You are on page 1of 26

All Product Catalogue

AP-MSM-11

Products manufactured in an ISO certified facility. This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com.

2011 McQuay International

www.mcquayup.com

A Global Leader in System Solutions for Air Conditioning, Heating, Ventilating and Refrigeration.

Chilled Water System Solution


Product Overview McQuay Offers : Chilled Water System Air cooled mini chiller series Air cooled Tandem Compressor Mini Chiller Inverter Mini Chiller Chilled Water Fan coil unit Wall Mounted Ceiling Cassette Ceiling Convertible Ceiling Concealed Ducted Blower Smart Manager Controller NIM Networking Control System

2 4 6 12 13 16
Cramlington

Wuhan Kuala Lumpur Jakarta

Suzhou Shenzhen

Cecchina

Minneapolis Faribault Owatonna Auburn Stauntan

23 28

Africa

Ghana South Africa

Kenya Sudan Chile

Madagascar Tanzania Guadeloupe

Mauritius Tunisia Mexico

Morocco Uganda Paraguay

Nigeria

Mexico City

Specifications
Mini Chiller Specifications Chilled Water Fan Coil Unit Specifications

Americas

S1 S6

Argentina Uruguay

Puerto Rico

Asia

Cambodia Nepal

China Pakistan Belgium Italy Serbia Bahrain Syria

Hong Kong Philippines Croatia Lithuania Spain

Indonesia Singapore Cyprus Malta Turkey

Maldives

Myanmar

Europe
Albania Hungary Russia

Czech Republic Greece Poland Portugal United Kingdom Lebanon Oman

Middle East
Azerbaijan Qatar Fiji

Iran Jordan United Arab Emirates

Oceania

Manufacturing Plant

Mini Chiller

Model Range R-22 R-407C R-410A

Cooling Heating Capacity Capacity (kW) (kW)

Electrical Supply 50Hz 60Hz

Fan Coil Unit

Model Range

Cooling Capacity (kW)

Heating Capacity (kW)

Electrical Supply 50Hz 60Hz

MAC 020/025/ 030 C/CR

M4AC 025/030 C

M5ACV 030 CR 4.9 - 8.8 M5AC 020/ 025 CR 6.4 - 9.7

MCK 020/025/030/040/050 AWH

3.81 - 5.16

10.55 - 13.77

MAC 040/050/ 060 C/CR

M4AC 040/ 050/060/ C M4AC 060CR

MCK 010/015/020 CW M5ACV 055/ 075 CR 11.1 - 20.5 12.6 - 21.3

2.34 - 4.25

3.22 - 5.42

MCM 007/010/015 CBW MAC 080/100/ M4AC 080/100/ 120/150 C/CR 120/150 C/CR M5ACV 100/ 135/210 CR

1.90 - 3.08

2.34 - 4.25

21.6 - 58.6

26.4 - 57.7

MCM 020/025/030/040/050 DW

5.19 - 13.19

6.45 - 15.10

M5AC 030/ 040/050/ 055 CR

7.3 - 13.2

9.5 - 16.1

MCM 015/020/25 EW

4.54-6.15

5.72-8.21

Fan Coil Unit

Model Range

Cooling Capacity (kW)

Heating Capacity (kW)

Electrical Supply 50Hz 60Hz

MCC 010/015/020/025/028 CW MCC 030/038/040/050/060 CW

2.9 - 15.8

3.4 - 19.6

MWM 007/010/015/020 G2W MWM 301W

2.34 - 5.28

3.02 - 6.74 MCW 200/300/400/600 C/H MCW 800/1000/1200 C/H 2.2 - 10.7 3.5 - 19.2

MCK 020/025/030/040/050 AW

6.62 - 10.80

8.40 - 12.90

MDB 075/100/125/150 BW

22.2 - 44

16.5 - 31.2

RELIABLE AND MORE EFFICIENT


The refrigerant of the system is confined to within the chiller itself and therefore no refrigerant is circulating throughout the building. This will be no risk of refrigerant leakages in building or risk of poor oil return that will damage compressor caused by poor installation. Multiple compressors in McQuay chiller series offers stages capacity control that will offer better efficiency.

YEAR ROUND COMFORT


Can be used in variety of climates with systems that are available in two versions, cooling only and heat pump.

LONG PIPING APPLICATIONS


McQuay chilled water system avoids the limitation of piping lengths and bends that exist in Direct Expansion refrigerant system. The chiller can be installed far away from the fan coil units, thus offering flexibility and creativity in the installation.

QUALITY, INNOVATIVE AND COMPACT DESIGN MCQUAY OFFERS CHILLED WATER SYSTEM
McQuay is committed to offer you with the better solution in your air conditioning needs. In the new series of chilled water products, McQuay is not just offering you with wide range of chilled water air conditioning equipments, but a better solution from selecting the equipments, designing the water piping systems to provide easy control of the complete chilled water system. This is facilitated by the user friendly computer selection programs and remote monitoring of the operation of complete system through the Smart Manager. The series of chilled water product has incorporated the technology of advanced communicating controls, microprocessor controlled chillers with a wide range and variety of fan coil unit that offers total flexibility.
4 3 5

McQuay chiller is equipped with reliable and quality components.

MULTIPLE TEMPERATURE ZONE CONTROL


The operation of the fan coil units can be managed independently by zones according to similar air conditioning comfort needs.

Model : MAC 025/030 C/CR M4AC 020/025/030 C/CR M5AC 020/025 CR M5ACV 030 CR Capacity : Cooling : Heating : 4.9 kW - 8.8 kW 6.4 kW - 9.7 kW

Model : MAC 040/050/060 C/CR M4AC 040/050/060 C/CR M5ACV 055/075 CR Capacity : Cooling : Heating : 11.1 kW - 20.5 kW 12.6 kW to 21.3 kW

Refrigerant : R-22, R-407C, R-410A

Refrigerant : R-22, R-407C, R-410A

McQuay offering you the range of air cooled chiller that is suitable for many applications from residential to commercial.

The McQuay chiller is incorporated with the basic necessary components such as circulating water pump, expansion tank, compact brazed plate heat exchanger, differential pressure switch and the microprocessor controller and wired control panel.

In addition, the selection of the McQuay chiller could not be more easy than the user friendly yet versatile selection softwares for chiller as well as connecting piping. In short, Smart Manager Chilled Water Product Range offers you the better solution to your chilled water product needs.

Model : MAC 080/100/120/150 C/CR M4AC 080/100/120/150 C/CR M5ACV 100/135/210 CR Capacity : Cooling Heating : 21.6 kW to 58.6 kW : 26.4 kW to 57.7 kW

Model : M5AC 030/040/050/055 CR Capacity : Cooling Heating : 7.3 kW to 13.2 kW : 9.5 kW to 18.0 kW 7

Refrigerant : R-22, R-407C, R-410A 6

Refrigerant : R-410A

LONG PIPING APPLICATION :


McQuay chilled water system has no limitation in piping lengths unlike Direct Expansion refrigerant system. As long as the water pump head pressure is sufficient to pump the water through the pipe network, the chiller can be installed far away from the fan coil units. McQuay Mini Chiller had been designed to support maximum water operating pressure up to 1000kPA. With such pressure, McQuay Mini Chiller is enough to support most HVAC application. In the case where the Mini Chiller's built in pump head is insufficient to support the overall friction loss, additional pump can be installed to cater for higher pump head requirement.

FACTORY PRECHARGED REFRIGERANT


Each heat exchanger in the chiller is brazed and tested against leakages through dried air at 30 bars. After that, another process to vacuum the system before it is accurately charged with refrigerant to ensure optimum performance. Thus, it saves the hustles of field charging by installers.

SERVICEABILITY & ERROR CODE FOR EASE OF TROUBLESHOOTING


By opening the front panel, one can access and service all the components in the chiller. The chiller is equipped with self diagnosis function which allow the chiller panel to display total of 19 type of faulty occurred in the system by showing different error code on the LCD screen of the panel.

EASY INSTALLATION AND MAINTENANCE :


INTEGRATED HYDRONIC COMPONENTS
McQuay Mini Chiller is fully integrated and equipped with key hydronic components such as expansion tank, water tank, brazed plate heat exchanger and water circulating pump. As all hydronic components are assembled and tested in the factory, installation of additional component on site can be eliminated.

MODULAR INSTALLATION
McQuay Mini Chiller provides flexibility in adding capacity for building extension. This can be done by installing the mini chiller in modular connection. A network of up to 50 chillers is possible to be connected in a system. For ease of controlling and setting, McQuay Mini Chiller panel implement Master and Slave function. This function allows user to do the setting at the Master unit only and all the slave unit in the group will follow the same setting.
Supported Up To 50 Units Of Chiller
Chiller 0 Chiller 1 Chiller 2

Multistage End Suction Water Pump


Impeller and all movable parts in contact with the water are made of stainless steels.

Diaphragm Expansion Tank


Prevent damage of hydraulic components and cracking of piping due to expansion of hot water in the pipes.

Water Storage Tank Filter Drier


Remove dirt and moisture in the refrigerant circuit. Prevent the compressor from switching ON/OFF too frequently during low load conditions such as night time.
NOTE: Model M4AC/MAC080~150C/CR water tank is offered as an optional device.

Chiller Panel 0 (Master)

Chiller Panel 1 (Slave)

5 way wire (CM8) Chiller Communication Bus

EFFICIENCY AND PERFORMANCE :


ANTI-FREEZE PROTECTION
The chiller unit has several anti-freeze protection features: 1. Built-in heater in BPHE The BPHE has a strip heater around it to prevent water freezing inside. 2. Anti-Freeze sensor BPHE can avoid the frosting as the anti-freeze sensor will send the signal to cut out the compressor if the water temperature becomes too cold. 3. Water pressure differential switch This protection feature will ensure there is water flow in pipings when the chiller is in operation. Otherwise, the compressor will cut out immediately.

CHILLER CONTROL PANEL


The chiller panel controller is designed to control the chiller operation. This device allows the user to have customized control for each connected unit. Each chiller will have a chiller control panel that comes as a standard accessory. At the same time, the chiller control panel is able to be installed remotely through the cable up to a distance of 100 meters. Example, the chiller panel can be installed in a centralized plant control room for the building. The chiller control panel has been designed taking into consideration of the user friendly and yet versatile control features. Features: Whole system configuration. Unique parameter settings. Operation status display. Tracing fault record (offer quick troubleshooting solutions). The display is shown in an 8-lines graphical LCD display. There are 8 dedicated keys available in the panel. Menu selection. Navigation on the screen. Modification of the selected value.

SEQUENCING CONTROL
For MAC/M4AC 080~150 C/CR, both compressors will cut in and cut out depending on their accumulative operating time. This sequencing control feature will ensure no single compressor is overload in operation as well as to ensure longer reliability of compressors.

MICROPROCESSOR CONTROL
McQuay chillers are equipped with microprocessor controller that will control and regulate the operation of the unit. Besides, the controller that contains the well developed algorithm will provide protection to the chiller by accurately sensing the key temperatures in both the water and refrigerant circuit. Should there be any abnormal reading received by controller, an alarm signal will be sent to chiller panel, followed by protection action plans such as to stop the operation of compressor, condenser fan motor or circulating water pump.

PARTIAL LOADING
Models MAC/M4AC 080~150 C/CR has been designed with two separate refrigerant circuits, i.e. it has two compressors. By doing so, the unit has part loading capabilities, i.e. 0-50-100% of rated capacity. This will improve the reliability and energy efficiency of the unit, especially during low loading operations.

SUPERIOR RELIABILITY :
State-Of-The-Art Components
SCROLL COMPRESSOR
Scroll Compressors are used for the units to offer a quieter and more reliable performance over a wide operating temperature range. (Except MAC/M4AC 020 C/CR which uses rotary compressor). For MAC/M4AC 030, 040, 050, 060, 080, 100, 120, 150 CR, phase protector is provided to prevent the compressor from rotating in the wrong directions.
Copeland Compliant Scrolls

ANTI CORROSION GOLD ALUMINUM FIN


Gold Aluminum fin is offered as the standard material of the condenser heat exchanger of this series of chiller.

BRAZED PLATE HEAT EXCHANGER


The heat exchanger is made of AISI 316 stainless steel plates closely arranged and brazed together to maximize possible heat exchange efficiency.
AISI 316 stainless steel BPHE

SAFETY PROTECTION
The safety protections provided for the McQuay chiller are: High & Low Pressure Switches Anti-Freeze Protection Sensor Discharge Temperature Sensor Over Pressure Relief Valve Water Pressure Differential Switch Anti-Freeze Heater on BPHE Compressor Water Pump & Fan Motor Overload Protector
11

High Efficiency Motor Quiet Shutdown Device

10

TRUE DUAL CIRCUITS BPHE


Apply sophisticated technology of true dual circuit BPHE. The true dual BPHE puts the secondary circuit (water) in contact with 2 primary circuits (refrigerant). So even if one primary circuit is shut off, each secondary channel is still in contact with a primary channel. These advantages have made the product the natural choice for flexible chillers, climate control applications and high-precision systems food cooling cabinets in supermarkets.
Ref.1 Ref.2 Ref.1 Ref.2 Ref.1

Air-Cooled Mini Chiller


Model: M5AC 030/040/050/055 CR This new line of innovative air cooled chiller by McQuay was designed with one purpose in mind, which is to offer cost and energy saving for users.

water

water

water

water

Model: M5ACV 030/055/075/100/135/210 CR

Energy Saving
ELIMINATION OF WATER TANK BETTER PERFORMANCE
Usage of higher efficient R-410A rotary compressors in tandem configuration Tight tolerances between moving parts resulting in high compressor volumetric efficiency Minimize mechanical losses Minimize gas flow losses and turbulence Optimize compressor oil return Combining the Tandem Compressors technology with the algorithm of the microprocessor control, water tank can be eliminated in most instances. Choices of Single Phase and 3 Phase Power Supply Connection Usage of single phase power supply compressors and circulating water pump. Offers flexibility to field installation.

The new series of Inverter Mini Chillers are specially designed / developed to achieve better system energy saving as well as towards perfect control during part load condition.

Water In

INVERTER COMPRESSOR
Inverter compressor is programmed to run at the optimum speed, which is regulated by the input frequency as it can varies according to the heat load requirement.

Primary Circuit 1

Primary Circuit 2

CAPACITY STEP CONTROL


3 steps compressor loading (0%-40%-60%-100%) for M5AC 040 CR & M5AC 050 CR 2 steps compressor loading (0%-50%-100%) for M5AC 030 CR & M5AC 055 CR
12

SEQUENTIAL CONTROL
Both compressors will cut in cut out depending on water temperature. This is possibly improving the compressor life cycle as well as the compressor reliability.

Water Out

13

BUILT IN FAN SPEED


Fan speed is now controlled by the built in algorithm, resulting in cost saving since installation of external FSC (Fan Speed Controller) can be exempted. It is regulated at 100%, 70% and 50% based on the ambient and outdoor condensing temperature.

ANTI CORROSION GOLD ALUMINUM FIN


Gold Aluminum fin is offered as the standard material of the condenser heat exchanger of this series of chiller.

SAFETY PROTECTION
High & Low Pressure Switches Anti-Freeze Protection Sensor Discharge Temperature Sensor Over Pressure Relief Valve Water Pressure Differential Switch Anti-Freeze Heater on BPHE Compressor, Water Pump Overload Protector

CAPACITY STEP CONTROL


3 steps compressor loading (0%-40%-60%-100%) for M5AC 040 CR & M5AC 050 CR 2 steps compressor loading (0%-50%-100%) for M5AC 030 CR & M5AC 055 CR

ELIMINATION OF WATER TANK


Inverter system provide constant water temperature band, or much lesser water temperature fluctuation. With this, water tank of the mini chiller system can be eliminated.

ADVANTAGES OF INVERTER COMPRESSOR APPLICATIONS ARE:


LESS START & STOP Frequency regulated compressor resulting in lesser in the sense of start and stop of compressor, which is greatly reduce the energy consumption. FAST COOLING / HEATING Unlike the other conventional systems, inverter compressor has the ability to produce faster cooling / heating capacity at the frequency higher than the dominant capacity frequency. BETTER COMPRESSOR RELIABILITY Reliability of inverter compressor is always better since there is lesser ON/OFF of the system especially during the low load condition. LOW STARTING SURGE Inverter compressor require lower starting torque and thus, resulting in lower starting current.
Room Temperature

MODULAR INSTALLATION
A network up to 50 chillers in a system is possible. Control on the operation of the chillers will be done through the microprocessor controller. The external water piping connection can be made either from the left or right side of the unit.

Chiller Panel Comes As The Standard Controller

Precise & Stable Temperature Control

Set Temperature

Room Temperature

Time

Compatible With Smart Manager

Fast Cooling

Set Temperature

Time

Inverter System

Conventional System

14

15

MWM 07/10/15/20/25 G2W

MWM 301 W

To complement the new innovative Smart Manager range of air cooled chillers, McQuay is offering an extensive range of chilled water fan coil units that will meet most of indoor application requirements covering residential, light commercial and commercial. The aesthetically attractive decorative fan coil units such as Wall Mounted models, Ceiling Cassette and Ceiling Convertible is compact and ergonomic, the ranges can blend in easily to any interior designs whether it is residential houses, office, restaurant or shops. In addition, the McQuay chilled water fan coil units are designed with easy installation and easy servicing in mind. The fan coil units also include the microprocessor controller that has built in algorithm to control the operation of the fan coil unit as well as to provide protection to the unit.

STANDARD

GS01 Wireless Controller

SLM Wired Controller

Netware 3C Wired Controller

Optional Field Installed Accessory


16

Slim and compact Wide capacity range Wide air flow range Incorporated with NanoGuard. Able to communicate with the versatile NIM for fan coil units networking Light weight Detachable and washable air intake grille Microprocessor control Self diagnosis features Automatic air swing Wireless Control as standard Mode selection, fan speed, 24 hours real timers Optional wired controller
17

MCM 007/010/015 CBW (Ceiling Exposed Only)

STANDARD
MCM 020/025/030/040/050 DW

GS01 Wireless Controller

SLM Wired Controller

Netware 3C Wired Controller

MCM 15/20/25 EW

Optional Field Installed Accessory

MCK 010/015/020 CW

2 Pipes System: MCK 020/025/030/040/050 AW 4 Pipes System: MCK 020/025/030/040/050 AWH

STANDARD

3 range of ceiling cassette to be chosen from. - MCK-CW - 570mm (w) x 570mm (l) - MCK-AW - 820mm (w) x 820mm (I) Aesthetically attractive and slim front panel 4 way air discharge to provide better air distribution to room Automatic air swing 4 pipes system is available for model MCK020/025/030/040/050AWH Easy servicing and maintenance Built in high pressure head drain pump - Ability to pump up condensate water to 700mm high Built in water float switch to protect the unit from problems of condensate water overflow Microprocessor control Able to communicate with the versatile NIM for fan coil units networking Self diagnosis feature Wireless Control as standard - Mode selection, fan speed, 24 hours real timers Optional wired controller
Netware 3C Wired Controller

GS01 Wireless Controller

SLM Wired Controller

Optional Field Installed Accessory


18

Ceiling Convertible feature offers flexibility on installation - Installation method of under ceiling or floor standing* 2 way air discharge** ensure better air distribution - Horizontal air throw and bottom air throw Automatic Air swing** Aesthetically attractive with round profile outlook fits into to any indoor architectural Strong air flow volume and strong air throw distance makes it a perfect choice for light commercial such as restaurant and shop

Microprocessor control Able to communicate with the versatile NIM for fan coil units networking Self diagnosis feature Wireless Control as standard - Mode selection, fan speed, 24 hours real timers Optional wired controller
* Applicable for MCM30-50DW and MCM15-25EW models only. ** Applicable for MCM30-50DW models only.

19


2 Pipes System: MCW 200/300/400/600/800/1000/1200 C 4 Pipes System: MCW 200/300/400/600/800/1000/1200 CH

Wide capacity range Multiple rooms can be cooled by just 1 unit of MCW Simple design with easy serviceability feature Extremely low height of unit - 251mm for complete range Water piping connection can be easily converted from one side to the other Fan motor assembly is not cased, allowing free return or back return or bottom return with optional return plenum Availability of optional extended drain to receive the condensate water dripping from the water piping connection Availability of 4 pipes MCW series Other optional accessory available: - Wired thermostat - Choice of external static pressure (ESP) - Four types of ESP are available: 0Pa, 30Pa, 60Pa, 80Pa. - PTC (Positive Temperature Coefficient) electric heater - 2 way & 3 way valves

MCC 010/015/020/025/030/040/050/060 CW

MCC 028/038 CW

STANDARD

Wide capacity range 4 speed fan motor offers flexibility for installation to suit application - Each speed will offer different external static pressure and air flow High External Static Pressure is available up to 18mm Extra secondary drain pan to provide protection against condensate water leaking Availability of various optional duct accessories specially designed to fit to MCC-CW range Microprocessor control Filter adaptor kit of 1 inch is available as optional accessory Able to communicate with the versatile NIM for fan coil units networking Self diagnosis feature Wired Control as standard - Mode selection, fan speed selection

(MCC010CW~MCC025CW)
Return Bracket Assembly come with Adaptor
(MCC 010CW - 1 outlet; MCC 015~025CW - 2 outlets)

Adaptor
Discharge and Return

Y-Joint

Return Grille Assembly come with Adaptor

Supply Grille Assembly come with Adaptor

(Front View)
SLM Wired Controller Netware III Wired Controller

(Side View)

(Front View)

OPTIONAL
20 21

These units are design with high air flow and high external static pressure, enables adequate distribution of air to the desired space Multiple rooms can be cooled by just 1 unit of MDB Simple design with easy serviceability feature The robust unit is designed with durability and reliability in mind MDB125/150BW is using the belt driven fan motor and blower fan thus it offers flexibility for upgrading should higher air flow is required MDB150BW is designed to cater for either horizontal air discharge or vertical air discharge
MDB 075/100/125/150 BW

By adopting the McQuay chilled water system, the comfort in residential and light commercial buildings such as offices, hospital, restaurant, hotel and shopping complex can be controlled and managed from just one point, that is through the Smart Manager. The Smart Manager is acting as a center to manage the operation of both the chilled water fan coil units and the chillers. Besides allowing the user to have customized control for each connected unit, the Smart Manager is also able to manage the overall system operating mode of all units based on the air conditioning system load demand of the building.

SUPPORTED UP TO 50 CHILLERS & 120 FAN COIL UNITS


Through the versatile Smart Manager controller, the operation of each equipments in the McQuay chilled water system connected through the chiller Bus and McQuay own proprietary NIM BUS can be managed and controlled.

Fan Coil Network BUS

Chiller Network BUS

22

23

DISPLAY UP TO 46 TYPES OF CHILLER FAULT/ ALARM AND 6 TYPES OF FCU FAULT/ALARM


Whenever a fault occurred in either the chiller or fan coil unit, a signal will be sent to Smart Manager and an alarm message will appear on the LCD, showing type of alarm, alarm occurred time, date and unit. This will greatly ease the troubleshooting process and thus reduce the valuable time of service technicians. As soon as the fault is being solved, the alarm will automatically dissolve from the LCD.

(Ch 0) Alarm 1

ENERGY SAVING PROGRAMMABLE TIMER


The operation of the chiller and each fan coil unit can be preset to operate and to stop at different time schedule and at different day of a week. Taking consideration of the fact that certain rooms in a building will be empty at certain period of the day, setting timer to On and to Off the operation of units in those areas will greatly reduce the energy cost of the building. At the same time, Smart Manager allows setting up to five sets of 7 days programmable operating schedules (2 On/Off timer per day) for each fan coil unit.
Unit

Comp 1 overload
01/01/00 12.00am

MCC MCK

MCM2 MCM1 MWM


8.00 am 9.00 am 10.00 am 11.00 12.00 am am 1.00 pm 2.00 pm 3.00 pm 4.00 pm 5.00 pm 6.00 pm 7.00 pm

Time

THRESHOLD VALUE SETTING


MCC

If the priority setting is being preset to fan coil unit, the operating mode of the complete McQuay chilled water system can be synchronized to operate under one same mode. This is achievable through the unique feature called Threshold Value Setting Smart Manager can command chiller operating mode to switch from current operating mode if the threshold value is meet. Example, In a network of 10 fan coil units that is currently operating in COOL mode and a threshold of 60% was set for COOL mode and threshold of 50% was set for HEAT mode. Should 6 of the fan coil units are requesting for HEAT mode then the threshold for HEAT is crossed. Signal will be sent by Smart Manager to chiller BUS to switch the operating mode of all chillers to HEAT mode. Requirement of users will be met.

MCK MCM 2

MCM 1 MWM

PRIORITY SETTINGS
Depending on the application requirement, the Smart Manager offers the flexibility to allow user to set the priority on the operation of fan coil unit and chiller in a complete McQuay chilled water product system. If priority is set to Fan Coil Unit, the chiller will be forced to OFF if all fan coil units are OFF. If Chiller Priority is being set, all fan coil units will be OFF if chillers are OFF.
24

Heat Treshold
Chiller to operate at Heat Mode

10

Chiller to operate at Cool Mode

Cool Treshold
25

HOLIDAY SETTING
While designing the Smart Manager, the practical aspects of equipment application were always the key points to be considered. Thus resulting in the creation of Holiday Setting feature. In this feature, users are allowed to set up to 10 holiday timers with each timer can last for duration of 99 days. During the duration of Holiday Timer set earlier, all fan coil units and chiller will automatically be turned Off.
HOLIDAY SETTINGS
Holiday 1 Holiday 2 Holiday 3 Holiday 4 Holiday 5

KEY PARAMETER DISPLAY


For easy serviceability and maintenance, Smart Manager is able to display the key parameter such as defrost and compressor discharge sensor temperature, water in/out temperature, status of compressor On/Off, Cool/Heat mode water in temperature, etc. Thus, it reduces the cumbersome of requiring the service technicians to physically go to site of chiller installation to do the troubleshooting process.

ACCUMULATIVE COMPRESSOR RUN TIME


User can also check the compressor run time of chiller in Smart Manager. It will provide a guideline as well as posting a reminder for requirement of routine system service.

MULTIPLE TEMPERATURE ZONE CONTROL


The operation of the fan coil units can be managed independently by zones according to similar air conditioning comfort needs.
Set Holiday 1
Month Day Duration : 1 : 1 : Disable

REAL TIME CLOCK (RTC)


RTC will always appear at the summary pages and the user is able to set the time and date.

MEMORY BACKUP (EEPROM), ALARM MEMORY FOR CHILLER AND FCU


When there is power failure occurs during operation, Smart Manager will load the last state memory from EEPROM after power On reset. Besides, extra memory space inside the Smart Manager will allow user to view the previous alarm records even though its have been dissolved. This useful information will benefit the service technician to view the history of maintenance record done to the unit.

LOW POWER MODE (CHILLER + FCU)


Smart Manager will turn into low power mode during electricity power breakdown. It will operate based on the built in backup battery and only one timer and interrupt is active. CPU operation is Off and no display on LCD as well for energy saving purpose.

26

27

Mini Chiller Specifications


MAC020C - MAC 060C (Cooling Only, R-22)
MODEL Btu/h W W V/Ph/Hz MAC020C 20000 5860 2660 MAC025C 24200 7090 2680 220-240 / 1 / 50 R-22 CAPILLARY TUBE HEIGHT UNIT DIMENSION WIDTH DEPTH UNIT WEIGHT SOUND PRESSURE LEVEL NOMINAL WATER FLOW PIPING CONNECTION JOINT TYPE and SIZE TANK MATERIAL CAPACITY/VOLUME L / ft3 22 / 0.78 0 - 100% mm/in mm/in mm/in kg/lb dBA l/s / m3/hr 116 / 256 57 0.28 / 1.0 800 / 31.5 1160 / 45.7 460 / 18.1 123 / 271 57 0.33 / 1.2 188 / 414 58 0.42 / 1.51 188 / 414 59 0.53 / 1.9 1410 / 55.5 1160 / 45.7 460 / 18.1 190 / 417 59 0.67 / 2.4 196 / 432 59 0.74 / 2.7 MAC030C 30000 8790 3520 MAC040C 39500 11580 4508 MAC050C 48500 14210 5150 380-415 / 3 / 50 MAC060C 54000 15830 5780

NOMINAL COOLING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE REFRIGERANT TYPE CONTROL

mm/in

BSPT 25.4 / 1 CAST IRON / STAINLESS STEEL 40 / 1.41

COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)

MAC020CR - MAC060CR (Heatpump, R-22)


MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE REFRIGERANT TYPE CONTROL HEIGHT UNIT DIMENSION UNIT WEIGHT SOUND PRESSURE LEVEL NOMINAL WATER FLOW COOLING HEATING WIDTH DEPTH mm/in mm/in mm/in kg/lb dBA l/s / m3/hr l/s / m3/hr mm/in L / ft3 22 / 0.78 0 - 100% 116 / 256 57 0.28 / 1.0 0.28 / 1.0 800 / 31.5 1160 / 45.7 460 / 18.1 123 / 271 57 0.32 / 1.2 0.35 / 1.3 128 / 282 58 0.39 / 1.4 0.49 / 1.75 195 / 430 59 0.56 / 2.0 0.56 / 2.0 COOLING HEATING Btu/h W Btu/h W W W V/Ph/Hz MAC020CR 19000 5570 22000 6450 2530 2600 MAC025CR 23000 6740 27000 7910 2670 2800 220-240 / 1 / 50 R-22 CAPILLARY TUBE 1410 / 55.5 1160 / 45.7 460 / 18.1 197 / 433 59 0.61 / 2.2 0.61 / 2.2 203 / 448 61 0.74 / 2.5 0.83 / 2.7 MAC030CR 27500 8060 35000 10260 3450 3430 MAC040CR 38000 11140 43000 12602 4300 4450 MAC050CR 44000 12900 50000 14650 5250 5150 380-415 / 3 / 50 MAC060CR 50000 14650 55000 16100 5600 5350

PIPING CONNECTION JOINT TYPE and SIZE TANK MATERIAL CAPACITY/VOLUME

BSPT 25.4 / 1 CAST IRON / STAINLESS STEEL 40 / 1.41

COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)

Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 12C / 7C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35C AIR AMBIENT TEMPERATURE. b) HEATING - 40C / 45C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7C AIR AMBIENT TEMPERATURE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.

S1

Mini Chiller Specifications


MAC080C - MAC150C (Cooling Only, R-22)
MODEL Btu/h W W V/Ph/Hz MAC080C 85000 24910 9050 MAC100C 95000 27840 10800 380-415 / 3 / 50 R-22 TXV HEIGHT UNIT DIMENSION WIDTH DEPTH UNIT WEIGHT SOUND PRESSURE LEVEL NOMINAL WATER FLOW PIPING CONNECTION JOINT TYPE and SIZE TANK MATERIAL CAPACITY/VOLUME L/ ft3 mm/in mm/in mm/in kg/lb dBA l/s / m3/hr mm/in 340 / 750 63 1.22 / 4.4 1500 / 59.1 900 / 35.4 340 / 750 63 1.36 / 4.9 BSPT 460 / 1014 67 1.67 / 6.0 31.75 / 1.25 NA NA 0 - 50 - 100% 1245 / 49.0 1800 / 70.9 1150 / 45.3 540 / 1190 69 2.00 / 7.2 MAC120C 116000 34000 10950 MAC150C 138000 40450 13740

NOMINAL COOLING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE REFRIGERANT TYPE CONTROL

COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)

MAC080CR - MAC150CR (Heatpump, R-22)


MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE REFRIGERANT TYPE CONTROL HEIGHT UNIT DIMENSION UNIT WEIGHT SOUND PRESSURE LEVEL NOMINAL WATER FLOW COOLING HEATING WIDTH DEPTH mm/in mm/in mm/in kg/lb dBA l/s / m3/hr l/s / m3/hr mm/in L / ft3 340 / 750 63 1.13 / 4.05 1.13 / 4.05 1500 / 59.1 900 / 35.4 340 / 750 63 1.33 / 4.8 1.47 / 5.3 BSPT NA NA 0 - 50 - 100% 480 / 1058 67 1.67 / 6.0 1.67 / 6.0 31.75 / 1.25 COOLING HEATING Btu/h W Btu/h W W W V/Ph/Hz MAC080CR 80000 23450 95000 27840 8650 8900 MAC100CR 95000 27840 105000 30770 11200 10500 380-415 / 3 / 50 R-22 CAPILLARY TUBE 1245 / 49.0 1800 / 70.9 1150 / 45.3 560 / 1235 69 2.00 / 7.2 2.00 / 7.2 MAC120CR 113000 33120 120000 35169 11650 11880 MAC150CR 138000 40450 132000 38686 13840 14530

PIPING CONNECTION JOINT TYPE and SIZE TANK MATERIAL CAPACITY/VOLUME

COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)

Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 12C / 7C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35C AIR AMBIENT TEMPERATURE. b) HEATING - 40C / 45C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7C AIR AMBIENT TEMPERATURE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.

S2

Mini Chiller Specifications


M4AC020C - M4AC060C (Cooling Only, R-407C)
MODEL Btu/h W W V/Ph/Hz M4AC025C 23000 6740 2950 220-240 / 1 / 50 R-407C CAPILLARY TUBE HEIGHT UNIT DIMENSION WIDTH DEPTH UNIT WEIGHT SOUND PRESSURE LEVEL NOMINAL WATER FLOW PIPING CONNECTION JOINT TYPE and SIZE TANK MATERIAL CAPACITY/VOLUME L / ft3 22 / 0.78 0 - 100% mm/in mm/in mm/in kg/lb dBA l/s / m3/hr mm/in 123 / 271 57 0.31 / 1.1 800 / 31.5 1160 / 45.7 460 / 18.1 188 / 414 58 0.39 / 1.4 188 / 414 59 0.53 / 1.9 BSPT 25.4 / 1 CAST IRON / STAINLESS STEEL 40 / 1.41 1410 / 55.5 1160 / 45.7 460 / 18.1 190 / 417 59 0.72 / 2.6 196 / 432 59 0.7 / 2.5 M4AC030C 26900 7880 3770 M4AC040C 38500 11280 4700 M4AC050C 47500 13920 5450 380-415 / 3 / 50 M4AC060C 50000 14650 6050

NOMINAL COOLING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE REFRIGERANT TYPE CONTROL

COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)

M4AC060CR (Heatpump, R-407C)


MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE REFRIGERANT TYPE CONTROL HEIGHT UNIT DIMENSION UNIT WEIGHT SOUND PRESSURE LEVEL NOMINAL WATER FLOW COOLING HEATING WIDTH DEPTH mm/in mm/in mm/in kg/lb dBA l/s / m3/hr l/s / m3/hr mm/in L / ft3 COOLING HEATING Btu/h W Btu/h W W W V/Ph/Hz M4AC060CR 50000 14650 55000 16120 6300 5600 380-415 / 3 / 50 R-407C CAPILLARY TUBE 1410 / 55.5 1160 / 45.7 460 / 18.1 203 / 448 60 0.64 / 2.3 0.78 / 2.8 25.4 / 1 CAST IRON / STAINLESS STEEL 40 / 1.41 0 - 100%

PIPING CONNECTION JOINT TYPE and SIZE TANK MATERIAL CAPACITY/VOLUME

COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)

Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 12C / 7C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35C AIR AMBIENT TEMPERATURE. b) HEATING - 40C / 45C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7C AIR AMBIENT TEMPERATURE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.

S3

Mini Chiller Specifications


M4AC080C - M4AC150C (Cooling Only, R-407C)
MODEL NOMINAL COOLING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE REFRIGERANT TYPE CONTROL HEIGHT UNIT DIMENSION WIDTH DEPTH UNIT WEIGHT SOUND PRESSURE LEVEL NOMINAL WATER FLOW PIPING CONNECTION JOINT TYPE and SIZE TANK MATERIAL CAPACITY/VOLUME
L/ ft3

M4AC080C Btu/h W W V/Ph/Hz 80000 23450 9600

M4AC100C 90000 26380 11400

M4AC120C 115000 33700 11750

M4AC150C 137000 40150 14490

380-415 / 3 / 50 R-407C TXV

mm/in mm/in mm/in kg/lb dBA


l/s/ m3 /hr

1245 / 49.0 1500 / 59.1 900 / 35.4 340 / 750 63 1.14 / 4.1 340 / 750 63 1.25 / 4.5 BSPT 480 / 1058 67 1.67 / 6.0 31.75 / 1.25 NA NA 0 - 50 - 100% 1800 / 70.9 1150 / 45.3 560 / 1234 69 2.00 / 7.2

mm/in

COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)

M4AC080CR - M4AC150CR (Heatpump, R-407C)


MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE REFRIGERANT TYPE CONTROL HEIGHT UNIT DIMENSION UNIT WEIGHT SOUND PRESSURE LEVEL NOMINAL WATER FLOW COOLING HEATING WIDTH DEPTH mm/in mm/in mm/in kg/lb dBA l/s/ m3 /hr l/s/ m3 /hr mm/in L / ft3 340 / 750 63 1.03 / 3.7 1.03 / 3.7 1500 / 59.1 900 / 35.4 340 / 750 63 1.25 / 4.5 1.25 / 4.5 BSPT NA NA 0 - 50 - 100% 480 / 1058 67 1.67 / 6.0 1.79 / 6.4 31.75 / 1.25 COOLING HEATING Btu/h W Btu/h W W W V/Ph/Hz M4AC080CR 74000 21700 90000 26400 9200 9500 M4AC100CR 87500 25640 96000 28140 11300 11300 380-415 / 3 / 50 R-407C TXV 1245 / 49.0 1800 / 70.9 1150 / 45.3 560 / 1234 69 1.89 / 6.8 1.89 / 6.8 M4AC120CR 110000 32240 118000 34600 12200 12300 M4AC150CR 130000 38100 144000 42200 15500 15700

PIPING CONNECTION JOINT TYPE and SIZE TANK MATERIAL CAPACITY/VOLUME

COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)

Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 12C / 7C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35C AIR AMBIENT TEMPERATURE. b) HEATING - 40C / 45C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7C AIR AMBIENT TEMPERATURE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.

S4

Mini Chiller Specifications


M5AC020CR - A5AC055CR (Heatpump, R-410A)
MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE REFRIGERANT TYPE CONTROL HEIGHT UNIT DIMENSION UNIT WEIGHT SOUND PRESSURE LEVEL NOMINAL WATER FLOW COOLING HEATING WIDTH DEPTH mm/in mm/in mm/in kg/lb dBA l/s/ m3 /hr l/s/ m3 /hr mm/in CAST IRON / STAINLESS STEEL L / ft3 22 / 0.78 0 - 100% 0 - 50 - 100% 128 / 282 58 0.23 / 0.86 0.32 / 1.16 CAPILLARY TUBE 791 / 31.1 1160 / 45.7 460 / 18.1 128 / 282 59 0.28 / 1.00 0.35 / 1.25 790 / 31.1 1059 / 41.7 460 / 18.1 128 / 282 59 0.42 / 1.5 0.42 / 1.5 BSPT COOLING HEATING Btu/h W Btu/h W W W V/Ph/Hz M5AC020CR 15700 4610 21500 6300 2620 2590 M5AC025CR 19400 5690 25000 7300 2830 2790 M5AC030CR 24800 7270 32500 9500 3830 3630 R-410A CAPILLARY TUBE & TXV 1410 / 55.5 1059 / 41.7 460 / 18.1 195 / 430 59 0.50 / 1.8 0.50 / 1.8 25.4 / 1 NA NA 0 - 40 - 60 - 100% 0 - 50 - 100% 195 / 430 59 0.60 / 2.15 0.60 / 2.15 1410 / 55.5 1059 / 41.7 460 / 18.1 195 / 430 61 0.75 / 2.7 0.75 / 2.7 M5AC040CR 34100 10000 43000 12600 5000 4650 M5AC050CR 41600 12200 48000 14100 5310 5150 M5AC055CR 45000 13200 55000 16100 5490 5440

220-240 / 1 / 50

380-415 / 3 / 50

PIPING CONNECTION JOINT TYPE and SIZE TANK MATERIAL CAPACITY/VOLUME

COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)

M5ACV0030CR - M5ACV0135CR (Inverter Heatpump, R-410A)


MODEL NOMINAL COOLING CAPACITY NOMINAL HEATING CAPACITY NOMINAL TOTAL INPUT POWER POWER SOURCE REFRIGERANT TYPE CONTROL HEIGHT UNIT DIMENSION UNIT WEIGHT SOUND PRESSURE LEVEL NOMINAL WATER FLOW COOLING HEATING WIDTH DEPTH mm/in mm/in mm/in kg/lb dBA l/s/ m3 /hr l/s/ m3 /hr mm/in L / ft3 0 - 100% ELECTRONIC EXPANSION VALVE (EXV) 790 / 31.1 1160 / 45.6 460 / 18.1 128 / 282 58 0.3 / 1.3 0.4 / 1.5 1410 / 55.5 1160 / 45.6 460 / 18.1 195 / 430 62 1.3 / 4.8 0.8 / 2.7 1460 / 57.5 1150 / 45.3 550 / 21.7 200 / 440 65 0.9 / 3.4 1.0 / 3.7 NA NA 0 - 50 - 100% 0 - 50 - 100% 0 - 20 - 40 - 60 - 100% 1245 / 49 1500 / 59 900 / 35 405 / 893 63 1.3 / 4.8 1.4 / 5.0 COOLING HEATING Btu/h W Btu/h W W W V/Ph/Hz M5ACV030CR 27000 7910 31900 9350 5370 4370 220-240 / 1 / 50 M5ACV055CR 50000 14700 53200 15600 7350 5640 M5ACV075CR 70000 20500 75000 22000 9050 7900 R-410A EXV / CAPILLARY TUBE 1245 / 49 1800 / 70 1150 / 45 525 / 1157 67 1.8 / 6.6 2.0 / 7.1 1786 / 70 2093 / 82 1192 / 47 642 / 1415 67 2.7 / 9.6 2.9 / 10.3 BSPT 38.10 / 1.5 M5ACV0100CR 95000 27800 96600 28300 12000 11000 380-415 / 3 / 50 M5ACV0135CR 131500 38540 136800 40100 15750 15700 M5ACV0210CR 200000 58600 196900 57700 22300 20500

PIPING CONNECTION JOINT TYPE and SIZE TANK MATERIAL CAPACITY/VOLUME

BSPT 31.75 / 1.25

COMPRESSOR STAGE OF CAPACITY CONTROL (Btu/h)

Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - 12C / 7C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35C AIR AMBIENT TEMPERATURE. b) HEATING - 40C / 45C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7C AIR AMBIENT TEMPERATURE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.

S5

Chilled Water Fan Coil Unit Specifications


MCK020AW - MCK050AW (Ceiling Cassette A Series)
MODEL NOMINAL TOTAL COOLING CAPACITY MCK020AW MCK025AW MCK030AW MCK040AW MCK050AW 22500 25500 30000 33500 36500 Btu/h 6620 7500 8800 9950 10800 W 16700 18400 21800 24200 26300 Btu/h NOMINAL SENSIBLE COOLING CAPACITY 4900 5400 6400 7100 7700 W 28500 32000 37500 40500 44000 Btu/h NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) 12900 8400 9500 11000 12000 W 50HZ 511 / 1083 364 / 771 383 / 812 433 / 918 483 / 1024 l/s / CFM HIGH NOMINAL AIR FLOW 467 / 989 314 / 665 328 / 695 367 / 777 425 / 901 l/s / CFM MEDIUM 428 / 906 297 / 630 297 / 630 336 / 712 372 / 789 l/s / CFM LOW 8.19 5.02 5.68 6.65 7.53 USGPM NOMINAL WATER FLOW RATE 30.97 19.00 21.55 25.23 28.52 LITRES/M 220-240/1/50 V/Ph/Hz POWER SOURCE 253 127 151 164 192 W TOTAL INPUT POWER 40000 24000 26000 29500 35000 Btu/h NOMINAL TOTAL COOLING CAPACITY 11720 7030 7620 8640 10250 W 42000 30000 32000 36000 39000 Btu/h NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) 12310 8790 9380 10550 11430 W 60HZ 492 / 1040 350 / 740 369 / 779 416 / 879 468 / 989 l/s / CFM HIGH NOMINAL AIR FLOW 7.49 5.51 5.81 6.70 7.31 USGPM NOMINAL WATER FLOW RATE 28.33 20.83 22.00 25.33 27.67 LITRES/M 208-230/1/60 V/Ph/Hz POWER SOURCE 312 132 155 198 306 W TOTAL INPUT POWER 305 / 12.0 ( 355 / 13.9 ) HEIGHT mm/in 824 / 32.4 ( 930 / 36.6 ) WIDTH mm/in UNIT DIMENSION - ( ) WITH PANEL 824 / 32.4 ( 930 / 36.6 ) DEPTH mm/in ( 25+4 ) / ( 55.1+8.8 ) ( 36+4 ) / ( 79.3+8.8 ) ( 38+4 ) / ( 83.7+8.8 ) ( 42+4 ) / (92.5+8.8 ) ( 44+4 ) / ( 97.0+8.8 ) kg/lb UNIT WEIGHT ( UNIT + PANEL ) 53 / 52 / 50 42 / 39 / 37 45 / 42 / 40 49 / 45 / 43 51 / 48 / 46 dBA SOUND PRESSURE LEVEL ( H/M/L ) 69 / 10 25 / 3.6 31 / 4.5 42 / 6 52 / 7.6 HEAD LOSS (COOLING) kPa / psi 64 / 9.3 21 / 3.1 27 / 3.9 35 / 5.1 45 / 6.6 HEAD LOSS (HEATING) : 50C kPa / psi 3/4" BSP FEMALE UNION CONNECTION Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27C (80.6F) DB / 19C (66.2F) WB, ENTERING WATER TEMP. : 7C (44.6F), LEAVING WATER TEMP. : 12C (53.6F) b) HEATING - ENTERING AIR TEMP.: 20C (68F) DB, ENTERING WATER TEMP. : 50C (122F), LEAVING WATER TEMP. : 55C (131F), WATER FLOW RATE BASED ON COOLING CYCLE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. MICROPHONE POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE CENTRE OF THE UNIT.

MCK020AWH - MCK050AWH (4 Pipes Ceiling Cassette)


MODEL NOMINAL TOTAL COOLING CAPACITY NOMINAL SENSIBLE COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) HIGH NOMINAL AIR FLOW MEDIUM LOW Cooling 50HZ NOMINAL WATER FLOW RATE Add.Heat Exch Btu/h W Btu/h W Btu/h W l/s / CFM l/s / CFM l/s / CFM USGPM LITRES/M USGPM LITRES/M V/Ph/Hz W HEIGHT UNIT DIMENSION - ( ) WITH PANEL WIDTH DEPTH UNIT WEIGHT ( UNIT + PANEL ) SOUND PRESSURE LEVEL ( H/M/L ) HEAD LOSS (COOLING) HEAD LOSS (HEATING) : 70C CONNECTION mm/in mm/in mm/in kg/lb dBA kPa / psi kPa / psi ( 25+4 ) / ( 55.1+8.8 ) ( 36+4 ) / ( 79.3+8.8 ) 42 / 39 / 37 4 / 0.5 5 / 0.7 45 / 42 / 40 4 / 0.5 6 / 0.8 122 138 MCK020AWH 13000 3810 11600 3400 36000 10550 364 / 771 314 / 665 297/ 630 2.90 10.92 4.00 15.12 MCK025AWH 13500 3960 12000 3520 37500 10990 383 / 812 328 / 695 297 / 630 3.00 11.35 4.18 15.75 MCK030AWH 15500 4630 13900 4070 42500 12510 433 / 918 367 / 777 336 / 712 3.52 13.27 4.76 17.93 220-240/1/50 153 305 / 12.0 ( 355 / 13.9 ) 824 / 32.4 ( 930 / 36.6 ) 824 / 32.4 ( 930 / 36.6 ) ( 38+4 ) / ( 83.7+8.8 ) ( 42+4 ) / (83.6+8.8 ) 49 / 45 / 43 5 / 0.7 7/1 3/4" BSP FEMALE UNION 51 / 48 / 46 6 / 0.8 9 / 1.2 ( 44+4 ) / ( 97+8.8 ) 53 / 52 / 50 6 / 0.9 9 / 1.3 184 232 MCK040AWH 17100 5010 15000 4400 45500 13480 484 / 1024 425 / 901 372 / 789 3.80 14.37 5.10 19.32 MCK050AWH 17500 5160 15500 4540 46500 13770 511 / 1083 467 / 989 428 / 906 3.92 14.80 5.20 19.73

POWER SOURCE TOTAL INPUT POWER

Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27C (80.6F) DB / 19C (66.2F) WB, ENTERING WATER TEMP. : 7C (44.6F), LEAVING WATER TEMP. : 12C (53.6F) b) HEATING - ENTERING AIR TEMP.: 20C (68F) DB, ENTERING WATER TEMP. : 70C (158F), LEAVING WATER TEMP. : 75C (167F), WATER FLOW RATE BASED ON COOLING CYCLE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. MICROPHONE POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE CENTRE OF THE UNIT.

S6

Chilled Water Fan Coil Unit Specifications


MCK010CW - MCK020CW (Ceiling Cassette C Series)
MODEL NOMINAL TOTAL COOLING CAPACITY NOMINAL SENSIBLE COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) HIGH NOMINAL AIR FLOW MEDIUM LOW 50HZ NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER HEIGHT UNIT DIMENSION - ( ) WITH PANEL UNIT WEIGHT ( UNIT + PANEL ) SOUND PRESSURE LEVEL ( H/M/L ) HEAD LOSS (COOLING) HEAD LOSS (HEATING) : 50C CONNECTION WIDTH DEPTH Btu/h W Btu/h W Btu/h W l/s / CFM l/s / CFM l/s / CFM USGPM LITRES/M V/Ph/Hz W mm/in mm/in mm/in kg/lb dBA kPa / psi kPa / psi ( 15+3 ) / (33.1+6.6) 42 / 35 / 29 19 / 2.8 17 / 2.5 63 MCK010CW 8500 2490 6500 1910 12000 3520 179 / 380 137 / 290 109 / 230 2.03 7.67 MCK015CW 14000 4100 10000 2930 16000 4690 189 / 400 146 / 310 104 / 220 3.43 13.00 220-240/1/50 64 250 / 9.8 ( 295 / 11.6 ) 570 / 22.4 ( 640 / 25.2 ) 570 / 22.4 ( 640 / 25.2 ) ( 17+3 ) / ( 37.5+6.6 ) 45 / 38 / 30 27 / 3.9 24 / 3.5 3/4" BSP FEMALE UNION 48 / 40 / 36 29 / 4.3 27 / 4.0 79 MCK020CW 15500 4540 11500 3370 18000 5280 208 / 440 156 / 330 132 / 280 3.57 13.50

NOTE : 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27C (80.6F) DB / 19C (66.2F) WB, ENTERING WATER TEMP. : 7C (44.6F), LEAVING WATER TEMP. : 12C (53.6F) b) HEATING - ENTERING AIR TEMP.: 20C (68F) DB, ENTERING WATER TEMP. : 50C (122F), LEAVING WATER TEMP. : 55C (131F), WATER FLOW RATE BASED ON COOLING CYCLE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. MICROPHONE POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE CENTRE OF THE UNIT.

MCM007CBW - MCM015CBW (Ceiling Exposed)


MODEL NOMINAL TOTAL COOLING CAPACITY NOMINAL SENSIBLE COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) HIGH NOMINAL AIR FLOW MEDIUM LOW 50 / 60HZ NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER HEIGHT UNIT DIMENSION UNIT WEIGHT SOUND PRESSURE LEVEL ( H/M/L ) HEAD LOSS (COOLING) HEAD LOSS (HEATING) : 50C CONNECTION WIDTH DEPTH Btu/h W Btu/h W Btu/h W l/s / CFM l/s / CFM l/s / CFM USGPM LITRES/M V/Ph/Hz w mm/in mm/in mm/in kg/lb dBA kPa / psi kPa / psi 45 / 42 / 37 9 / 1.4 7.0 / 1.01 824 / 32.4 33 / 72.8 46 / 43 / 38 15 / 2.2 13 / 1.8 3/4" BSP FEMALE ADAPTOR 49.00 MCM007CBW 6500 1910 5000 1460 8000 2340 94 / 200 82 / 173 71 / 150 1.45 5.49 MCM010CBW 8500 2490 6700 1960 11000 3220 142 / 300 134 / 280 119 / 250 1.89 7.15 220-240/1/50 , 208-230/1/60 50.00 235 / 9.3 666 / 26.2 1174 / 46.2 35 / 77.2 47 / 44 / 39 5 / 0.7 4 / 0.5 81.00 MCM015CBW 10500 3080 8600 2520 14500 4250 190 / 400 156 / 330 139 / 292 2.33 8.82

NOTE : 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27C (80.6F) DB / 19C (66.2F) WB, ENTERING WATER TEMP. : 7C (44.6F), LEAVING WATER TEMP. : 12C (53.6F) b) HEATING - ENTERING AIR TEMP.: 20C (68F) DB, ENTERING WATER TEMP. : 50C (122F), LEAVING WATER TEMP. : 55C (131F), WATER FLOW RATE BASED ON COOLING CYCLE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. MCM020/025DW : POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT MICROPHONE POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE CENTRE OF THE UNIT.

S7

Chilled Water Fan Coil Unit Specifications


MCM020DW - MCM050DW (Ceiling Convertibele)
MODEL NOMINAL TOTAL COOLING CAPACITY NOMINAL SENSIBLE COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) HIGH MEDIUM NOMINAL AIR FLOW LOW NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER NOMINAL TOTAL COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) HIGH NOMINAL AIR FLOW NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER UNIT DIMENSION - ( ) WITH PANEL UNIT WEIGHT ( UNIT + PANEL ) SOUND PRESSURE LEVEL ( H/M/L ) HEAD LOSS (COOLING) HEAD LOSS (HEATING) : 50C CONNECTION HEIGHT WIDTH DEPTH Btu/h W Btu/h W Btu/h W l/s / CFM l/s / CFM l/s / CFM USGPM LITRES/M V/Ph/Hz W Btu/h W Btu/h W l/s / CFM USGPM LITRES/M V/Ph/Hz W mm/in mm/in mm/in kg/lb dBA kPa / psi kPa / psi MCM020DW 17700 5190 13700 4000 22000 6450 264 / 560 238 / 505 189 / 400 3.92 14.84 96.00 17700 5190 22000 6450 264 / 560 3.92 14.84 104.00 MCM025DW 20800 6100 15000 4400 25900 7590 297 / 630 293 / 620 262 / 555 4.62 17.49 130.00 20800 6100 25900 7590 297 / 630 4.62 17.49 163.00 214 / 8.4 1214 / 47.8 MCM030DW 24600 7210 17700 5190 28000 8210 329 / 697 324 / 687 307 / 650 5.46 20.67 220-240/1/50 132.00 24600 7210 28000 8210 329 / 697 5.46 20.67 208-230/1/60 163.00 MCM040DW 31200 9140 25600 7500 42300 12400 451 / 956 428 / 908 419 / 889 6.91 26.16 240.00 31200 9140 42300 12400 451 / 956 6.91 26.16 306.00 249 / 9.8 1714 / 67.5 MCM050DW 45000 13190 31400 9200 51500 15090 500 / 1059 483 / 1023 451 / 956 9.99 37.82 240.00 45000 13190 51500 15090 500 / 1059 9.99 37.82 306.00

50HZ

60HZ

670 / 26.4 43 / 94.8 45 / 99.2 70 / 154.3 50 / 47 / 40 54 / 53 / 50 51 / 50 / 48 54 / 53 / 52 54 / 53 / 52 46 / 6.6 56 / 8.1 49 / 7.2 24.0 / 3.5 38 / 5.5 39 / 5.7 48 / 7 43 / 6.2 22 / 3.1 32 / 4.6 3/4" BSP FEMALE ADAPTOR

NOTE : 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27C (80.6F) DB / 19C (66.2F) WB, ENTERING WATER TEMP. : 7C (44.6F), LEAVING WATER TEMP. : 12C (53.6F) b) HEATING - ENTERING AIR TEMP.: 20C (68F) DB, ENTERING WATER TEMP. : 50C (122F), LEAVING WATER TEMP. : 55C (131F), WATER FLOW RATE BASED ON COOLING CYCLE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. MICROPHONE POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE CENTRE OF THE UNIT.

MCM015EW - MCM025EW (Ceiling Convertible)


MODEL NOMINAL TOTAL COOLING CAPACITY NOMINAL SENSIBLE COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) 50HZ NOMINAL AIR FLOW HIGH MEDIUM LOW NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER HEIGHT UNIT DIMENSION - ( ) WITH PANEL WIDTH DEPTH UNIT WEIGHT ( UNIT + PANEL ) SOUND PRESSURE LEVEL ( H/M/L ) HEAD LOSS (COOLING) HEAD LOSS (HEATING) : 50C CONNECTION Btu/h W Btu/h W Btu/h W l/s / CFM l/s / CFM l/s / CFM USGPM LITRES/M V/Ph/Hz W mm/in mm/in mm/in kg/lb dBA kPa / psi kPa / psi 50 / 43 / 41 27 / 4.0 24 / 3.5 101.00 MCM015EW 15500 4540 12700 3720 19500 5720 236 / 500 213 / 450 189 / 400 3.43 12.98 MCM020EW 20300 5950 15400 4510 25000 7330 274 / 580 250 / 530 231 / 490 4.49 17.00 220-240/1/50 109.00 212 / 8.3 1090 / 42.9 630 / 24.8 27 / 59.5 53 / 51 / 49 48 / 7.0 42 / 6.1 1/2" BSP FEMALE ADAPTOR 56 / 51 / 44 57 / 8.3 50 / 7.3 113.00 MCM025EW 21000 6150 16200 4750 28000 8210 293 / 620 269 / 570 245 / 520 4.67 17.68

Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27C (80.6F) DB / 19C (66.2F) WB, ENTERING WATER TEMP. : 7C (44.6F), LEAVING WATER TEMP. : 12C (53.6F) b) HEATING - ENTERING AIR TEMP.: 20C (68F) DB, ENTERING WATER TEMP. : 50C (122F), LEAVING WATER TEMP. : 55C (131F), WATER FLOW RATE BASED ON COOLING CYCLE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. MICROPHONE POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE CENTRE OF THE UNIT.

S8

Chilled Water Fan Coil Unit Specifications


MCC010CW - MCC028CW (Ceiling Concealed)
MODEL NOMINAL TOTAL COOLING CAPACITY NOMINAL SENSIBLE COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) HIGH NOMINAL AIR FLOW MEDIUM LOW NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER NOMINAL TOTAL COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) NOMINAL AIR FLOW HIGH NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER EXTERNAL STATIC ( H/M/L ) UNIT DIMENSION - ( ) WITH PANEL UNIT WEIGHT ( UNIT + PANEL ) SOUND PRESSURE LEVEL ( H/M/L ) HEAD LOSS (COOLING) HEAD LOSS (HEATING) : 50C CONNECTION HEIGHT WIDTH DEPTH Btu/h W Btu/h W Btu/h W l/s / CFM l/s / CFM l/s / CFM USGPM LITRES/M V/Ph/Hz W Btu/h W Btu/h W l/s / CFM USGPM LITRES/M V/Ph/Hz W mmAq mm/in mm/in mm/in kg/lb dBA kPa / psi kPa / psi MCC010CW 9900 2900 7000 2050 11500 3370 142 / 300 123 / 260 104 / 220 2.20 8.33 67.60 9900 2900 11500 3370 142 / 300 2.20 8.33 78.00 5/4/3 261 / 10.3 765 / 30.1 411 / 16.2 17 / 37.5 33 / 30 / 26 11 / 1.5 9 / 1.3 MCC015CW 11600 3400 10600 3100 15000 4400 241 / 510 208 / 440 170 / 360 2.55 9.65 MCC020CW MCC025CW 22500 6590 15800 4620 29000 8500 344 / 730 340 / 720 274 / 580 4.98 18.85 165.00 22500 6590 29000 8500 382 / 810 4.98 18.85 219.00 6/4/3 261 / 10.3 1200 / 47.2 411 / 16.2 25 / 55.1 40 / 39 / 36 32 / 4.7 28 / 4 MCC028CW 24600 7210 17090 5009 30900 9056 382 / 810 363 / 770 335 / 710 5.73 21.70 170.00 18000 5280 12600 3690 23000 6740 330 / 700 321 / 680 293 / 620 4.00 15.14 220-240/1/50 97.20 141.00 11600 18000 3400 5280 15000 23000 4400 6740 330 / 700 344 / 730 2.55 4.00 9.65 15.14 208-230/1/60 114.00 165.00 5/4/2 7/6/3 261 / 10.3 261 / 10.3 905 / 35.6 1065 / 41.9 411 / 16.2 411 / 16.2 21 / 46.3 22 / 48.5 37 / 34 / 29 38 / 36 / 34 24 / 3.5 20 / 2.9 20 / 2.9 17 / 2.5 3/4" BSP FEMALE ADAPTOR

50HZ

60HZ

-NA-

8/7/6 285 / 11.3 992 / 39.0 600 / 23.7 39 / 86.0 41 / 38 / 34 24 / 3.5 22 / 3.2

MCC030CW - MCC060CW (Ceiling Concealed)


MODEL NOMINAL TOTAL COOLING CAPACITY NOMINAL SENSIBLE COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) 50HZ NOMINAL AIR FLOW HIGH MEDIUM LOW Btu/h W Btu/h W Btu/h W l/s / CFM l/s / CFM l/s / CFM USGPM LITRES/M V/Ph/Hz W Btu/h W Btu/h W l/s / CFM USGPM LITRES/M V/Ph/Hz W mmAq mm/in mm/in mm/in kg/lb dBA kPa / psi kPa / psi MCC030CW 26500 7767 18700 5481 33700 9877 392 / 830 359 / 760 335 / 710 6.18 23.38 333 26500 7767 33710 9880 392 / 830 6.18 23.38 208-230/1/60 486 17 / 13 / 9 378 / 14.8 990 / 39.0 541 / 21.3 42 / 92.6 46 / 42 / 38 15 / 2.1 12 / 1.8 MCC038CW 32200 9437 23900 7005 42600 12485 548 / 1160 487 / 1030 435 / 920 7.51 28.41 406 MCC040CW 30000 8792 21000 6155 42200 12368 458 / 970 449 / 950 406 / 860 6.99 26.47 220-240/1/50 389 30000 8792 42200 12368 458 / 970 6.99 26.47 661 18 / 13 / 9 378 / 14.9 1106 / 43.6 541 / 21.3 MCC050CW 44560 13060 31250 9159 53700 15739 652 / 1380 605 / 1280 572 / 1210 10.39 39.32 428 44560 13060 53700 15739 652 / 1380 10.39 39.32 208-230/1/60 767 16 / 14 / 11 378 / 14.9 1358 / 53.5 541 / 21.3 MCC060CW 51200 15006 35860 10510 62800 18406 723 / 1530 675 / 1430 609 / 1290 11.93 45.17 560 51200 15006 62850 18420 723 / 1530 11.93 45.17 804 16 / 14 / 10 378 / 14.9 1558 / 61.4 541 / 21.3 57 / 126 53 / 50 / 47 38.3/5.6 34.8/5.1

NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER NOMINAL TOTAL COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) 60HZ NOMINAL AIR FLOW NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER EXTERNAL STATIC ( H/M/L ) UNIT DIMENSION - ( ) WITH PANEL UNIT WEIGHT ( UNIT + PANEL ) SOUND PRESSURE LEVEL ( H/M/L ) HEAD LOSS (COOLING) HEAD LOSS (HEATING) : 50C CONNECTION HEIGHT WIDTH DEPTH HIGH

-NA-

12 / 11 / 9 315 / 12.5 1297 / 51.1 638 / 25.2 50 / 110.2 51 / 48 / 45 32.2/4.7 30/4.4

45 / 100 49 / 109 49 / 45 / 41 52 / 50 / 47 21 / 3 41 / 5.9 18 / 2.6 36 / 5.2 3/4" BSP FEMALE ADAPTOR

Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27C (80.6F) DB / 19C (66.2F) WB, ENTERING WATER TEMP. : 7C (44.6F), LEAVING WATER TEMP. : 12C (53.6F) b) HEATING - ENTERING AIR TEMP.: 20C (68F) DB, ENTERING WATER TEMP. : 50C (122F), LEAVING WATER TEMP. : 55C (131F), WATER FLOW RATE BASED ON COOLING CYCLE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. MICROPHONE POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE CENTRE OF THE UNIT. Tested with 2m length duct at the air discharge outlet and air return inlet

S9

Chilled Water Fan Coil Unit Specifications


MCW200C - MCW1200C (Ceiling Concealed)
MODEL NOMINAL TOTAL COOLING CAPACITY NOMINAL SENSIBLE COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 60C) HIGH NOMINAL AIR FLOW MEDIUM LOW HIGH MEDIUM LOW HIGH For Conversion purpose MEDIUM LOW HIGH MEDIUM LOW EXTERNAL STATIC ( H/M/L ) HEIGHT UNIT DIMENSION UNIT WEIGHT SOUND PRESSURE LEVEL ( H/M/L ) AT 60Pa NOMINAL WATER FLOW RATE HEAD LOSS (COOLING) HEAD LOSS (HEATING) : 60C CONNECTION WIDTH DEPTH Btu/h W Btu/h W Btu/h W l/s / CFM l/s / CFM l/s / CFM l/s l/s l/s CFM CFM CFM m3h m3h m3h mmAq mm/in mm/in mm/in kg/lb dBA USGPM LITRES/M kPa / psi kPa / psi 251 / 9.88 714 / 28.11 490 / 19.29 19 / 41.9 37 / 34 / 31 1.80 6.80 14.6 / 2.12 14.6 / 2.12 251 / 9.88 884 / 34.8 490 / 19.29 20 / 44.1 38 / 35 / 31 2.50 9.45 12 / 1.74 12 / 1.74 251 / 9.88 1014 / 39.92 490 / 19.29 26 / 57.3 41 / 36 / 33 3.40 12.85 21.6 / 3.13 21.6 / 3.13 MCW200C 7507 2200 5930 1738 11942 3500 109 / 230 73 / 153 53 / 112 109 73 53 230 153 112 390 260 190 MCW300C 10919 3200 8049 2359 17402 5100 148 / 312 103 / 218 67 / 142 148 103 67 312 218 142 530 370 240 MCW400C 14979 4390 11062 3242 24909 7300 212 / 447 137 / 289 95 / 200 212 137 95 447 289 200 760 490 340 MCW600C 21019 6160 15017 4401 33985 9960 290 / 612 217 / 459 139 / 294 290 217 139 612 459 294 1040 780 500 8.16 / 6.12 / 3.06 251 / 9.88 1214 / 47.8 490 / 19.29 30 / 66.1 47 / 44 / 38 4.80 18.14 38.2 / 5.54 38.2 / 5.54 251 / 9.88 1464 / 57.64 490 / 19.29 41 / 90.4 47 / 44 / 39 6.10 23.06 18.4 / 2.67 18.4 / 2.67 251 / 9.88 1564 / 61.57 490 / 19.29 44 / 97.0 49 / 46 / 40 6.90 26.08 21 / 3.05 21 / 3.05 251 / 9.88 1824 / 71.81 490 / 19.29 46 / 101.4 49 / 45 / 42 8.50 32.13 32.7 / 4.74 32.7 / 4.74 MCW800C 26649 7810 20609 6040 44631 13081 395 / 835 304 / 641 206 / 436 395 304 206 835 641 436 1420 1090 740 MCW1000C 30129 8830 21868 6409 50431 14780 451 / 953 317 / 671 231 / 489 451 317 231 953 671 489 1620 1140 830 MCW1200C 36510 10700 26488 7763 65411 19171 568 / 1200 417 / 882 284 / 600 568 417 284 1200 882 600 2040 1500 1020

3/4" BSP FEMALE ADAPTOR

MCW200H - MCW1200H (Ceiling Concealed)


MODEL NOMINAL TOTAL COOLING CAPACITY Btu/h W Btu/h W Btu/h W l/s / CFM l/s / CFM l/s / CFM mmAq HEIGHT UNIT DIMENSION WIDTH DEPTH UNIT WEIGHT SOUND PRESSURE LEVEL ( H/M/L ) AT 60Pa NOMINAL WATER FLOW RATE - 3 ROWS mm/in mm/in mm/in kg/lb dBA USGPM LITRES/M USGPM LITRES/M kPa / psi kPa / psi kPa / psi kPa / psi 251 / 9.9 714 / 28.1 490 / 19.3 20 / 44.1 37 / 34 / 31 1.80 6.80 1.10 4.16 14.6 / 2.12 14.6 / 2.12 12 / 1.74 12 / 1.74 251 / 9.9 884 / 34.8 490 / 19.3 24 / 52.9 38 / 35 / 31 2.50 9.45 1.10 4.16 12 / 1.74 12 / 1.74 13.5 / 1.96 13.5 / 1.96 251 / 9.9 1014 / 39.9 490 / 19.3 28 / 61.7 41 / 36 / 33 3.40 12.85 1.10 4.16 21.6 / 3.13 21.6 / 3.13 14.8 / 2.15 14.8 / 2.15 MCW200H 7268 2130 5742 1683 4606 1350 101 / 212 70 / 147 51 / 106 MCW300H 10578 3100 7798 2285 7780 2280 142 / 300 98 / 206 64 / 136 MCW400H 14536 4260 10735 3146 10953 3210 209 / 441 131 / 277 92 / 195 MCW600H 20405 5980 14578 4273 14638 4290 281 / 594 215 / 453 137 / 289 8.16 / 6.12 / 3.06 251 / 9.9 1214 / 47.8 490 / 19.3 32 / 70.5 47 / 44 / 38 4.80 18.14 1.10 4.16 38.2 / 5.54 38.2 / 5.54 20.7 / 3 20.7 / 3 3/4" BSP FEMALE ADAPTOR 251 / 9.9 1464 / 57.6 490 / 19.3 44 / 97 47 / 44 / 39 6.10 23.06 1.10 4.16 18.4 / 2.67 18.4 / 2.67 4 / 0.58 4 / 0.58 251 / 9.9 1564 / 61.6 490 / 19.3 47 / 103.6 49 / 46 / 40 6.90 26.08 2.20 8.32 21 / 3.05 21 / 3.05 12.8 / 1.86 12.8 / 1.86 251 / 9.9 1824 / 71.8 490 / 19.3 49 / 108 49 / 45 / 42 8.50 32.13 2.20 8.32 32.7 / 4.74 32.7 / 4.74 14.6 / 2.12 14.6 / 2.12 MCW800H 25864 7580 20002 5862 17470 5120 384 / 812 298 / 630 201 / 424 MCW1000H 29242 8570 21224 6220 23680 6940 437 / 924 309 / 653 228 / 483 MCW1200H 35418 10380 25696 7531 28969 8490 556 / 1176 409 / 865 281 / 594

NOMINAL SENSIBLE COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 60C) - 1 ROW HIGH NOMINAL AIR FLOW MEDIUM LOW EXTERNAL STATIC ( H/M/L )

NOMINAL WATER FLOW RATE - 1 ROW HEAD LOSS (COOLING) - 3 ROWS HEAD LOSS (HEATING) : 60C - 3 ROWs HEAD LOSS (COOLING) - 1 ROW HEAD LOSS (HEATING) : 60C - 1 ROW CONNECTION

Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27C (80.6F) DB / 19.5C (67.1F) WB, ENTERING WATER TEMP. : 7C (44.6F), LEAVING WATER TEMP. : 12C (53.6F) b) HEATING - ENTERING AIR TEMP.: 21C (69.8F) DB, ENTERING WATER TEMP. : 60C (140F), LEAVING WATER TEMP. : 55C (131F) 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW THE FACIA.

S10

Chilled Water Fan Coil Unit Specifications


MWM007G2W - MWM025G2W (Wall Mount)
MODEL NOMINAL TOTAL COOLING CAPACITY NOMINAL SENSIBLE COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) 50HZ NOMINAL AIR FLOW HIGH MEDIUM LOW Btu/h W Btu/h W Btu/h W l/s / CFM l/s / CFM l/s / CFM USGPM LITRES/M V/Ph/Hz W Btu/h W Btu/h W l/s / CFM USGPM LITRES/M V/Ph/Hz W mm/in mm/in mm/in kg/lb dBA kPa / psi kPa / psi MWM007G2W 8000 2340 5900 1730 10300 3020 130 / 275 106 / 225 83 / 175 1.76 6.66 24.00 MWM010G2W 9500 2780 6900 2030 12800 3750 142 / 300 118 / 250 94 / 200 2.11 7.99 25.00 9500 2780 12800 3750 142 / 300 2.11 7.99 28.60 260 / 10.2 799 / 31.5 198 / 7.8 8.5 / 18.8 38 / 33 / 28 48 / 7 42 / 6.1 260 / 10.2 899 / 35.4 198 / 7.8 9.4 / 20.8 39 / 34 / 28 65 / 9.4 59 / 8.5 42 / 36 / 29 77 / 11.1 MWM015G2W 11000 MWM020G2W 15500 MWM025G2W 18000 5280 14800 4330 23000 6740 312 / 660 274 / 580 222 / 470 4.00 15.14 69.00 18000 5280 23000 6740 312 / 660 4.00 15.14 65.80 304 / 12.0 1062 / 41.8 222 / 8.7 15 / 33.1 49 / 44 / 42 50 / 48 / 45 50 / 7.3 69 / 10 71 / 10.2 291 / 11.4 815 / 32.1 181 / 7.1 17.6 / 38.8 49 / 47 / 45 52 / 7.6 19 / 2.7 MWM301W 22000 6450 16720 4900 23000 6740 316 / 670 297 / 630 236 / 500 4.90 18.50 74.00

NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER NOMINAL TOTAL COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) 60HZ NOMINAL AIR FLOW HIGH

3220 4540 8000 12500 2350 3650 14000 20500 4100 6010 163 / 345 297 / 630 130 / 275 231 / 490 104 / 220 208 / 440 2.42 3.43 9.16 12.98 220-240/1/50 29.00 66.00 11000 15500 3220 4540 14000 20500 4100 6010 163 / 345 297 / 630 2.42 3.43 9.16 12.98 208-230/1/60 28.60 63.00

-NA-

-NA-

NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER HEIGHT UNIT DIMENSION - ( ) WITH PANEL WIDTH DEPTH UNIT WEIGHT ( UNIT + PANEL ) SOUND PRESSURE LEVEL ( H/M/L ) HEAD LOSS (COOLING) HEAD LOSS (HEATING) : 50C CONNECTION

64 / 9.2 51 / 7.3 1/2" BSP FEMALE ADAPTOR

Notes: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE. 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW : a) COOLING - ENTERING AIR TEMP. : 27C (80.6F) DB / 19C (66.2F) WB, ENTERING WATER TEMP. : 7C (44.6F), LEAVING WATER TEMP. : 12C (53.6F) b) HEATING - ENTERING AIR TEMP.: 20C (68F) DB, ENTERING WATER TEMP. : 50C (122F), LEAVING WATER TEMP. : 55C (131F), WATER FLOW RATE BASED ON COOLING CYCLE. 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 0.8m BELOW THE VERTICAL CENTRE LINE OF THE UNIT.

MDB075BW - MDB0150BW (Ducted Blower)


MODEL NOMINAL TOTAL COOLING CAPACITY NOMINAL SENSIBLE COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) NOMINAL AIR FLOW NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER NOMINAL TOTAL COOLING CAPACITY NOMINAL TOTAL HEATING CAPACITY (ENTERING WATER TEMP. = 50C) 60HZ NOMINAL AIR FLOW NOMINAL WATER FLOW RATE POWER SOURCE TOTAL INPUT POWER EXTERNAL STATIC ( H/M/L ) HEIGHT UNIT DIMENSION - ( ) WITH PANEL WIDTH DEPTH UNIT WEIGHT ( UNIT + PANEL ) SOUND PRESSURE LEVEL ( H/M/L ) HEAD LOSS (COOLING) HEAD LOSS (HEATING) : 50C CONNECTION Btu/h W Btu/h W Btu/h W l/s / CFM USGPM LITRES/M V/Ph/Hz W Btu/h W Btu/h W l/s / CFM USGPM LITRES/M V/Ph/Hz W mmAq mm/in mm/in mm/in kg/lb dBA kPa / psi kPa / psi 572 / 22.5 1502 / 59.1 761 / 30.0 96 / 211.6 56 35 / 5 33 / 4.8 810.00 75600 22160 78000 22860 1180 / 2500 16.78 63.52 208-230/1/60 1098.00 10.2 572 / 22.5 1502 / 59.1 761 / 30.0 100 / 220.5 57 42 / 6.1 27 / 4 1 1/8" BRAZING 1396.00 1063.00 15.2 885 / 34.8 1640 / 64.6 1040 / 40.9 140 / 308.6 58 49 / 7.1 32 / 4.6 MDB075BW 75600 22160 53700 15730 78000 22860 1180 / 2500 16.78 63.52 220-240/1/50 1840.00 95000 27840 97500 28580 1510 / 3200 21.09 79.83 1550.00 122500 36640 138000 40450 1982 / 4200 27.74 105.01 208-230/3/60 1575.00 15.2 885 / 34.8 1640 / 64.6 1040 / 40.9 145 / 319.7 58 53 / 7.7 63 / 9.1 MDB0100BW 95000 27840 69400 20330 97500 28580 1510 / 3200 21.09 79.83 MDB0125BW 125000 36640 90000 26380 138000 40450 1982 / 4200 27.74 105.01 380-415/3/50 1620.00 150000 43960 170000 49820 2171 / 4600 33.29 126.02 MDB0150BW 150000 43960 106500 31210 170000 49820 2171 / 4600 33.29 126.02

50HZ

NOTES: 1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE 2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253. 3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW a) COOLING - ENTERING AIR TEMP. : 27C (80.6F) DB / 19C (66.2F) WB, ENTERING WATER TEMP. : 7C (44.6F), LEAVING WATER TEMP. : 12C (53.6F) b) HEATING - ENTERING AIR TEMP.: 20C (68F) DB, ENTERING WATER TEMP. : 50C (122F), LEAVING WATER TEMP. : 55C (131F), WATER FLOW RATE BASED ON COOLING CYCLE 4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS C 9612 STANDARD Microphone position: 1.4m below the centre of the unit Tested with 2m length duct at the air discharge outlet and air return inlet

S11