You are on page 1of 63

Emax power breakers

Po

16
we Em
r b ax
re
ak
e

rs

ABBs Emax series of low voltage power


circuit breakers embodies over half a
centurys experience and technological
development in power circuit breakers.
The Emax offers a series of breakers that is
totally innovative in its technological design,
ease of installation and use, making it the
ideal solution for the growing requirements
of designers, switchboard and switchgear
manufacturers, installers, OEMs and users.
The Emax power circuit breakers are UL
Listed and meet the ANSI Standard for low
voltage power circuit breakers.

ABB Emax power circuit breakers are


available in five different models (four sizes)
with rated continuous current from 800A to
5000A and rated short-circuit current range
from 42kA to 125kA (480V).
Technical catalog 1SDC200003 D0201 is
available upon request.

16

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16

rs
ax ake
m
e
E br
er
ow

General information
UL general ratings and specifications

E1

Circuit breaker type

E1

Performance level
Rated continuous current, UL1066
File # E194191

Rated short circuit current

240VAC
480VAC
600VAC

Rated short time current

E2

E3

E2

E3

B-A

B-A

N-A

N-A

S-A

H-A

V-A

A
A
A
A

800
1200

1600

1200
1600

2000
2500

1200
1600
2000
2500

1200
1600
2000
2500

1200
1600
2000
2500

kA
kA
kA

42
42
35

42
42
42

65
50
50

65
50
50

85
65
65

85
85
65

100
100
85

kA

35

42

50

50

65

65

65

80
70
30

80
70
30

80
70
30

80
70
30

80
70
30

80
70
30

80
70
30

Trip units
PR111/P-A
PR112/P-A
Operation times
Make time (max)
Break time (I<ST current)(max)
Break time (I>ST current)(max)

ms
ms
ms

Overall dimensions, 3 pole


Fixed:

Drawout:

H=418mm / 16.46in
D=302mm / 11.89in
W (3 poles)

mm/in

296/11.65

296/11.65

404/15.91

H=461mm / 18.15in
D=396.5mm / 15.61in
W (3 poles)

mm/in

324/12.76

324/12.76

432/17.01

Weights (CB with releases, RH terminals and CTs, accessories excluded)


Fixed 3 pole
Drawout 3 pole

Kg/lbs
Kg/lbs

42/93
65/143

46/101
72/159

68/150
100/220

H=418mm / 16.46in
D=302mm / 11.89in
W (4 poles)

mm/in

386/15.20

386/15.20

530/20.87

H=461mm / 18.15in
D=396.5mm / 15.61in
W (4 poles)

mm/in

414/16.30

414/16.30

558/21.97

55/121
89/196

80/176
125/275

Overall dimensions, 4 pole

16

Fixed:

Drawout:

Weights (CB with releases, RH terminals and CTs, accessories excluded)


Fixed 4 pole
Drawout 4 pole

Kg/lbs
Kg/lbs

50/110
80/176

Specifications common to the entire range


Rated max voltage
Rated voltage
Test voltage (1min 50/60Hz)
Frequency
Service temperature
Storage temperature
Number of poles
Versions

635VAC
600VAC
2.2kV
50-60Hz
-5... +70C
-40... +70C
3/4
Fixed/Drawout

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Po

16
we Em
r b ax
re
ak
e

General information
UL general ratings and specifications

rs

E4

Circuit breaker type

E4

Performance level
Rated continuous current, UL 1066
File # E194191

Rated short circuit current

240VAC
480VAC
600VAC

Rated short time current

E6

E6

S-A

H-A

V-A

H-A

V-A

A
A
A
A

3200
3600

3200
3600

3200
3600

4000
5000

4000
5000

kA
kA
kA

85
65
65

100
85
85

100
100
85

125
85
85

125
125
85

kA

65

85

85

100

100

80
70
30

80
70
30

80
70
30

80
70
30

80
70
30

Trip units
PR111/P-A
PR112/P-A
Operation times
Make time (max)
Break time (I<ST current)(max)
Break time (I>ST current)(max)

ms
ms
ms

Overall dimensions, 3 pole


Fixed:

Drawout:

H=418mm / 16.46in
D=302mm / 11.89in
W (3 poles)

mm/in

566/22.28

782/30.79

H=461mm / 18.15in
D=396.5 / 15.61in
W (3 poles)

mm/in

594/23.39

810/31.89

Kg/lbs
Kg/lbs

95/209
147/324

140/309
210/463

H=418mm / 16.46in
D=302mm / 11.89in
W (4 poles)

mm/in

656/25.83

908/35.75

H=461mm / 18.15in
D=396.5 / 15.61in
W (4 poles)

mm/in

684/26.93

936/36.85

115/253
190/418

170/374
260/573

Weights (CB with releases, RH terminals and CTs, accessories excluded)


Fixed 3 poles
Drawout 3 poles
Overall dimensions, 4 pole
Fixed:

Drawout:

16

Weights (CB with releases, RH terminals and CTs, accessories excluded)


Fixed 4 pole
Drawout 4 pole

Kg/lbs
Kg/lbs

Specifications common to the entire range


Rated max voltage
Rated voltage
Test voltage (1min 50/60Hz)
Frequency
Number of poles
Versions

635VAC
600VAC
2.2kV
50-60Hz
3/4
Fixed/Drawout

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16

rs
ax ake
m
e
E br
er
ow

General information
Catalog number information
Emax breaker, UL

E 1 S

16

X X X X X X X X X X
Accessories: X = none
A = mechanical counter
B = button guard
Accessories: X = none
A = mechanical trip indicator
B = mechanical trip indicator
& bell alarm
C = padlock provision (open)
D = keylock (open)
E = position lock
F = access pos. lock
Undervoltage trip: 0 =
50/60Hz & VDC:
A =
C =
E =
G =
J =
Second shunt trip: L =
N =
Q =
S =
U =

F = A&B
G
H
J
K
L
M
N
P

=
=
=
=
=
=
=
=

none
24VDC
48V
110 120V
220 240V
380 400VAC
24VDC
48V
110 120V
220 240V
380 400VAC

A&C
A&D
A&E
A&F
A, C & E
A, C & F
B&C
B&D

Q =
R =
S =
T =
U =
V =
W=
Y =

B&E
B&F
B, C & E
B, C & F
C&E
C&F
D&E
D&F

B = 30V
D = 60V
F = 125 127V
H = 250V
K = 440 480VAC
M = 30V
P = 60V
R = 125 127V
T = 250V
V = 440 480VAC

Shunt trip: 0 = none


50/60Hz & VDC: A = 24VDC, B = 30V, C = 48V, D = 60V,
E = 110 120V, F = 125 127V, G = 220 240V, H = 250V,
J = 380 400VAC, K = 440 480VAC
Spring charging motor: (includes spring charged signal, P/N does not show)
0 = none, A = 24 30VAC/VDC, B = 48 60VAC/VDC, C = 110-130VAC/VDC,
D = 220 250VAC/VDC, E = spring charged signal only
Contacts:
A = 4 aux
E = UV energ.NC
J=B&E

B = 10 aux
F=A&D
K=C&D

C = 15 aux
G=A&E
L=C&E

D = UV energ. N.O.
H=B&D

Closing coil: 0 = none


50/60Hz & VDC: A = 24VDC, B = 30, C = 48, D = 60, E = 110 120, F = 125 127, G = 220
240, H = 250, J = 380 400VAC, K = 440 480VAC
Terminal types: (1st letter is upper terminal, 2nd letter is lower terminal)
H = rear horz 2., V = rear vert. 1
H = HH, V = VV
A = HV, B = VH

16

Trip unit: A = PR111/P, LI


D = non-automatic
G = PR112/PD, LSI
P = PR113/PD

B = PR111/P, LSI
E = PR112/P, LSI
H = PR112/PD, LSIG

C = PR111/P, LSIG
F = PR112/P, LSIG
N = PR113/P

Version: B = fixed breaker, UL; D = withdrawable breaker, UL, less cradle

Max. ampere rating: 02 = 250, 04 = 400, 08 = 800, 10 = 1000, 12 = 1200, 16 = 1600, 20 = 2000, 25 = 2500, 32 = 3200,
36 = 3600, 40 = 4000, 50 = 5000
Breaking capacity: B = basic, N = normal, S = standard, H = high, V = very high

Frame size: 1 = 1, 3P; 2 = 2, 3P; 3 = 3, 3P; 4 = 4, 3P; 6 = 6, 3P; A = 1, 4P; B = 2, 4P, C = 3, 4P; D = 4, 4P; F = 6, 4P

1 Will be shipped separately.


2 For withdrawable breakers, use "H".
3 Not available with PR112 trip units. External 15A auxiliary kit can be used.

16.4

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Po

16
we Em
r b ax
re
ak
e

General information
Catalog number information
Emax, cradle (fixed part) UL
E 1 X

12

rs

X X X

Accessories: X = none
A = Shutter padlock

Contacts: 0 = none,
A = 5 position auxiliaries
B = 10 position auxiliaries

Terminal types:

(1st letter is upper terminal, 2nd letter is lower terminal)


H = rear horz., V = rear vert.
H = HH, V = VV
A = HV, B = VH

Max. ampere rating: UL: 12 = 1200 (E1); 16 = 1600 (E2); 20 = 2000 (E3); 25 = 2500 (E3); 36 = 3600 (E4); 50 = 5000 (E6)

Version: K = cradle, UL
V = cradle for E3V

Frame size: 1 = 1, 3P; 2 = 2, 3P; 3 = 3, 3P; 4 = 4, 3P; 6 = 6, 3P;


A = 1, 4P; B = 2, 4P; C = 3, 4P; D = 4, 4P; F = 6, 4P

16
General information
Standard features
Fixed breaker
Manual operated

T.U. PR111/P, LI
Aux. SW., 4
Spring charged indicator
Flange
Accessory support
Terminal block
Lifting plate

Drawout breaker
Electrically operated

T.U PR111/P, LI
Motor operator
Closing coil
Shunt trip
Aux. SW., 4
Spring charged indicator
Flange
Accessory support
Terminal block
Lifting plate

Manual operated

Electrically operated

T.U. PR111/P, LI
Aux. SW., 4
Spring charged indicator
Flange
Crank
Accessory support
Sliding contacts
Anti-insertion lock
Lifting plate

T.U. PR111/P, LI
Motor operator
Closing coil
Shunt trip
Aux. SW., 4
Spring charged indicator
Flange
Crank
Accessory support
Sliding contacts
Anti-insertion lock
Lifting plate

NOTE: Switches provided standard without 4 auxiliary contacts.

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16

rs
ax ake
m
e
E br
er
ow

Fixed breakers, 3 pole


UL

Fixed breakers
Circuit
breaker
type

Frame
amps

Interrupting
ratings
kA, 480V

Manually
operated

Electrically
operated

Set of three
vertical terminals

E1B-A08

800

42

$ 6815

$ 9176

$ 644

E1B-A12
E2N-A12
E3S-A12
E3H-A12
E3V-A12

1200
1200
1200
1200
1200

42
50
65
85
100

7321
7819
8780
9048
9953

9682
10,180
11,141
11,409
12,314

644
690
790
790
790

E2B-A16
E2N-A16
E3S-A16
E3H-A16
E3V-A16

1600
1600
1600
1600
1600

42
50
65
85
100

7871
9082
9797
10,352
11,387

10,232
11,443
12,158
12,713
13,748

690
690
790
790
790

E3N-A20
E3S-A20
E3H-A20
E3V-A20

2000
2000
2000
2000

50
65
85
100

10,032
11,053
13,602
14,962

12,393
13,414
15,963
17,323

790
790
790
790

E3N-A25
E3S-A25
E3H-A25
E3V-A25

2500
2500
2500
2500

50
65
85
100

14,778
16,451
17,708
19,479

17,139
18,812
20,069
21,840

790
790
790
790

E4S-A32
E4H-A32
E4V-A32

3200
3200
3200

65
85
100

21,102
21,566
24,047

23,463
23,927
26,408

1664
1664
1664

E4S-A36
E4H-A36
E4V-A36

3600
3600
3600

65
85
100

23,939
27,302
28,666

26,300
29,663
31,027

1664
1664
1664

E6H-A40
E6V-A40

4000
4000

85
125

31,528
43,932

33,889
46,293

2783
2783

E6H-A50
E6V-A50

5000
5000

85
125

43,221
51,684

45,582
54,045

2783
2783

Standard features manually operated UL breaker

Rear horizontal terminals


PR111 trip unit with LI protection functions
Manual mechanical close and open pushbuttons
CB open/closed mechanical indicator
Spring charged/discharged mechanical indicator
2NO & 2NC auxiliary contacts for open/closed position indication
Lifting plates
Current transformers
Terminal box

16

16.6

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Po

16
we Em
r b ax
re
ak
e

Fixed breakers, 4 pole


UL

rs

Fixed breakers
Circuit
breaker
type

Frame
amps

Interrupting
ratings
kA, 480V

Manually
operated

Electrically
operated

Set of four
vertical terminals

E1B-A08

800

42

$ 9200

$ 11,561

$ 837

E1B-A12
E2N-A12
E3S-A12
E3H-A12
E3V-A12

1200
1200
1200
1200
1200

42
50
65
85
100

9883
10,556
11,853
12,215
13,436

12,244
12,917
14,214
14,576
15,797

837
897
1027
1027
1027

E2B-A16
E2N-A16
E3S-A16
E3H-A16
E3V-A16

1600
1600
1600
1600
1600

42
50
65
85
100

10,626
12,261
13,226
13,975
15,373

12,987
14,622
15,587
16,336
17,734

897
897
1027
1027
1027

E3N-A20
E3S-A20
E3H-A20
E3V-A20

2000
2000
2000
2000

50
65
85
100

13,543
14,922
18,363
20,199

15,904
17,283
20,724
22,560

1027
1027
1027
1027

E3N-A25
E3S-A25
E3H-A25
E3V-A25

2500
2500
2500
2500

50
65
85
100

19,950
22,209
23,906
26,296

22,311
24,570
26,267
28,657

1027
1027
1027
1027

E4S-A32
E4H-A32
E4V-A32

3200
3200
3200

65
85
100

28,488
29,114
32,463

30,849
31,475
34,824

2163
2163
2163

E4S-A36
E4H-A36
E4V-A36

3600
3600
3600

65
85
100

32,318
36,858
38,699

34,679
39,219
41,060

2163
2163
2163

E6H-A40
E6V-A40

4000
4000

85
125

42,563
59,308

44,924
61,669

3618
3618

E6H-A50
E6V-A50

5000
5000

85
125

58,348
69,773

60,709
72,134

3618
3618

Standard features manually operated UL breaker

Neutral pole rating

E1 E3 = 100% rating
E4 E6 = 50% rating

Rear horizontal terminals


PR111 trip unit with LI protection functions
Manual mechanical close and open pushbuttons
CB open/closed mechanical indicator
Spring charged/discharged mechanical indicator
2NO & 2NC auxiliary contacts for open/closed position indication
Lifting plates
Current transformers
Terminal box

16

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.7

16

rs
ax ake
m
e
E br
er
ow

Withdrawable breakers, 3 pole


UL

Withdrawable breakers
Circuit

Interrupting

breaker
type

16

Frame
amps

ratings
kA, 480V

Moving part only

Fixed part only

Manually
operated

Electrically
operated

RH
terminals

E1B-A08

800

42

$ 7383

$ 9744

$ 2281

$ 644

E1B-A12
E2N-A12
E3S-A12
E3H-A12
E3V-A12

1200
1200
1200
1200
1200

42
50
65
85
100

8375
8814
9220
9633
10,596

10,736
11,175
11,581
11,994
12,957

2281
2400
2925
2925
2925

644
690
790
790
790

E2B-A16
E2N-A16
E3S-A16
E3H-A16
E3V-A16

1600
1600
1600
1600
1600

42
50
65
85
100

9320
10,483
10,931
11,445
12,590

11,681
12,844
13,292
13,806
14,951

2400
2400
2925
2925
2925

690
690
790
790
790

E3N-A20
E3S-A20
E3H-A20
E3V-A20

2000
2000
2000
2000

50
65
85
100

11,386
12,700
14,262
15,688

13,747
15,061
16,623
18,049

2925
2925
2925
2925

790
790
790
790

E3N-A25
E3S-A25
E3H-A25
E3V-A25

2500
2500
2500
2500

50
65
85
100

17,767
20,315
22,622
24,884

20,128
22,676
24,983
27,245

2925
2925
2925
2925

790
790
790
790

E4S-A32
E4H-A32
E4V-A32

3200
3200
3200

65
85
100

23,800
24,447
25,863

26,161
26,808
28,224

6259
6259
6259

1664
1664
1664

E4S-A36
E4H-A36
E4V-A36

3600
3600
3600

65
85
100

26,863
30,865
31,948

29,224
33,226
34,309

6259
6259
6259

1664
1664
1664

E6H-A40
E6V-A40

4000
4000

85
125

34,676
46,570

37,037
48,931

7398
7398

2783
2783

E6H-A50
E6V-A50

5000
5000

85
125

46,402
57,078

48,763
59,439

7398
7398

2783
2783

Standard features electrically operated breaker


Moving part

Standard features electrically operated breaker


Fixed part

PR111 trip unit with LI protection feature


Spring charging motor
Shunt trip
Closing coil
Manual mechanical close and open pushbuttons
CB open/closed mechanical indicator
Spring charged/discharged mechanical indicator
2NO & 2NC auxiliary contacts for open-closed position indication
Lifting plates
Current transformers
Racking device with closed door
Circuit breaker racking position indicator
Sliding contacts
Fail safe device (not available with YU)

16.8

Set of three
vertical terminals

Safety shutters
Rear horizontal terminals
Sliding contacts
Anti-insertion lock
Ground connection

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Po

16
we Em
r b ax
re
ak
e

Withdrawable breakers, 4 pole


UL

rs

Withdrawable breakers
Circuit
breaker
type

Interrupting
Frame
amps

ratings
kA, 480V

Moving part only

Fixed part only

Manually
operated

Electrically
operated

RH
terminals

Set of four
vertical terminals

E1B-A08

800

42

$ 9967

$ 12,328

$ 3079

$ 837

E1B-A12
E2N-A12
E3S-A12
E3H-A12
E3V-A12

1200
1200
1200
1200
1200

42
50
65
85
100

11,306
11,899
12,447
13,005
14,305

13,667
14,260
14,808
15,366
16,666

3079
3240
3949
3949
3949

837
897
1027
1027
1027

E2B-A16
E2N-A16
E3S-A16
E3H-A16
E3V-A16

1600
1600
1600
1600
1600

42
50
65
85
100

12,582
14,152
14,757
15,451
16,996

14,943
16,513
17,118
17,812
19,357

3240
3240
3949
3949
3949

897
897
1027
1027
1027

E3N-A20
E3S-A20
E3H-A20
E3V-A20

2000
2000
2000
2000

50
65
85
100

15,371
17,145
19,254
21,179

17,732
19,506
21,615
23,540

3949
3949
3949
3949

1027
1027
1027
1027

E3N-A25
E3S-A25
E3H-A25
E3V-A25

2500
2500
2500
2500

50
65
85
100

23,985
27,425
30,540
33,594

26,346
29,786
32,901
35,955

3949
3949
3949
3949

1027
1027
1027
1027

E4S-A32
E4H-A32
E4V-A32

3200
3200
3200

65
85
100

32,130
33,003
34,915

34,491
35,364
37,276

8450
8450
8450

2163
2163
2163

E4S-A36
E4H-A36
E4V-A36

3600
3600
3600

65
85
100

36,265
41,668
43,130

38,626
44,029
45,491

8450
8450
8450

2163
2163
2163

E6H-A40
E6V-A40

4000
4000

85
125

46,813
62,870

49,174
65,231

9987
9987

3618
3618

E6H-A50
E6V-A50

5000
5000

85
125

62,643
77,055

65,004
79,416

9987
9987

3618
3618

Standard features electrically operated breaker


Moving part

Standard features electrically operated breaker


Fixed part

PR111 trip unit with LI protection feature


Spring charging motor
Shunt trip
Closing coil
Manual mechanical close and open pushbuttons
CB open/closed mechanical indicator
Spring charged/discharged mechanical indicator
2NO & 2NC auxiliary contacts for open-closed position indication
Lifting plates
Current transformers
Racking device with closed door
Circuit breaker racking position indicator
Sliding contacts
Fail safe device (not available with YU)

Safety shutters
Rear horizontal terminals
Sliding contacts
Anti-insertion lock
Ground connection

Neutral pole rating


E1 E3 = 100% rating
E4 E6 = 50% rating

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16

16.9

16

rs
ax ake
m
e
E br
er
ow

Non-automatic air circuit breakers


Fixed switches (without trip unit & c.t.s.), 3 pole
UL

Fixed switches
Circuit
breaker
type

Frame
amps

Interrupting
ratings
kA, 480V

Manually
operated

Electrically
operated

Set of three
vertical terminals

E1B-A/MS08

800

42

$ 5086

$ 7447

$ 644

E1B-A/MS12
E2N-A/MS12
E3S-A/MS12

1200
1200
1200

42
50
65

5592
6090
6944

7953
8451
9305

644
690
790

E2B-A/MS16
E2N-A/MS16
E3S-A/MS16

1600
1600
1600

42
50
65

6142
7353
7961

8503
9714
10,322

690
690
790

E3N-A/MS20
E3S-A/MS20

2000
2000

50
65

8196
9217

10,557
11,578

790
790

E3N-A/MS25
E3S-A/MS25

2500
2500

50
65

12,942
14,615

15,303
16,976

790
790

E4S-A/MS32
E4H-A/MS32

3200
3200

65
85

18,733
19,197

21,094
21,558

1664
1664

E4S-A/MS36
E4H-A/MS36

3600
3600

65
85

21,570
24,933

23,931
27,294

1664
1664

E6H-A/MS40

4000

85

28,946

31,307

2783

E6H-A/MS50

5000

85

40,639

43,000

2783

Standard features manually operated UL switch

Rear horizontal terminals


Manual mechanical close and open pushbuttons
CB open/closed mechanical indicator
Spring charged/discharged mechanical indicator
Lifting plates
Terminal box

16

16.10

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Non-automatic air circuit breakers


Fixed switches (without trip unit & c.t.s.), 4 pole
UL

Po

16
we Em
r b ax
re
ak
e

rs

Fixed switches
Circuit
breaker
type

Frame
amps

Interrupting
ratings
kA, 480V

Manually
operated

Electrically
operated

Set of four
vertical terminals

E1B-A/MS08

800

42

$ 6866

$ 9227

$ 644

E1B-A/MS12
E2N-A/MS12
E3S-A/MS12

1200
1200
1200

42
50
65

7549
8222
9374

9910
10,583
11,735

644
690
790

E2B-A/MS16
E2N-A/MS16
E3S-A/MS16

1600
1600
1600

42
50
65

8292
9927
10,747

10,653
12,288
13,108

690
690
790

E3N-A/MS20
E3S-A/MS20

2000
2000

50
65

11,065
12,443

13,426
14,804

790
790

E3N-A/MS25
E3S-A/MS25

2500
2500

50
65

17,472
19,730

19,833
22,091

790
790

E4S-A/MS32
E4H-A/MS32

3200
3200

65
85

25,290
25,916

27,651
28,277

1664
1664

E4S-A/MS36
E4H-A/MS36

3600
3600

65
85

29,120
33,660

31,481
36,021

1664
1664

E6H-A/MS40

4000

85

39,077

41,438

2783

E6H-A/MS50

5000

85

54,863

57,224

2783

Standard features manually operated UL switch

Neutral pole rating

E1 E3 = 100% rating
E4 E6 = 50% rating

Rear horizontal terminals


Manual mechanical close and open pushbuttons
CB open/closed mechanical indicator
Spring charged/discharged mechanical indicator
Lifting plates
Terminal box

16

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.11

16

rs
ax ake
m
e
E br
er
ow

Non-automatic air circuit breakers


Withdrawable switches (without trip unit & c.t.s.), 3 pole
UL

Withdrawable switches
Circuit

Interrupting

breaker
type

Frame
amps

ratings
kA, 480V

Moving part only

Fixed part only

Manually
operated

Electrically
operated

RH
terminals

Set of three
vertical terminals

E1B-A/MS08

800

42

$ 5654

$ 8015

$ 2281

$ 644

E1B-A/MS12
E2N-A/MS12
E3S-A/MS12

1200
1200
1200

42
50
65

6646
7085
7384

9007
9446
9745

2281
2400
2925

644
690
790

E2B-A/MS16
E2N-A/MS16
E3S-A/MS16

1600
1600
1600

42
50
65

7591
8754
9095

9952
11,115
11,456

2400
2400
2925

690
690
790

E3N-A/MS20
E3S-A/MS20

2000
2000

50
65

9550
10,864

11,911
13,225

2925
2925

790
790

E3N-A/MS25
E3S-A/MS25

2500
2500

50
65

15,931
18,479

18,292
20,840

2925
2925

790
790

E4S-A/MS32
E4H-A/MS32

3200
3200

65
85

21,431
22,078

23,792
24,439

6259
6259

1664
1664

E4S-A/MS36
E4H-A/MS36

3600
3600

65
85

24,494
28,496

26,855
30,857

6259
6259

1664
1664

E6H-A/MS40

4000

85

32,094

34,455

7398

2783

E6H-A/MS50

5000

85

43,820

46,181

7398

2783

Standard features manually operated switch


Moving part

Standard features manually operated switch


Fixed part

Manual mechanical close and open pushbuttons


Circuit breaker open/closed mechanical indicator
Spring charged/discharged mechanical indicator
Lifting plates
Racking device with closed door
Circuit breaker racking position indicator
Sliding contacts
Fail-safe device (not available with YU)

Safety shutters
Rear horizontal terminals
Sliding contacts
Anti-insertion lock
Ground connection

16

16.12

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16

ow Em
Non-automatic air circuit breakers
er ax
Withdrawable switches (without trip unit & c.t.s.), 4 pole break
er
s
UL
Withdrawable switches
Circuit
breaker
type

Interrupting
Frame
amps

ratings
kA, 480V

Moving part only

Fixed part only

Manually
operated

Electrically
operated

RH
terminals

Set of four
vertical terminals

E1B-A/MS08

800

42

$ 7633

$ 9994

$ 3079

$ 837

E1B-A/MS12
E2N-A/MS12
E3S-A/MS12

1200
1200
1200

42
50
65

8972
9565
9968

11,333
11,926
12,329

3079
3240
3949

837
897
1027

E2B-A/MS16
E2N-A/MS16
E3S-A/MS16

1600
1600
1600

42
50
65

10,248
11,818
12,278

12,609
14,179
14,639

3240
3240
3949

897
897
1027

E3N-A/MS20
E3S-A/MS20

2000
2000

50
65

12,893
14,666

15,254
17,027

3949
3949

1027
1027

E3N-A/MS25
E3S-A/MS25

2500
2500

50
65

21,507
24,947

23,868
27,308

3949
3949

1027
1027

E4S-A/MS32
E4H-A/MS32

3200
3200

65
85

28,932
29,805

31,293
32,166

8450
8450

2163
2163

E4S-A/MS36
E4H-A/MS36

3600
3600

65
85

33,067
38,470

35,428
40,831

8450
8450

2163
2163

E6H-A/MS40

4000

85

43,327

45,688

9987

3618

E6H-A/MS50

5000

85

59,157

61,518

9987

3618

Standard features manually operated switch


Moving part

Standard features manually operated switches


Fixed part

Manual mechanical close and open pushbuttons


Circuit breaker open/closed mechanical indicator
Spring charged/discharged mechanical indicator
Lifting plates
Racking device with closed door
Circuit breaker racking position indicator
Sliding contacts
Fail-safe device (not available with YU)

Safety shutters
Rear horizontal terminals
Sliding contacts
Anti-insertion lock
Ground connection

Neutral pole rating


E1 E3 = 100% rating
E4 E6 = 50% rating

16

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.13

16

rs
ax ake
m
e
E br
er
ow

General information
IEC general ratings and specifications 2

E1

E2

Circuit breaker type

E3

E1

Performance level

E4

E2

E3

A
A
A
A
A

800
1250

1600
2000

1250
1600
2000

1250
1600

2500
3200

1250
1600
2000
2500
3200

1250
1600
2000
2500
3200

2000
2500

%lu

100

100

100

100

100

100

100

100

kA
kA
kA
kA
kA

40
40
36

36

40
40
40

40

65
65
55

55

130
110
85

65
65
65

65

75
75
75

75

100
100
85
100
75

130
110
85

kA
kA
kA
kA

40
40
36
36

40
40
40
40

65
65
55
55

130
110
65

65
65
65
65

75
75
75
75

85
85
85
75

130
110
65

(1S) kA

36

40

55

10

65

75

75

15

84
84
75.6

84
84
84

143
143
121

286
242
187

143
143
143

165
165
165

220
220
187

286
242
187

Utilization category (in accordance with CEI EN 60947-2)

Isolation behavior (in accordance with CEI EN 60947-2)

ms
ms
ms

80
70
30

80
70
30

80
70
30

80
70
12

80
70
30

80
70
30

80
70
30

80
70
12

mm
mm

296/386
324/414

kg
kg

42/50
65/80

Rated uninterrupted current (at 40C) lu


breaking capacity

Capacity of neutral pole on four-pole circuit breakers


Rated ultimate short-circuit
breaking capacity

lcu 220/230/380/400/415V~

Rated duty short-circuit


breaking capacity

lcs 220/230/380/400/415V~

Rated short-time
withstand current

440V~
500/660/690V~
600V~
250V (switches)
440V~
500/660/690V~
250V (switches)

lcw

Rated short-circuit making


capacity (peak value)

lcm 220/230//380/400/415V~
440V~
500/660/690V~

kA
kA
kA

Overcurrent protection
Microprocessor-based releases for a.c. applications
Operating time

16

Closing time (max)


Break time for I<lcw (max) 1
Break time for I>lcw (max)
Dimensions
Fixed:
Withdrawable:

H=418mm D=302mm
H=461mm D=396.5mm

L(3/4 poli)=
L(3/4 poli)=

296/386
324/414

404/530
432/558

Weights
(circuit-breaker complete with releases and CT, excluding accessories)

Fixed 3/4 pole


Withdrawable 3/4 pole (including fixed part)

Circuit-breaker type
Rated uninterupted current
(at 40C)

lu

46/55
72/89

E1B
A

800

1250

46/55
72/89

E2 B-N
1250

1600

45/53
70/87

68/80 68/80 68/80 67/79


100/125 100/125 100/125 100/120

E2L
2000

1250

E3 N-S-H

1600

1250

1600

2000

2500

3200

Mechanical life with regular


routine maintenance
Frequency

No. operations x 1000

25

25

25

25

25

20

20

20

20

20

20

20

Operations per hour

60

60

60

60

60

60

60

60

60

60

60

60

Electrical life (440V~)


Frequency

No. operations x 1000


Operations per hour

10
30

10
30

15
30

12
30

10
30

4
20

3
20

12
20

10
20

9
20

8
20

6
20

1 Without intentional delays.


2 Consult factory for drawings.

16.14

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Po

16
we Em
r b ax
re
ak
e

General information
IEC general ratings and specifications

rs

Specifications common to the entire range


Voltages
Rated service voltage
Rated insulation voltage
Rated impulse withstand voltage
Service temperature
Storage temperature
Frequency
Number of poles
Versions

Ue
Ui
Uimp

690~ / 250 V
1000 V
12 kV
-5 +70 C
-40 +70 C
5060 Hz
34
Fixed / Withdrawable

E6

Circuit breaker type

E4

Performance level

A
A
A
A
A

4000

3200
4000

5000
6300

3200
4000
5000
6300

%lu

50

50

50

50

kA
kA
kA
kA
kA

75
75
75

75

100
100
85
100
100

100
100
75

100

150
150
85

100

kA
kA
kA
kA

75
75
75
75

100
100
85
100

100
100
100
100

125
125
100
100

Rated uninterrupted current (at 40C) lu

Capacity of neutral poles on four-pole circuit breakers


Rated ultimate short-circuit
breaking capacity

lcu 220/230/380/400/415V~

Rated duty short-circuit


breaking capacity

lcs 220/230/380/400/415V~

Rated short-time
withstand current

440V~
500/660/690V~
600V~
250V (switches)
440V~
500/660/690V~
250V (switches)

lcw

E6

(1S)kA

75

100

100

100

kA
kA
kA

165
165
165

220
220
187

220
220
165

330
330
187

Utilization category (in accordance with CEI EN 60947-2)

Isolation behavior (in accordance with CEI EN 60947-2)

80
70
30

80
70
30

80
70
30

80
70
30

Rated short-circuit making


capacity (peak value)

lcm 220/230/380/400/415V~
440V~
500/660/690V~

Overcurrent protection
Microprocessor-based releases for a.c. applications
Operating time
Closing time (max)
Break time for l<lcw (max)1
Break time for l>lcw (max)

ms
ms
ms

16

Dimensions
Fixed:
Withdrawable:

H=418mm D=302mm
H=461mm D=396.5mm

L(3/4 poli)=
L(3/4 poli)=

566/656
594/684

mm
mm

782/908
810/936

Weights
(circuit-breaker complete with releases and CT, excluding accessories)

Fixed 3/4 pole


Withdrawable 3/4 pole (including fixed part)

kg
kg

95/115
147/190

Circuit-breaker type
Rated uninterupted current
(at 40C)
Mechanical life with regular
routine maintenance
Frequency

lu

Electrical life (440V~)


Frequency

95/115
147/190

E3L
(A)

2000

140/170
210/260

140/170
210/260

E4 S-H
2500

E6 H-V

3200

4000

3200

4000

5000

6300

(No. operations x 1000)

15

15

15

15

12

12

12

12

(Operations per hour)

60

60

60

60

60

60

60

60

(Operations x 1000)

1.8

(Operations per hour)

20

20

10

10

10

10

10

10

1 Without intentional delays.


2 Consult factory for drawings.

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16

rs
ax ake
m
e
E br
er
ow

General information
Catalog number information
IEC

E 1 S

16

X X X X X X X X X X
Accessories: X = none
A = mechanical counter
B = button guard

Accessories: X = none
A = mechanical trip indicator
B = mechanical trip indicator
& bell alarm
C = padlock provision (open)
D = keylock (open)
E = position lock
F = access pos. lock
Undervoltage trip: 0 =
50/60Hz & VDC:
A =
C =
E =
G =
J =
Second shunt trip: L =
N =
Q =
S =
U =

F=A&B

G
H
J
K
L
M
N
P

=
=
=
=
=
=
=
=

none
24VDC
48V
110 120V
220 240V
380 400VAC
24VDC
48V
110 120V
220 240V
380 400VAC

A&C
A&D
A&E
A&F
A, C & E
A, C & F
B&C
B&D

Q =
R =
S =
T =
U =
V =
W=
Y =

B&E
B&F
B, C & E
B, C & F
C&E
C&F
D&E
D&F

B = 30V
D = 60V
F = 125 127V
H = 250V
K = 440 480VAC
M = 30V
P = 60V
R = 125 127V
T = 250V
V = 440 480VAC

Shunt trip: 0 = none


50/60Hz & VDC: A = 24VDC, B = 30, C = 48, D = 60, E = 110 120,
F = 120 127, G = 220 240, H = 240 - 250, J = 380 400VAC,
K = 440 480VAC
Spring charging motor: (includes spring charged signal, P/N does not show)
0 = none, A = 24 30VAC/VDC, B = 48 60VAC/VDC, C = 110-130VAC/VDC,
D = 220 250VAC/VDC, E = spring charged signal only
Contacts:
A = 4 aux
E = UV energ.NC
J=B&E

B = 10 aux
F=A&D
K=C&D

C = 15 aux
G=A&E
L=C&E

D = UV energ. N.O.
H=B&D

Closing coil: 0 = none


50/60Hz & VDC: A = 24VDC, B = 30, C = 48, D = 60, E = 110 120, F = 120 127,
G = 220 240, H = 240 - 250, J = 380 400VAC, K = 440 480VAC

16
Terminal types: (Ist letter is upper terminal, 2nd letter is lower terminal) 1
H = rear horz., V = rear vert., F = front, L = rear flat
H = HH, V = VV, F = FF, L = LL,
A = HV, B = VH, C = HF, D = FH, E = HL, G = LH, J = VF, K = FV, M = VL, N = LV,
P = FL, Q = LF
Trip unit: A = PR111/P, LI
D = non-automatic
G = PR112/PD, LSI
P = PR113/PD
Version:

B = PR111/P, LSI
E = PR112/P, LSI
H = PR112/PD, LSIG

C = PR111/P, LSIG
F = PR112/P, LSIG
N = PR113/P

F = fixed breaker, IEC; W = withdrawable breaker, IEC, less cradle

Max. ampere rating: 02 = 250, 04 = 400, 08 = 800, 10 = 1000, 12 = 1250, 16 = 1600, 20 = 2000, 25 = 2500, 32 = 3200,
40 = 4000, 50 = 5000, 63 = 6300
Breaking capacity: B = basic, N = normal, S = standard, H = high, V = very high, L = limiting

Frame size: 1 = 1, 3P; 2 = 2, 3P; 3 = 3, 3P; 4 = 4, 3P; 6 = 6, 3P; A = 1, 4P; B = 2, 4P; C = 3, 4P; D = 4, 4P; F = 6, 4P

1 For withdrawable breakers, use "H".


2 Not available with PR112 trip units; use external 15 auxiliary kit.

16.16

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Po

16
we Em
r b ax
re
ak
e

General information
Catalog number information
Cradle (fixed part), IEC
E 1 X

12

rs

X X X

Accessories: X = none
A = Shutter padlock

Contacts: 0 = none
A = 5 position auxiliaries
B = 10 position auxiliaries

Terminal types: (Ist letter is upper terminal, 2nd letter is lower terminal.)
H = rear horz., V = rear vert., F = front, L = rear flat
H = HH, V = VV, F = FF, L = LL,
A = HV, B = VH, C = HF, D = FH, E = HL, G = LH, J = VF, K = FV, M = VL, N = LV,
P = FL, Q = LF

Max. ampere rating: IEC: 12 = 1250 (E1); 20 = 2000 (E2); 32 = 3200 (E3); 40 = 4000 (E4); 63 = 6300 (E6)

Version: C = cradle, IEC

Frame size: 1 = 1, 3P; 2 = 2, 3P; 3 = 3, 3P; 4 = 4, 3P; 6 = 6, 3P


A = 1, 4P; B = 2, 4P; C = 3, 4P; D = 4, 4P; F = 6, 4P

General information
Standard features

16
Fixed breaker

Manual operated

T.U. PR111/P, LI
Aux. SW., 4
Spring charged indicator
Flange
Accessory support
Terminal block
Lifting plate

Drawout breaker
Electrically operated

T.U PR111/P, LI
Motor operator
Closing coil
Shunt trip
Aux. SW., 4
Spring charged indicator
Flange
Accessory support
Terminal block
Lifting plate

Manual operated

Electrically operated

T.U. PR111/P, LI
Aux. SW., 4
Spring charged indicator
Flange
Crank
Accessory support
Sliding contacts
Anti-insertion lock
Lifting plate

T.U. PR111/P, LI
Motor operator
Closing coil
Shunt trip
Aux. SW., 4
Spring charged indicator
Flange
Crank
Accessory support
Sliding contacts
Anti-insertion lock
Lifting plate

NOTE: Switches provided standard without 4 auxiliary contacts.

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16

rs
ax ake
m
e
E br
er
ow

Fixed breakers, 3 poles


IEC

Fixed breakers
Circuit
breaker
type

Frame
amps

Interrupting
ratings
kA, 415V

Manually
operated

Electrically
operated

Set of three
vertical terminals

Set of three
front terminals

E1B08

800

40

$ 6027

$ 8388

$ 644

$ 367

E1B12
E2N12
E3S12
E3H12
E2L12

1250
1250
1250
1250
1250

40
65
75
100
130

6656
7314
7808
8036
10,066

9017
9675
10,169
10,397
12,427

644
690
790
790
690

367
888
1232
1232
888

E2B16
E2N16
E3S16
E3H16
E2L16

1600
1600
1600
1600
1600

40
65
75
100
130

7293
8014
8700
9232
11,422

9654
10,375
11,061
11,593
13,783

690
690
790
790
690

888
888
1232
1232
888

E2B20
E2N20
E3S20
E3H20
E3L20

2000
2000
2000
2000
2000

40
65
75
100
130

8509
9024
9817
11,762
13,425

10,870
11,385
12,178
14,123
15,786

690
690
790
790
790

888
888
1232
1232
1232

E3N25
E3S25
E3H25
E3L25

2500
2500
2500
2500

65
75
100
130

13,870
15,242
16,948
19,454

16,231
17,603
19,309
21,815

790
790
790
790

1232
1232
1232
1232

E3N32
E3S32
E3H32
E4H32
E6V32

3200
3200
3200
3200
3200

65
75
100
100
150

17,963
18,662
20,217
22,085
36,328

20,324
21,023
22,578
24,446
38,689

790
790
790
1664
2783

1232
1232
1232
1696
2464

E4S40
E4H40
E6V40

4000
4000
4000

75
100
150

26,873
30,645
42,739

29,234
33,006
45,100

1664
1664
2783

1696
1696
2464

E6H50
E6V50

5000
5000

100
150

42,047
50,281

44,408
52,642

2783
2783

2464
2464

E6H63
E6V63

6300
6300

100
150

50,456
60,337

52,817
62,698

2783
2783

2464
2464

Standard features manually operated breaker


Fixed breaker

16

Rear horizontal terminals


PR111 trip unit with LI protection functions
Manual mechanical close and open pushbuttons
CB open/closed mechanical indicator
Spring charged/discharged mechanical indicator
2NO & 2NC auxiliary contacts for open-closed position indication
Lifting plates
Current transformers
Terminal box

16.18

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Po

16
we Em
r b ax
re
ak
e

Fixed breakers, 4 poles


IEC

rs

Fixed breakers
Circuit
breaker
type

Frame
amps

Interrupting
ratings
kA, 415V

Electrically
operated

Set of four
vertical terminals

Set of four
front terminals

E1B08

800

40

$ 7475

$ 9836

$ 837

$ 489

E1B12
E2N12
E3S12
E3H12
E2L12

1250
1250
1250
1250
1250

40
65
75
100
130

8293
9148
9306
9591
12,725

10,654
11,509
11,667
11,952
15,086

837
897
1027
1027
897

489
1183
1643
1643
1183

E2B16
E2N16
E3S16
E3H16
E2L16

1600
1600
1600
1600
1600

40
65
75
100
130

9121
10,059
10,413
10,550
14,488

11,482
12,420
12,774
12,911
16,849

897
897
1027
1027
897

1183
1183
1643
1643
1183

E2B20
E2N20
E3S20
E3H20
E3L20

2000
2000
2000
2000
2000

40
65
75
100
130

10,701
11,371
11,795
13,621
17,093

13,062
13,732
14,156
15,982
19,454

897
897
1027
1027
1027

1183
1183
1643
1643
1643

E3N25
E3S25
E3H25
E3L25

2500
2500
2500
2500

65
75
100
130

17,671
19,454
21,672
24,930

20,032
21,815
24,033
27,291

1027
1027
1027
1027

1643
1643
1643
1643

E3N32
E3S32
E3H32
E4H32
E6V32

3200
3200
3200
3200
3200

65
75
100
100
150

22,992
23,900
27,307
28,351
45,410

25,353
26,261
29,668
30,712
47,771

1027
1027
1027
2163
3618

1643
1643
1643
2260
3286

E4S40
E4H40
E6V40

4000
4000
4000

75
100
150

34,610
39,516
53,424

36,971
41,877
55,785

2163
2163
3618

2260
2260
3286

E6H50
E6V50

5000
5000

100
150

52,558
62,852

54,919
65,213

3618
3618

3286
3286

E6H63
E6V63

6300
6300

100
150

63,070
75,422

65,431
77,783

3618
3618

3286
3286

Standard features manually operated breaker


Fixed breaker

Manually
operated

Rear horizontal terminals


PR111 trip unit with LI protection functions
Manual mechanical close and open pushbuttons
CB open/closed mechanical indicator
Spring charged/discharged mechanical indicator
2NO & 2NC auxiliary contacts for open-closed position indication
Lifting plates
Current transformers
Terminal box

Neutral pole rating


E1 E3 = 100% rating
E4 E6 = 50% rating 1

16

1 Consult factory for special 100% neutral pole rating.

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.19

16

rs
ax ake
m
e
E br
er
ow

Withdrawable breakers, 3 poles


IEC

Withdrawable breakers
Circuit
breaker
type

16

Moving part only

Fixed part

Frame
amps

Interrupting
ratings
kA, 415V

E1B08

800

40

$ 6501

$ 8862

$ 2281

$ 644

$ 367

E1B12
E2N12
E3S12
E3H12
E2L12

1250
1250
1250
1250
1250

40
65
75
100
130

7757
8626
8760
8897
12,180

10,118
10,987
11,121
11,258
14,541

2281
2400
2925
2925
2400

644
690
790
790
690

367
888
1232
1232
888

E2B16
E2N16
E3S16
E3H16
E2L16

1600
1600
1600
1600
1600

40
65
75
100
130

9097
10,234
10,674
11,100
15,920

11,458
12,595
13,035
13,461
18,281

2400
2400
2925
2925
2400

690
690
790
790
690

888
888
1232
1232
888

E2B20
E2N20
E3S20
E3H20
E3L20

2000
2000
2000
2000
2000

40
65
75
100
130

10,987
11,182
11,361
13,256
17,817

13,348
13,543
13,722
15,617
20,178

2400
2400
2925
2925
2925

690
690
790
790
790

888
888
1232
1232
888

E3N25
E3S25
E3H25
E3L25

2500
2500
2500
2500

65
75
100
130

15,220
17,896
19,528
22,892

17,581
20,257
21,889
25,253

2925
2925
2925
2925

790
790
790
790

1232
1232
1232
1232

E3N32
E3S32
E3H32
E4H32
E6V32

3200
3200
3200
3200
3200

65
75
100
100
150

22,337
23,340
23,724
23,842
38,539

24,698
25,701
26,085
26,203
40,900

2925
2925
2925
6259
7398

790
790
790
1664
2783

1232
1232
1232
1696
2464

E4S40
E4H40
E6V40

4000
4000
4000

75
100
150

30,399
34,540
45,340

32,760
36,901
47,701

6259
6259
7398

1664
1664
2783

1696
1696
2464

E6H50
E6V50

5000
5000

100
150

45,541
53,341

47,902
55,702

7398
7398

2783
2783

2464
2464

E6H63
E6V63

6300
6300

100
150

64,163
78,427

66,524
80,788

7398
7398

2783
2783

2464
2464

Manually
operated

Electrically
operated

RH
terminals

Set of three
vertical terminals

Standard features electrically operated breaker


Moving part

Standard features electrically operated breaker


Fixed part

PR111 trip unit with LI protection functions


Spring charging motor
Shunt trip
Closing coil
Manual mechanical close and open pushbuttons
CB open/closed mechanical indicator
Spring charged/discharged mechanical indicator
2NO & 2NC auxiliary contacts for open-closed position indication
Lifting plates
Current transformers
Racking device with closed door
Circuit breaker racking position indicator
Sliding contacts

16.20

Set of three
front terminals

Safety shutters
Rear horizontal terminals
Sliding contacts
Anti-insertion lock
Ground connection

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Po

16
we Em
r b ax
re
ak
e

Withdrawable breakers, 4 poles


IEC

rs

Withdrawable breakers
Circuit
breaker
type

Moving part only

Fixed part

Frame
amps

Interrupting
ratings
kA, 415V

E1B08

800

40

$ 7717

$ 10,078

$ 2572

$ 837

$ 489

E1B12
E2N12
E3S12
E3H12
E2L12

1250
1250
1250
1250
1250

40
65
75
100
130

10,649
11,372
11,906
12,229
15,402

13,010
13,733
14,267
14,590
17,763

2572
3192
3890
3890
3192

837
897
1027
1027
897

489
1183
1643
1643
1183

E2B16
E2N16
E3S16
E3H16
E2L16

1600
1600
1600
1600
1600

40
65
75
100
130

11,395
12,873
12,472
13,304
20,264

13,756
15,234
14,833
15,665
22,625

3192
3192
3890
3890
3192

897
897
1027
1027
897

1183
1183
1643
1643
1183

E2B20
E2N20
E3S20
E3H20
E3L20

2000
2000
2000
2000
2000

40
65
75
100
130

13,851
15,661
14,873
16,784
22,714

16,212
18,022
17,234
19,145
25,075

3192
3192
3890
3890
3890

897
897
1027
1027
1027

1183
1183
1643
1643
1643

E3N25
E3S25
E3H25
E3L25

2500
2500
2500
2500

65
75
100
130

20,380
22,816
24,938
29,312

22,741
25,177
27,299
31,673

3890
3890
3890
3890

1027
1027
1027
1027

1643
1643
1643
1643

E3N32
E3S32
E3H32
E4H32
E6V32

3200
3200
3200
3200
3200

65
75
100
100
150

29,555
29,893
32,017
32,589
49,722

31,916
32,254
34,378
34,950
52,083

3890
3890
3890
8324
9839

1027
1027
1027
2163
3618

1643
1643
1643
2260
3286

E4S40
E4H40
E6V40

4000
4000
4000

75
100
150

41,350
44,409
58,496

43,711
46,770
60,857

8324
8324
9839

2163
2163
3618

2260
2260
3286

E6H50
E6V50

5000
5000

100
150

58,680
68,820

61,041
71,181

9839
9839

3618
3618

3286
3286

E6H63
E6V63

6300
6300

100
150

82,888
101,432

85,249
103,793

9839
9839

3618
3618

3286
3286

Manually
operated

Electrically
operated

RH
terminals

Set of four
vertical terminals

Standard features electrically operated breaker


Moving part

Standard features electrically operated breaker


Fixed part

PR111 trip unit with LI protection functions


Spring charging motor
Shunt trip
Closing coil
Manual mechanical close and open pushbuttons
CB open/closed mechanical indicator
Spring charged/discharged mechanical indicator
2NO & 2NC auxiliary contacts for open-closed position indication
Lifting plates
Current transformers
Racking device with closed door
Circuit breaker racking position indicator
Sliding contacts

Set of four
front terminals

Safety shutters
Rear horizontal terminals
Sliding contacts
Anti-insertion lock
Ground connection

16

Neutral pole rating


E1 E3 = 100% rating
E4 E6 = 50% rating 1

1 Consult factory for special 100% neutral pole rating.


Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.21

16

rs
ax ake
m
e
E br
er
ow

Non-automatic air circuit breaker


Fixed switches (Without trip unit & c.t.s.), 3 pole
IEC

Fixed switches, 3 pole


Circuit
breaker
type

Frame
amps

Manually
operated

Electrically
operated

Set of three
vertical terminals

Set of three
front terminals

E1B/MS08

800

$ 4298

$ 6659

$ 644

$ 367

E1B/MS12
E2N/MS12
E3S/MS12

1250
1250
1250

4927
5585
5972

7288
7946
8333

644
690
790

367
888
1232

E2B/MS16
E2N/MS16
E3S/MS16

1600
1600
1600

5564
6285
6864

7925
8646
9225

690
690
790

888
888
1232

E2B/MS20
E2N/MS20
E3S/MS20

2000
2000
2000

6780
7295
7981

9141
9656
10,342

690
690
790

888
888
1232

E3N/MS25
E3S/MS25

2500
2500

12,034
13,406

14,395
15,767

790
790

1232
1232

E3N/MS32
E3S/MS32

3200
3200

16,127
16,826

18,488
19,187

790
790

1232
1232

E4S/MS40
E4H/MS40

4000
4000

24,504
28,276

26,865
30,637

1664
1664

1696
1696

E6H/MS50

5000

39,465

41,826

2783

2464

E6H/MS63

6300

47,874

50,235

2783

2464

Standard features manually operated switch

Rear horizontal terminals


Manual mechanical close and open pushbuttons
Circuit breaker open/closed mechanical indicator
Spring charged/discharged mechanical indicator
Lifting plates
Terminal box

16

16.22

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Non-automatic air circuit breaker


Fixed switches (Without trip unit & c.t.s.), 4 pole
IEC

Po

16
we Em
r b ax
re
ak
e

rs

Fixed switches, 4 pole


Circuit
breaker
type

Frame
amps

Manually
operated

Electrically
operated

Set of four
vertical terminals

Set of four
front terminals

E1B/MS08

800

$ 5533

E1B/MS12
E2N/MS12
E3S/MS12

1250
1250
1250

6351
7206
7221

$ 7894

$ 837

$ 489

8712
9567
9582

837
897
1027

489
1183
1643

E2B/MS16
E2N/MS16
E3S/MS16

1600
1600
1600

7179
8117
8328

9540
10,478
10,689

897
897
1027

1183
1183
1643

E2B/MS20
E2N/MS20
E3S/MS20

2000
2000
2000

8759
9429
9710

11,120
11,790
12,071

897
897
1027

1183
1183
1643

E3N/MS25
E3S/MS25

2500
2500

15,586
17,369

17,947
19,730

1027
1027

1643
1643

E3N/MS32
E3S/MS32

3200
3200

20,907
21,815

23,268
24,176

1027
1027

1643
1643

E4S/MS40
E4H/MS40

4000
4000

31,815
36,721

34,176
39,082

2163
2163

2260
2260

E6H/MS50

5000

49,479

51,480

3618

3286

E6H/MS63

6300

59,991

62,352

3618

3286

Standard features manually operated switch

Neutral pole rating

E1 E3 = 100% rating
E4 E6 = 50% rating 1

Rear horizontal terminals


Manual mechanical close and open pushbuttons
Circuit breaker open/closed mechanical indicator
Spring charged/discharged mechanical indicator
Lifting plates
Terminal box

16

1 Consult factory for special 100% neutral pole rating.


Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.23

16

rs
ax ake
m
e
E br
er
ow

Non-automatic air circuit breaker


Withdrawable switches (Without trip unit & c.t.s.), 3 pole
IEC

Withdrawable switches, 3 pole


Circuit
breaker
type

Ampere
frame
amps

Moving part only


Manually
Electrically
operated
operated

Fixed part
RH
terminals

Set of 3
vertical terminals

Set of 3
front terminals

E1B/MS08

800

$ 4772

$ 7133

$ 2281

$ 644

$ 367

E1B/MS12
E2N/MS12
E3S/MS12

1250
1250
1250

6028
6897
6924

8389
9258
9285

2281
2400
2925

644
690
790

367
888
1232

E2B/MS16
E2N/MS16
E3S/MS16

1600
1600
1600

7368
8505
8838

9729
10,866
11,199

2400
2400
2925

690
690
790

888
888
1232

E2B/MS20
E2N/MS20
E3S/MS20

2000
2000
2000

9258
9453
9525

11,619
11,814
11,886

2400
2400
2925

690
690
790

888
888
1232

E3N/MS25
E3S/MS25

2500
2500

13,384
16,060

15,745
18,421

2925
2925

790
790

1232
1232

E3N/MS32
E3S/MS32

3200
3200

20,501
21,540

22,862
23,865

2925
2925

790
790

1232
1232

E4S/MS40
E4H/MS40

4000
4000

28,030
32,171

30,391
34,532

6259
6259

1664
1664

1696
1696

E6H/MS50

5000

42,959

45,320

7398

2783

2464

E6H/MS63

6300

61,581

63,942

7398

2783

2464

Standard features manually operated switch


Moving part

Standard features manually operated switch


Fixed part

Manual mechanical close and open pushbuttons


Circuit breaker open/closed mechanical indicator
Spring charged/discharged mechanical indicator
Lifting plates
Racking device with closed door
Circuit breaker racking position indicator
Sliding contacts

Safety shutters
Rear horizontal terminals
Sliding contacts
Anti-insertion lock
Ground connection

16

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16

ow Em
Non-automatic air circuit breaker
er ax
Withdrawable switches (Without trip unit & c.t.s.), 4 pole break
er
s
IEC
Withdrawable switches, 4 pole
Circuit
breaker
type

Ampere
frame
amps

Moving part only


Manually
Electrically
operated
operated

Fixed part
RH
terminals

Set of 4
vertical terminals

Set of 4
front terminals

E1B/MS08

800

$ 5775

$ 8136

$ 2572

$ 837

$ 489

E1B/MS12
E2N/MS12
E3S/MS12

1250
1250
1250

8707
9430
9821

11,068
11,791
12,182

2572
3192
3890

837
897
1027

489
1183
1643

E2B/MS16
E2N/MS16
E3S/MS16

1600
1600
1600

9453
10,931
10,387

11,814
13,292
12,748

3192
3192
3890

837
897
1027

1183
1183
1643

E2B/MS20
E2N/MS20
E3S/MS20

2000
2000
2000

11,909
13,719
12,788

14,270
16,080
15,149

3192
3192
3890

837
897
1027

1183
1183
1643

E3N/MS25
E3S/MS25

2500
2500

18,295
20,731

20,656
23,092

3890
3890

1027
1027

1643
1643

E3N/MS32
E3S/MS32

3200
3200

27,470
27,808

29,831
30,169

3890
3890

1027
1027

1643
1643

E4S/MS40
E4H/MS40

4000
4000

38,555
41,614

40,916
43,975

8324
8324

2163
2163

2260
2260

E6H/MS50

5000

55,601

57,962

9839

3618

3286

E6H/MS63

6300

79,809

82,170

9839

3618

3286

Standard features manually operated switch


Moving part

Standard features manually operated switch


Fixed part

Manual mechanical close and open pushbuttons


Circuit breaker open/closed mechanical indicator
Spring charged/discharged mechanical indicator
Lifting plates
Racking device with closed door
Circuit breaker racking position indicator
Sliding contacts

Safety shutters
Rear horizontal terminals
Sliding contacts
Anti-insertion lock
Ground connection

Neutral pole rating


E1 E3 = 100% rating
E4 E6 = 50% rating 1

16

1 Consult factory for special 100% neutral pole rating.

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16

rs
ax ake
m
e
E br
er
ow

Air circuit breakers


Installed optional features
UL & IEC

1. 20. Options for trip units


Item

Factory installation
list price adder

Field installation
catalog number

Field install.
list price

1. Trip unit PR111/P-A LI (UL version)


2. Trip unit PR111/P-A LSI (UL version)
3. Trip unit PR111/P-A LSIG (UL version)

$ 515
1208

PR111/P-A-LI
PR111/P-A-LSI
PR111/P-A-LSIG

$ 1089
1604
2297

4.
5.
6.
7.

Trip unit PR112/P-A LSI (UL version)


Trip unit PR112/P-A LSIG (UL version)
Trip unit PR112/PD-A LSI (UL version)
Trip unit PR112/PD-A LSIG (UL version)

2210
2904
6890
7583

PR112/P-A-LSI
PR112/P-A-LSIG
PR112/PD-A-LSI
PR112/PD-A-LSIG

3299
3993
7979
8672

8. Trip unit PR113/P-A-LSIG (UL version)


9. Trip unit PR113/PD-A-LSIG (UL version)

7323
12,002

PR113/P-A-LSIG
PR113/PD-A-LSIG

8412
13,091

10. Trip unit PR111/P LI (IEC version)


11. Trip unit PR111/P LSI (IEC version)
12. Trip unit PR111/P LSIG (IEC version)

515
1208

PR111/P-LI
PR111/P-LSI
PR111/P-LSIG

1089
1604
2297

13.
14.
15.
16.

2210
2904
6890
7583

PR112/P-LSI
PR112/P-LSIG
PR112/PD-LSI
PR112/PD-LSIG

3299
3993
7979
8672

7323
12,002

PR113/P-LSIG
PR113/PD-LSIG

8412
13,091

Trip unit PR112/P LSI (IEC version)


Trip unit PR112/P LSIG (IEC version)
Trip unit PR112/PD LSI (IEC version)
Trip unit PR112/PD LSIG (IEC version)

17. Trip unit PR113/PLSIG (IEC version)


18. Trip unt PR113/PDLSIG (IEC version)
19. Mechanical trip indication (manual reset)
20. Mechanical trip indication and bell alarm

188
348

KE6TSM
KE6TBA

188
348

21. 27. Electrical and mechanical accessories


Item

21a.

21b.

Factory
installation
list price
adder

Shunt trip coil (included in the electrically operated breaker)


Rated voltage
24V
30V
48V
60V
110/120V
125/127V
220/240V
250V
380/400V
440/480V

22.Closing coil (included in the electrically operated breaker)


Rated voltage
24V
30V
48V
60V
110/120V
125/127V
220/240V
250V
380/400V
440/480V
23.

Field
installation
list price

KE6S0
KE6S9
KE6S8
KE6S7
KE6S6
KE6S5
KE6S4
KE6S3
KE6S2
KE6S1

$ 374

Second shunt trip coil (includes accessory support) 1


24V
30V
48V
60V
110/120V
125/127V
220/240V
250V
380/400V
440/480V

16

$ 374

Field installation
catalog
number

Spring charging motor with limit switch and electrical indication charged spring
(included in the electrically operated breaker)
Rated voltage
24/30V
48/60V
100/130V
220/250V
Spring charged signal only

456

KE6S0-2
KE6S9-2
KE6S8-2
KE6S7-2
KE6S6-2
KE6S5-2
KE6S4-2
KE6S3-2
KE6S2-2
KE6S1-2

456

374

KE6C0
KE6C9
KE6C8
KE6C7
KE6C6
KE6C5
KE6C4
KE6C3
KE6C2
KE6C1

374

1613

KE6M9
KE6M7
KE6M5
KE6M3

1613

73

KE6SC

73

1 Order as alternative to UV trip.

Discount schedule EX

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Po

16
we Em
r b ax
re
ak
e

Air circuit breakers


Installed optional features
UL & IEC
Item

24.

Factory
installation
list price
adder

26.

$ 456

Energized undervoltage release signalling contact


Auxiliary contact normally open
Auxiliary contact normally closed

82

Field
installation
list price

KE6U0
KE6U9
KE6U8
KE6U7
KE6U6
KE6U5
KE6U4
KE6U3
KE6U2
KE6U1
KE6UE10
KE6UE01

$ 456

82

Auxiliary contacts for breakers


Rated 5A-250VAC / 0.3A 125VDC
26a. 2NO +2NC
26b. 5NO + 5NC (not available with PR112)
26c. 15 additional auxiliary contacts for field installation on fixed breakers (connected to breaker with
flexible cable) 1
26d. 15 additional auxiliary contacts for field installation on withdrawable breakers (connected to breaker
with flexible cable) 1

27.

Field installation
catalog
number

Instantaneous under voltage trip release


Rated voltage
24V
30V
48V
60V
110/120V
125/127V
220/240V
250V
380/400V
440/480V

25.

rs

Auxiliary contacts for switches


27a. 2NO + 2NC
27b. 5NO + 5NC

753
1507

KE6A4
KE6A10
KE6A15

297
1050
1507

1507

KE6A15-W

1507

297
1050

KE6A4
KE6A10

297
1050

28. 29. Electrical and mechanical accessories


Item

28.

29.

Factory
installation
list price
adder

Field installation
catalog
number

Field
installation
list price

Auxiliary contacts for service/test/disconnected position indication


Cradle mounted
28a . 5 auxiliary contacts
28b. 10 auxiliary contacts for E1/2
3 pole
28c. 10 auxiliary contacts for E1/2
4 pole
28d. 10 auxiliary contacts for E3
3 pole
28e. 10 auxiliary contacts for E3
4 pole
28f. 10 auxiliary contacts for E4/6
3/4 pole

377
753
753
753
753
753

KE6PS1
KE2PS3
KE2PS4
KE3PS3
KE3PS4
KE6PS2

377
753
753
753
753
753

Mechanical operation counter

418

KE6MC

418

16

1 Order as alternative to various types of interlock and kirk key lock. For mounting on fixed breaker, also requires accessory 32 (KE6MLP).

Low Voltage Products & Systems

Discount schedule EX

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.27

16

rs
ax ake
m
e
E br
er
ow

Air circuit breakers


Installed optional features
UL & IEC

30. 35. Locks and interlocks


Item

30.

Button guard

31.

Key lock in open position


31a. Key lock N. 3004222 1
31b. Key lock N. 0025431
31c. Key lock N. 0233424
31d. Key lock N. 0335452
31e. Key lock different keys

Factory
installation
list price
adder

32.

Padlocking button cover (padlocks not supplied)

33.

Key and padlocking device to lock the breaker in disconnected, test or connected position (position lock)
33a. Key + padlocking N3004222 1
33b. Key + padlocking N0025451
33c. Key + padlocking N0233424
33d. Key + padlocking N0335452
33e. Key + padlocking different keys

34.

Accessory to lock the breaker in test or disconnected position only 2


Position lock

35.

Padlocking device for the safety shutters on the cradle


Cradle padlock

Field installation
catalog
number

Field
installation
list price

$ 48

KE6PG

$ 48

202

KE6KL2
KE6KL3
KE6KL4
KE6KL5
KE6KL1

202

162

KE6PD1

162

202

KE6PL2
KE6PL3
KE6PL4
KE6PL5
KE6PL1

202

212

KE6PLA

212

43

KE6SP

43

16

1 Keylock number when factory installed is N3004222.


2 Also requires position lock (accessory 29).

Discount schedule EX

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Po

16
we Em
r b ax
re
ak
e

External accessories
Current transformers, UL & IEC

rs

36a. Neutral current transformer (required for 4 wire ground fault systems)
For breaker

Amps

E1 E2

250A
400A
800A
1000A
1200A
1250A
1600A

KE2NCT-250
KE2NCT-400
KE2NCT-800
KE2NCT-1000
KE2NCT-1200
KE2NCT-12001
KE2NCT-1600

250A
400A
800A
1000A
1200A
1250A
1600A
2000A
2500A

KE3NCT-250
KE3NCT-400
KE3NCT-800
KE3NCT-1000
KE3NCT-1200
KE3NCT-1250 1
KE3NCT-1600
KE3NCT-2000
KE3NCT-2500

1600A
2000A
2500A
3200A
3600A
4000A

KE4NCT-1600
KE4NCT-2000
KE4NCT-2500
KE4NCT-3200
KE4NCT-3600
KE4NCT-4000 1

3200A
4000A
5000A
6300A

KE6NCT-3200 1
KE6NCT-4000
KE6NCT-5000
KE6NCT-6300 1

E3

E4

E6

Catalog
number

List
price

$ 406

414

36b. Current transformer sets (sets of three)


For breaker

Amps

E1 E2

250A
400A
800A
1000A
1200A
1250A
1600A

KE2CT250
KE2CT400
KE2CT800
KE2CT1000
KE2CT1200
KE2CT1250 1
KE2CT1600

$ 840

250A
400A
800A
1000A
1200A
1250A
1600A
2000A
2500A

KE3CT250
KE3CT400
KE3CT800
KE3CT1000
KE3CT1200
KE3CT1250 1
KE3CT1600
KE3CT2000
KE3CT2500

1090

1600A
2000A
2500A
3200A
3600A
4000A

KE4CT1600
KE4CT2000
KE4CT2500
KE4CT3200
KE4CT3600
KE4CT4000 1

1640

3200A
4000A
5000A
6300A

KE6CT3200
KE6CT4000
KE6CT5000
KE6CT6300 1

2188

E3

E4

E6

Catalog
number

List
price

16

1 IEC only.

Low Voltage Products & Systems

Discount schedule EX

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.29

16

rs
ax ake
m
e
E br
er
ow

External accessories
Mechanical interlocks1

37. Mechanical interlocks (base plate for fixed circuit breaker)


For breaker

Interlock type

E1 E6

All

Catalog
number

KE6MLP

List
price

$ 241

NOTE: order for fixed circuit breaker only; order one accessory for each fixed breaker.

38. Interlock for fixed circuit breaker/fixed part of withdrawable circuit breaker (cable attachment plate)
For breaker

Interlock type

E1 E6

A, B, D
C

Catalog
number

KE6MLA
KE6MLC

List
price

$ 628

NOTE: order one accessory for each fixed circuit breaker/fixed part of withdrawable circuit breaker

39. Interlock for fixed circuit breaker/moving part of withdrawable circuit breaker (internal interlocking shaft)
For breaker

Interlock type

E1 E2
E3
E4, 3 pole
E4, 4 pole/ E6, 3 pole
E6, 4 pole

Catalog
number

KE2ML
KE3ML
KE4ML-3
KE6ML-3
KE6ML-4

All

List
price

$ 145

NOTE: order one accessory for each fixed circuit breaker/mobile part of withdrawable circuit breaker

40. Interlock cables


For breaker

Interlock type

E1 E6

A
B
C
D

Horizontal
Catalog
number

Vertical
Catalog
number

KE6MLC-HA
KE6MLC-HB
KE6MLC-HC
KE6MLC-HD

KE6MLC-VA
KE6MLC-VB
KE6MLC-VC
KE6MLC-VD

List
price

$ 97
193
193
193

NOTE: order one type of cable for each interlock

16

1 Order as an alternative to the Accessory number 15 auxiliary contact (see page 16.27) and kirk key lock.

16.30

Discount schedule EX

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Po

16
we Em
r b ax
re
ak
e

External accessories
Other items

rs

41. Electronic time delay for undervoltage release 1

Item

41.

Delay

Time delay
Voltage
24/30V
48V
60V
110/125V
220/250V

0.5-1-1.5-2-3.5 s

Field
installation
catalog
number

KE6TL9
KE6TL8
KE6TL7
KE6TL5
KE6TL3

List
price

$ 428

42. Transparent front cover (IP54)


For breaker

42.

Cover

E1 E6

Catalog
number

KE6DC

List
price

$ 557

43. Kirk key lock adaptor plate (in open position) 2


For breaker

43.

Kirk key lock adaptor plate


43a. E1 E2 fixed breaker, 3-4 pole
43b. E1 E2 withdrawable breaker, 3-4 pole
43c. E3 fixed breaker, 3-4 pole
43d. E3 withdrawable breaker, 3-4 pole
43e. E4 fixed breaker, 3 pole
43f. E4 withdrawable breaker, 3 pole
43g. E6 fixed breaker, 3 pole
43h. E6 withdrawable breaker, 3 pole
43i. E4 fixed breaker, 4 pole
43j. E4 withdrawable breaker, 4 pole
43k. E6 fixed breaker, 4 pole
43l. E6 withdrawable breaker, 4 pole

Catalog
number

KE6KKB-E2F
KE6KKB-E2W
KE6KKB-E3F
KE6KKB-E3W
KE6KKB-E4F
KE6KKB-E4W
KE6KKB-E6F
KE6KKB-E6W
KE6KKB-E4F-F
KE6KKB-E4W-4
KE6KKB-E6F-4
KE6KKB-E6W-4

List
price

$ 1436
1195
1436
1195
1436
1195
1436
1195
1436
1195
1436
1195

NOTE: Provision for kirk lock (kirk key lock not included; use lock Type F 1 inch bolt projection in withdrawn position).

44. Kit for converting fixed breaker with rear horizontal terminals to rear vertical (set of three terminals)
Item

44.

Conversion kit
44a. 1/2 3p F HR > F VR E1-A
44b. 1/2 3p F HR > F VR E2-A
44c. 1/2 3p F HR > F VR E3-A (12, 16, 20)
44d. 1/2 3p F HR > F VR E3-A (25)
44e. 1/2 3p F HR > F VR E4-A
44f. 1/2 3p F HR > F VR E6-A

Catalog
number

KE1FHRVR
KE2FHRVR
KE3FHRVR
KE3F25HRVR
KE4FHRVR
KE6FHRVR

List
price

$ 644
690
790
790
1664
2783

45. 47. Test kits


Item

45.
46.
47.

Hand-held test kit (for PR111 only)


Hand-held battery unit for PR112
Test and configuration unit SACE PR010/T

K7TUT
PR120/B
PR010/T

48. 55. Spare parts


Item

48.
49.
50.
51.
52.
53.
54.
55.

Catalog
number

Racking crank
Door escutcheon
Terminal board for fixed circuit breaker
Support plate for auxiliary releases
Sliding contacts for the moving part
Sliding contacts for the fixed part
Lifting plates
Transparent cover for the trip unit

Catalog
number

1SDA038092R1
1SDA038096R1
1SDA038342R1
1SDA038339R1
1SDA038328R1
1SDA038362R1
1SDA038093R1
1SDA045724R1

1 IEC only.
2 Kirk key not provided. Order as an alternative to the various types of interlocks and auxiliary contacts (see Accessory 26c and 26d on page 16.27).

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

List
price

$ 210
275
12,500

List
price

$ 122
153
722
244
946
793
224
61

16

16

rs
ax ake
m
e
E br
er
ow

Approximate dimensions (for UL version)


E1, fixed with horizontal rear terminals
3 pole

12.09
307

1.3

0.71

33

2.36

3.54

3.54

90

90

60

18

1.38
35

0.51
13

0.51
13

9.92
252

9.53

0.39

242

10

Part. "Z"

12.44
316

12.05

9.45

306

240

3.35

3.94

3.94

100

100

0.2
5

85

Y
3.94

339

379

440

5.51
12.28 140

16.46

100

418

312

3.94

6.02

100

7.58

0.65

374

3.94

17.32
14.92

384

14.72

13.35

10

15.12

0.2

100

0.39

153

R 0.08

192.5

4.63 16.5

117.5

5.91

Y
Z
11.65

1.93
1.3
33

6.97
177

49

296

150

6.63
168.5

1.97
50

16

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

00.00

Inches

00.00

[Millimeters]

Po

16
we Em
r b ax
re
ak
e

Approximate dimensions (for UL version)


E1, fixed with horizontal rear terminals
4 pole

rs

15.63

1.30
33

3.54

3.54

90

90

90

2.36

1.38

18

3.54

0
13 .51

397

0.71

35

60

Part. "Z"

9.92 9.53
252

0.51

242

0
M1

13

12.44

1.77

316

45

12.99

12.05

330

306

3.35 MIN.

3.94

3.94

100

100

85

.20

Y
3.94

17.32 MIN.
440

14.92
379

12.28

13.35
16.46

5.51 0.39
140

.2
05

100

418

15.12

339

3.94
100

10

384

X
14.72

312

374

7.58

192.5

3.94

0.65

100

4.63 16.5

117.5

R 0.08
2

Y
Y
1.30

6.97

33

177

1.93 1.97
49

50

15.20
386

5.91
6.63

150

168.5

16

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.33

16

rs
ax ake
m
e
E br
er
ow

Approximate dimensions (for UL version)


E1, withdrawable with horizontal rear terminals
3 pole

00.00

Inches

00.00

[Millimeters]

12.87
327

1.3

0.59

33

15

2.36
60

3.54

3.54

90

90

1.38
35

1.34

0.12

34

0.51
13

0.51
13

5.08
129

15.49

0.24

0.39

393.5

10

14.96
380

5.43
138

Part. "Z"

12.44
316

12.05
306

3.94

3.94

100

100

0.2
5

Y
3.94
10

339
465

18.31

18.15

465

461

384

14.72

13.35

18.31

15.12

0.2

100

0.39

374

3.94
100

5.51
140

3.94

6.02

100

7.85
4.90
124.5

199.5

0.71

153

R 0.08
2

18

5.91
150

Y
Z
2.32
59

12.76
324

9.45
240

6.63
168.5

1.93
49

16

16.34

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

00.00

Inches

00.00

[Millimeters]

Po

16
we Em
r b ax
re
ak
e

Approximate dimensions (for UL version)


E1, withdrawable with horizontal rear terminals
4 pole

rs

16.42
417

0.59

1.30

3.54

15

33

2.36 90

3.54

3.54

90

90

60

0.12

1.34

0.51

34

13

1.38

1
0.5
13

35

N
6.85

174

9
0.3
10

15.49

8.86
9.45 225

393,5

240

14.96
380

Part. "Z"

0.24
6

1.93 2.76
70
49

12.44

1.77

8.66

316

45

6.89

12.05

175

220

306

3.94

3.94

100

100

.20

Y
0.39

3.94

10

18.31

.2
05

100

18.31 MIN.

465

13.35

465

5.51

15.12

339

18.15

3.94
100

461

140

384

X
14.72
374

3.94
100

7.85

0.71
4.90 18

199,5

R 0.08
2

124,5

5.91
Z

13.70

16.30 Y
414

6.63

150

168,5

348

16

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.35

16

rs
ax ake
m
e
E br
er
ow

Approximate dimensions (for UL version)


E1 - E2, withdrawable with vertical rear terminals
3 pole

00.00

Inches

00.00

[Millimeters]

12.87
327

0.79
20

1.34
0.12

34

3.54

3.54

90

90

0.51
13

5.08

129

15.49

0.39

393.5

10

"

0.24

14.96

380

5.43
138

Part. "Z"

12.44
316

12.05
306

0.2

3.94

3.94

100

100

0.75

19.05

3.94

1.00

13.35
339

18.31

18.31
465

4.49

18.15

465

461

15.12

0.2

100

25.4

384

14.72

374

3.94
100

114

3.94

3.15

100

80

5.41
137.5

199.5

0.71

0.51

6.02
153

R 0.08
2

7.85

18

13

5.91
150

0.12

3.94
100

12.76
324

9.45
2.32

240

6.63
168.5

1.93
49

59

16

16.36

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

00.00

Inches

00.00

[Millimeters]

Po

16
we Em
r b ax
re
ak
e

Approximate dimensions (for UL version)


E1 - E2, withdrawable with vertical rear terminals
4 pole

rs

16.42
417

0.79
20

0.12

1.34

0.51

34

13

9
0.3
10

15.49
393,5

3.54

3.54

90

90

90

8.86
9.45 225

6.85

240

174

14.96
Part. "Z"

3.54

380

0.24
6

2.76
1.93 70
49

12.44

1.77
0.75

8.66

19,05

316

45

6.89

12.05

175

220

306

3.94

3.94

100

100

.20

Y
1.00

3.94

51
0. 3
1

25,4

.2
05

100

18.31 MIN.

13.35

465

15.12

339

18.15

18.31
465
4.49

3.94
100

461

14.72
374

114

3.94

3.15

100

80

R 0.08
2

7.85

5.41

199,5

137,5

384

5.91
Z

0.71

13.70

18

16.30
414

6.63

150

168,5

348

3.94

0.12

100

16

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.37

16

rs
ax ake
m
e
E br
er
ow

Approximate dimensions (for UL version)


E2, fixed with horizontal rear terminals
3 pole

00.00

Inches

00.00

[Millimeters]

12.09
307

1.3

0.71

33

2.36

3.54

3.54

90

90

60

18

1.38
35

0.51
13

0.51
13

9.92
252

9.53

0.39

242

10

Part. "Z"

12.44
316

12.05

9.45

306

240

3.35

3.94

3.94

100

100

0.2
5

85

Y
3.94

339

379

440

5.51
12.28 140

16.46

100

418

312

3.94

6.02

100

7.58

0.65

374

3.94

17.32
14.92

384

14.72

13.35

26

15.12

0.2

100

1.02

153

R 0.08

192.5

4.63 16.5

117.5

5.91

Y
Z
11.65

1.93
1.3
33

6.97
177

49

296

150

6.63
168.5

1.97
50

16

16.38

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

00.00

Inches

00.00

[Millimeters]

Po

16
we Em
r b ax
re
ak
e

Approximate dimensions (for UL version)


E2, fixed with horizontal rear terminals
4 pole

rs

15.63

33

3.54

90

90

90

2.36

1.38

18

1.30

3.54

0
13 .51

397

0.71

3.54

35

60

Part. "Z"

9.92 9.53
252

0.51

242

0
M1

13

12.44

1.77

316

45

12.99

12.05

330

306

3.35 MIN.

3.94

3.94

100

100

0
.20

85

Y
3.94

440

14.92
379

12.28 140 1.02


312

13.35
16.46

5.51

.2
05

100

17.32 MIN.
418

15.12

339

3.94
100

384

X
14.72

26

374

7.58

192,5

3.94

0.65

100

4.63 16,5

117,5

R 0.08
2

Y
Y
1.30

6.97

33

177

1.93 1.97
49

50

15.20
386

5.91
6.63

150

168,5

16

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.39

16

rs
ax ake
m
e
E br
er
ow

Approximate dimensions (for UL version)


E2, withdrawable with horizontal rear terminals
3 pole

00.00

Inches

00.00

[Millimeters]

12.87
327

1.3

0.59

33

15

2.36
60

3.54

3.54

90

90

1.38
35

1.34

0.12

34

0.51
13

0.51
13

5.08
129

15.49

0.24

0.39

393.5

10

14.96
380

5.43
138

Part. "Z"

12.44
316

12.05
306

3.94

3.94

100

100

0.2
5

Y
3.94
26

339
465

18.31

18.15

465

461

384

14.72

13.35

18.31

15.12

0.2

100

1.02

374

3.94
100

5.51
140

3.94

6.02

100

7.85
4.90
124.5

199.5

0.71

153

R 0.08
2

18

5.91
150

Y
Z
2.32
59

12.76
324

9.45
240

6.63
168.5

1.93
49

16

16.40

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

00.00

Inches

00.00

[Millimeters]

Po

16
we Em
r b ax
re
ak
e

Approximate dimensions (for UL version)


E2, withdrawable with horizontal rear terminals
4 pole

rs

16.42
417

0.59

1.30

3.54

15

33

2.36 90

3.54

3.54

90

90

60

0.12

1.34

0.51

34

13

1.38

1
0.5
13

35

N
6.85

174

9
0.3
10

15.49

8.86
9.45 225

393,5

240

14.96
380

Part. "Z"

0.24
6

1.93 2.76
70
49

12.44

1.77
8.66

316

45

6.89

12.05

175

220

306

3.94

3.94

100

100

.20

Y
1.02

3.94

26

.2
05

100

18.31

18.31 MIN.

465

13.35

465

5.51

15.12

339

18.15

3.94
100

461

140

384

X
14.72
374

3.94
100

7.85

0.71
4.90 18

199,5

R 0.08
2

124,5

5.91
Z

13.70

16.30
414

6.63

150

168,5

348

16

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.41

16

rs
ax ake
m
e
E br
er
ow

Approximate dimensions (for UL version)


E3, fixed with horizontal rear terminals
3 pole

00.00

Inches

00.00

[Millimeters]

16.34
415

4.96

4.96

126

126

3.78
96

1.3

1.38

0.71

33

35

18

0.51
13

0.51
13

9.92
252

Part. "Z"

9.53
242

0.39
10

12.44
316

12.05
306

13.70
348

3.94

100

100

0.2

3.35

3.94
5

85

Y
3.94

339

14.92
379

5.51
12.28 140

17.32

3.94

440

100

16.46

374

418

312

3.94

6.02

100

7.58

0.65

384

14.72

13.35

26

15.12

0.2

100

1.02

153

R 0.08

192.5

4.63 16.5

117.5

5.91

Y
Z
15.91

1.93
1.3
33

6.97
177

49

404

150

6.63
168.5

1.97
50

16

16.42

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

00.00

Inches

00.00

[Millimeters]

Po

16
we Em
r b ax
re
ak
e

Approximate dimensions (for UL version)


E3, fixed with horizontal rear terminals
4 pole

rs

21.30
1.30

3.78

33

4.96

4.96

126

126

126

1.38

96

18

4.96

0
13 .51

541

0.71

35

9.92 9.53
252
242

Part. "Z"

0
M1

0.51
13

2.48
63

12.44
316

18.66
474

12.05
306

3.35 MIN.

3.94

3.94

100

100

0
.20
5

85

Y
3.94

440

14.92
379

12.28 140 1.02


312

13.35
16.46

5.51

.2
05

100

17.32 MIN.
418

15.12

339

3.94
100

384

X
14.72

26

374

7.58

192,5

3.94

0.65

100

4.63 16,5

117,5

R 0.08
2

Y
Y
1.30

6.97

33

177

1.93 1.97
49

50

20.87
530

5.91
6.63

150

168,5

16

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.43

16

rs
ax ake
m
e
E br
er
ow

Approximate dimensions (for UL version)


E3, withdrawable with horizontal rear terminals
3 pole

00.00

Inches

00.00

[Millimeters]

17.13
435

1.3

0.59

33

4.96

126

126

1.38

3.78

35

96

0.51

0.51

1.34

0.12

15

4.96

13

13

34

14.41
366

0.24

15.49

0.39

393.5

10

14.96
380

Part. "Z"

9.45
240

12.44
316

12.05
306

3.94

3.94

100

100

0.2
5

Y
3.94
26

339

18.31

465

18.31

465

384

14.72

13.35

18.31

15.12

0.2

100

1.02

374

3.94
100

465

5.51
140

3.94

6.02

100

7.85
4.90
124.5

153

R 0.08

199.5

0.71

18

5.91
150

Y
Z
2.32
59

9.45
240

1.93

17.01
432

6.63
168.5

49

16

16.44

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

00.00

Inches

00.00

[Millimeters]

Po

16
we Em
r b ax
re
ak
e

Approximate dimensions (for UL version)


E3, withdrawable with horizontal rear terminals
4 pole

rs

22.09
561

0.59

4.96

15

1.30
33

4.96

126

3.78

1.34

0.51

34

13

.39
0 10

15.49
393,5

1.38

35

51
0. 13

35

9.69

2.48

246

63

12.80

8.86

325

14.96
380
Part. "Z"

126

1.38

96

0.12

4.96

126

225

14.57

9.45

370

240

0.24
6

2.76
70

12.44
316

1.93

12.05

49

306

3.94

3.94

100

100

.20

Y
3.94

1.02
26

.2
05

100

18.31 MIN.

13.35

465

15.12

339

18.15

18.31
465

5.51

3.94
100

14.72

461

374

140

3.94
100

R 0.08
2

7.85

199,5

4.90

384

124,5

5.91
6.63

0.71
18

13.70
348

21.97

150

168,5

558

16

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.45

16

rs
ax ake
m
e
E br
er
ow

Approximate dimensions (for UL version)


E3 (2500A), withdrawable with vertical rear terminals
00.00
3 pole

Inches

00.00

[Millimeters]

17.13
0.24
6

1.34

0.12

34

435

4.96

4.96
126

126

0.25
6.35

0.51
13

14.41
366

0.24

15.49

0.39

393.5

10

14.96

Part. "Z"

380

9.45
240

12.44
316

12.05

1.00

306

25.4

0.2

3.94

3.94

100

100

1.75

3.94

44.45

100

3.94
339

18.31

18.31
465

7.24
184

1.75

18.15

465

461

15.12

0.2

100

13.35

384

14.72
374

3.94
100

44.45

3.94
100

6.02
153

R 0.08
2

7.85
199.5

4.04
102.5

0.71
18

5.91

0.51
13

9.45
2.32

240

1.93

Y
17.01
432

150

6.63
168.5

49

59

7.87
200

0.12
3

16

16.46

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

00.00

Inches

00.00

[Millimeters]

Approximate dimensions (for UL version)


E3 (2500A), withdrawable with vertical rear terminals
4 pole

Po

16
we Em
r b ax
re
ak
e

rs

22.09
561

0.24

4.96

4.96

4.96

126

126

126

0.12

1.34

0.51

34

13

.39
0 10

15.49

9.69

2.48

246

63

12.80

8.86

325

393,5

225

14.57
14.96

Part. "Z"

6,35

9.45

370

240

380

0.24

0.25

2.76
70

12.44
316

1.93
1.00

1.75

25,4

44,45

306

3.94

44,45

100

.
13 51

465

3.94

100

0
.20
5

1.75

18.31

12.05

49

3.94
18.31MIN.

13.35

465

15.12

339

18.15
7.24

3.94
100

374
100

R 0.08
2

7.85

199,5

4.04

384

X
14.72

3.94
100

461

184

3.94

.2
05

100

102,5

5.91
6.63

0.71

13.70

18

348

7.87

0.12

200

21.97

150

168,5

558

16

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.47

16

rs
ax ake
m
e
E br
er
ow

Approximate dimensions (for UL version)


E3 (1200A/1600A/2000A), withdrawable with
Vertical rear terminals, 3 pole

00.00

Inches

00.00

[Millimeters]

17.13
435

4.96

4.96

126

126

0.25

0.24
6

6.35

1.34

0.12

34

0.51
13

14.41
366

0.24

15.49

0.39

393.5

10

14.96
380

Part. "Z"

9.45
240

12.44
316

12.05
306

0.2

3.94

3.94

100

100

1.00
25.4

3.94
3.94
465

339

100

18.31

18.31
X

5.28

18.15

465

461

15.12

0.2

100

13.35

384

14.72
374

3.94
100

134

3.94
100

5.02
127.5

199.5

1.75
44.45

6.02

5.91
150

Y
13

0.71
18

0.51

153

R 0.08
2

7.85

0.12

3.94
100

9.45
2.32

240

1.93

17.01
432

6.63
168.5

49

59

16

16.48

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

00.00

Inches

00.00

[Millimeters]

Po

16
we Em
r b ax
re
ak
e

Approximate dimensions (for UL version)


E3 (1200A/1600A/2000A), withdrawable with
Vertical rear terminals, 4 pole

rs

22.09
561

4.96

4.96

4.96

126

126

126

0.25
6,4

0.24
6

0.12

1.34

0.51

34

13

.39
0 10

15.49

2.48

246

63

12.80

8.86

325

393,5

14.96
380

Part. "Z"

9.69

225

14.57

9.45

370

240

0.24
6

2.76
70

12.44
316

1.93

12.05

49

1.00

306

25,4

3.94

3.94

100

100

.20

465

3.94

13

44,5

0.5
1

1.75
18.31

.2
05

100

18.31 MIN.
465

13.35

15.12

339

18.15

5.28

3.94
100

14.72

461

374

134

3.94
100

3.94
100

R 0.08
2

7.85

199,5

5.02

384

127,5

5.91
6.63

0.71

13.70

18

348

3.94

0.12

100

21.97

150

168,5

558

16

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.49

16

rs
ax ake
m
e
E br
er
ow

Approximate dimensions (for UL version)


E4, fixed with horizontal rear terminals
3 pole

00.00

Inches

00.00

[Millimeters]

12.44
316

12.05
306

3.94

3.94

100

100

0.2

22.72
577

7.09

7.09

180

180

Y
3.94

18

66

384

0.71

2.60

15.12

0.2

100

5.91

1.38

150

35

14.72

13.35

339

0.51
13

374

3.94
100

3.94

6.02

100

153

R 0.08
2

9.92
252

9.53
242

0.39
10

5.91
150

6.63
168.5

1.77
3.35
85

510

17.32

1.02

440

26

14.92
379

45

20.08

5.51

16.46

12.28 140
1.3
312

418

33

7.58

0.51

192.5

0.65
4.63 16.5

13

117.5

Part. "Z"

Z
1.93
1.3
33

6.97
177

49

1.97
50

Y
22.28
566

16

16.50

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

00.00

Inches

00.00

[Millimeters]

Po

16
we Em
r b ax
re
ak
e

Approximate dimensions (for UL version)


E4, fixed with horizontal rear terminals
4 pole

rs

26.26
667

5.31
2.60

1.30

66

0.71
18

33

2.36

7.09

135

35

1.38

1.38

35

35

60

1.38

7.09

180

180

1.38
35

0.71

5.91

18

150

1
0.53
1

9.92
252

Part. "Z"

9.53

0.51

M1

242

13

1.77
45

12.44
316

23.62
600

12.05
306

3.35 MIN.
85

3.94

3.94

100

100

0
.20

Y
3.94

440

14.92

.2
05

100

17.32 MIN.
13.35

379

15.12

339

1.02
26 1.30
33
12.28 5.51
140

3.94
16.46

100

418

312

14.72
374

7.58

192,5

4.63

117,5

384

3.94
100

0.65
16,5

R 0.08
2

Y
Y
1.30

6.97

33

177

1.93 1.97
49

50

25.83
656

5.91
6.63

150

168,5

16

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.51

16

rs
ax ake
m
e
E br
er
ow

Approximate dimensions (for UL version)


E4, withdrawable with horizontal rear terminals
3 pole

00.00

Inches

00.00

[Millimeters]

23.5
597

7.09
1.3

180

0.59

33

15

7.09
180

1.38

5.91

35

150

0.12

1.34
34

0.51
13

0.51
13

20.79
528

15.49

0.24

0.39

393.5

10

14.96

15.75

380

400

Part. "Z"

12.44
316

12.05
306

1.77
45

0.2

3.94

3.94

100

100

Y
3.94
26

13.35
339

18.31
465

18.31 18.15
465

15.12

0.2

100

1.02

384

14.72
374

3.94
100

461

5.51
140

3.94
100

6.02

199.5

4.90 0.71
18

153

R 0.08
2

7.85

124.5

5.91
Z
2.32
59

9.45
240

1.93

Y
23.39
594

150

6.63
168.5

49

16

16.52

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

00.00

Inches

00.00

[Millimeters]

5.31
0.59
15

1.30
33

0.12

Po

16
we Em
r b ax
re
ak
e

Approximate dimensions (for UL version)


E4, withdrawable with horizontal rear terminals
4 pole

1.34

0.51

34

13

2.36
60

135

5.91
150

27.05
687
7.09
180
1.38 1.38
35

35

7.09
180

1.38
35

rs

51
0. 13

1.77
45

0.39

10

15.49

19.29
490

393,5

14.96
380

24.33

9.45

618

240

0.24

Part. "Z"

12.44
316

1.93

12.05

49

306

3.94

3.94

100

100

0
.20
5

Y
3.94

1.02
26

.2
05

100

18.31 MIN.
465

13.35

15.12

339

100

18.15

18.31
465

3.94

5.51

461

14.72
374

140

3.94
100

R 0.08
2

7.85

199,5

4.90

384

124,5

5.91
Z

0.71
18

13.70
348

6.63

150

168,5

26.93
684

16

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.53

16

rs
ax ake
m
e
E br
er
ow

Approximate dimensions (for UL version)


E4, withdrawable with vertical rear terminals
3 pole

00.00

Inches

00.00

[Millimeters]

23.5
597

7.09

7.09

180

180

0.24

3.54

90

0.25
6.35

12.44
316

12.05
306

0.2

3.94

3.94

100

100

Y
3.94

13.35
339

15.12

0.2

100

384

14.72
374

3.94

20.79

100

528

3.94

15.49

6.02

100

393.5

153

R 0.08
2

0.39
10

14.96

15.75

380

400

5.91
150

6.63
168.5

1.00

1.77

25.4

45

1.75
3.94

44.45

100

0.12

1.34
34

0.51
13

18.31

18.31

465

7.24
184

1.75

465

18.15
461

44.45

0.24
6

7.85
199.5

Part. "Z"

4.04
102.5

0.71
18

0.51

23.39

594

13

9.45
2.32

240

1.93
49

59

7.87
200

16

16.54

0.12
3

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

00.00

Inches

00.00

[Millimeters]

Po

16
we Em
r b ax
re
ak
e

Approximate dimensions (for UL version)


E4, withdrawable with vertical rear terminals
4 pole

rs

27.05
687

5.31

7.09

7.09

135

180

180

3.54
90

0.25

0.24

6,35

0.79
20

0.12

1.34

0.51

34

13

1.77
45

9
0.3
10

15.49
14.96
380
Part. "Z"

19.29
490

393,5

24.33

9.45

618

240

0.24
6

12.44
316

1.93
49

1.00

1.75

25,4

44,45

12.05
306

3.94

Y
1.75
44,45

100

0.

51

13

18.31

3.94

100

0
.20
5

3.94

465

18.31MIN.
465

7.24

13.35

15.12

339

3.94
100

18.15

374
100

R 0.08
2

7.85

100

384

X
14.72

3.94
3.94

461

184

199,5

4.04

.2
05

100

102,5

5.91
Z

0.71

13.70

18

348

7.87

0.12

200

6.63

150

168,5

26.93
684

16

0.75
1.00

25,4

0.5
13 1

19,1

4.49
114

3.15
80

5.41
137,5

3.94
100

0.12
3

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.55

16

rs
ax ake
m
e
E br
er
ow

Approximate dimensions (for UL version)


E6, fixed with horizontal rear terminals
3 pole

00.00

Inches

00.00

[Millimeters]

12.44
316

31.22
12.05
306

3.94

3.94

100

100

0.2

9.92

0.51

252

13

18

66

252

56

1.38

35

35

0.51
13

15.12

0.2

100

8.74

9.92

222

Part. "Z"

3.94

1.38

0.71

2.60

793

2.20

384

14.72

13.35

339

374

3.94
100

9.92
252

3.94

9.53
242

6.02

100

0.39

153

R 0.08
2

10

5.91

2.48

150

63

28.58

6.63

726

168.5

30.79

782

3.35
85

17.32

1.02
379

440

26

14.92

5.51
12.28 140
1.3
312

16.46
418

33

7.58
192.5

0.65
4.63 16.5

117.5

1.93
1.3
33

6.97
177

49

1.97
50

16

16.56

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Inches

00.00

[Millimeters]

16
we Em
r b ax
re
ak
e

3.78
96
1.30 0.71 1.38
33
18 35

2.60
66

7.44
189
1.38
35

9.92
252
8.74
222

1.38
35

36.18
919

rs

9.92
252

1.38
35

1.38
35

2.20
56

1.38
35
0.71
18

0
.51
13

00.00

Po

Approximate dimensions (for UL version)


E6, fixed with horizontal rear terminals
4 pole

9.92
252
Part. "Z"

0.51
13

9.53
242

0
M1

2.48
63
33.54
852

12.44
316
12.05
306

35.75
908

3.35 MIN.
85

3.94
100

3.94
100

.20

Y
14.92
379

3.94
100

17.32 MIN.
440
1.02
26 1.30
33

12.28 5.51
140
312

4.63
117,5

16.46
418

.2
05

13.35
339
3.94
100

15.12
384
14.72
374

7.58
192,5

3.94
100

0.65
16,5

R 0.08
2

Y
Y
1.30
33

6.97
177

1.93 1.97
49 50

6.63
168,5

5.91
150

16

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.57

16

rs
ax ake
m
e
E br
er
ow

Approximate dimensions (for UL version)


E6, withdrawable with horizontal rear terminals
3 pole

Inches

00.00

[Millimeters]

0.51

1.34
0.12

00.00

13

34

0.24
6

Part. "Z"
32.01

12.44

813

316

9.92

12.05
306

0.2

3.94

3.94

100

100

1.3

0.59
15

Y
100
339

1.38

35

35

8.74
222

0.51
13

56

15.12

0.2

13.35

252

2.20

1.38
33

3.94

9.92

252

384

14.72
374

29.29

3.94

744

100

15.49

0.39

393.5

3.94

6.02

100

10

24.41

14.96

153

R 0.08

620

380

5.91
150

6.63
168.5

2.48

63

1.02

18.15

26

461

18.31

18.31

465

465

5.51
140

7.85
4.90
124.5

199.5

0.71
18

16

Y
Z
2.32
59

16.58

9.45
240

1.93

31.89
810

49

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

00.00

Inches

00.00

[Millimeters]

Po

16
we Em
r b ax
re
ak
e

Approximate dimensions (for UL version)


E6, withdrawable with horizontal rear terminals
4 pole

rs

36.97
939

9.92

189

15

1.30
33

8.74

96

222

0.12

0.51

34

13

35

1.38
35

2.20

1.38

1.38
35

1.34

252

1.38

56

35

1.38
35

3.78

0.59

9.92

252

.
13 51

7.44

1.38
35

2.48
63

9
0.3

15.49
393,5

10
14.96
380

Part. "Z"

29.13
740

34.25
870

0.24
6

12.44
316

12.05
306
3.94
3.94

0
.2
5

100

100

0
Y

1.02

18.31

3.94

26

465

18.31MIN.

13.35

465

5.51

339

3.94

15.12
X

14.72

461

374

140

3.94
100

R 0.08
2

7.85

199,5

4.90

384

100

18.15

.2
05

100

124.5

5.91
Z

0.71
18

2.32
59

9.45
240

1.93
49

6.63

150

168,5

36.85
936

16

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.59

16

rs
ax ake
m
e
E br
er
ow

Approximate dimensions (for UL version)


E6, withdrawable with vertical rear terminals
3 pole

00.00

Inches

00.00

[Millimeters]

32.01
813

9.92

9.92

252

1.34

12.44

0.12

316

34

252

0.25

0.51

0.24

4.96

126

6.35

13

12.05
306

0.2

3.94

3.94

100

100

0.24
6

Y
3.94
13.35
339

15.12

0.2

100

Part. "Z"

384

14.72
374

3.94

29.29

100

744

15.49

3.94
100

393.5

6.02
153

R 0.08
2

0.39
10

14.96

24.41

380

620

5.91
150

6.63
168.5

2.48

1.00

63

25.4

1.75
3.94

44.45

100

18.31

18.31

465

7.24
184

1.75

465

18.15
461

44.45

7.85
199.5

4.04
102.5

0.71
18

0.51

0.12

13

9.45
2.32

240

31.89
810

1.93
49

59

7.87
200

16

16.60

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

00.00

Inches

00.00

[Millimeters]

Po

16
we Em
r b ax
re
ak
e

Approximate dimensions (for UL version)


E6, withdrawable with vertical rear terminals
4 pole

rs

36.97
7.44

9.92

189

0.24
6

1.34

0.51

34

13

393,5

Part. "Z"

4.96
126

63

29.13
740

34.25

9.45

870

14.96

0.24

2.48

.39
0 10

15.49

252

0.24

6,35

9.92

0.25

0.25
6,4

0.12

939

252

240

380

12.44
316

1.00
25,4

100

3.94
100

13 .51

3.94

0
.2
5 0

1.75

18.31

306

49

44,45

44,45

12.05

1.93

1.75

3.94

465

18.31MIN.

13.35

465

7.24

339

3.94
100

18.15

100

14.72
R 0.08
2

7.85

100

384

X
374

3.94
3.94

15.12
X

461

184

199,5

4.04

.2
05

100

102,5

5.91
Z

0.71

13.70
348

18

7.87
200

0.12

6.63

150

168,5

36.85
936

16

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.61

16

rs
ax ake
m
e
E br
er
ow

Approximate dimensions (for UL version)


E1 - E6, fixed with vertical rear terminals
3 pole

E1

4.11
1.97 0.75
50

6.54

104.5

166

3.15

19.05

1.00

80

3.54

3.54

90

90

00.00

Inches

00.00

[Millimeters]

0.79

25.4

20

0.51
13

1.89
48

4.11

E2

1.97 0.75
50

6.54

104.5

166

3.15

19.05

1.00

80

3.54

3.54

90

90

0.79

25.4

20

0.51
13

1.89
48

E3 (1200A - 2000A)

1.97 0.75
50

19.05

4.11

6.54

104.5

166

1.75

3.94

0.25

44.45

100

4.96

4.96

126

126

0.24
6

6.35

0.51
"
13

1.89
48

E3 (2500A)

1.00

4.11

6.54

104.5

166

25.4

3.94

1.75

100

4.96

4.96

126

126

0.24

0.25

44.45

6.35

5.71
145

1.75

0.51
"

44.45

13

1.89
48

16
E4

1.00

4.11

6.54

104.5

166

25.4

3.94

1.75

100

44.45

3.54

0.24

90

7.09

7.09

180

180

0.25
6.35

5.71
145

1.75

0.51
"

44.45

13

1.89
48

E6

1.00
25.4

4.11

6.54

104.5

166

3.94
100

1.75
44.45

9.92

9.92

252

252

4.96

0.25

0.24

126

6.35

5.71
145

1.75
44.45

0.51
"
13

1.89
48

16.62

Low Voltage Products & Systems

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

0.79
20

3.54
90

90

3.54

25.4

80

3.15

1.00

3.54
90

166

6.54

4.11

0.
51
50

1.97

48

1.89

0.79
20

3.54
90

90

3.54

3.54

25.4

80

3.15

1.00

90

166

6.54

4.11

104.5

0.75

19.05
50

1.97

48

1.89

0.25
6.35

0.24

4.96

0.25
6.35

1.75

100

44.45

4.11

1.00
25.4

104.5

3.94

6.54
166

4.96
126

126

126

126

126

126

4.96

48

1.89

4.96

13

4.96

44.45

1.75

0.24

4.96

166

6.54

100

3.94
4.11

104.5

0.75

19.05
50

1.97

145

1.75

44.45

5.71

48

1.89

180

5.31

90

6.35

0.24

1.75

44.45

0.25

3.54

7.09

16
135

166

3.94
6.54 100

4.11

104.5

1.00
25.4

166

1.75
44.45

5.71
145

0.79
20

E4

25.4

0.75

19.05

3.15
6.54 80 1.00

4.11

104.5

50

1.97

48

1.89

48

1.89

0.24

6.35

0.25

252

9.92

126

4.96

189 0.25
6.35

7.44

1.75

100

3.94

44.45

0.24

166

6.54

4.11

104.5

1.00

25.4

0.
51

44.45

5.71

E6

145

13

1.75

0.
51

13 1

E2

E6

13

0
.5

51
13

E3 2500A

E4

0.

0.
51

E3 1200...2000A

E3 (2500A)

13

E2

E3 (1200A - 2000A)

0.
51

rs

[Millimeters]

13

E1

E2

16
Inches
00.00

we Em
r b ax
re
ak
e

00.00

104.5

0.75

19.05

E1

Po

Approximate dimensions (for UL version)


E1 - E6, fixed with vertical rear terminals
4 pole

48

1.89

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

16.63

Low Voltage Products & Systems

You might also like