You are on page 1of 11

INSTRUCTION MANUAL

FOR
PTF 03
PT fuse Failure Relay
CONTENTS
SECTION I Introduction
SECTION II Installation
2.1 Preliminary check
2.2 ConIiguration Settings
2.3 Mounting & Wiring
SCTION III Operation
3.1 Operation
3.2 Maintenance
SECTION IV SpeciIications
4.1 Panel cutout drawing
4.2 Wiring Diagram
Warranty
SECTION I
INTRODUCTION
PT Fuse Failure Relay Model PTF03 is an electronic static relay,
designed to monitor the inadvertent removal or Iailure oI the PT
Iuse. It is suitable Ior 3 phase, 3 wire or 3 phase, 4-wire application.
This work at a phase-to-phase voltage oI 110 V.
PTF03 is very easy to install at any site. Its compact size reduces
the panel space requirement and the draw-out construction makes
the maintenance work easy.
SECTION II
INSTALLATION
2.1 Preliminary check:
Check the relay Ior any obvious damage. II Iound damaged, repack
it and inIorm nearest L&T s oIIice /dealer.
This is a selI-powered relay, due to which an auxiliary supply is not
required. But this is suitable Ior 3 phase 3 or 4 wire application with
phase to phase voltage oI 110 Volts.
2.2 Mounting and Wiring:
PTF03 is designed Ior Ilush mounting on the panel. ReIer Fig.1 Ior
panel cutout dimensions and space required behind the panel, Fix
the mounting clamps supplied along with to the top and bottom side
oI the relay. Insert the relay through panel cutout and hold it Iirmly
against the panel cutout and hold it Iirmly against the panel. Tighten
the screws on the mounting bracket.
Wire the relay terminal s as shown in the wiring diagram. ( ReIer
Fig.2) Relay terminals are suitable Ior 2.5 mm. Sq. lugs. Fix the
protective cover back on the terminal block with the help oI two
screws aIter completing the wiring.
NOTE:
1 REMOVE THE RELAY FROM THE PANEL DURING
TRANSPORTATION.
2. ENSURE PROPER EARTH CONNECTION TO THE
RELAY
2.3 Settings
PTF03 will not require any settings Irom the user, so it can be
connected across the Iuse as per the wiring diagram.
SECTION III
3.1 Operation
During the normal operation oI PTF03 only power on LED will be
glowing. II there is any Iuse Iailure in any phase it trips and
indicates in which phase the Iuse has Iailed. AIter tripping iI there is
any other Iuse Iailure the corresponding LED s will glow. Only
aIter replacing all Iuses the relay will come back to it`s normal
position until then it will remain in tripped condition.
3.2 Maintenance
PTF03 does not need any routine maintenance during its working
liIe. It does not contain any user replaceable / serviceable parts. In
case oI any Iailure oI the relay inIorm nearest L&T oIIice.
PTF03 has draw out construction hence in case oI Iailure control
card alone can be removed and replaced without removing the
complete relay Irom the panel. The control card contains electronic
component sensitive to static electrical charge hence should be
handled careIully taking precautions such as ensuring the human
body is at 'Ground potential beIore removing the control card Irom
the relay, packing the card using 'anti static material, not touching
any components on the card as Iar as possible.
To remove the control card Irom the relay Iollow the instructions
given below:
1. Remove the transparent cover Irom the Iront panel by
removing the two screws.
2. Turn the two screws located at top right and bottom leIt
corner oI the panel through 90 degrees ( clockwise / anti
clockwise)
3. Pull the panel out using the handle provided on the Iront
panel
To install the control card back in the relay Iollow the
instructions given below:
1. Observe that locking pins on two screws at top and bottom
corners oI the panel is sin horizontal direction. ( This pin is
on the backside oI the panel.)
2. Engage the card careIully between two card guides mounted
in the relay enclosure
3. Push the card in Iully till Iront panel locks n with click
sound.
4. Turn the two screws at top and bottom corners oI the Iront
panel through 90 degrees
5. Pull the handle to insure that card has locked in properly.
6. Fix the transparent cover back with two screws.
SECTION IV
SPECIFICATIONS
Ratings:
PT secondary rating 110V, 50 Hz /-10
Operating Time Less than or equal to 7 msec
between Iailure or removal oI
PT secondary Iuse and
operating oI relay
PTF03 Relay Burden PT Less than 0.5VA per phase
Min Load Burden required on Greater than or equal to 0.5VA
PT Ior proper Operation oI per phase
Relay
Operation Indicators Separate LED indications Ior
each three phase PT Iuse
status( auto reset type)
Relay status (manually reset
type)
Insulation 2kV AC RMS, 50 Hz Ior 1
minute As per IS:3231:1987
1kV AC RMS. 50 Hz Ior 1
minute across N/O contact
As per IS :3231:1987
Alarm Contacts:
ConIiguration 2 pairs oI C / O contacts, selI
reset
Contact Rating
Rated Voltage 250V Ac/ 30V DC
Max Switching Voltage 440V AC/ 300 V DC
Rated Current 8 Amps
Max. Switching Current 14 Amps
Max Breaking capacity 200 VA / 240W Resistive
Impulse withstand 5 kV peak, 1.2/50 microsec
As per IS:3231:1987
High Disturbance 1 MHz, 1.0 kV peak across
input circuits
1MHz, 2.5 kV peak between
independent circuits as per
IS:8686:1977
Temperature
Operating -10 to 55 degrees C
Storage -20 to 70degrees C
Case Draw out suitable Ior Ilush
mounting
Weight Approx 1.0 Kg
Overall Dimensions (L x B x H) 224 x 71 x 158
4.1 Panel Cutout drawing
Fig. 1
4.2 Wiring Diagram
Fig. 2
WARRANTY
LARSEN & TOUBRO LIMITED ( L&T) warrants that the
protective Relay model PTF 03 will meet L&T s published
speciIications and will be Iree Irom deIects in workmanship and
materials Ior a period oI 12 months Irom the date oI shipment.
L&T`s obligation under this warranty shall be limited to servicing
or replacing the deIective parts provided that notice oI such deIects
and satisIactory prooI thereoI is given to L&T by it`s customer
within the warranty period.
This warranty does not cover any deIect caused by accident, misuse,
neglect alteration, modiIication or substitution oI any oI the
components or parts or any attempts at internal adjustment by
unauthorized service personnel.
Under no circumstances shall L&T will liable Ior any consequential
damage, resulting injury, loss or expanse, directly or indirectly,
arising Irom the use oI this product.
This Iorgoing warranty is in lieu oI all other warranties expressed or
implied and is the sole and exclusive remedy Ior any claim arising
Irom the deIect in the product.
Manufactured by
LARSEN & TOUBRO LIMITED,
KIADB INDUSTRIAL AREA,
HEBBAL, HOOTAGALLY,
MYSORE - 570 018.
INDIA.
Visit us @ www.Intmps.com
www.Intebg.com
www.Iarsentoubro.com
Reach us @ mpsinfo@myw.Itindia.com
Part No. 4D060080 Rev. 1