You are on page 1of 14

SIRCOVER and

SIRCOVER by-pass
125 to 3150 A

Changeover switches

Functions
References
Accessories
Characteristics
Dimensions

Functions

svr_107_a_1_cat

SIRCOVER 3 pole

SIRCOVER products are manually


operated multipolar changeover switches.
They ensure switching, transfer of sources
or transfer of two low voltage circuits on
load as well as their safety disconnection.
SIRCOVER By-Pass are manually
operated changeover switches.
They are a combination of three
interlocked switches enabling the use with
3 + 6 pole or 4 + 8 pole.
They insulate by providing simultaneous
safety isolation top and bottom and by
passing loads or low voltage circuits
mainly during maintenance operations.

Conformity to standards
IEC 60947-3
EN 60947-3
VDE 0660 Part 107 (1992)
NBN EN 60947-3
BS EN 60947-3

SIRCOVER by-pass 4 pole

Approvals
and certifications(1)
Bureau Vritas
BBJ Poland (attestation of verification)
(1) In progress for certain ratings.

svr_125_a_1_cat

General characteristics
3 stable positions (I, 0, II) or overlapping
contacts on request (I, I + II, II) , and on
load changeover switching (AC-22 and
AC-23)
Fully visible breaking
IP20 device and accessories.

Available on request
Devices 6 or 8 pole
Devices with overlapping (make before
break) contacts (I, I+II, I)
Devices with over-sized neutral e.g.:
3 x 250 A + N 400 A
Devices with advanced neutral.

A. 112

This document is not a contract. SOCOMEC reserves the right to modify features
without prior notice in view of continued improvement. 2006-2007

SOCOMEC general catalogue

Changeover switches

SIRCOVER and
SIRCOVER by-pass

Illustrations
SIRCOVER 125 to 3 150 A

Overview (for further details, please see the


installation instructions supplied with each
device).
1. Direct front operation.
5

2. External front operation.


3 et 4. Auxiliary contacts.
1

5. Bridging bar.

svr_103_a_1_x_cat

6. Terminal shrouds.
7. Inter phase barrier.

Typical application
SIRCOVER by-pass 125 to 1 600 A
O

atys_570_a_1_x_cat

I
Charge
I

Charge

II
I

I+II

I+II
II

II

Charge

II
I

I
II

II

II
I

II

II
I

SIRCOVER by-pass (I,0,II)

SIRCOVER by-pass with overlapping contacts (on request)

Break before make application.

Make before break application.

SOCOMEC general catalogue

II

I
II

I+II

O
I II II

O
I O II

II

atys_571_a_1_x_cat

I I

This document is not a contract. SOCOMEC reserves the right to modify features
without prior notice in view of continued improvement. 2006-2007

II
I

A. 113

Changeover switches
Functions
References
Accessories
Characteristics
Dimensions

SIRCOVER and
SIRCOVER by-pass
125 to 3150 A
svr_112_a_1_cat

References

160 A

200 A

250 A

400 A

Front operation changeover switch (switch body only) - SIRCOVER


References
No. of poles
Changeover operation type
3 pole
I - 0 - II
4100 3013
4 pole
I - 0 - II
4100 4013
3 pole
I - I+II - II
4190 3013
4 pole
I - I+II - II
4190 4013

125 A

References
4100 3016
4100 4016
4190 3016
4190 4016

References
4100 3019
4100 4019
4190 3019
4190 4019

References
4100 3025
4100 4025
4190 3025
4190 4025

References
4100 3039
4100 4039
4190 3039
4190 4039

Front operation changeover switch (switch body only) - SIRCOVER by-pass


3 + 6 pole
I - 0 - II
4100 7013
4 + 8 pole
I - 0 - II
4100 9013

4100 7016
4100 9016

4100 7019
4100 9019

4100 7025
4100 9025

4100 7039
4100 9039

4199 5012
4199 5012

4199 5012
4199 5012

4199 5012
4199 5012

4199 5012
2799 7052

4199 5012
2799 7052

1421 2113
1423 2113
1423 2114
1421 2113
1423 2113

1421 2113
1423 2113
1423 2114
1421 2113
1423 2113

1421 2113
1423 2113
1423 2114
1421 2113
1423 2113

1421 2113
1423 2113
1423 2114
1433 3113

1421 2113
1423 2113
1423 2114
1433 3113

Shaft extension for external operation (for dimensions see Accessories pages)
200 mm
SIRCOVER
1400 1020
1400 1020
320 mm
SIRCOVER
1400 1032
1400 1032
200 mm
SIRCOVER by-pass
1400 1020
1400 1020
320 mm
SIRCOVER by-pass
1400 1032
1400 1032

1400 1020
1400 1032
1400 1020
1400 1032

1400 1020
1400 1032
1401 1520
1401 1532

1400 1020
1400 1032
1401 1520
1401 1532

Bridging bars
1 pole

4109 0019

4109 0019

4109 0019

4109 0025

4109 0039

Auxiliary contacts (1 per position)


1st / 2nd AC
NO/NC

4109 0021

4109 0021

4109 0021

4109 0021

4109 0021

Terminal shrouds (1 set) (1)(2)


3 pole
top / bottom / front(I) / rear (II)
4 pole
top / bottom / front(I) / rear (II)

2694 3014
2694 4014

2694 3014
2694 4014

2694 3014
2694 4014

2694 3021
2694 4021

2694 3021
2694 4021

Terminal screens (1 per position)


top / bottom
3 pole
top / bottom
4 pole

1509 3012
1509 4012

1509 3012
1509 4012

1509 3012
1509 4012

1509 3025
1509 4025

1509 3025
1509 4025

Handle key interlocking accessories - For direct front operation


Locking using RONIS EL11AP lock in position O(3)(4)
4109 1006
Locking using RONIS EL11AP lock in position I, O, II(3)(4)
4109 1002

4109 1006
4109 1002

4109 1006
4109 1002

4109 1006
4109 1002

4109 1006
4109 1002

Handle key interlocking accessories - For external front operation


Locking using RONIS EL11AP lock in position O(4)
1499 7701
Locking using CASTELL type K lock in position O(4)
1499 7702

1499 7701
1499 7702

1499 7701
1499 7702

1499 7701
1499 7702

1499 7701
1499 7702

Switches

Accessories
Direct operation handle
Black
SIRCOVER
Black
SIRCOVER by-pass
External operation handle
I - 0 - II
SIRCOVER
I - 0 - II
SIRCOVER
I - I+II - II
SIRCOVER
I - 0 - II
SIRCOVER by-pass
I - 0 - II
SIRCOVER by-pass

IP55
IP65
IP65
IP55
IP65

(1) To shroud front switch top and bottom 2 references required for SIRCOVER and 3 references required for SIRCOVER by-pass.
(2) To fully shroud front and rear / top and bottom 4 references required for SIRCOVER and 6 references required for SIRCOVER by-pass.
(3) Specific handle included.
(4) Lock not included.

A. 114

This document is not a contract. SOCOMEC reserves the right to modify features
without prior notice in view of continued improvement. 2006-2007

SOCOMEC general catalogue

T O

SIRCOVER and
SIRCOVER by-pass

EXTERNAL OPERATION
FT
HA

NEW
H

NEW
S

picto_080_b_1_gb

Changeover switches

O R D E R

DIRECT OPERATION

DLE
AN

New handle

New shaft
Switch
body

Direct
handle

Switch
body

Shaft

External
handle

OTHER ACCESSORIES

svr_113_a_1_cat

References

Switches

630 A

800 A

1250 A

1600 A

Front operation changeover switch (switch body only) - SIRCOVER


No. of poles
Changeover operation type
References
3 pole
I - 0 - II
4100 3050
4100 4050
4 pole
I - 0 - II
3 pole
I - I+II - II
4190 3050
4 pole
I - I+II - II
4190 4050

500 A

References
4100 3063
4100 4063
4190 3063
4190 4063

References
4100 3080
4100 4080
4190 3080
4190 4080

References
4100 3120
4100 4120
4190 3120
4190 4120

References
4100 3160
4100 4160
4190 3160
4190 4160

Front operation changeover switch (switch body only) - SIRCOVER by-pass


3 + 6 pole
I - 0 - II
4100 7050
4 + 8 pole
I - 0 - II
4100 9050

4100 7063
4100 9063

4100 7080
4100 9080

4100 7120
4100 9120

4100 7160
4100 9160

4199 5012
2799 7052

4199 5012
2799 7052

2799 7052
2799 7012

2799 7052
2799 7012

2799 7052
2799 7012

1421 2113
1423 2113
1423 2114
1433 3113

1421 2113
1423 2113
1423 2114
1433 3113

1433 3113
1433 3114
4199 7146

1433 3113
1433 3114
4199 7146

1433 3113
1433 3114
4199 7146

Shaft extension for external operation (for dimensions see Accessories pages)
200 mm
SIRCOVER
1400 1020
1400 1020
320 mm
SIRCOVER
1400 1032
1400 1032
200 mm
SIRCOVER by-pass
1401 1520
1401 1520
320 mm
SIRCOVER by-pass
1401 1532
1401 1532
450 mm
SIRCOVER by-pass
-

1401 1520
1401 1532
2799 3015
2799 3019

1401 1520
1401 1532
2799 3015
2799 3019

1401 1520
1401 1532
2799 3015
2799 3019

Bridging bars
1 pole

Accessories
Direct operation handle
Black
SIRCOVER
Black
SIRCOVER by-pass
External operation handle
I - 0 - II
SIRCOVER
I - 0 - II
SIRCOVER
I - I+II - II
SIRCOVER
I - 0 - II
SIRCOVER by-pass

IP55
IP65
IP65
IP65

4109 0050

4109 0063

4109 0080

4109 0120

4109 0160

4109
3/4 0021
poles

4109 0021

4109 0021

4109 0021

4109 0021

Terminal shrouds (1 set)


3 pole
top / bottom / front (I) / rear (II)
4 pole
top / bottom / front (I) / rear (II)

2694 3051
2694 4051

2694 3051
2694 4051

Terminal screens (1 per position)


3 pole
top / bottom
4 pole
top / bottom

1509 3063
1509 4063

1509 3063
1509 4063

1509 3080
1509 4080

1509 3080
1509 4080

1509 3160
1509 4160

Handle key interlocking accessories - For direct front operation


Locking using RONIS EL11AP lock in position O(3)(4)
4109 1006
Locking using RONIS EL11AP lock in position I, O, II(3)(4)
4109 1002
Locking in the 0 position with a 230 VAC undervoltage coil system
consult us

4109 1006
4109 1002
consult us

4109 1004(5)
4109 1004(5)
consult us

4109 1004(5)
4109 1004(5)
consult us

4109 1004(5)
4109 1004(5)
consult us

Handle key interlocking accessories - For external front operation


Locking using RONIS EL11AP lock in position O(4)
1499 7701
Locking using CASTELL type K lock in position O(4)
1499 7702

1499 7701
1499 7702

1499 7701
1499 7702

1499 7701
1499 7702

1499 7701
1499 7702

Auxiliary contacts (1 per position)


1st / 2nd AC NO/NC
(1)(2)

(1) To shroud front switch top and bottom 2 references required for SIRCOVER and 3 references required for SIRCOVER by-pass.
(2) To fully shroud front and rear / top and bottom 4 references required for SIRCOVER and 6 references required for SIRCOVER by-pass.
(3) Specific handle included.
(4) Lock not included.
(5) This locking facility can be configured by the user in the 3 positions.

SOCOMEC general catalogue

This document is not a contract. SOCOMEC reserves the right to modify features
without prior notice in view of continued improvement. 2006-2007

A. 115

Changeover switches

LL

SIRCOVER and
SIRCOVER by-pass

Functions
References
Accessories
Characteristics
Dimensions

125 to 3150 A

svr_053_a_1_cat

svr_113_a_2_cat

References

1800 A

2000 A

2500 A

3150 A

References
4100 3180
4100 4180
4190 3180
4190 4180

References
4200 3200
4200 4200
-

References
4200 3250
4200 4250
-

References
4200 3310
4200 4310
-

2799 7052

2799 7012

2799 7012

2799 7012

1433 3113
1433 3114

2799 7146
-

2799 7146
-

2799 7146
-

Shaft extension for external operation (for dimensions see Accessories pages)
200 mm
SIRCOVER
1401 1520
320 mm
SIRCOVER
1401 1532

2799 3018

2799 3018

2799 3018

Bridging bars
1 pole

4109 0160

consult us

consult us

consult us

4109 0021
4109 0021

4409 0021
4409 0022

4409 0021
4409 0022

4409 0021
4409 0022

Terminal screens (1 per position)


3 pole
4 pole

1509 3160
1509 4160

standard
standard

standard
standard

standard
standard

Handle key interlocking accessories - For direct front operation


Locking using RONIS EL11AP lock in position O (1)
Locking using RONIS EL11AP lock in position I, O, II (1)
Locking in the 0 position with a 230 VAC undervoltage coil system.

4109 1004(2)
4109 1004(2)
consult us

4409 2007
4409 2003
4409 9161

4409 2007
4409 2003
4409 9161

4409 2007
4409 2003
4409 9161

Handle key interlocking accessories - For external front operation


Locking using RONIS EL11AP lock in position O (1)
Locking using CASTELL type K lock in position O (1)

1499 7701
1499 7702

2799 7002(2)
2799 7003

2799 7002(2)
2799 7003

2799 7002(2)
2799 7003

Switches
Front operation changeover switch (switch body only) - SIRCOVER
No. of poles
Changeover operation type
3 pole
I - 0 - II
4 pole
I - 0 - II
3 pole
I - I+II - II
4 pole
I - I+II - II

Accessories
Direct operation handle
Black
SIRCOVER
External operation handle
I - 0 - II
SIRCOVER
I - I+II - II
SIRCOVER

Auxiliary contacts (1 per position)


1st AC
2nd AC

IP65
IP65

NO/NC
NO/NC

(1) Lock not included.


(2) This locking facility can be configured by the user in the 3 positions.

A. 116

This document is not a contract. SOCOMEC reserves the right to modify features
without prior notice in view of continued improvement. 2006-2007

SOCOMEC general catalogue

T O

SIRCOVER and
SIRCOVER by-pass

EXTERNAL OPERATION
FT
HA

NEW
H

NEW
S

picto_080_b_1_gb

Changeover switches

O R D E R

DIRECT OPERATION

DLE
AN

New handle

New shaft
Switch
body

Direct
handle

Switch
body

Shaft

External
handle

OTHER ACCESSORIES

Accessories
Direct operation handles

acces_153_a_1_cat

acces_129_a_1_cat

References
SIRCOVER
Rating (A)
125 630
800 1800
2000 3150

Handle colour
Black
Black
Black

Handle type
Single lever
Single lever
Double lever

References
4199 5012
2799 7052
2799 7012

SIRCOVER by-pass
Rating (A)
125 200
250 630
800 1600

Handle colour
Black
Black
Black

Handle type
Single lever
Single lever
Double lever

References
4199 5012
2799 7052
2799 7012

Handle type
S2
S2
S2
S3
S3

References
1421 2113
1423 2113
1423 2114
1433 3113
1433 3114
2799 7146(1)

Handle type
S2
S2
S3

References
1421 2113
1423 2113
1433 3113
4199 7146

Pack qty
10

Reference
1493 0000

Pack qty
50
50

References
1401 0001
1401 0011

Use
The door interlocked external
operation includes one lockable
handle, one escutcheon and
must be associated with a shaft
extension.

acces_151_a_1_cat

acces_150_a_1_cat

External operation handles


References
SIRCOVER

Rating (A)
125 630
125 630
125 630
800 1800
800 1800
2000 3150

Changeover
operation External
type
IP(1)
I - 0 - II
I - 0 - II
I - I+II - II
I - 0 - II
I - I+II - II
I - 0 - II

IP55
IP65
IP65
IP65
IP65
IP65

(1) Double lever handle.

SIRCOVER by-pass

Rating (A)
125 200
125 200
250 630
800 1600

Changeover
operation External
type
IP
I - 0 - II
I - 0 - II
I - 0 - II
I - 0 - II

IP55
IP65
IP65
IP65

acces_187_a_2_cat

S type handle adapter


Use
Enables new S type handles
to be mounted using old fixing
holes for replacement or retrofit
applications.
Dimensions
Adds 12 mm to the depth.

Reference
Handle colour
Black

External IP
IP65

acces_198_a_2_cat

Alternative S type handle cover colours

SOCOMEC general catalogue

Use
For single lever handles type S1,
S2 and S3.
Others colours: please consult us.

References
Handle colour
Light grey
Dark grey

This document is not a contract. SOCOMEC reserves the right to modify features
without prior notice in view of continued improvement. 2006-2007

A. 117

Changeover switches

125 to 3150 A

SIRCOVER and
SIRCOVER by-pass

Functions
References
Accessories
Characteristics
Dimensions

Accessories
Shaft extension for external front operation

acces_034_a_1_x_cat

acces_143_a_1_cat

Use
For standard lenghts external
operation:
- 200 mm
- 320 mm
- 450 mm
Other lengths:
please consult us.

References
SIRCOVER
Rating (A)
125 400
125 400
500 630
500 630
800 1800
800 1800
2000 3150

Shaft length (mm) Dimension X (mm)


200
210 310
320
210 430
200
280 390
320
280 510
200
425 577
320
425 697
320
653 923

References
1400 1020
1400 1032
1400 1020
1400 1032
1401 1520
1401 1532
2799 3018

Dimension X (mm)
320 450
320 570
298 420
298 540
417 539
417 659
550 680
550 800

References
1400 1020
1400 1032
1401 1520
1401 1532
1401 1520
1401 1532
2799 3015
2799 3019

SIRCOVER by-pass
Rating (A)
125 200
125 200
250 400
250 400
500 630
500 630
800 1600
800 1600

Shaft length (mm)


200
320
200
320
200
320
200
450

Bridging bars

acces_205_a_1_cat

Use
Creation of a common link,
on the top or bottom side
of the switch, in order to feed
load with either power supply
I or/and II.
For a by-pass SIRCOVER, two
sets of bridging bars are needed
as the switch is composed of
three basic switch frames
Position I: 6 or 8 poles
Position II: 3 or 4 poles

Assembly
customer
customer
customer
customer
customer
customer
customer
customer
factory

References
4109 0019
4109 0025
4109 0039
4109 0050
4109 0063
4109 0080
4109 0120
4109 0160
consult us

acces_041_a_1_cat

SIRCOVER

References
Rating (A)
No. of poles Section (mm)
125 200
1
20 x 2.5
250
1
25 x 2.5
400
1
32 x 5
500
1
32 x 5
630
1
50 x 5
800
1
50 x 6
1250
1
60 x 8
1600 ... 1800
1
90 x 10
2000 ... 3150
1

acces_208_a_1_cat

SIRCOVER

SIRCOVER

A. 118

svr_068_a_1_x_cat

svr_124_a

SIRCOVER by-pass

SIRCOVER by-pass
This document is not a contract. SOCOMEC reserves the right to modify features
without prior notice in view of continued improvement. 2006-2007

SOCOMEC general catalogue

Changeover switches

SIRCOVER and
SIRCOVER by-pass

Accessories

acces_065_a_1_cat

Auxiliary contacts
Use
Pre breaking and positions
I and II signalling: 1 or 2 NO/NC
auxiliary contacts in each
position.
Low level auxiliary contacts
and more auxiliary contacts
requirement: please, consult us.

svr_058_a_1_cat

Connection to control circuit


Via 6,35 mm fast-on tags.

References
NO/NC auxiliary contact
Rating (A)
125 1800
2000 3150
2000 3150

Contact(s)
1st / 2nd
1st
2nd

References
4109 0021
4409 0021
4409 0022

Characteristics

Rating (A)

Electrical characteristics
30 000 operations.

125 3150

Use
Protection against direct
contacts with terminals
or connecting parts.
Supplied as pair.

References

Nominal
current (A)

250 VAC
AC-13
12

16

Operating current Ie (A)


400 VAC 24 VDC
48 VDC
AC-13
DC-13
DC-13
8
14
6

acces_206_a_1_cat

Terminal shrouds

Advantage of terminal
shrouds
Holes enable remote thermal
checking without removing.

Rating (A)
125 200
125 200
250 400
250 400
500 630
500 630

No. of poles
Position
3
top / bottom / front (I) / rear (II)
4
top / bottom / front (I) / rear (II)
3
top / bottom / front (I) / rear (II)
4
top / bottom / front (I) / rear (II)
3
top / bottom / front (I) / rear (II)
4
top / bottom / front (I) / rear (II)

References
2694 3014(1)(2)
2694 4014(1)(2)
2694 3021(1)(2)
2694 4021(1)(2)
2694 3051(1)(2)
2694 4051(1)(2)

(1) To shroud front switch top and bottom 2 references required


for SIRCOVER and 3 references required for SIRCOVER by-pass.
(2) To fully shroud front and rear / top and bottom 4 references required
for SIRCOVER and 6 references required for SIRCOVER by-pass.

Terminal screens

acces_207_a_1_cat

Use
Top or bottom protection
against direct contacts with
terminals or connecting parts.
Top and bottom pair.

References
Rating (A)
No. of poles
125 200
3
125 200
4
250 400
3
250 400
4
500 630
3
500 630
4
800 1250
3
800 1250
4
1600 ... 1800
3
1600 ... 1800
4
2000 3150
3/4

Position
top / bottom
top / bottom
top / bottom
top / bottom
top / bottom
top / bottom
top / bottom
top / bottom
top / bottom
top / bottom
top / bottom

Pack qty
2
2
2
2
2
2
2
2
2
2
2

References
1509 3012
1509 4012
1509 3025
1509 4025
1509 3063
1509 4063
1509 3080
1509 4080
1509 3160
1509 4160
standard

bd_01_01_03

Other specific accessories

SOCOMEC general catalogue

Special protection screens


(for specific dimensions or
high ambiant temperatures).
Phase barrier shields between
terminals.
Connection accessories.
Low level auxiliary contacts.

This document is not a contract. SOCOMEC reserves the right to modify features
without prior notice in view of continued improvement. 2006-2007

A. 119

Changeover switches

125 to 3150 A

LL

SIRCOVER and
SIRCOVER by-pass

Functions
References
Accessories
Characteristics
Dimensions

Accessories

acces_061_a_1_x_cat

Handle key interlocking accessories

acces_001_a_1_x_cat

Fig. 1

acces_132_a_1_x_cat

Fig. 2

acces_158_a_1_x_cat

Fig. 3

Fig. 4

A. 120

Use
Can be locked in
position 0
or in positions I, 0 or II
of front operation:
using padlock (not
supplied) (Fig.1). This
device is factory
mounted in the direct
or external operation
handle.
The lock escutcheon
contains sections to
be pushed out
according to locking
position required.
However, locking in
the 3 positions for
external operation on
the range requires
special orhandle.
using a lock (not
included) for direct
operation using:
- a special handle
which receives the
lock bolt on
SIRCOVER 125
to 630 A (Fig. 2)
- a locking disk for
SIRCOVER 800
to 3150 A (Fig. 3)
using a lock (not
included) for
detachable external
operation using:
- a device which lifts
the lock inside the
cabinet door for
SIRCOVER 125
to 630 A (Fig. 4)
- a locking disk for
SIRCOVER 800 to
3150 A
using undervoltage
coil for SIRCOVER
800 to 3150 A.
Operation on
SIRCOVER is only
possible when coil is
under voltage.

Rfrences
Lockable in position I, 0 or II
Rating (A)
SIRCOVER
125 630

Rating (A)
SIRCOVER by-pass
125 200

Operation
external

Figure
1

Reference
4199 5015

Figure
2
3
3
3
4

References
4109 1006(1)
consult us
4109 1004(2)
4409 2007
1499 7701
2799 7002(2)

Figure
2
3
3
3
4

References
4109 1002(1)
consult us
4109 1004(2)
4409 2003
1499 7701
2799 7002(2)

Operation
direct
direct

Figure
3
3

References
consult us
4409 9161

Operation
external
external

Figure
4
4

References
1499 7702
2799 7003

Locking using RONIS EL11AP lock in position 0 (not included)


Rating (A)
SIRCOVER
125 630
800 1800
2000 3150
125 1800
2000 3150

Rating (A)
SIRCOVER by-pass
125 200
250 630
800 1600
125 630
800 1600

Operation
direct
direct
direct
direct
external
external

Locking using RONIS EL11AP lock in positions I, 0, II (not included)


Rating (A)
SIRCOVER
125 630
800 1800
2000 3150
125 630

Rating (A)
SIRCOVER by-pass
125 200
250 630
800 1600

800 1600

Operation
direct
direct
direct
direct
external
external

Locking using 230 VAC undervoltage coil in position 0 (factory fitted)


Rating (A)
SIRCOVER
800 1800
2000 3150

Rating (A)
SIRCOVER by-pass
800 1600

Locking using CASTELL type K lock (not included)


Rating (A)
SIRCOVER
125 1800
2000 3150

Rating (A)
SIRCOVER by-pass
125 630
800 1600

(1) Specific handle included.


(2) This locking facility can be configured by the user in the 3 positions.

This document is not a contract. SOCOMEC reserves the right to modify features
without prior notice in view of continued improvement. 2006-2007

SOCOMEC general catalogue

Changeover switches

SIRCOVER and
SIRCOVER by-pass

Characteristics (according to IEC 60947-3)


Thermal current Ith (40C)
Rated insulation voltage Ui (V)
Rated impulse withstand voltage Uimp (kV)

125 A

160 A

200 A

250 A

400 A

500 A

630 A

800
8

800
8

800
8

800
8

800
8

1000
12

1000
12

A/B(1)
125/125
125/125
125/125
125/125
125/125
125/125
63/80
125/125
125/125
125/125
125/125
125/125
125(3)/125(3)
125(3)/125(3)
125(4)/125(4)

A/B(1)
160/160
160/160
160/160
160/160
160/160
125/125
63/80
160/160
160/160
160/160
125/125
160/160
125(3)/125(3)
125(3)/125(3)
125(4)/125(4)

A/B(1)
200/200
200/200
160/160
200/200
160/160
125/125
63/80
200/200
160/160
160/160
125/125
200/200
125(3)/125(3)
125(3)/125(3)
125(4)/125(4)

A/B(1)
250/250
250/250
250/250
250/250
200/250
125/160
100/125
250/250
250/250
250/250
200/200
250/250
200(3)/200(3)
200(3)/200(3)
200(4)/200(4)

A/B(1)
400/400
400/400
250/250
400/400
200/250
125/160
100/125
400/400
250/250
250/250
200/200
400/400
200(3)/200(3)
200(3)/200(3)
200(4)/200(4)

A/B(1)
500/500
500/500
500/500
500/500
400/400
250/315
160/200
500/500
500/500
400/500
400/400
500/500
400(3)/400(3)
315(3)/400(3)
400(4)/400(4)

A/B(1)
630/630
630/630
500/500
630/630
500/500
315/315
160/200
630/630
630/630
500/500
500/500
630/630
500(3)/500(3)
500(3)/500(3)
500(4)/500(4)

63/63
55/75

80/80
55/75

80/80
55/75

132/132
90/110

132/132
90/110

280/280
150/185

280/280
150/185

55

75

90

115

185

230

290

100
125

100
160

50
200

50
250

18
400

100
500

70
630

7
20

7
20

7
20

9
30

9
30

13
45

13
45

35
50
25
9

50
95
25
9

50
95
25
9

95
150
32
20

185
240
32
20

240
240
40
20

2 x 150
2 x 30 x 5
2 x 300
50
20

10 000
1.5
1.6

10 000
1.6
1.7

10 000
1.8
1.9

10 000
2
2.1

10 000
3
3.5

5 000
3.5
4

5 000
3.5
4

Rated operation currents Ie (A)


Rated voltage
400 VAC

690 VAC(2)

220 VDC

440 VDC

Load duty category


AC-21 A / AC-21 B
AC-22 A / AC-22 B
AC-23 A / AC-23 B
AC-20 A / AC-20 B
AC-21 A / AC-21 B
AC-22 A / AC-22 B
AC-23 A / AC-23 B
DC-20 A / DC-20 B
DC-21 A / DC-21 B
DC-22 A / DC-22 B
DC-23 A / DC-23 B
DC-20 A / DC-20 B
DC-21 A / DC-21 B
DC-22 A / DC-22 B
DC-23 A / DC-23 B

Operational power in AC-23 (kW)(1)(5)


At 400 VAC without pre-break AC
At 690 VAC without pre-break AC

Reactive power (kvar)(5)


At 400 VAC

Fuse protected short-circuit withstand (kA rms prospective)(6)


Prospective short-circuit current (kA rms)
Associated fuse rating (A)

Overload capacity
Rated short-time withstand current 1 s. Icw (kA rms)
Short-circuit making capacity (kA peak)(6)

Connection
Minimum Cu cable section (mm2)
Minimum Cu busbar section (mm2)
Maximum Cu cable section (mm2)
Maximum Cu busbar width (mm)
Min. tightening torque (Nm)

Mechanical characteristics
Endurance (number of operating cycles)(7)
Weight of 3 p switch (kg)
Weight of 4 p switch (kg)

(1) A/B: Category with index A = frequent operation - Category with index B = infrequent operation.
(2) With terminal shrouds or phase barrier.
(3) 3-pole device with 2 pole in series for the + and 1 pole for the -.
(4) 4-pole device with 2 pole in series by polarity.
(5) The power value is given for information only, the current values vary from one manufacturer to another.
(6) For a rated operating voltage Ue = 400 VAC.
(7) Increased endurances: please consult us.

SOCOMEC general catalogue

This document is not a contract. SOCOMEC reserves the right to modify features
without prior notice in view of continued improvement. 2006-2007

A. 121

Changeover switches
Functions
References
Accessories
Characteristics
Dimensions

LL

SIRCOVER and
SIRCOVER by-pass
125 to 3150 A
Characteristics (according to IEC 60947-3)
Thermal current Ith (40C)
Rated insulation voltage Ui (V)
Rated impulse withstand voltage Uimp (kV)

800 A

1250 A

1600 A

1800 A

2000 A

2500 A

3150 A

1000
12

1000
12

1000
12

1000
12

1000
12

1000
12

1000
12

A/B(1)
1800/1800
1800/1800
1250/1250
1800/1800
1000/1000
1000/1000
500/500
1800/1800
1250/1250
1250/1250
1250/1250
1800/1800
1250(3)/1250(3)
1250(3)/1250(3)
1250(3)/1250(3)

A/B(1)
2000/2000
2000/2000
1250/1250
2000/2000
2000/2000
1000/1000
800/800
2000/2000
2000/2000
1250/1600
1250(3)/1250(3)
2000/2000
1250/1250
1250(3)/1250(3)
1000(3)/1000(3)

A/B(1)
2500/2500
2000/2500
1250/1250
2500/2500
2000/2500
1000/1000
800/800
2500/2500
2000/2500
1250/1600
1250(3)/1250(3)
2500/2500
1250/1250
1250(3)/1250(3)
1000(3)/1000(3)

A/B(1)
3150/3150
2500/2500
1250/1250
3150/3150
2000/2500
1000/1000
800/800
3150/3150
2000/2500
1250/1600
1250(3)/1250(3)
3150/3150
1250/1250
1250(3)/1250(3)
1000(3)/1000(3)

Rated operation currents Ie (A)


Rated voltage
400 VAC

690 VAC(2)

220 VDC

440 VDC

Load duty category


AC-21 A / AC-21 B
AC-22 A / AC-22 B
AC-23 A / AC-23 B
AC-20 A / AC-20 B
AC-21 A / AC-21 B
AC-22 A / AC-22 B
AC-23 A / AC-23 B
DC-20 A / DC-20 B
DC-21 A / DC-21 B
DC-22 A / DC-22 B
DC-23 A / DC-23 B
DC-20 A / DC-20 B
DC-21 A / DC-21 B
DC-22 A / DC-22 B
DC-23 A / DC-23 B

A/B(1)
A/B(1)
A/B(1)
800/800
1250/1250
1600/1600
800/800
1250/1250
1600/1600
800/800
1250/1250
1250/1250
800/800
1250/1250
1600/1600
800/800
800/800
1000/1000
800/800
800/800
1000/1000
200/250
200/250
500/500
800/800
1250/1250
1600/1600
800/800
1250/1250
1250/1250
800/800
1250/1250
1250/1250
800/800
1250/1250
1250/1250
800/800
1250/1250
1600/1600
800(3)/800(3) 1250(3)/1250(3) 1250(3)/1250(3)
800(3)/800(3) 1250(3)/1250(3) 1250(3)/1250(3)
800(3)/800(3) 1250(3)/1250(3) 1250(3)/1250(3)

Operational power in AC-23 (kW)(1)(4)


At 400 VAC without pre-break AC
At 690 VAC without pre-break AC

450/450
185/220

710/710
185/220

710/710
475/475

710/710
475/475

710/710
750/750

710/710
750/750

710/710
750/750

365

575

Reactive power (kvar)(4)


At 400 VAC

Fuse protected short-circuit withstand (kA rms prospective)(5)


Prospective short-circuit current (kA rms)
Associated fuse rating (A)

50
800

100
1250

100
2 x 800

100
2 x 800

100
2 x 1000

100
2 x 1250

26
55

35
80

50
110

50
110

50
110

50
110

55
120

2 x 185
2 x 40 x 5
2 x 300
63
-

2 x 60 x 5
4 x 185
63
20

2 x 80 x 5
6 x 185
100
40

2 x 80 x 5
6 x 185
100
40

3 x 100 x 5
125
40

4 x 100 x 5
125
40

4 x 100 x 5
125
40

3 000
17.5
21

3 000
22.5
27.5

4 000
34
42

4000
34
42

3 000
70
85

2 500
72
88

2 500
98
110

Overload capacity
Rated short-time withstand current 1 s. Icw (kA rms)
Short-circuit making capacity (kA peak) (5)

Connection
Minimum Cu cable section (mm2)
Minimum Cu busbar section (mm2)
Maximum Cu cable section (mm2)
Maximum Cu busbar width (mm)
Min. tightening torque (Nm)

Mechanical characteristics
Endurance (number of operating cycles)(6)
Weight of 3 p switch (kg)
Weight of 4 p switch (kg)

(1) A/B: Category with index A = frequent operation - Category with index B = infrequent operation.
(2) With terminal shrouds or phase barrier.
(3) 4-pole device with 2 pole in series by polarity.
(4) The power value is given for information only, the current values vary from one manufacturer to another.
(5) For a rated operating voltage Ue = 400 VAC.
(6) Increased endurances: please consult us.

A. 122

This document is not a contract. SOCOMEC reserves the right to modify features
without prior notice in view of continued improvement. 2006-2007

SOCOMEC general catalogue

Changeover switches

SIRCOVER and
SIRCOVER by-pass

Dimensions
SIRCOVER 125 to 1800 A
External front operation

Direct front operation


Z1

CA

Z
Y

II

10

8.5

II

90

125

AC
AA
BA

2
II

45

90

B
I

37

47

210

CA

svr_072_f_1_x_cat

L1

40

T
J

28

H
T

H
C

HA
E min.

18

61

A. External operation handle S2 type: 125 to 630 A.

1. Terminal shrouds.

B. External operation handle S3 type: 800 to 1800 A.

2. Direct operation handle:


- 125 to 630 A: L1 = 140 mm.
- 800 to 1800 A: L1 = 210 mm.

Terminal
Switch body
Rating Overall dimensions shrouds
(A)
A 3p. A 4p. C E min AC
H
HA J 3p.
125 221 251 218 210 235 148 25 182
160 221 251 218 210 235 148 25 182
200 221 251 218 210 235 148 25 182
250 262 312 218 210 280 148 25 223
400 262 312 218 210 280 148 25 223
500 319 379 295 280 401 225 25 272
630 319 379 295 280 400 225 25 272
800 386 466 375 425 459 298 29 306.5
1250 386 466 375 425 459 298 29 306.5
1600 478 598 375 425 461 298 29 388.5
1800 478 598 375 425 461 298 29 388.5

J 4p.
212
212
212
273
273
332
332
386.5
386.5
518.5
518.5

Switch mounting
M 3p. M 4p. N
156 186 101
156 186 101
156 186 101
196 246 116
196 246 116
246 306 176
246 306 176
336 336 250
336 336 250
347 467 250
347 467 250

T
36
36
36
50
50
65
65
80
80
120
120

U
20
20
20
25
35
32
45
50
60
90
90

Connection terminals
V
W X 3p. X 4p. Y
Z
25 8.5 56 50 3.5 28
25 8.5 56 50 3.5 28
25 8.5 56 50 3.5 28
30 11 61 61 3.5 30
35 11 61 61 3.5 30
37 13 70.5 65.5 5
43
50 13 70.5 65.5 5
43
60,5 15 48 48
7 66.5
65 16x11 48 48
7 66.5
43.5 12.5x5 54 54
8 66.5
43.5 12.5x5 54 54
8 66.5

Z1
124
124
124
124
124
180
180
253.5
255.5
255.5
255.5

AA
135
135
135
160
170
235
260
321
330
288
288

BA
115
115
115
130
140
205
220

CA
10
10
10
10
15
15
20
26.5
29.5
15
15

SIRCOVER 2000 to 3150 A


Direct front operation

External front operation


A

Z3

Z2
Z1

88
Z

11

1-5 3-7

Y
1-5 3-7

7 - 7 5 - 5 3 - 3 1 - 1

svr_095_b_1_x_cat

65
50

561
AA
350

545

50

4 4.5

8 - 8 6 - 6 4 - 4 2 - 2
1
12.5 60.5 120

120

120 46.5

4-8 2-6

2000
2500
3150

Overall dimensions
A 3p.
A 4p.
576
696
576
696
576
696

SOCOMEC general catalogue

31

4-8 2-6
518
610

51.5

1. Terminal screen.

Rating
(A)

545

590
2

110

2. Minimum length with shaft extension: 650.

Switch body
F 3p.
F 4p.
447.5
567.5
447.5
567.5
447.5
567.5

Switch mounting
M 3p.
M 4p.
347
467
347
467
347
467

Y
10
10
15

Z
78.5
78.5
78.5

Connection terminals
Z1
Z2
225.5
309.5
225.5
309.5
230.5
309.5

This document is not a contract. SOCOMEC reserves the right to modify features
without prior notice in view of continued improvement. 2006-2007

Z3
456.5
456.5
461.5

AA
455
455
505

A. 123

Changeover switches
Functions
References
Accessories
Characteristics
Dimensions

SIRCOVER and
SIRCOVER by-pass
125 to 3150 A
Dimensions
SIRCOVER by-pass 125 to 1600 A
Direct front operation
Z2

A
M

Z
8.5

2
II

CA

L1

AC
AA
BA

CA

Z1

II

10

T
J

18

External front operation


II

90

II
=

C
330

90

HA

47

45

E min.

40

4 4.5
31

103

50

HA
E min.

50

svr_070_g_1_x_cat

210

28

37

90

90

125

61

A. External operation handle S2 type: 125 to 200 A.

1. Terminal shrouds.
2. Direct operation handle:
- 125 to 200 A: L1 = 140 mm.
- 250 to 630 A: L1 = 210 mm.
- 800 to 1600 A: L1 = 330 mm.

B. External operation handle S3 type: 250 to 630 A.


C. External operation handle: 800 to 1600 A.

Overall
dimensions
Rating
(A)
125
160
200
250
400
500
630
800
1250
1600

A. 124

A
A
3+6 p 4+8 p
221
221
221
262
262
319
319
386
386
478

251
251
251
312
312
379
379
466
466
598

C
313
313
313
313
313
432
432
560
560
560

Terminal
shrouds
E
AC
min.
320
320
320
298
298
417
417
550
550
550

235
235
235
280
280
401
400
459
459
461

Switch
body
H

243
243
243
243
243
362
362
479
479
479

HA

Switch
mounting

J
J
M
M
3+6 p 4+8 p 3+6 p 4+8 p

25 182 212 156


25 182 212 156
25 182 212 156
25 223 273 196
25 223 273 196
25 272 332 246
25 272 332 246
29 306.5 386.5 255
29 306.5 386.5 255
29 388.5 518.5 347

186
186
186
246
246
306
306
335
335
467

Connection terminals
N

101 36
101 36
101 36
116 50
116 50
176 65
176 65
250 80
250 80
250 120

U
20
20
20
25
35
32
45
50
60
90

X
X
3+6 p 4+8 p

25 8.5 56 50
25 8.5 56 50
25 8.5 56 50
30 11 61 61
35 11 61 61
37 13 70.5 65.5
50 13 70.5 65.5
60.5 15 48 48
65 16 x 11 48 48
43.5 12.5 x 5 54 54

This document is not a contract. SOCOMEC reserves the right to modify features
without prior notice in view of continued improvement. 2006-2007

Z1

Z2

3.5 28 124 219


3.5 28 124 219
3.5 28 124 219
3.5 30 124 219
3.5 30 124 219
5
43 180 317
5
43 180 317
7 66.5 253.5 439.5
7 66.5 253.5 439.5
8 66.5 253.5 439.5

AA

BA

CA

135
135
135
160
170
235
260
321
320
288

115
115
115
130
140
205
220

10
10
10
10
15
15
20
26.5
29.25
15

SOCOMEC general catalogue

Changeover switches

SIRCOVER and
SIRCOVER by-pass

Dimensions
L

Connection terminals
SIRCOVER and SIRCOVER by-pass
800 A

SIRCOVER and SIRCOVER by-pass


1250 A

SIRCOVER 1600 to 1800 A


SIRCOVER by-pass 1600 A

16 x 11

12.5

33

8.5

50

SIRCOVER 2000 to 2500 A

15.75

28.5

15
sirco_271_a_1_x_cat

8.5

15 28.5

svr_077_a_1_x_cat

15

svr_078_b_1_x_cat

10 33

12.5

15.75

60

25
30
45

25
30
45
90

SIRCOVER 3150 A

13

20

40

50
100

20

80

25

svr_080_b_1_x_cat

20

svr_079_a_1_x_cat

40

13

35

50
120

35

Door drilling with RONIS EL11AP lock


SIRCOVER 125 to 1800 A
SIRCOVER by-pass 125 to 630 A
4 5.5
26

26

14 14
5
3.

45

svr_102_a_1_x_cat

24

73
.5

28

37
47
20 20

Door drilling with CASTELL K lock


SIRCOVER 125 to 1800 A
SIRCOVER by-pass 125 to 630 A

SIRCOVER 2000 to 3150 A and


SIRCOVER by-pass 800 to 1600 A

22

50

79

96

37
47

50
sirco_224_b_1_x_cat

14 14

2 6.5

45

svr_101_a_1_x_cat

.5
28

37

25

28

4 x 6.5

31

3 x 6.5

20 20

SOCOMEC general catalogue

This document is not a contract. SOCOMEC reserves the right to modify features
without prior notice in view of continued improvement. 2006-2007

A. 125