You are on page 1of 42

CSC-211 Numerical Backup Protection Equipment Users Manual

CAUTION
1) This manual applies only to CSC-211. 2) Please read the manual and the specification of the installation, adjustment, testing, operation and maintenance carefully. 3) To prevent damage to equipment, dont plug-hot-plug any unit of the equipment and touch the chips and components in printed circuit board. 4) Please use the eligible testing equipments and devices to test and detect the CSC-211 protection equipment. 5) If any abnormity occurred in the equipment or unusual maintenance is needed, please promptly contact with the agents or our service hotline. 6) The operation password is: 8888.

WARNING
1) 2) During operation of electrical equipment, certain parts of this equipment are under high voltage. Improper behavior could result in severe personal injury or significant equipment damage. Only qualified personnel should work on this equipment or in vicinity of the equipment. These persons must be familiar with warning & service procedure described in this manual, as well as with safety regulations. Prerequisites to proper & safety operation of the equipment are proper storage, setup, installation, operation & maintenance of the equipment. In particularly cases, the general rules & safety regulations according to relating standards (e.g. IEC, National standards or other International standards) for work with high voltage equipment must be observed.

3) 4)

COPYRIGHT
All rights reserved.

Registered trademark
are registered trademark of Beijing sifang automation co., ltd.

CONTENTS
1 Introduction ........................................................................................................................ 1 2 Features .............................................................................................................................. 3 3 Construction ....................................................................................................................... 4 4 Protection functions .......................................................................................................... 5 4.1 HS/LS OC protection (Both MODEL 1 and MODEL 2) ................................................ 5 4.2 HS/LS EF protection (Both MODEL 1 and MODEL 2) ................................................. 7 4.3 INV OC/EF protection (Both MODEL 1 and MODEL 2) ............................................... 9 4.4 Overload protection (Only MODEL 1)......................................................................... 12 4.5 UV&OV protection (Both MODEL 1 and MODEL 2)................................................... 12 4.6 Thermal overload protection (Only MODEL 1) .......................................................... 13 4.7 CBF protection (Only MODEL 1) ................................................................................. 14 4.8 U/F protection (Only MODEL 2)................................................................................... 15 4.9 VT supervision.............................................................................................................. 16 5 Technical Data .................................................................................................................. 18 6 Measurement and Control............................................................................................... 20 6.1 Measurement ................................................................................................................ 20 6.2 Operation method control ........................................................................................... 20 6.3 Programmable scheme logic ...................................................................................... 20 7 Fault Record and Analysis .............................................................................................. 21 7.1 Fault records ................................................................................................................. 21 7.2 Disturbance records..................................................................................................... 21 7.3 Events records.............................................................................................................. 21 7.4 Operation records ........................................................................................................ 22 8 Communications .............................................................................................................. 22 9 Diagnostics ....................................................................................................................... 22 10 Setting Table ................................................................................................................. 23 10.1 Setting list for MODEL 1 .............................................................................................. 23 10.2 Setting list for MODEL 2 .............................................................................................. 26 11 Selection and ordering data ....................................................................................... 30 12 Terminal Diagram ......................................................................................................... 31 12.1 Terminal Diagram of MODEL 1 .................................................................................... 31 12.2 Terminal Diagram of MODEL 2 .................................................................................... 32 13 Dimension drawings in mm......................................................................................... 33 14 The Principle Outline of Logic Module....................................................................... 34 14.1 Logic 1 Module ............................................................................................................. 34 14.2 Logic 2 Module ............................................................................................................. 35 15 Menu Frame................................................................................................................... 36

CSC-211 Numerical Backup Protection equipment

Manual

1 Introduction

Fig.1 Actual photo of CSC-211 Numerical Backup Protection Equipment

The CSC-211 provides protection, control, and monitoring functions with both local and remote humanization interfaces. It also displays the present trip/alarm conditions and records past trip, alarm or control events, maximum demand levels, and energy consumption is also performed. Logic scheme file and setting file can be entered with a PC running the EPPC software provided for the CSC-211. EPPC software provides easy access to all front panel functions. Actual values and status can be displayed, altered, stored, and printed. Settings can be downloaded at any time to the front panel program port of the relay via a computer cable connected to the serial port of any personal computer. A summary of the available protection functions is shown as follow. For a complete understanding of each features operation, refer to Section 4: Protection Functions. High set over-current protection with direction or non-direction ( HS OC ); Low set over-current protection with direction or non-direction ( LS OC ); Inverse definite minimum time Lag of over-current protection with direction or nondirection (INV OC ); High set earth fault protection with direction or non-direction ( HS EF ); Low set earth fault protection with direction or non-direction ( LS EF ); Inverse definite minimum time Lag of earth fault protection with direction or non-direction ( INV EF ); Overload protection ( O L); Under voltage and over voltage protection ( UV&OV ); Thermal over load protection ( Therm OL ); Under frequency protection ( U/F ); Circuit breaker failure protection ( CBF ); Not only as a protection relay, CSC-211 also performs control and monitoring functions and therefore helps the user in cost-effective power system management, and ensures reliable supply of electric power to the customers.

-1-

CSC-211 Numerical Backup Protection equipment

Manual

-2-

CSC-211 Numerical Backup Protection equipment

Manual

2 Features
Equipped with 32 bits embedded micro-control unit (MCU) and 14 bits A/D converter, the equipment has very strong capacity of data processing. Relay logic and the control logic schemes can be customized by means of friendly graphic tools. Detailed operation information and fault records are provided for the optimization operation and the fault analysis. Independent high precision measurement system is designed to meet the demands of the remote monitoring and metering. All of important hardware and software components are supervised continuously, and irregularities in hardware and program sequence can be detected and alarmed, which improve the security and availability of the protection system significantly. Friendly user interface provided 11 specified LEDs and graphical crystal display, which can clearly indicate the operation information and implement easy maintenance. High precision real-time clock is embedded in the equipment, and the networks synchronization and the GPS pulse synchronization are provided for fault record and analysis, which require precise time sequence. High-standard performance of EMC (Electro Magnetic Compatibility), ensures that the equipment can work in rigorous electrical environment and atmospheric environment.

-3-

CSC-211 Numerical Backup Protection equipment

Manual

3 Construction
The enclosure for equipment is 19/2 inches in width and 4U in height according to IEC 60297-3. The equipment is flush mounted with panel cutout. The equipment for cabinet mounting has rear connection terminals. The front panel of the equipment is unclosed from the top of the equipment. LCD, LEDs and keys are mounted on the panel. There is a serial interface on the panel. Draw-out modules for serviceability are fixed by lock component. The modules can be combined through the bus on the rear board. Both the equipment and the other system can be combined through the rear interfaces

Fig 1 shows the Flush-mounted enclosure of CSC-211 with panel cutout.

-4-

CSC-211 Numerical Backup Protection equipment

Manual

4 Protection functions 4.1 HS/LS OC protection (Both MODEL 1 and MODEL 2)


Both HS and LS OC protections can be selected as instantaneous or definite time delayed protection according to the time delay setting. If the time setting is zero, it will be worked as instantaneous over current protection. Otherwise will be definite time delay over current protection. These two protections can be configured as forward directional, reverse directional or non-directional. And the non-directional element will block the forward and the reverse elements. Characteristic angle of directional element is selectable, 30 or 45. These two over current protections are all blocked by VT fail. Direction element adopts 90o connection (shown as Tab.1), and it takes effect to A, B, C phase respectively. The direction arrangement of U/I is shown as Fig.2. To avoid dead zone when voltage is too low to determine direction, direction element takes the voltage memory. Tab.1 Voltage and current of direction element Phase A B C Current Ia Ib Ic Voltage Ubc Uca Uab

C.A.+90 C.A.+87.5

RVD. ZONE

FWD. ZONE

Characteristic Angle (C.A.)

C.A.-87.5 C.A.-90
Fig 2. Forward and reverse zone of direction element

-5-

CSC-211 Numerical Backup Protection equipment


Ia>I FWD
AND Phase A at FWD

Manual

Ib>IFWD
AND Phase B at FWD

OR

AND

T FWD

Relay Trip

Ic>I FWD
AND Phase C at FWD ON

FWD element
OFF

VT Fail

Ia>I RVD
AND Phase A at RVD

Ib>I RVD
AND Phase B at RVD

OR

AND

T RVD

Relay Trip

Ic>I RVD
AND Phase C at RVD ON

RVD element
OFF

Ia>I NOD Ib>I NOD Ic>I NOD


ON OR AND

T NOD

Relay Trip

NOD element
OFF ON

Function
OFF

Fig 3. Logic of HS/LS OC protection The settings for HS OC protection is showed in Tab.2 and Tab.3. Tab.2 Settings list for HS OC protection
No. 5 6 7 8 9 10 Caption HS OC FWD I HS OC RVD I HS OC NOD I HS OC FWD T HS OC RVD T HS OC NOD T Scope 0.05~100 0.05~100 0.05~100 0.00~60.0 0.00~60.0 0.00~60.0 Unit A A A s s s Memo

High set of current for over current at forward direction High set of current for over current at reverse direction High set of current for over current at non-direction High set of time for over current at forward direction High set of time for over current at reverse direction High set of time for over current at non-direction

Tab.3 Function element ON/OFF for HS OC protection

-6-

CSC-211 Numerical Backup Protection equipment


Bit Func Dir F/R Bit 2 Func Dir F/R Bit 3 Func Non Dir Bit 1 Func Bit Bit 1 Func Setting Bit 13 Set to 0 HS OC FWD OFF HS OC RVD OFF HS OC NOD OFF HS OC FUNC OFF C.A. of OC 30 Set to 1

Manual

HS OC FWD ON HS OC RVD ON HS OC NOD ON HS OC FUNC ON C.A. of OC 45

The settings for LS OC protection is showed in Tab.4 and Tab.5. Tab.4 Settings list for LS OC protection
No. 11 12 13 14 15 16 Caption LS OC FWD I LS OC RVD I LS OC NOD I LS OC FWD T LS OC RVD T LS OC NOD T Scope 0.05~100 0.05~100 0.05~100 0.00~300 0.00~300 0.00~300 Unit A A A s s s Remark

Low set of current for over current at forward direction Low set of current for over current at reverse direction Low set of current for over current at non-direction Low set of time for over current at forward direction Low set of time for over current at reverse direction Low set of time for over current at non-direction

Tab.5 Function element ON/OFF for LS OC protection


Bit Func Dir F/R Bit 4 Func Dir F/R Bit 5 Func Non Dir Bit 2 Func Bit Bit 2 Func Setting Bit 13 Set to 0 LS OC FWD OFF LS OC RVD OFF LS OC NOD OFF LS OC FUNC OFF C.A. of OC 30 Set to 1 LS OC FWD ON LS OC RVD ON LS OC NOD ON LS OC FUNC ON C.A. of OC 45

4.2 HS/LS EF protection (Both MODEL 1 and MODEL 2)


Both HS and LS EF protection can be selected as instantaneous or definite time delayed protection according to the time delay setting. If the time setting is zero, it will be worked as instantaneous earth fault protection. Otherwise will be definite time delay earth fault protection.

These two protections can be configured as forward directional, reverse directional or non-directional. And the non-directional element will block the forward and the reverse elements. Characteristic angle of directional element is selectable, -45 or -60. These two earth fault protections are all blocked by VT fail. The direction arrangement of U/I is shown as Fig.2. The U is calculated by three phase Voltage, and the current I comes from analog input IN.

U = UA + UB + UC
The logic of HS/LS EF is showed as Fig4.

-7-

CSC-211 Numerical Backup Protection equipment


IN>IFWD
AND IN at FWD ON

Manual

FWD element
OFF

AND

T FWD

Relay Trip

VT Fail

IN>IRVD
AND IN at RVD ON AND

T RVD

Relay Trip

RVD element
OFF

IN>INOD
AND ON

T NOD

Relay Trip

NOD element
OFF ON

Function
OFF

Fig 4. Logic of HS/LS EF protection The settings for HS EF protection is showed in Tab.6 and Tab.7. Tab.6 Settings list for HS EF protection
No. 17 18 19 20 21 22 Caption HS EF FWD I HS EF RVD I HS EF NOD I HS EF FWD T HS EF RVD T HS EF NOD T Scope 0.05~100 0.05~100 0.05~100 0.00~60.0 0.00~60.0 0.00~60.0 Unit A A A s s s Memo

High set of current for earth fault at forward direction High set of current for earth fault at reverse direction High set of current for earth fault at non-direction High set of time for earth fault at forward direction High set of time for earth fault at reverse direction High set of time for earth fault at non-direction

Tab.7 Function element ON/OFF for HS EF protection


Bit Func Dir F/R Bit 8 Func Dir F/R Bit 9 Func Non Dir Bit 4 Func Bit Bit 4 Func Setting Bit 14 Set to 0 HS EF FWD OFF HS EF RVD OFF HS EF NOD OFF HS EF FUNC OFF C.A. of EF -45 Set to 1 HS EF FWD ON HS EF RVD ON HS EF NOD ON HS EF FUNC ON C.A. of EF -60

The settings for LS EF protection is showed in Tab.8 and Tab.9. Tab.8 Settings list for LS EF protection
No. 23 24 25 Caption LS EF FWD I LS EF RVD I LS EF NOD I Scope 0.05~100 0.05~100 0.05~100 Unit A A A Remark

Low set of current for earth fault at forward direction Low set of current for earth fault at reverse direction Low set of current for earth fault at non-direction
-8-

CSC-211 Numerical Backup Protection equipment


26 27 28 LS EF FWD T LS EF RVD T LS EF NOD T 0.00~300 0.00~300 0.00~300 s s s

Manual

Low set of time for earth fault at forward direction Low set of time for earth fault at reverse direction Low set of time for earth fault at non-direction

Tab.9 Function element ON/OFF for LS EF protection


Bit Func Dir F/R Bit 10 Func Dir F/R Bit 11 Func Non Dir Bit 5 Func Bit Bit 5 Func Setting Bit 14 Set to 0 LS EF FWD OFF LS EF RVD OFF LS EF NOD OFF LS EF FUNC OFF C.A. of EF -45 Set to 1 LS EF FWD ON LS EF RVD ON LS EF NOD ON LS EF FUNC ON C.A. of EF -60

4.3 INV OC/EF protection (Both MODEL 1 and MODEL 2)


The operating time of the INV OC/EF function reduces when the fault current increases and it can therefore achieve shorter operating time for fault location closer to the source. Four different characteristics are provided and described as follow: Curve 1 (Normal/Standard inverse): t =

(I I )
p

0.14
0.02

t p refer relay setting menu

Curve 2 (Very inverse): t =

13.5 (I I p ) 1 t p

refer relay setting menu

Curve 3 (Extremely inverse): t =

(I I )
p

80
2

tp

refer relay setting menu

Curve 4 (Long time inverse): t =

120 (I I p ) 1 t p

refer relay setting menu

INV OC/EF protection can be set as directional and is also affected by VT fail similar with HS/LS OC/EF protection as above. The directional unit has been showed in Fig.2 The logic of INV OC is showed as Fig5.

-9-

CSC-211 Numerical Backup Protection equipment

Manual

Ia>I FWD
Phase A at FWD

AND

AND

t FWD EXP FWD

Ib>IFWD
AND Phase B at FWD AND

t FWD EXP FWD t FWD EXP FWD

OR

Relay Trip

Ic>I FWD
Phase C at FWD

AND

AND

ON

FWD element
OFF

VT Fail

Ia>I RVD
Phase A at RVD

AND

AND

t RVD EXP RVD

Ib>I RVD
AND Phase B at RVD AND

t RVD EXP RVD t RVD EXP RVD

OR

Relay Trip

Ic>I RVD
AND Phase C at RVD ON AND

RVD element
OFF

Ia>I NOD Ib>I NOD Ic>I NOD


ON OR AND

t NOD EXP NOD

Relay Trip

NOD element
OFF ON

Function
OFF

Fig 5. Logic of INV OC protection The settings for the INV OC protections are showed in Tab.10 and Tab.11. Tab.10 Setting list for INV OC protection
No 29 30 Caption INV OC FWD I INV OC FWD T Scope 0.05~100 0.005~5 Unit A s Remark

31

CRV SEL OF FOC

1~4

32 33 34

INV OC RVD I INV OC RVD T CRV SEL OF ROC

0.05~100 0.005~5 1~4

A s -

Current set for INV over current at forward direction Time set for INV over current at forward direction I IEC SI or NI 2 IEC VI 3 IEC EI 4 ANSI LTI Current set for INV over current at reverse direction Time set for INV over current at reverse direction I IEC SI or NI 2 IEC VI
-10-

CSC-211 Numerical Backup Protection equipment

Manual

35 36

INV OC NOD I INV OC NOD T

0.05~100 0.005~5

A s

37

CRV SEL OF NOC

1~4

3 IEC EI 4 ANSI LTI Current set for INV over current at non-direction Time set for INV over current at non-direction I IEC SI or NI 2 IEC VI 3 IEC EI 4 ANSI LTI

Tab.11 Function element ON/OFF for INV OC protection


Bit Func Dir F/R Bit 12 Func Dir F/R Bit 13 Func Non Dir Bit 6 Func Bit Bit 6 Func Setting Bit 13 Set to 0 INV OC FWD OFF INV OC RVD OFF INV OC NOD OFF INV OC FUNC OFF C.A. of EF 30 Set to 1 INV OC FWD ON INV OC RVD ON INV OC NOD ON INV OC FUNC ON C.A. of EF 45

The logic of INV EF is showed as Fig6.


IN>IFWD
IN at FWD ON AND AND

t FWD EXP FWD

Relay Trip

FWD element
OFF

VT Fail

IN>IRVD
AND IN at RVD AND

t RVD EXP RVD

Relay Trip

ON

RVD element
OFF AND

IN>INOD
ON

t NOD EXP NOD

Relay Trip

NOD element
OFF ON

Function
OFF

Fig 6. Logic of INV EF protection

The settings for INV EF protections are showed in Tab.12 and Tab.13.

Tab.12 Setting list for INV EF protection

-11-

CSC-211 Numerical Backup Protection equipment


No 38 39 Caption INV EF FWD I INV EF FWD T Scope 0.05~100 0.005~250 Unit A s Remark

Manual

40

CRV SEL OF FEF

1~4

41 42

INV EF RVD I INV EF RVD T

0.05~100 0.005~5

A s

43

CRV SEL OF REF

1~4

44 45

INV EF NOD I INV EF NOD T

0.05~100 0.005~5

A s

46

CRV SEL OF NEF

1~4

Current set for INV earth fault at forward direction Time set for INV earth fault at forward direction I IEC SI or NI 2 IEC VI 3 IEC EI 4 ANSI LTI Current set for INV earth fault at reverse direction Time set for INV earth fault at reverse direction I IEC SI or NI 2 IEC VI 3 IEC EI 4 ANSI LTI Current set for INV earth fault at non-direction Time set for INV earth fault at non-direction I IEC SI or NI 2 IEC VI 3 IEC EI 4 ANSI LTI

Tab.13 Function element ON/OFF for INV EF protection


Bit Func Dir F/R Bit 14 Func Dir F/R Bit 15 Func Non Dir Bit 7 Func Bit Bit 7 Func Setting Bit 14 Set to 0 INV EF FWD OFF INV EF RVD OFF INV EF NOD OFF INV EF FUNC OFF C.A. of EF -45 Set to 1 INV EF FWD ON INV EF RVD ON INV EF NOD ON INV EF FUNC ON C.A. of EF -60

4.4 Overload protection (Only MODEL 1)


This protection is just a definite time-delayed (time can be set very long) over-current element. The settings for overload protection are showed in Tab.14 and Tab.15. Tab.14 Setting list for overload protection
No 50 51 Caption Overload I Overload T Scope 0.2~10 0.1~1000 Unit A s Remark

Current set for overload protection Time set for overload protection

Tab.15 Function element ON/OFF for overload protection Bit Func Bit Bit 10 Set to 0 OL FUNC OFF Set to 1 OL FUNC ON

4.5 UV&OV protection (Both MODEL 1 and MODEL 2)


When any phase-to-phase voltage in normal state turns to be less than or more than predetermined value, it will result in tripping after predetermined time. This protection includes two stages. Either stage can be chose either over voltage protection or under voltage protection, and they have the same time setting delay. It is
-12-

CSC-211 Numerical Backup Protection equipment showed as Fig7.


Max U phase-phase > U OV AND

Manual

UV&OV is OV 1 UV&OV is UV OR AND Min

Uphase-phase
VT Fail

<

UUV
AND

DI input (CB closed)


ON

AND

DO-UV&OV

Function
OFF

Fig 7. Logic of UV&OV protection The settings for the UV&OV protection is showed in Tab.16 and Tab.17 Tab.16 Setting list for UV&OV protection
No 52 for model 1 47 for model 2 53 for model 1 48 for model 2 54 for model 1 49 for model 2 55 for model 1 50 for model 2 56 for model 1 51 for model 2 57 for model 1 52 for model 2 Caption UV stg1 V OV stg1 V UV&OV stg1 T UV stg2 V OV stg2 V UV&OV stg2 T Scope 66~110 110~154 0.1~10 66~110 110~154 0.1~10 Unit V V s V V s Remark

Voltage set of under voltage for UV&OV at stage1 Voltage set of over voltage for UV&OV at stage1 Time set for UV&OV at stage1 Voltage set of under voltage for UV&OV at stage2 Voltage set of over voltage for UV&OV at stage2 Time set for UV&OV at stage2

Tab.17 Function element ON/OFF for UV&OV protection


Bit Func Setting Bit 11 Func Setting Bit 12 Func Bit Bit 8 Set to 0 UV&OV stg1 UV UV&OV stg2 UV UV&OV FUNC OFF Set to 1 UV&OV stg1 OV UV&OV stg2 OV UV&OV FUNC ON

4.6 Thermal overload protection (Only MODEL 1)


Transformer design has changed over the years, with less and less metal being used per MVA of transformer power. This has reduced the withstand time which a transformer can be allowed to be run in an over loaded state. This equipment provides thermal overload protection to cut down the transformer. IEC curve:

-13-

CSC-211 Numerical Backup Protection equipment

Manual

I eq 2 (1 H / C )I P 2 t = ln 2 2 I eq I
t thermal trip time equivalent thermal current thermal time constant rms thermal current setting hot spot weighting factor prior current takes into account cyclic loading

I eq

I H /C Ip
Here,

, 1 H / C and I are all settings, and I eq =

IA + IB + IC 3

, I p equals to the

equivalent current before overload. The settings for the thermal overload protection is showed in Tab.18 and Tab.19 Tab.18 Setting list for the thermal overload protection
No 47 48 48 Caption Thermal I Thermal T Thermal H/C Scope 0.2~10 6~7200 0~1 Unit A s Remark

Current set for thermal overload protection Time set thermal for overload protection (thermal time constant) hot spot weighting factor

Tab.19 Function element ON/OFF for thermal overload protection


Bit Func Bit Bit 9 Set to 0 THERM FUNC OFF Set to 1 THERM FUNC ON

4.7 CBF protection (Only MODEL 1)


Both single phase CBF and 3 phases CBF are provided in the CSC-211 equipment model 1.

-14-

CSC-211 Numerical Backup Protection equipment


Ia>I CBF
AND DI-START A_ph AND

Manual

T CBF

DO-START A_ph

Ib>I CBF
AND DI-START B_ph AND

T CBF

DO-START B_ph

Ic>I CBF
AND DI-START C_ph OR AND OR

T CBF

DO-START C_ph

T CBF

DO-START 3_ph

Internal trip
OR DI-START 3_ph ON

AND

Function
OFF

Fig 8. Logic of CBF protection The settings for the CBF protection is showed in Tab.20 and Tab.21 Tab.20 Setting list for the CBF protection
No 58 59 Caption CBF OC I CBF OC T Scope 0.05~100 0~32.00 Unit A s Remark

Current set for CBF protection Time set for CBF protection

Tab.21 Function element ON/OFF for CBF protection


Bit Func Bit Bit 11 Set to 0 CBF FUNC OFF Set to 1 CBF FUNC ON

4.8 U/F protection (Only MODEL 2)


When network frequency in normal state is less than predetermined value, this protection will result in tripping after predetermined time. It has 4 stages .And Df/Dt is another operate element only for stage 1 and 2 to trip after the same time. The relative of two elements U/F and Df/Dt can be chosen as OR or AND. The U/F and the Df/Dt are all calculated by software from voltage of phase A to B. There are two elements to block this protection: VT failure and the minimum of voltage of phase to phase is less than 70V. The U/F logic of stage 1 is showed at Fig 9, so is stage 2.

-15-

CSC-211 Numerical Backup Protection equipment


Df/Dt > AND Df/Dt AND AND Df/Dt OR AND Df/Dt > ON OR OR

Manual

Df/Dt element
OFF AND

F<
ON AND

Function
OFF

DO-UF

VT Fail Min.Uphase-phase < 70V

Fig 9. Logic of U/F protection The settings for the U/F protection is showed in Tab.22 and Tab.23 Tab.22 Setting list for UF protection
No 53 54 55 56 57 58 59 60 61 62 Caption U/F stg1 F U/F stg1 T U/F stg12 F U/F stg2 T U/F stg3 F U/F stg3 T U/F stg4 F U/F stg4 T Df/Dt stg1 Df/Dt stg2 Scope 45.0 50.0 0.3 5.0 45.0 50.0 0.3 5.0 45.0 50.0 0.3 5.0 45.0 50.0 0.3 5.0 0.2 1.0 0.2 1.0 Unit Hz s Hz s Hz s Hz s Hz/s Hz/s Remark

Current set for under frequency protection at stage 1 Time set for under frequency protection at stage 1 Current set for under frequency protection at stage 2 Time set for under frequency protection at stage 2 Current set for under frequency protection at stage 3 Time set for under frequency protection at stage 3 Current set for under frequency protection at stage 4 Time set for under frequency protection at stage 4 Df/Dt set for under frequency protection at stage 1 Df/Dt set for under frequency protection at stage 2

Tab.23 Function element ON/OFF for UF protection


Bit Func Bit bit 11 Func Bit bit 12 Func Bit bit 13 Func Bit bit 14 Func Setting Bit 4 Func Setting Bit 5 Func Setting Bit 9 Func Setting Bit 10 Set to 0 U/F stg1 OFF U/F stg2 OFF U/F stg3 OFF U/F stg4 OFF Df/Dt stg1 OFF Df/Dt stg2 OFF Df/Dt stg1 AND Df/Dt stg2 AND Set to 1 U/F stg1 ON U/F stg2 ON U/F stg3 ON U/F stg4 ON Df/Dt stg1 ON Df/Dt stg2 ON Df/Dt stg1 OR Df/Dt stg2 OR

4.9 VT supervision
Voltage transformer supervision can supervise bus voltage and report single-phase broken, two-phase broken and three-phase broken. Any of the following conditions satisfy and last 9 seconds, CSC-211 will report the alarm of TV broken or no-voltage. Self-generated zero sequence voltage and three-phase voltage are all less than 8V,
-16-

CSC-211 Numerical Backup Protection equipment

Manual

and any phase current is more than 0.125A (considered as no-voltage); Self-generated zero sequence voltage is more than 8V, and minimum phase-tophase voltage is less than 16V (considered as two-phase broken); Self-generated zero sequence voltage is more than 8V, and the difference between maximum phase-to-phase voltage and minimum phase-to-phase voltage is more than 16V (considered as single-phase broken). For the directional protection, the perfect bus-voltage is significant to their operation. Therefore, VT fail will block the protection with directional elements, under voltage, and under frequency.

-17-

CSC-211 Numerical Backup Protection equipment

Manual

5 Technical Data
DC Voltage:220V/110V Rated inputs AC Voltage: 100 / 3 V i.e 63.5 V Ph-N AC Current: 1A/5A Frequency: 50Hz DC circuit: < 5W standby + 0.5 per energized relay AC Voltage/phase < 0.15VA AC Current/phase < 0.25VA AC Current 1s @ 40In 10s @ 20In continuous @ 4In AC Voltage 10s @ 1.4Un continuous @ 1.2Un Make/Break: 1A; 220Vdc Protection thresholds : 3% Time delay : 3% with a minimum of 20ms Measurements: typical 0.2 % at I,U typical 0.5 % at P,Q, kW, kVA Voltage : 0.4V-120V Current: 0.04In -30In Frequency: 40-55Hz/50 Distinguishability of event record: 1ms Precision of GPS: 1ms RS485: Screened twisted pair,19200bps max Electrical Ethernet: UTP5, RJ45 connection Fiber Ethernet: optical fiber,820nm ST connection Insulation resistance: IEC 60255-5 > 1000 MV Dielectric withstand: IEC 60255-5 2kV common mode 1kV differential mode Impulse voltage: IEC 60255-5 5kV common mode 1kV differential mode Fast transient disturbance: IEC 61000-4-4 4kV auxiliary voltage, class 4 Electrostatic discharge: IEC 61000-4-2 8kV, class 4 Radio Frequency: ANSI C37.90.2 35V/m Impulse: IEC 61000-4-3 10V/m High frequency disturbance: IEC 61000-4-1 2.5kV common mode, class 3 1kV differential mode, class 3 Vibrations: IEC 60255-21-1 Response and endurance, class 1
-18-

Burdens

Thermal withstand

Contacts

Accuracy

Working range Report accuracy Communications

High voltage withstand

EMC

Mechanical performance

CSC-211 Numerical Backup Protection equipment

Manual

Atmospheric environment

Fault recording

Shock: IEC 60255-21-2 Response and withstand, class 1 Bump: IEC 60255-21-2 Response and withstand, class 1 Temperature: IEC 60255-6 Storage 25C to +70C Operation 25C to + 55C Humidity: IEC 60068-2-3 56 days at 93% RH and 40C Instantaneous values of all analog quantities fed to the relay. Record capacity: 6*1second

-19-

CSC-211 Numerical Backup Protection equipment

Manual

6 Measurement and Control


6.1 Measurement
The CSC-211 equipment monitors permanently all the current and voltage inputs, calculates the frequency, the phase to phase voltage, P, and Q, shows the values on the LCD display and stores the measurements in memory. The measured values are measured by the independent high precision module, which can ensure the true RMS with 0.2% accuracy (nominal conditions). Instantaneous measurements Phase current: Ia, Ib, Ic; Phase voltage: Ua, Ub, Uc; Three phase active power P, reactive power Q, power factor; Frequency; Forward/reverse active power, forward/reverse reactive power; Mean, maximum, minimum value of the current and voltage during some time; Sequence currents and voltages; Thermal status.

6.2

Operation method control

The settings are divided into two categories: protection settings, and control and support settings. 32 setting groups are provided for different operating conditions and adaptive relaying. The soft function pressboards are provided for activation or inhibition of the protection element. All settings and the states of the soft function pressboards are stored in E2PROM.

6.3

Programmable scheme logic

The programmable scheme logic feature of support software EPPC allows user to customize the protection and control functions. It is also used to program the functionality of the optically isolated inputs, relay outputs and LED indications. The trigger conditions and the record length could easy set by this function.

-20-

CSC-211 Numerical Backup Protection equipment

Manual

7 Fault Record and Analysis


The CSC-211 equipment can supervise the operation information of the devices and correlative circuit, which include fault records, events records, disturbance records and operation records. The internal real-time clock provides the time time-tag for all type records, the time distinguish ability is 1ms. The networks synchronization and the GPS pulse (adaptive second or minute pulse) synchronization are supported by the real-time clock system. A lithium battery provides a backup for the real time clock and all records in the event of supply failure. This battery is supervised and easily replaced from the front of the relay.

7.1

Fault records

Records of the last 40 faults are stored in battery backed memory. Some important data during the fault or manual operation are record. The information provided in the fault record includes: Fault time tag: date and time Operation event table: operation protection, operation time Operation data: current, voltage, frequency, phase angle Active setting groups States of the soft function pressboards

7.2

Disturbance records

Disturbance records are used to capture the analog and digital data of certain length before or after some event, it can reappearance the operation states of the devices during the fault period, any logic element and digital input could trigger the disturbance records. The internal disturbance recorder has 12 analogue channels, 32 digital channels (digital inputs, digital outputs, element states) and time tag. Data is sampled 20 times a cycle and typically 2 disturbance records, each of up to 5 seconds duration are stored in battery backed memory. Disturbance records can be extracted from the relay via the remote communications and saved in the COMTRADE format. These records may be examined using support software EPPC.

7.3

Events records

Up to 1000 time-tagged event records are stored in battery backed memory, and can be extracted using the communication ports or showed on the front panel display. The event
-21-

CSC-211 Numerical Backup Protection equipment

Manual

records include: operation events, alarm events, changing of digital input state or digital output state, time tag and the current status of the protection.

7.4

Operation records

The latest 40 time-tagged operation records are stored in the battery backed memory, it includes: the modification or switch of the setting groups, close or open control of the circuit breaker. These data could provide information for the detailed fault analysis.

8 Communications
All models of CSC-211 series equipments provide the following communications ports and protocols for the user: Double or single 10M Ethernet port of cable or fiber. One RS485 communication port One RS232 debug port IEC60870-5-103 CSC-211 equipment can transmit real-time data to the local monitoring system, or remotely to the SCADA, these data include settings, measurements and alarms, as well as fault, event and disturbance records. The communication settings (relay address, data rate, parity, etc.) can be programmed using the relay front port. Software allows easy setting of any CSC-211 model, in addition to uploading of event, fault and disturbance records, settings and measurements. The detailed protocols are provided in the products manual.

9 Diagnostics
Automatic tests including power-on diagnostics and continuous self-monitoring, ensure a high degree of reliability. When any abnormal status is detected, the alarm indicators and related relay are driven, and the dependent events could be record immediately. For some fatal faults, the relay could be blocked to avoid the unwanted operation. The results of the self-test functions are stored in non-volatile memory. The virtual test function is provided for the automatic tests of the substation automation system. The function contains automatic counter point of digital input, automatic triggering of SOE. Test features available on the user interface provide examination of input quantities, states of the digital inputs and relay outputs. A local monitor port provides digital outputs, selected from a prescribed list of signals, including the status of protection element, and may be used in conjunction with test equipment. These test signals can also be viewed using the communications ports, and the front panel user interface.

-22-

CSC-211 Numerical Backup Protection equipment

Manual

10 Setting Table 10.1 Setting list for MODEL 1


Setting List and Description
No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 Caption Func Dir F/R Func Setting 1 Func Bit Func Non Dir HS OC FWD I HS OC RVD I HS OC NOD I HS OC FWD T HS OC RVD T HS OC NOD T LS OC FWD I LS OC RVD I LS OC NOD I LS OC FWD T LS OC RVD T LS OC NOD T HS EF FWD I HS EF RVD I HS EF NOD I HS EF FWD T HS EF RVD T HS EF NOD T LS EF FWD I LS EF RVD I LS EF NOD I LS EF FWD T LS EF RVD T LS EF NOD T INV OC FWD I INV OC FWD T Scope 0000 - FFFF 0000 - FFFF 0000 - FFFF 0000 - FFFF 0.05 - 100 0.05 - 100 0.05 - 100 0.0 - 60.00 0.0 - 60.00 0.0 - 60.00 0.05 - 100 0.05 - 100 0.05 - 100 0.0 - 300.0 0.0 - 300.0 0.0 - 300.0 0.05 - 100 0.05 - 100 0.05 - 100 0.0 - 60.00 0.0 - 60.00 0.0 - 60.00 0.05 - 100 0.05 - 100 0.05 - 100 0.0 - 300.0 0.0 - 300.0 0.0 - 300.0 0.05 - 100 0.005 - 5 A A A s s s A A A s s s A A A s s s A A A s s s A s EF OC Unit Memo For forward and reverse directional element For UV/OV, C.A. and rated current Function selective For non-directional element Function

31

CRV SEL OF FOC

1~4

-----

I IEC SI or NI 2 IEC VI 3 IEC EI 4 ANSI LTI

32 33

INV OC RVD I INV OC RVD T

0.05 - 100 0.005 - 5

A s

34

CRV SEL OF ROC

1~4

-----

I IEC SI or NI 2 IEC VI 3 IEC EI 4 ANSI LTI

INV OC

35 36

INV OC NOD I INV OC NOD T

0.05 - 100 0.005 - 5

A s

-23-

CSC-211 Numerical Backup Protection equipment


No. Caption Scope Unit Memo

Manual
Function

37

CRV SEL OF NOC

1~4

-----

I IEC SI or NI 2 IEC VI 3 IEC EI 4 ANSI LTI

38 39

INV EF FWD I INV EF FWD T

0.05 - 100 0.005 - 5

A s

40

CRV SEL OF FEF

1~4

-----

I IEC SI or NI 2 IEC VI 3 IEC EI 4 ANSI LTI

41 42

INV EF RVD I INV EF RVD T

0.05 - 100 0.005 - 5

A s

43

CRV SEL OF REF

1~4

-----

I IEC SI or NI 2 IEC VI 3 IEC EI 4 ANSI LTI

INV EF

44 45

INV EF NOD I INV EF NOD T

0.05 - 100 0.005 - 5

A s

46

CRV SEL OF NEF

1~4

-----

I IEC SI or NI 2 IEC VI 3 IEC EI 4 ANSI LTI

47 48 49 50 51 52 53 54 55 56 57 58 59 60 61

Thermal I Thermal T Thermal H/C Overload I Overload T UV stg1 V OV stg1 V UV&OV stg1 T UV stg2 V OV stg2 V UV&OV stg2 T CBF OC I CBF OC T Mea CT Ratio Mea VT Ratio

0.2 - 10.0 6 - 7200 0.0 - 1 0.2 - 10.0 0.1 - 6000 66.0 - 110.0V 110.0 - 154.0 0.1 - 10.0 66.0 - 110.0V 110.0 - 154.0 0.1 - 10.0 0.05 A - 100 0.1 - 32.00 0.001 - 10.0 0.01 - 10.0

A s OL A s V V s V V s A s kA/A kV/V Primary Mea CT /1000 Primary PT/1000 CBF Phase-to-Phase Phase-to-Phase Phase-to-Phase Phase-to-Phase UV&OV

Definition of Func Dir F/R


BIT 15 14 13 12 11 10 9 8 0 INV EF FWD OFF INV EF FWD OFF INV OC RVD OFF INV OC FWD OFF LS EF RVD OFF LS EF FWD OFF HS EF RVD OFF HS EF FWD OFF 1 INV EF FWD ON INV EF FWD ON INV OC RVD ON INV OC FWD ON LS EF RVD ON LS EF FWD ON HS EF RVD ON HS EF FWD ON

-24-

CSC-211 Numerical Backup Protection equipment


7 6 5 4 3 2 1 0 Not used Not used LS OC RVD OFF LS OC FWD OFF HS OC RVD OFF HS OC FWD OFF Not used Not used Not used Not used LS OC RVD ON LS OC FWD ON HS OC RVD ON HS OC FWD ON Not used Not used

Manual

Definition of Func Setting 1


BIT 15 14 13 12 11 10 9 8 7 4~6 0~3 0 Not used C.A. of EF -45 C.A.of OC 30 UV&OV stg2 UV UV&OV stg1 UV Not used Not used Neu CT Rated 5A Pha CT Rated 5A Not used Not used 1 Not used C.A.of EF -60 C.A.of OC 45 UV&OV stg2 OV UV&OV stg1 OV Not used Not used Neu CT Rated 1A Pha CT Rated 1A Not used Not used

Definition of Func Bit


BIT 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 0 Not used Not used Not used Not used CBF FUNC OFF OL FUNC OFF THERM FUNC OFF UV&OV FUNC OFF INV EF FUNC OFF INV OC FUNC OFF LS EF FUNC OFF HS EF FUNC OFF Not used LS OC FUNC OFF HS OC FUNC OFF Not used 1 Not used Not used Not used Not used CBF FUNC ON OL FUNC ON THERM FUNC ON UV&OV FUNC ON INV EF FUNC ON INV OC FUNC ON LS EF FUNC ON HS EF FUNC ON Not used LS OC FUNC ON HS OC FUNC ON Not used

Definition of Func Non Dir


BIT 8~15 0 Not used
-25-

1 Not used

CSC-211 Numerical Backup Protection equipment


7 6 5 4 3 2 1 0 INV EF NOD OFF INV OC NOD OFF LS EF NOD OFF HS EF NOD OFF Not used LS OC NOD OFF HS OC NOD OFF Not used INV EF NOD ON INVOC NOD ON LS EF NOD ON HS EF NOD ON Not used LS OC NOD ON HS OC NOD ON Not used

Manual

10.2 Setting list for MODEL 2


Setting List and Description
No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 Caption Func Dir F/R Func Setting Func BIT Func Non Dir HS OC FWD I HS OC RVD I HS OC NOD I HS OC FWD T HS OC RVD T HS OC NOD T LS OC FWD I LS OC RVD I LS OC NOD I LS OC FWD T LS OC RVD T LS OC NOD T HS EF FWD I HS EF RVD I HS EF NOD I HS EF FWD T HS EF RVD T HS EF NOD T LS EF FWD I LS EF RVD I LS EF NOD I LS EF FWD T LS EF RVD T LS EF NOD T INV OC FWD I INV OC FWD T Scope 0000 - FFFF 0000 - FFFF 0000 - FFFF 0000 - FFFF 0.05 - 100 0.05 - 100 0.05 - 100 0.0 - 60.00 0.0 - 60.00 0.0 - 60.00 0.05 - 100 0.05 - 100 0.05 - 100 0.0 - 300.0 0.0 - 300.0 0.0 - 300.0 0.05 - 100 0.05 - 100 0.05 - 100 0.0 - 60.00 0.0 - 60.00 0.0 - 60.00 0.05 - 100 0.05 - 100 0.05 - 100 0.0 - 300.0 0.0 - 300.0 0.0 - 300.0 0.05 - 100 0.005 - 5 A A A s s s A A A s s s A A A s s s A A A s s s A s INV OC EF OC Unit Memo For forward and reverse directional element For UV/OV, U/F , C.A. and rated current Function selective ON oor OFF For non-directional element Function

-26-

CSC-211 Numerical Backup Protection equipment


No. Caption Scope Unit Memo

Manual
Function

31

CRV SEL OF FOC

1~4

-----

I IEC SI or NI 2 IEC VI 3 IEC EI 4 ANSI LTI

32 33

INV OC RVD I INV OC RVD T

0.05 - 100 0.005 - 5

A s

34

CRV SEL OF ROC

1~4

-----

I IEC SI or NI 2 IEC VI 3 IEC EI 4 ANSI LTI

35 36

INV OC NOD I INV OC NOD T

0.05 - 100 0.005 - 5

A s

37

CRV SEL OF NOC

1~4

-----

I IEC SI or NI 2 IEC VI 3 IEC EI 4 ANSI LTI

38 39

INV EF FWD I INV EF FWD T

0.05 - 100 0.005 - 5

A s

40

CRV SEL OF FEF

1~4

-----

I IEC SI or NI 2 IEC VI 3 IEC EI 4 ANSI LTI

41 42

INV EF RVD I INV EF RVD T

0.05 - 100 0.005 - 5

A s

43

CRV SEL OF REF

1~4

-----

I IEC SI or NI 2 IEC VI 3 IEC EI 4 ANSI LTI

INV EF

44 45

INV EF NOD I INV EF NOD T

0.05 - 100 0.005 - 5

A s

46

CRV SEL OF NEF

1~4

-----

I IEC SI or NI 2 IEC VI 3 IEC EI 4 ANSI LTI


Phase-to-Phase Phase-to-Phase Phase-to-Phase Phase-to-Phase UV&OV

47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62

UV stg1 V OV stg1 V UV&OV stg1 T UV stg2 V OV stg2 V UV&OV stg2 T U/F stg1 F U/F stg1 T U/F stg2 F U/F stg2 T U/F stg3 F U/F stg3 T U/F stg4 F U/F stg4 T U/F dF/dt Mea CT Ratio

66.0 - 110.0V 110.0 - 154.0 0.1 - 10.0 66.0 - 110.0V 110.0 - 154.0 0.1 - 10.0 45.00 - 50.00 0.40 - 5.00 45.00 - 50.00 0.40 - 5.00 45.00 - 50.00 0.40 - 5.00 45.00 - 50.00 0.40 - 5.00 1.0 - 10.0 0.001 - 10.0

V V s V V s Hz s Hz s Hz s Hz s Hz/s kA/A

U/F

Primary Mea CT /1000

-27-

CSC-211 Numerical Backup Protection equipment


No. 63 Caption Mea PT Ratio Scope 0.01 - 10.0 Unit kV/V Memo Primary PT/1000

Manual
Function

Definition of Func Dir F/R


BIT 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 0 INV EF FWD OFF INV EF FWD OFF INV OC RVD OFF INV OC FWD OFF LS EF RVD OFF LS EF FWD OFF HS EF RVD OFF HS EF FWD OFF Not used Not used LS OC RVD OFF LS OC FWD OFF HS OC RVD OFF HS OC FWD OFF Not used Not used 1 INV EF FWD ON INV EF FWD ON INV OC RVD ON INV OC FWD ON LS EF RVD ON LS EF FWD ON HS EF RVD ON HS EF FWD ON Not used Not used LS OC RVD ON LS OC FWD ON HS OC RVD ON HS OC FWD ON Not used Not used

Definition of Func Setting 1


BIT 15 14 13 12 11 10 9 8 7 6 5 4 0~3 0 Not used C.A. of EF -45 C.A.of OC 30 UV&OV stg2 UV UV&OV stg1 UV Df/Dt stg2 AND Df/Dt stg1 AND Neu CT Rated 5A Pha CT Rated 5A Not used Df/Dt stg2 OFF Df/Dt stg1 OFF Not used 1 Not used C.A.of EF -60 C.A.of OC 45 UV&OV stg2 OV UV&OV stg1 OV Df/Dt stg2 OR Df/Dt stg1 OR Neu CT Rated 1A Pha CT Rated 1A Not used Df/Dt stg2 ON Df/Dt stg1 ON Not used

Definition of Func Bit


BIT 15 14 13 12 0 Not used U/F stg4 OFF U/F stg3 OFF "U/F stg2 OFF 1 Not used U/F stg4 ON U/F stg3 ON U/F stg2 ON

-28-

CSC-211 Numerical Backup Protection equipment


11 10 9 8 7 6 5 4 3 2 1 0 U/F stg1 OFF Not used Not used UV&OV FUNC OFF INV EF FUNC OFF INV OC FUNC OFF LS EF FUNC OFF HS EF FUNC OFF Not used LS OC FUNC OFF HS OC FUNC OFF Not used U/F stg1 ON Not used Not used UV&OV FUNC ON INV EF FUNC ON INV OC FUNC ON LS EF FUNC ON HS EF FUNC ON Not used LS OC FUNC ON HS OC FUNC ON Not used

Manual

Definition of Func Non Dir


BIT 8~15 7 6 5 4 3 2 1 0 0 Not used INV EF NOD OFF INV OC NOD OFF LS EF NOD OFF HS EF NOD OFF Not used LS OC NOD OFF HS OC NOD OFF Not used 1 Not used INV EF NOD ON INVOC NOD ON LS EF NOD ON HS EF NOD ON Not used LS OC NOD ON HS OC NOD ON Not used

-29-

CSC-211 Numerical Backup Protection equipment

Manual

11

Selection and ordering data


1 2 3 4 5 6 7 8 9 / 10

CSC-211 0 Numerical Backup Protection Equipment Position


Ordering Codes

CSC 211-

1. AC1 Module
2 Phases Mea TA(Ia,Ic) 3 Phases Mea TA 5NSF.081.009(blank) 6NSF.001.002H 0 H

2. AC2 Module
Phase rated current 1A and neutral 1A Phase rated current 1A and neutral 5A Phase rated current 5A and neutral 5A Phase rated current 5A and neutral 1A 6NSF.001.003G 6NSF.001.003Q 6NSF.001.003L 6NSF.001.003B G Q L B

3. COM Module
Communication Port Configuration : 6NSF.001.003G 6

4. CPU Module
Enhanced Configuration (double Ethernet ): 6NSF.004.002A 2

5. LOGIC1 Module
Configuration : F6SF.006.006 5

6. LOGIC2 Module
Configuration : F6SF.06.005 7

7. POWER Module
DC110V DC220V 6SF.009.031.1 6SF.009.031.2 1 2

8. MMI Module
Standard Configuration (LCD resolution 160X80 ) 6NSF.005.002A 1

9. Structural Style Pack screen (cabinet) mounting (default configuration ) Switch cabinet mounting

D K

10. Software Version Mode 1 (CBF) Mode 2 (UF) Standard Configuration


DC110V DC220V CSC 211-HG625711D1 CSC 211-HG625721D1

1 2

-30-

12.1 Terminal Diagram of MODEL 1

12 Terminal Diagram

CSC-211 Numerical Backup Protection equipment

PO ER W X8
1 2 3 4 5 6 NT U O SED NT U O SED NT U O SED D gi t al I nput s i N T SU O ED C C SED B LO STAR C T BF_3ph

LO I C G 1 X7
1 2 3 4 5 6 7 8 9 10
24V O put ut STAR A- PH T C 1 BFSTAR A- PH T C 2 BFSTAR A- PH T C 3 BFSTAR B- PH T C 1 BFSTAR B- PH T C 2 BFSTAR C PH T C 1 BFSTART 3- PH CBF- 1 O ATI O PER N ALAR M NO U T SED

LO I C G 2 X6
1 2 3 4 5 6 7 8 9 10 11 12 13 14
UV&O STG V 2 U V STG V&O 2 R ELAY TR P2 I RELAY TR P1 I

C PU X5
1 REM ACCESS BLK I nput s 2
R ESET

CM O X4
Et her net

AC 2 X3
2 3 4 5 6
Bus/ Li ne Vol t age

AC 2 X2
1 2 3 4 5 6 7 8
M easur em ent Pr ot ect i on cur r ent

AC 1 X1
1 2 3 4 5 6 7 8 10 11 12
M easur em ent

3 RELAY TEST
T SED 4 NO U

R ELAY TR P1 I

5 24V C M O 6 NT U O SED O SED 7 NT U O SED 8 NT U 9 10 11 12

7 STAR C T BF_Aph 8 STAR C T BF_Bph 9 STAR C T BF_C ph C PU 10 D - I N T 11 12 13 14 16 O SED 17 N T U 18 O SED 19 N T U N 20 G D +24V 24V C M O PO ER O W FF

R ELAY TR P2 I

16 Pow I nput er 17 18 19 20

16 17 18 19 20
O VERLO AD

Et her net

-31-

U V STG V&O 1

9 10 11 12

11 12 13 14 15

U V STG V&O 2

O SED 15 N T U

15

Manual

ALAR M

C ALAR BF M

12.2 Terminal Diagram of MODEL 2

CSC-211 Numerical Backup Protection equipment

PO ER W X8
1 2 3 4 5 6 7 NT U O SED NT U O SED NT U O SED NT U O SED C C SED B LO NT U O SED NT U O SED NT U O SED NT U O SED D- IN T C PU +24V 24V C M O PO ER O W FF D gi t al I nput s i

LO I C G 1 X7
1 2 3 4 5 6 7 8 9 10
24V O put ut UF1 /

LO I C G 2 X6
1 2 3 4 5 6 7 8 9 10
U V STG V&O 1 U V STG V&O 2 R ELAY TR P2 I R ELAY TR P1 I

C PU X5
1 REM ACCESS BLK I nput s 2 R ESET 3
R ELAY TEST T 4 NO USED

CM O X4
Et her net

AC 2 X3
2 3 4 5 6
Bus/ Li ne Vol t age

AC 2 X2
1 3 4 5 6 7 8
M easur em ent Pr ot ect i on cur r ent

AC 1 X1
1 2 3 4 5 6 7 8 9 10 11 12
M easur em ent

UF 1 /

UF 1 /

R ELAY TR P1 I

5 24V C M O O SED 6 NT U 7 8 9 10 11 12 NT U O SED NT U O SED

8 9 10 11 12 13 14 16

UF 2 / UF 2 /

R ELAY TR P2 I

16 Pow I nput er 17 18 19 20

16 17 18 19 20

U V STG V&O 2

O SED 17 N T U 18 O SED 19 N T U N 20 G D

NT U O SED

NT U O SED

Et her net

-32-

9 10 11 12

11 12 13 14 15

UF 3 /

11 12 13 14

UF 4 / O ATI O PER N ALAR M

U V STG V&O 2

O SED 15 N T U

15

Manual

ALAR M

NT U O SED

CSC-211 Numerical Backup Protection equipment

Manual

13 Dimension drawings in mm
Dimension drawings for CSC-211 used 19/2 inch (4U) enclosure for panel flush-mounting and cabinet mounting.

Fig.10 Flush-mounted enclosure of CSC-211 with panel cutout

-33-

CSC-211 Numerical Backup Protection equipment

Manual

14 The Principle Outline of Logic Module 14.1 Logic 1 Module


24V COM +24V DO12 HARDWARE ALARM
CKJ1A GJB 5 16 V20 DSP2A-24V CKJ2A 1 + DSP1A-24V V1 12 CKJ3A GJE 9 16 GJXA 1 + U1 DSP2A-L2-24V X5 V18 5 CKJ2B 8 START A-PH CBF-3/UF 1 X6 X7 CKJ3B 12 9 START B-PH CBF-1/UF 2 X8 X9 8 QDJC 5 DI14 5 CKJ3E 8 START B-PH CBF-2/UF 2 X10 X11 BHXHB FGJB 16 9 QDJD DSP2A-L2-24V CKJ5B GJXB 2 CKJ5A + U2 DSP2A-L2-24V 5 V9 DSP1A-24V V4 FGJA BHXHD 5 1 + DSP1A1B-24V X19 V34 V35 1 V36 DSP1A-24V V37 V38 V6 + 16 DSP2A-L2-24V BHXH1A J2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 X1 X2 X3 X4 X5 X6 X7 X8 X9 X10 X11 X12 X13 X14 X15 X16 X17 X18 X19 X20 V8 GJXD 5 QDJA 8 X20 ALARM 16 X17 OPERATION ALARM (LATCHED) 8 X18 15 X15 BHXH1B 8 OPERATION ALARM X16 5 8 12 5 8 2 + U2 15 X13 START 3-PH CBF-1/UF 4 X14 5 CKJ4B 8 START C-PH CBF-1/UF 3 X12 16 5 CKJ1E 8 X3 START A-PH CBF-2/UF 1 X4 8 V16 1 + DSP1A1B-24V CKJ1B V17 12 9 16 9 GJA FGJC 12 X1 START A-PH CBF-1/UF 1 X2

24V COM

DO2
START A- PH CBF/ UF 1

DO11
ALARM

V19

+24B
TOBLOCK DIGITAL OUTPUTS

DO3 START B- PH CBF/ UF 2

+ DSP2A-24V V2 CKJ4A

16

TO CPU AS A DIGITAL INPUT

DO4 START C- PH CBF/ UF 3

+ DSP1A-24V V3

DO5
START 3- PH CBF/ UF 4

16

DO2 DO3 DO4 DO5 DO6 DO7 DO8 DO9 DO10

V32 BHXHA V33 1 + U1 16

DO13
SI GNAL RESET

DO1
STARTUP

+ DSP2A-24V V7

16

V39 V40

-34-

CSC-211 Numerical Backup Protection equipment

Manual

14.2

Logic 2 Module
CKJ1A

24V COM
16

DO7
RELAY TRI P

+ DSP2A-24V CKJ2A

X1 16 12 QDJB 9 12 CKJ1B 9 X2 X3 CKJ1E 5 8 X4 X5 16 12 CKJ2B 9 X6 X7

+ DSP2A-24V V1

RELAY TRIP 1

5 QDJE

RELAY TRIP 2

CKJ3A

DO6
UV&OV STG 1
J2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 X1 X2 X3 X4 X5 X6 X7 X8 X9 X10 X11 X12 X13 X14 X15 X16 X17 X18 X19 X20

+ DSP1A-24V V6

RELAY TRIP 1

5 CKJ4A

CKJ2E

X8 X9

RELAY TRIP 2

DO8
UV&OV STG 2

+ DSP2A-24V CKJ5A

16 5

CKJ3B 8 X10 X11

UV&OV STG 1

+ DSP1A-24V V2

16 12

CKJ4B 9 X12 X13 CKJ4E 5 8 X14 X15 CKJ5B 5 8 X16 X17 CKJ6B 5 8

UV&OV STG 2

UV&OV STG 2

CKJ6A

DO9
OVERLOAD/ NOT USED

+ DSP1A-24V V3 CKJ7A

16

UV&OV STG 2

OVERLOAD/NOT USED
X18 X19

DO10
CBF ALARM/ NOT USED

16

DSP1A1B-24V V4 QDJA CKJ7B 5 8 3 2 16 12 CKJ7E 9 1 LX1

CBF ALARM/NOT USED


X20

DO1
STARTUP

+ DSP2A-24V V5

-35-

CSC-211 Numerical Backup Protection equipment

Manual

15 Menu Frame
Tab.24 Abbr. (LCD Display) OpStatus Analog Measure DI OpConfig SetGr Time Settings Read Write Switch Delete Report Event Meaning Operating Status Analog Input Measurement analog input Status of digital inputs Settings Group Configuring time Settings operation Read settings Write settings Switch settings group Delete settings Query and manage report Query the event report Inspecting the analog input of the equipment. Inspecting the measurement analog input of the equipment. Inspecting the status of digital inputs. Switching setting group Remarks

Alarm

Query the alarm report

Wave

Query the report with wave

Operate Erase Erase event Erase Alarm Erase Wave ComConf Ether 1# Ether 2# Serial Type BaudRate Parity Label Dev Addr STA name Bay name Testing

Query the operate report Erase report Erase the event reports Erase the alarm reports Erase the reports with wave Communication Configure Ethernet port 1 Ethernet port 2 Set serial port Communication type Baud rate Parity verify Set the address Equipment address Name of station

Listing the time of the event reports which is searched by time sect, selecting the report with and key, inspecting the content with SET key. Listing the time of the alarm reports which is searched by time sect, selecting the report with and key, inspecting the content with SET key. Listing the time of the reports with wave which is searched by time sect, selecting the report with and key, inspecting the content with SET key. Listing the time of the operate reports which is searched by time sect, selecting the report with and key, inspecting the content with SET key. Erase all the event reports Erase all the alarm reports Erase all the reports with wave Set Ethernet port 1 in CPU module Set Ethernet port 2 in CPU module select COM for 61850, select RS232 for EPPC, and select RS485 for IEC103 select 9600 Hex ASCII ASCII

-36-

CSC-211 Numerical Backup Protection equipment DO DI Pilot Accuracy zero remote Event Alarm Signal Metering exper Setup Module Network DIO Set Remote Return Analog Status Parameter Setting Measure Zero Scale Save Clear Printer DevInfo version OpInfo ETH1# ETH2# MMI Remote setup Return mode Protection AI or measurement AI Real time or extend Time parameter Settings inside equipment Measurement analog timing Zero drift Adjust AI Scale Save the adjustment Clear the energy Printer setup Device information Version of software Operation information Ethernet port 1 Ethernet port 2 Man machine interface Digital input Measurement analog input Experiment status Select the network module Setup the network module Test the digital output Test the digital input Test the LED Test the accuracy of AI Test the zero drift of AI Remote test Function operation

Manual

Show the zero drift of protection AI

Include hardware alarm, VT fail and trip failure

Only for the network in CPU module If configure the DIO module. For 61850 protocal, it is OFF Only used for 2000 protocal, not for 61850 Manual return or automatic return of information. Active deliver AI of IEC 103 (measurement AI or measurement and protection AI)

Threshold of non-current Adjust zero drift of measurement AI again Adjust scale of measurement AI Save the adjustment for zero drift and scale Clear the pulse energy calculate

In CPU module In CPU module

-37-

CSC-211 Numerical Backup Protection equipment

Manual

-38-

You might also like