole installation is commissioned by the French government vehicle testing service to be allowed to circulate in France and European countries. 3) TARPAULIN PROTECTION The plant can be equipped with a protection type tarpaulin, which protects it from the bad weather. The tarpaulin can be opened on the four side panels to enable the access to all the components of the plant. 4) METALLIC COVER PROTECTION The plant can be equipped with a metallic cover type protection, which protects it from the bad weather. It is made of aluminium with a frame made of iron steel. The side panels opens horizontally, closing per key and are maintained thanks to gas jacks. The panels enable the access to the components of the plant.

The transformers drying


(The vacuum technology)

1) TRANSFORMER DRYING This option enables to make vacuum in the transformer in order to dry the active parts while the oil is treated. The pump is installed parallel to the first one to increase the pumping capacity of the plant. 2) DOUBLE STAGE PUMPING GROUP In case of this option, the primary vacuum pump mounted on the plant is completed with a second pump stage composed of a roots. 3) AUXILIARY VACUUM CONNECTION This option enables to have an additional vacuum connection on the plant. 4) CONDENSOR AND COOLING GROUP This option enables an optimal protection of the pump group in case of high water content treatment.

The transformers drying

1) TRANSFER PUMP This option enables to increase the hoses length between the plant and the transformer. 2) HIGHER HEATING POWER The standard heating power of the ARRAS MAXEI oil treatment plants has been calculated for a weight ratio between oil and transformer about 4. In case of a higher ratio, we recommend to increase the heating power of the plant. 3) AUXILIARY HEATING CONNECTION This option enables to have an additional heating connection. It allows to heat the transformer per oil circulation through the plant heater. 4) SAFETY LEVEL ON TRANSFORMER This option is installed on the upper part of the transformer to control the variations of the oil level in this one. 5) CONNEXION FEATURES AND ACCESSORIES 6) PULVERIZATION

(Oil heating and transfer)

Telecontrol

TELECONTROL standard or GSM