Kepware Technologies KEPServerEX Client Connectivity Guide for Rockwell Softwares FactoryTalk View Studio

April, 2010 V. 1.00

Kepware Technologies

Table of Contents
1. 2. 3. 4. 5. 6. 7. 8. Overview and Requirements ...................................................................... 1 Creating a New FactoryTalk Project ............................................................. 1 Adding a New Data Server to the Project ..................................................... 2 Synchronizing the New FactoryTalk Project with the OPC Server ..................... 6 Creating a Tag for Indirect Addressing ........................................................ 6 Creating a FactoryTalk Project Display......................................................... 8 Creating an SE Client Configuration File ..................................................... 12 Using Kepwares OPC Quick Client ............................................................ 16

________________________________________________________________________________________ www.kepware.com i the title

1. Overview and Requirements


This guide will demonstrate how to establish a connection between the KEPServerEX OPC server and a FactoryTalk runtime project. Users must complete the following before continuing with this tutorial: Configure a server project: Users may either select the appropriate driver and settings or run the Simulation Driver Demo that is included with KEPServerEX. The Simulation Driver Demo project will be used for all examples in this tutorial. Start KEPServerEX and load the Simulation Driver Demo project. Once the server project has been loaded, open the Runtime menu on the main menu bar and verify that the server project has been connected.

2. Creating a New FactoryTalk Project


Note: For this tutorial, FactoryTalk View Studio version 5.10.00 will be used. 1. Start the program FactoryTalk View Studio. 2. In Application Type Selection, select Site Edition (Local) and then click Continue.

________________________________________________________________________________________ www.kepware.com 1 the title

3. In New/Open Site Edition (Local) Application, select the New tab and then enter a name for the application being created. In this tutorial, the application is named KEPDemo. Descriptions are optional and may be added if desired. When finished, click Create.

4. In Add Process Faceplates, click Clear All. Faceplates will not be used in this tutorial. Click OK.

3. Adding a New Data Server to the Project


1. In the main FactoryTalk View Studio window, locate Explorer KEPDemo.

________________________________________________________________________________________ www.kepware.com 2 KEPServerEX Client Connectivity Guide for Rockwell Softwares FactoryTalk View Studio

2. In the project tree, right-click on KEPDemo to invoke the context menu.

3. Hover over Add New Server and then select OPC Data Server.

________________________________________________________________________________________ www.kepware.com 3 KEPServerEX Client Connectivity Guide for Rockwell Softwares FactoryTalk View Studio

4. In OPC Data Server Properties, enter a name for the server connection. Then, select the Server will be hosted on local computer radio button.

5. Next, click Browse in order to locate the OPC server. If the server has been installed and started on the machine, Kepware Communications Server 5.2 should be visible in the list. Note: Users who have selected a remote server connection and are unable to browse for the server may need to configure DCOM security. For more information, refer to the "DCOM Configuration for KEPServerEX manual. 6. Select the server for the desired connection, and then click OK.

________________________________________________________________________________________ www.kepware.com 4 KEPServerEX Client Connectivity Guide for Rockwell Softwares FactoryTalk View Studio

7. In OPC Data Server Properties, make sure that the server name is visible and then click OK to accept the configuration. In this tutorial, "KepEx" is used.

Note: The project tree should now contain the icon KepEx.

________________________________________________________________________________________ www.kepware.com 5 KEPServerEX Client Connectivity Guide for Rockwell Softwares FactoryTalk View Studio

4. Synchronizing the New FactoryTalk Project with the OPC Server


Even though a server has been added, the new FactoryTalk project will not be able to access server tags until the following synchronization steps are completed. The server must remain connected for the duration of the synchronization. 1. To start, shut down FactoryTalk by clicking File | Exit. 2. Restart FactoryTalk and then re-open the KEPDemo project.

5. Creating a Tag for Indirect Addressing


FactoryTalk has two methods for accessing tags: Indirect Addressing and Direct Addressing. Indirect addressing requires the creation of a tag database, whereas direct addressing allows OPC items to be accessed directly. 1. In the Explorer-KEPDemo window, expand the HMI Tags folder and then double-click Tags.

2. In Tags - /KEPDemo/, make the following changes: Under the Tag group, enter a descriptive name in the Name field. In this tutorial, "Test" is used. Then, specify Analog as the Type. Leave the remaining parameters at their default settings. Under the Data Source group, select Device.

________________________________________________________________________________________ www.kepware.com 6 KEPServerEX Client Connectivity Guide for Rockwell Softwares FactoryTalk View Studio

3. Next, click on the Address browse button to open the Tag Browser. 4. In the Folders pane, expand the tree view and then locate the folder that contains the desired tag. In this tutorial Channel1/Device1 is used. 5. In the View pane, select the desired tag. In this tutorial, "Tag1" is used. Then click OK.

6. In Tags - /KEPDemo/, the chosen tag will be displayed in the Address field. Review the other parameters and make sure that the Minimum, Scale, Maximum, Offset and Data Type fields are set accordingly. The Description and Units fields may be left empty.

________________________________________________________________________________________ www.kepware.com 7 KEPServerEX Client Connectivity Guide for Rockwell Softwares FactoryTalk View Studio

7. Next, click Accept to add the tag to the tag database.

8. Then, click Close.

6. Creating a FactoryTalk Project Display


To verify a runtime connection to KEPServerEX, a display must be added to the FactoryTalk client project. 1. In the Explorer - KEPDemo window, open the Graphics folder. 2. Right-click on Displays and then select New.

________________________________________________________________________________________ www.kepware.com 8 KEPServerEX Client Connectivity Guide for Rockwell Softwares FactoryTalk View Studio

3. The Graphics Toolbar should now appear below the main menu bar. Select the Text tool icon and then add two text labels to the display. In this tutorial, they are named "Display1" and "Display2".

4. Next, select the Numeric Display tool and then add a numeric display beneath "Display1."

5. The dialog Numeric Display Properties will appear. Click Tags to invoke the tag browser.

________________________________________________________________________________________ www.kepware.com 9 KEPServerEX Client Connectivity Guide for Rockwell Softwares FactoryTalk View Studio

6. In the Tag Browser, indirect tags will be located in the main root of the project tree, immediately beneath the project icon. Select the tag "Test" and then click OK Note: If the indirect tag is not visible in the Contents window, click the KEPDemo icon in the Folders window to view tags located at the root.

7. In Numeric Display Properties, the Expression field should now display "Test," the indirect tag created earlier. Click OK.

________________________________________________________________________________________ www.kepware.com 10 KEPServerEX Client Connectivity Guide for Rockwell Softwares FactoryTalk View Studio

8. Repeat the process for "Display2," but now directly reference an object in the server. Select the same tag that was used to create the indirect tag.

Note: The untitled display should appear as shown below.

9. Next, click File | Save. In this tutorial, the display is named Win1.

________________________________________________________________________________________ www.kepware.com 11 KEPServerEX Client Connectivity Guide for Rockwell Softwares FactoryTalk View Studio

7. Creating an SE Client Configuration File


In order for the HMI to function, an SE Client configuration file must be created. 1. To start, launch the SE Client through the icon located on the menu bar.

2. In Launch FactoryTalk View SE Client, leave the text entry field blank and then select New.

3. In FactoryTalk View SE Client Wizard, leave the text entry field blank and then select New.

________________________________________________________________________________________ www.kepware.com 12 KEPServerEX Client Connectivity Guide for Rockwell Softwares FactoryTalk View Studio

4. In FactoryTalk View SE Client Configuration Name, enter a name for the configuration file. In this tutorial, it is named RunDemo. Leave the file storage location at its default setting and then click Next.

5. In FactoryTalk View SE Client Application Type, select Local. Then, click Next.

________________________________________________________________________________________ www.kepware.com 13 KEPServerEX Client Connectivity Guide for Rockwell Softwares FactoryTalk View Studio

6. In FactoryTalk View SE Client Application Name, select KEPDemo from the drop-down list beneath the application name field. Leave all other parameters at their default settings and then click Next.

7. In FactoryTalk View SE Client Components, select the graphic display "Win1" beneath Initial Display. Leave all other parameters empty and then click Next.

________________________________________________________________________________________ www.kepware.com 14 KEPServerEX Client Connectivity Guide for Rockwell Softwares FactoryTalk View Studio

8. In FactoryTalk View SE Client Window Properties, leave all parameters at their default settings and then click Next.

9. In FactoryTalk View SE Client Auto Logout, leave all parameters at their default settings and then click Next.

10. In FactoryTalk View SE Client Completion Options, select Save configuration and open FactoryTalk View SE Client now and then click Finish. This will prompt the HMI to load.

________________________________________________________________________________________ www.kepware.com 15 KEPServerEX Client Connectivity Guide for Rockwell Softwares FactoryTalk View Studio

11. Once the HMI starts, it should appear as shown below. Changing data should be visible in the numeric displays. Note: The indirect tag display updates slightly slower than the direct tag display. This is because the indirect tag display must update the FactoryTalk View tag database before displaying its update from the cache. The direct tagged object does not have this wait.

8. Using Kepwares OPC Quick Client


Kepware provides an OPC client application for testing purposes with each installation of KEPServerEX. For more information, refer to the OPC Quick Client help documentation.