Professional Documents
Culture Documents
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced. 2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an outdoor unit with anti-corrosion treatment.
PCV0320
The air conditioners manufactured by Daikin Industries have received ISO 9000 series certification for quality assurance.
Certificate Number.
(ISO9001) JMI-0107 JQA-0495 (ISO9002) JQA-1452
The airconditioning factories of Daikin Industries have received environmental management system standard ISO 14001
Shiga Plant
Certificate Number. EC99J2044
Sakai Plant
Certificate Number. JQA-E80009
Yodogawa Plant
Certificate Number. EC99J2057
Dealer
Head Office: Umeda Center Bldg., 4-12, Nakazaki-Nishi 2-chome, Kita-ku, Osaka, 530-8323 Japan Tokyo Office: Shinjuku Sumitomo Bldg., 6-1, Nishi-Shinjuku 2-chome, Shinjuku-ku, Tokyo, 163-0235 Japan
http://www.daikin.com/global/
c All rights reserved Printed in Japan 02/03/003 Y.K.
The specifications, designs, and information in this brochure are subject to change without notice.
impler
The is now four times better. Even earth friendly with a higher COP.
Daikin has put comprehensive cutting-edge technologies into the VRV II, derived from its Customer First policy and 20 years of experience with the VRV system. The results are quieter operation, smaller units, sleeker design, and simpler installation and maintenance, with less impact on the environment with higher COP.
R410A...
a refrigerant with ZERO ozone layerdepleting coefficient and no chlorone. R410A is a new mixed refrigerant that exhibits superior safety characteristics. Even with a zero coefficient of ozone layer depletion, R410A offers a better performance to the conventional R22.
DC fan motor
First use across entire range of models (from 5 to 48 HP). Efficiency improvement by 40% especially in low speed.
DC fan motor structure
100
DC motor efficiency
(comparison with a conventional AC motor) Efficiency (%)
80 60 40
RSXYP-L AC motor
20 0 200 300
400 500
600
700 800
900 1000
SCe-bridge Circuit
The new sub-cool feature prevents the flushing of liquid refrigerant from long piping due to the effects of SCe-bridge. This can reduce the refrigerant volume required in piping and thereby enable a reduction in piping size.
Ferrite magnet
Reluctance DC motor
Neodymium magnet
Neodymium magnet is much more powerful than the widely used ferrite magnets.
2
Wide range
The new VRV II is a significantly improved version of the original VRV, which revolutionized building air conditioning. The latest in air conditioning technologies are applied to fulfill all the needs of our customers. The VRV II opens the door to the future of air conditioning.
Energy saving
Highest COP available during both cooling and heating operation
Heat Pump Type
RXYQ5MY1B
Heat RecoveryType
2 HP increments
By providing a range of horse power levels in 2 HP 1 increments* , Daikin responds exactly to customer needs.
*1.Except for 5 HP
34, 36 HP
38, 40, 42 HP
44, 46, 48 HP
RXYQ8MY1B RXYQ20MY1B
Value represents that to be achieved by a single outdoor unit. What is COP? COP (Coefficient of Performance) indicates energy consumption efficiency. A higher COP means less electricity used, resulting in greater energy efficiency. Capacity (kW) Power consumption (kW)
Indoor units
COP=
A wide range of indoor units includes 10 types and 63 models, so the needs of all customers can be precisely met.
10 series, 63 models
Model Capacity Range
20 (0.8 HP) 25 (1 HP) 32 (1.25 HP) 40 (1.6 HP) 50 (2 HP) 63 (2.5 HP) 80 (3.2 HP)
Capacity Range
100 (4 HP) 125 (5 HP) 200 (8 HP) 250 (10 HP)
Page 25 Page 26 Page 27 Page 28 Page 29 Page 30 Page 31 Page 32 Page 33 Page 34
Ceiling mounted cassette (Double flow) Ceiling mounted cassette (Multi flow) super cassette 600 x 600 multi flow ceiling mounted cassette Ceiling mounted cassette corner Ceiling mounted built-in Ceiling mounted duct Ceiling suspended Wall mounted Floor standing Concealed floor standing
FXCQ20MVE
FXCQ25MVE FXFQ25MVE
FXCQ63MVE FXFQ63MVE
FXCQ125MVE FXFQ125MVE
FXZQ20MVE
FXZQ25MVE FXKQ25MVE
FXKQ63MVE FXSQ50MVE FXMQ50MVE FXSQ63MVE FXMQ63MVE FXHQ63MVE FXSQ80MVE FXMQ80MVE FXSQ100MVE FXMQ100MVE FXHQ100MVE FXSQ125MVE FXMQ125MVE FXMQ200MVE FXMQ200MVE
FXSQ20MVE
FXSQ25MVE
FXHQ32MVE FXAQ20MVE FXLQ20MVE FXNQ20MVE FXAQ25MVE FXLQ25MVE FXNQ25MVE FXAQ32MVE FXLQ32MVE FXNQ32MVE FXAQ40MVE FXLQ40MVE FXNQ40MVE FXAQ50MVE FXLQ50MVE FXNQ50MVE
Flexible design
1 An incredible 50 %* reduction in installation space
The VRV II has drastically reduced the installation space required, making it the most space saving system in the industry.
*1.At 16 HP
Easy installation
RSXYP
Transportation by Lift
All units can be transported by lift. This makes installation dramatically easy, and effectively reduces time and labor.
RSXYP24KJ x 2
RXYQ48M
VRV II requires fewer pipes and therefore less room for piping than VRV, resulting in a reduction in piping work and significant space saving.
40 m
First branch Indoor unit
Current model
15m
Level difference between indoor units.
50m
Height difference
High reliability
Double backup operation in compressors and units
If one of the three compressors in an outdoor unit malfunctions, one of the other compressors takes over emergency operation. Furthermore, if one outdoor unit malfunctions in a system of more than 18 HP, other outdoor units provide emergency operation until repair is effected.
If one compressor malfunctions... If one outdoor unit malfunctions...
Quiet operation
Nighttime quiet operation function
1 2 modes* with low operating sound level at night.
Set on the outdoor PCB. Time of maximum temperature is memorized. The low 2 operating mode will become active 8 hours* after the peak temperature in the daytime, 3 and operation will return to normal 9 hours* after that.
Mode 2. Customized mode
50
Starting time and ending time can be input. (External control adaptor for outdoor unit, DTA104A61 or DTA104A62, and a subsequently obtained timer are necessary.)
*1. Determine which mode to select depending on the climatic characteristics of each country. *2. Initial setting. Can be selected from 6, 8 and 10 hours. *3. Initial setting. Can be selected from 8, 9 and 10 hours.
0 58 50
8 hrs
9 hrs
Night Mode max. -8 dB( HP) 10
Note: This function is available in setting at site. The relationship of outdoor temperature (load) and time shown in the graph is just an example.
Environmental friendly
Extended operating range
By employing a high-pressure dome-type compressor, the operating range in heating has been extended from -15C to -20C.
VRV II uses less refrigerant than VRV and hence has less environmental impact.
Heating 15.5C WB
-20C WB
-20 C WB
Saves energy
The heat recovery system supports separate heating and cooling in different rooms, making the system ideal for the constantly changing occupancy of a typical building. Using the HRV for ventilation dramatically boosts energy efficiency.
Simplifies installation
The lightweight, compact units can be transported using a regular lift. The pipes are few in number, making layout simpler. Units can be installed on each floor. Inspection after installation is straightforward.
Conserves space
Space efficiency is enhanced by the compact size of the individual units, the long maximum piping length, and the ability to realize a largescale air conditioning system with a single piping circuit.
10
The DAIKIN VRV system offers low running costs, considerable savings in both energy and space, and high reliability. The innovative inverter technology ensures sufficient air conditioning in every stage of operation.
The VRV system can be interlocked with Daikin's energy-saving HRV ventilation system. The HRV system exchanges heat between the supplied air and exhausted air in order to recover the heat energy contained in the exhausted air, thus allowing ventilation without increasing the load on the air conditioning system. Operating the HRV system interlocked with the air conditioning system further improves the efficiency of air conditioning.
High Reliability
Conventional VAV systems or systems comprising a fan coil and chiller require an expensive, bulky standby system to prevent air conditioning in the entire building from being stopped when there is a problem in the system. The VRV system air-conditions each room individually, allowing any possible problems affect only the The VRV II system can duty cycle up to nine compressors to balance compressor usage for longevity and stability. Multiple outdoor units are switched with different starting sequences. By employing a high-pressure dome-type compressor, the operating range of heating has been extended from 15C to 20C. immediate system and not to require that all air conditioning be stopped. If an outdoor unit compressor malfunctions, another compressor takes over emergency operation. If an outdoor unit malfunctions in an over 18 HP system, another outdoor unit provides emergency operation until repair.
Reception room
Office
Office
11
12
Daikin's VRV systems include indoor and outdoor units available in a wide variety of models for all sizes of buildings and installation conditions. Long refrigerant piping lengths and other features put few restrictions on design for greater flexibility in meeting the needs of the building.
Air conditioning
Interlocked Control
Ventilation
150 m
3 5
Lightweight outdoor units featuring minimized vibrations do not require floor reinforcement as do conventional systems.
15 m
Level difference between indoor units
50 m
1
150 m
3 5
15 m
Level difference between indoor units
4
50 m
1
Intelligent touch Controller is a simplified but highly advanced central control air conditioning management system that gives complete control of your air conditioning equipment. Our large-scale air conditioning management system consists of the intelligent Manager ECO 21, which allows BMS*-level monitoring and control simply using a personal computer, or the BACnet Gateway / DMS-IF (for LONWORKS ), which connects air conditioning system to a BMS to perform monitoring and control.
* BMS: Building Management System
* LONWORKS is a registered trade mark of Echelon Corporation.
By flexibly combining the central controller, on/off controller and schedule timer, a versatile central control system can be easily constructed to control up to 128 indoor units.
13
14
Unique piping and wiring systems and lightweight, compact indoor units make it possible for just a few people to install a VRV system quickly and easily. The Auto Address Setting function and the Auto Check function for piping and wiring errors allow anyone with just the ability to install regular direct expansion type air conditioning equipment to perform a highly reliable installation.
Conventional
Outdoor unit
Indoor unit
Indoor unit
Sequential Starting
By employing D -net, systems on the same power line will be started sequentially. This holds down the starting current, allowing the capacities of breakers to remain small (possible up to 100 HP).
The REFNET Joint and REFNET Header (both optional) reduce the amount of work involved in installation and increases the reliability of the system.
REFNET Header for REFNET Header
Wiring can be fed from the front panel, both left and right side panels or bottom panel of the outdoor unit. Piping can be fed from 4 directions, front, both left and right or bottom of the outdoor unit.
These features increase installation flexibility, minimizing the space required for installation and simplifying maintenance of the wiring and piping.
Left
Right
Simple Wiring
Two-wire multiplex transmission system makes it possible to connect multiple indoor units to one outdoor unit with one 2-core wire, thus simplifying the wiring operation.
Power supply Front Bottom
Note: Refer to engineering data for details of the exterior design of the outdoor unit and the locations of connection points for piping and wiring.
Mistakes in piping or wiring in the system can be checked via lamps on the printed circuit board of the outdoor unit.
15
16
The VRV system is an advanced system that offers convenience and comfort for end users.
Malfunction code A1 A9 U4
Nature of malfunction Indoor unit : Print circuit board error Indoor unit: Electronic expansion valve drive unit (YIE) error Transmission error : Indoor unit Outdoor unit Outdoor BS unit ; BS unit
Time
5 HP Outdoor Unit
100% Compressor Capacity Control Compressor Capacity Control
210 Hz52 Hz No. 1 + No. 2 Compressor Inverter Control Compressor 29 Steps No. 2 Compressor 100% Operation
Inverter Control
24%
11%
Elevator
Installation by Floor
If necessary, installation can be performed by floor. The installers do not have to wait until the entire system is installed in the building to test the system in each section.
Auto Swing
Whether it be a ceiling-mounted cassette (double- flow/multiflow/600 x 600 multi-flow) type, ceiling-mounted cassette corner type, ceiling-suspended type or wall-mounted type, all these indoor units have an Auto Swing mechanism that helps keep the room temperature uniform.
17
18
One remote controller can control the operation of max.16 indoor units at the same time.
The indoor unit can be connected by the two remote controller, for example one in the room and the other one in the control room, which can control the operation of indoor unit freely. (The last command has a priority.) Of course, the group control by two remote controller is also possible.
The remote controller has centralized its frequently used operation selectors and switches (on/off, operation mode, temperature setting and airflow volume), making itself suitable for use in hotel rooms or conference rooms.
Concealed type
(For hotel use)
2
Remote controller Remote controller Indoor unit
Remote control
The wiring of remote controller can be extended to max.500m and it is possible to install the remote controllers for the different indoor units in one place.
Exposed type The concealed-type remote controller smartly fits into a night table or console panel in a hotel room.
Remote controller
The operation of HRV can be controlled by the remote controller of the indoor unit. Of course, the remote controller can display the time to clean the filter.
Remote controller
The system can be expanded to add several controllers, such as BMS, Forced OFF input and etc.
19
20
Unified on/off controller (DCS301B61) Connection of up to 8 units possible Address setting of central control can be performed from the remote controller.
DCS302B61
DCS301B61
6 cores
7 cores max.
Interlink Building Management System (host computer monitor panel) also possible
Schedule timer (DST301B61) 1 unit connection possible ; 8 weekly schedule control patterns possible
Max. 128 indoor units controllable 8 types of weekly schedule Max. 48 hours back up power supply Max. wiring length 1,000 m (Total : 2,000 m) Compact size casing (Thickness : 16 mm) Combination with Central Remote controller, Unified ON/OFF controller and BMS system
DST301B61
Indoor unit Maximum 128 units Indoor unit for VRV Indoor unit of SkyAir
(separate adaptor is required)
Associated with adaptor PC board Maximum 10 units Wiring adaptor for electrical appendices (Max. 1 unit) External control adaptor for outdoor unit Part name Model No. Function Interface between the central monitoring board and central control units. Combined with the central remote controller, this adaptor enables the central monitoring board to centralize such functions as the on/off control, operation status monitoring, and normal/malfunction monitoring.(*1) Adaptors required to connect products other than those of the VRV System to the high-speed DIII-NET communication system adopted for the VRV System.
* To use any of the above optional controllers, an appropriate adaptor must be installed on the product unit to be controlled.
Details
DCS302A52
Interface adaptor for SkyAir series Central control adaptor kit Wiring adaptor for other air-conditioner
Note : 1. Installation box for adaptor must be procured on site.
DTA102A52
( For SkyAir, FD(Y)M-FA, FDYB-KA, FDY-KA, FVYP)J-A
DTA107A55
For UAT(Y)-K(A), FD-K
DTA103A51
For air conditioners otherthan mentioned above.
21
22
The all-in-one color LCD controller offers high functionality in the smallest of size
Color LCD touch panel icon display Small manageable size Simplified engineering Multi language (English, French, Italian, German, Spanish and Chinese) Yearly schedule P.P.D. (Power Proportinal Distribution function) AIRNET service (optional failure prediction) Auto heat/cool change-over Temperature limitation History of 300 actions
(Optional) For power proportional distribution Display or print out power distribution (User PC)
DCS601B51
Maximum of 64 groups
Via internet
Wiring adaptor required for connection with other equipment not compatible with D -NET Wiring adaptor A/C Wiring adaptor Pump Wiring adaptor Others
Centralized control system for easy provision of effective control and monitoring of VRV system functions
Floor visual navigation Graphical report Remote intelligent manager Multi-PC access Watch dog function for remote error monitoring Power limit control Sliding temperature Automatic heat/cool change-over ECO mode Temperature limitation
*
Contact signal
Fire alarm Security
Ethernet
D -NET
VRV System
HRV
and
Ethernet BMS
Integrated control systems that recognize the trend of open control systems
(for LONWORKS )
VRV System
Compatibility with BMS enhanced by utilizing the international communication standards, BACnet or LONWORKS .
HRV
Local Controller
(for LONWORKS )
DMS502A51 DMS504B51 (for LONWORKS )
XIF file for confirming of specifications of the units. (LONWORKS) Programmable Delay Start Up for the setting of delay time for starting communication when power is turned on. First in the industry. (LONWORKS) Connectable up to 10 outdoor units and 64 indoor unit groups. (LONWORKS )
INTERNET
Mainfunction information by E-mail
Local dealers
Conformance class 3 (ASHRAE 1351995) Standard BACnet Device B-ASC (ASHRAE 1352001) BACnet OPC server compatibility BACnet/IP over Ethernet Up to 40 outdoor units and 256 indoor uit groups on one gateway. (optional adapter)
1. * There are restrictions in applicable areas and release times, therefore please consult us separately for details. 2. upon the system size. * Model nameavaries communication protocol specified as an international standard by ASHRAE (American Society of Heating Refriger ation and Air Conditioning Engineers). 3. * BACnet is data registered trade mark of Echelon Corporation. 4. LONWORKS is a * For an I/F unit, one of the following can be selected:Local Controller, intelligent touch Controller, or intelligent Manager ECO 21. 5. *
23
24
20
25
32
40
50
63
80
100
FXCQ-MVE
FXFQ-MVE
FXZQ-MVE
FXKQ-MVE
350mm
(dB(A)) 125
FXMQ-MVE
Operating 220V 32/27 34/28 34/29 37/32 39/34 44/38 Sound (H/L) 240V 34/29 36/30 37/32 39/34 41/36 46/40
Designed with higher air flow suitable for high ceiling application up to 3 meter.
Ceiling Suspended
FXHQ-MVE
Wall Mounted
FXAQ-MVE
Providing 2 different settings of standard and ceiling soiling prevention, the auto swing mechanism ensures even distribution of airflow and room temperature. Drain-up pump is equipped as standard accessory with 600mm lift.
A long-life filter (maintenance free up to one year) is equipped as standard accessory. Major maintenance work can be performed by removing the panel. A flat-type suction grille and a detachable blade make cleaning easy.
Floor Standing
FXLQ-MVE
600mm
FXNQ-MVE
* R410A VRV system indoor units are not compatible with the R22 VRV system.
Two types of optional high-efficiency filter are available (65% and 95% NBS).
25
26
Operating 30/27 30/27 31/27 32/27 33/28 36/31 39/33 42/36 sound (H/L)
Note: Operating sound may increase more than that when using with 3-way discharge or 2-way discharge, or when using together with a optional kit.
Provided with high lift drain water lift-up mechanism. (Increased lift of drain pipe up to 750mm from the ceiling.)
20
25 33/27
32
40
50
Installing the fresh air intake is now easier using the new optional kit which requires no special chambers. A new long-life filter (maintenance-free period extended from one year to two) is equipped as standard accessory.
7 discharge patterns in 2 to 4 directions can be selected to suit the requirements of installation site or the shape of the room. The number of installation method using ducts has increased as shown below. Single branch 8 patterns
Branched Number of discharge outlets used FXFQ25M-80M FXFQ100M-125M 4-way air 3-way air 2-way air 4-way air 3-way air 2-way air discharge discharge discharge discharge discharge discharge Standard 2.7m 3.0m 3.5m 3.2m 3.6m 4.2m Ceiling 3.0m 3.3m 3.8m 3.6m 4.0m 4.2m height High ceiling 1 High ceiling 2 3.5m 3.5m 4.2m 4.2m Note: Set standard 4-way discharge when shipped. High ceiling types 1 and 2 will be set for remote control operation Closed Piping location
Pattern Pattern
0 60 60
Settable to 5 different levels between 0 and 60 Angles can be set on site to prevent drafts (0-35) or soiling of the ceiling (25-60)
2 branches 2 patterns
Branched Closed
Switch box is inside the unit, which makes maintainance and installation easy.
25 60 60 25 10 40 40 10
Piping location
Has been set to standard setting at time of shipment. This can be changed using the remote control
27
28
Front discharge is possible with a air discharge unit (optional), which allows the installation in the drop-ceiling or sagging wall.
Main body
Installation examples
( Optional parts)
Standard
Downward discharge
Long-life filter
Screening door
Access panel
Main body
Long-life filter
Ceiling return
Long-life filter
Access panel
Screening door
Access panel
High external static pressure allows to use even flexible ducts of various length.
Downward discharge is shut off and air is blown straight out (front discharge).
(dB(A)) 125
Slim body needs only 220mm space above the ceiling. If you use panel spacer (optional), the unit can be installed in the min. space of 195mm.
Min.195mm Panel spacer 20mm
Operating 220V 37/32 37/32 38/32 38/32 41/36 42/35 43/37 43/37 46/41 Sound (H/L) 240V 39/34 39/34 40/34 40/34 43/38 44/37 45/39 45/39 48/37
Two types of optional high-efficiency filter are available (65% and 95% NBS). A long-life filter (maintenance free up to one year) is equipped as standard accessory.
29
30
FXHQ32M/FXHQ63M/FXHQ100M
(220V-240V)(dB(A))
63 39/34
100 45/37
FXMQ200M / FXMQ250M
Non-dew Flap
Min
Min
Maintenance is easier because everything can be performed from below the unit A long-life filter (maintenance free up to one year) is equipped as standard
590 mm
470 mm
New model 100
Indoor unit
31
32
FXLQ20M/FXLQ25M/FXLQ32M FXLQ40M/FXLQ50M/FXLQ63M
Perfect unit for perimeter zone air conditioning. Sophisticated design and compact casing harmonized in any interior dcor
Compact and stylish design that does not detract from the decor of the room. More compact than compared with previous model. (50, 63 class)
For 50, 63 Class
Floor standing types can be hung on the wall for easier cleaning. Since running the piping from the back allows the unit to be hung on walls. Cleaning under the unit, where dust tends to accumulate, is now easier. The adoption of a fiber-less discharge grille featuring an original design to prevent condensation also helps prevent staining and makes cleaning easier. A long-life filter (maintenance free up to one year) is equipped as standard accessory.
70 mm 290 mm 200 mm
Wall hanging
Floor installation
1,050 mm
Drastic 10 kg weight reduction from 24 kg to 14 kg. Volume reduced by 22%. Space savings of up to 47%.
(220V-240V)(dB(A)) 50 42/36
39/34
FXNQ20M/FXNQ25M/FXNQ32M FXNQ40M/FXNQ50M/FXNQ63M
Drain pan and air filter can be kept clean by mildew-proof polystyrene. Washable grille, the front grille can be easily removed for washing. Auto-swing ensures efficiency of air distribution. The louver closes automatically when the unit stops. 5 steps of discharge angle can be set by remote controller. Discharge angle is automatically set at the same angle as the previous operation when restarts. (Initial setting; 10 for cooling and 70 for heating)
33
Drain-pump kit is available as optional accessory, which lifts the drain 1,000mm from the bottom of the unit. Flexible installation. Drain pipe can be fitted to from either left or right sides.
Height of drain-up
1,000mm
34
RXYQ5MY1B
RXYQ8MY1B RXYQ10MY1B
RXYQ18MY1B RXYQ20MY1B
Modern office buildings are highly airtight and subject to an increasing heat load due to the use of computers, lighting equipment and other office equipment. In these buildings some rooms may require artificial cooling even in winter, depending on the amount of sunshine received and the number of people in the room. In order to meet such requirements the Heat Recovery Series enables the simultaneous operation of cooling and heating by controlling the BS unit that switches cooling and heating. This series also substantially improves energy efficiency by recycling exhaust heat.
The adoption of an inverter-controlled R-HIDECS circuit has achieved an efficient exhaust heat recovery operation. This circuit enables exhaust gas generated during cooling operation to be utilized for heating operation, reducing power consumption by 15 to 20% compared with that of conventional systems. Cooling and heating modes switch over automatically according to preset temperatures. The system also responds flexibly to changes in the room's heat load.
28, 30, 32 HP
34, 36 HP
38, 40, 42 HP
44, 46, 48 HP
RXYQ34MY1B RXYQ36MY1B
Total load
Heating load
(equipment HP) (equipment HP)
BS unit
10
2.5 No.1
2.5 No.2
2.5 No.3
2.5 No.4
Indoor unit
(A)
Heat radiation
cooling cooling cooling cooling
10
10
10
(B)
7.5
cooling cooling cooling heating
2.5
10
Heat radiation
Heat recovery operation
28, 30, 32 HP
34, 36 HP
38, 40, 42 HP
44, 46, 48 HP
(C)
cooling cooling heating heating
10
(D)
2.5
cooling heating heating heating
7.5
10
Heat absorption
Heat absorption operation
(all heating operation)
Series Line Up
Series
Heat pump type Heat recovery type
(E)
Capacity range
heating heating heating heating
10
10
10
5 HP 8 HP 10 HP 12 HP 14 HP 16 HP 18 HP 20 HP 22 HP 24 HP 26 HP 28 HP 30 HP 32 HP 34 HP 36 HP 38 HP 40 HP 42 HP 44 HP 46 HP 48 HP
Note: Operation modes (A) and (E) are applicable when the outdoor temperature is 35C and 0C respectively; The other modes are applicable under typical outdoor conditions.
35
(equipment HP)
(equipment HP)
Unit load
100
48
47
72
89
36
8 13 16
kcal/h Btu/h kW
Casing Air flow rate (Hi/Lo) m3/min cfm Sound level (Hi/Lo) Dimensions (HXW XD) Machine weight dB(A) 220V 240V 7/5 247/177 32/27 34/29 305X775X600 26.0 6.4 12.7 9/6.5 318/230 34/28 36/30 305X775X600 26.0 6.4 12.7 9/6.5 318/230 34/28 36/30 305X775X600 26.0 6.4 12.7
Galvanized steel plate 12/9 424/318 34/29 37/32 305X990X600 31.0 6.4 12.7 12/9 424/318 34/29 37/32 16.5/13 582/459 37/32 39/34 26/21 918/741 39/34 41/36 33/25 1,165/883 44/38 46/40
mm kg
305X990X600 305X1,175X600 305X1,665X600 305X1,665X600 32.0 6.4 12.7 35.0 9.5 15.9 47.0 9.5 15.9 48.0 9.5 15.9
VP25 (External Dia, 32/Internal Dia, 25) BYBC32GJW1 BYBC32GJW1 BYBC32GJW1 BYBC50GJW1 BYBC50GJW1 BYBC63GJW1 BYBC125GJW1 BYBC125GJW1 BYBC32G-W1 BYBC32G-W1 BYBC32G-W1 BYBC50G-W1 BYBC50G-W1 BYBC63G-W1 BYBC125G-W1 BYBC125G-W1
mm weight kg
8.0
8.0
8.0
8.5
8.5
9.5
12.0
12.0
MODEL
Power supply Cooling capacity kcal/h (*1) Btu/h (*1) kW Heating capacity (*1) (*2)
kcal/h Btu/h kW
Galvanized steel plate m3/min cfm dB(A) mm kg 13/10 459/353 30/27 13/10 459/353 30/27 15/11 530/388 31/27 16/11 565/388 32/27 18.5/14 653/494 33/28 20/15 706/530 36/31 26/21 918/741 39/33 30/24 1,059/847 42/36
246X840X840 246X840X840 246X840X840 246X840X840 246X840X840 246X840X840 288X840X840 288X840X840 24.0 6.4 12.7 24.0 6.4 12.7 24.0 6.4 12.7 24.0 6.4 12.7 25.0 9.5 15.9 25.0 9.5 15.9 29.0 9.5 15.9 29.0 9.5 15.9
Piping connections Liquid(Flare)mm Gas(Flare)mm Drain piping Panel(Option) Model Colour Dimensions (HXW XD) mm weight kg
VP25 (External Dia, 32/Internal Dia, 25) BYCP125D-W1 BYCP125D-W1 BYCP125D-W1 BYCP125D-W1 BYCP125D-W1 BYCP125D-W1 BYCP125D-W1 BYCP125D-W1 White 45X950X950 5.5 45X950X950 5.5 45X950X950 5.5 45X950X950 5.5 45X950X950 5.5 45X950X950 5.5 45X950X950 5.5 45X950X950 5.5
Note : Specifications are based on the following conditions; CDB, 19.5CWB, and outdoor temp. of 35.0 CDB. (*2) Indoor temp. of 27 CDB, 19.0CWB, and outdoor temp. of 35.0 CDB. Cooling : (*1) Indoor temp. of 27 Heating : Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. Equivalent piping length : 7.5m Level difference : 0m Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See ENGINEERING DATA for detail.) Sound level : Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation, these values are normally somewhat higher as a result of ambient conditions.
37
38
kcal/h
Dimensions
(HXW XD)
260(286)X575X575
Machine weight
mm
Piping connections Liquid(Flare)mm Gas(Flare)mm Drain piping Panel(Option) Dimensions (HXW XD) Model Colour mm weight kg
VP25 (External Dia, 32/Internal Dia, 25) BYBS32DJW1 BYBS32DJW1 BYBS32DJW1 BYBS45DJW1 BYBS45DJW1 BYBS71DJW1 BYBS125DJW1 BYBS125DJW1 BYBS125DJW1 White 55X650X500 55X650X500 55X650X500 55X800X500 55X800X500 55X1,100X500 55X1,500X500 55X1,500X500 55X1,500X500
3.0 3.0 3.0 3.5 3.5 4.5 6.5 6.5 6.5
FXKQ25MVE
FXKQ40MVE
4,000 15,900 4.7 4.5 4,300 17,000 5.0 13/10 459/353 40/34 42/36 215X1,110X710 31.0 6.4 12.7 BYK45FJW1
FXKQ63MVE
6,300 25,000 7.3 7.1 6,900 27,300 8.0 18/15 635/530 42/37 44/39 215X1,310X710 34.0 9.5 15.9 BYK71FJW1
MODEL
Power supply Cooling capacity kcal/h (*1) Btu/h (*1) (*1) kW Heating capacity (*2)
kcal/h
kcal/h Btu/h kW
Galvanized steel plate m3/min cfm 14/11.5 494/406 39/35 41/37 14/11.5 494/406 39/35 41/37 14/11.5 494/406 39/35 41/37 19.5/16 688/565 42/38 44/40 29/23 36/29 58/50 72/62
1,024/812 1,271/1,024 2,047/1,765 2,542/2,189 43/39 45/41 45/42 47/44 48/45 49/46 48/45 49/46
mm
dB(A)
220V 240V
Machine weight
mm kg
390X720X690 390X720X690 390X720X690 390X720X690 390X1,110X690 390X1,110X690 470X1,380X1,100 470X1,380X1,100 44.0 6.4 12.7 44.0 6.4 12.7 44.0 9.5 15.9 45.0 9.5 15.9 63.0 9.5 15.9 65.0 9.5 15.9 137.0 9.5 137.0 9.5
Note : Specifications are based on the following conditions; Cooling : (*1) Indoor temp. of 27 CDB, 19.5CWB, and outdoor temp. of 35.0 CDB. (*2) Indoor temp. of 27 CDB, 19.0CWB, and outdoor temp. of 35.0 CDB. Heating : Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. Equivalent piping length : 7.5m Level difference : 0m Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See ENGINEERING DATA for detail.) Sound level : (FXZQ-M) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center. (FXKQ-M) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During actual operation, these values are normally somewhat higher as a result of ambient conditions.
39
40
FXHQ63MVE
1 phase, 220-240V/220V, 50/60Hz 6,300 25,000 7.3 7.1 6,900 27,300 8.0 White
FXHQ100MVE
10,000 39,700 11.6 11.2 10,800 42,700 12.5
MODEL
Power supply Cooling capacity kcal/h (*1) Btu/h (*1) kW Heating capacity (*1) (*2) kcal/h Btu/h kW
FXLQ20MVE FXLQ25MVE FXLQ32MVE FXLQ40MVE FXLQ50MVE FXLQ63MVE FXNQ20MVE FXNQ25MVE FXNQ32MVE FXNQ40MVE FXNQ50MVE FXNQ63MVE
1 phase, 220 - 240V/220V, 50/60Hz 2,000 7,900 2.3 2.2 2,200 8,500 2.5 2,500 9,900 2.9 2.8 2,800 10,900 3.2 3,150 12,500 3.7 3.6 3,400 13,600 4.0 4,000 15,900 4.7 4.5 4,300 17,000 5.0 5,000 19,900 5.8 5.6 5,400 21,500 6.3 6,300 25,000 7.3 7.1 6,900 27,300 8.0
FXLQ
17.5/14 618/494 39/34 195X1,160X680 28.0 9.5 15.9 VP20 (External Dia, 26/Internal Dia, 20)
FXNQ
Casing Air flow rate (Hi/Lo) m3/min cfm Sound level (Hi/Lo) dB(A) 220V 240V Dimensions (HXW XD) mm 7/6 247/212 35/32 37/34
FXLQ:Ivory white / FXNQ:Galvanized steel plate 7/6 247/212 35/32 37/34 600X1,000X222 610X930X220 25.0 19.0 6.4 12.7 8/6 282/212 35/32 37/34 600X1,140X222 610X1,070X220 30.0 23.0 6.4 12.7 21O.D. 11/8.5 388/300 38/33 40/35 600X1,140X222 610X1,070X220 30.0 23.0 6.4 12.7 14/11 494/388 39/34 41/36 600X1,420X222 610X1,350X220 36.0 27.0 6.4 12.7 16/12 565/424 40/35 42/37 600X1,420X222 610X1,350X220 36.0 27.0 9.5 15.9
Machine weight
kg
FXLQ FXNQ
Note : Specifications are based on the following conditions; Cooling : (*1) Indoor temp. of 27 CDB, 19.5CWB, and outdoor temp. of 35.0 CDB. (*2) Indoor temp. of 27 CDB, 19.0CWB, and outdoor temp. of 35.0 CDB. Heating : Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB. Equivalent piping length : 7.5m Level difference : 0m Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See ENGINEERING DATA for detail.) Sound level : Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation, these values are normally somewhat higher as a result of ambient conditions.
41
42
RXYQ12MY1B
30,000 118,000 34.6 33.5 32,300 128,000 37.5 14 -100
RXYQ14MY1B
35,500 141,000 41.3 40.0 38,700 154,000 45.0 10-100
RXYQ16MY1B MODEL
40,000 157,000 45.9 44.5 43,000 171,000 50.0 10-100 Heating capacity (*3) Power supply Cooling capacity kcal/h(*1) Btu/h(*1) kW kcal/h Btu/h kW (*1) (*2)
RXYQ34MY1B RXYQ36MY1B RXYQ38MY1B RXYQ40MY1B RXYQ42MY1B RXYQ44MY1B RXYQ46MY1B RXYQ48MY1B Constituent Model RXYQ10MY1B RXYQ10MY1B RXYQ10MY1B RXYQ10MY1B RXYQ10MY1B RXYQ12MY1B RXYQ14MY1B RXYQ16MY1B RXYQ10MY1B RXYQ10MY1B RXYQ12MY1B RXYQ14MY1B RXYQ16MY1B RXYQ16MY1B RXYQ16MY1B RXYQ16MY1B RXYQ14MY1B RXYQ16MY1B RXYQ16MY1B RXYQ16MY1B RXYQ16MY1B RXYQ16MY1B RXYQ16MY1B RXYQ16MY1B
3 phase, 380-415V, 50Hz 85,500 338,000 99.1 96.0 92,700 370,000 108 4-100 90,000 354,000 104 101 97,000 387,000 113 4-100 95,000 374,000 109 106 102,000 407,000 119 4-100 101,000 397,000 117 113 109,000 433,000 127 4-100 105,000 413,000 121 117 113,000 450,000 132 4-100 110,000 432,000 127 123 118,000 470,000 138 4-100 116,000 455,000 133 129 125,000 496,000 145 3-100 120,000 471,000 138 134 129,000 513,000 150 3-100
Ivory white (5Y7.5/1) Hermetically sealed scroll type (2.7+4.5)X1 180 (4.2+4.5)X1 210 (2.0+4.5+4.5)X1 210 1,600X1,240X765 300 60 300 60 Air flow rate Dimensions(HXW XD) Machine weight Sound level (380V) (*4) Refrigerant Refrigerant charge Refrigerant oil Refrigerant oil charge Piping connections (3.0+4.5+4.5)X1 210 Capacity control Casing color Compressor
Ivory white (5Y7.5/1) Hermetically sealed scroll type Motor output kW m /min mm kg dB(A) kg
3
(2.7+4.5)+(2.7+4.5) (2.7+4.5)+(2.7+4.5) (2.7+4.5)+(4.2+4.5) (2.7+4.5)+(2.0+4.5+4.5) (2.7+4.5)+ (4.2+4.5)+ (2.0+4.5+4.5)+ X X X X (2.0+4.5+4.5) (3.0+4.5+4.5) (3.0+4.5+4.5) (3.0+4.5+4.5) (3.0+4.5+4.5) 2 (3.0+4.5+4.5) 2 (3.0+4.5+4.5) 2 (3.0+4.5+4.5) 3 180+180+210 180+180+210 180+210+210 180+210+210 180+210+210 210+210+210 210+210+210 210+210+210 (1,600X930X765)+(1,600X930X765)+ (1,600X1,240X765) 230+230+300 64 9.6+9.6+12.9 230+230+300 64 9.6+9.6+14.4 (1,600X930X765)+(1,600X1,240X765)+ (1,600X1,240X765) 230+260+300 64 230+300+300 64 R410A 9.6+11.4+14.4 9.6+12.9+14.4 9.6+14.4+14.4 11.4+14.4+14.4 12.9+14.4+14.4 14.4+14.4+14.4 Synthetic (ether) oil (1.9+1.6)+(1.9+1.6)+(1.9+1.6+1.6) (1.9+1.6)+(1.9+1.6+1.6)+(1.9+1.6+1.6) 19.1 (Brazing) 41.3 (Brazing) 6.4 (Flare) 19.1 (Brazing) 41.3 (Brazing) 6.4 (Flare) 19.1 (Brazing) 41.3 (Brazing) 6.4 (Flare) (1.9+1.6+1.6)+(1.9+1.6+1.6)+(1.9+1.6+1.6) 19.1 (Brazing) 41.3 (Brazing) 6.4 (Flare) 19.1 (Brazing) 41.3 (Brazing) 6.4 (Flare) 230+300+300 64 (1,600X1,240X765)+(1,600X1,240X765)+ (1,600X1,240X765) 260+300+300 65 300+300+300 65 300+300+300 65
RXYQ18MY1B RXYQ20MY1B RXYQ22MY1B RXYQ24MY1B RXYQ26MY1B RXYQ28MY1B RXYQ30MY1B RXYQ32MY1B MODEL Constituent Model
kcal/h (*1) Btu/h (*1) kW Heating capacity (*3) kcal/h Btu/h kW Capacity control Casing color Compressor Motor output kW Air flow rate Dimensions(HXW XD) Machine weight Sound level (380V) (*4) Refrigerant Refrigerant charge Refrigerant oil Refrigerant oil charge Piping connections Liquid mm Gas mm Oil mm 15.9 (Flare) 28.6 (Brazing) 6.4 (Flare) (1.9+1.6)+(1.9+1.6) 15.9 (Flare) 28.6 (Brazing) 6.4 (Flare) 15.9 (Flare) 28.6 (Brazing) 6.4 (Flare) kg 8.6+9.6 9.6+9.6 9.6+11.4 9.6+12.9 m /min mm kg dB(A)
3
RXYQ8MY1B RXYQ10MY1B RXYQ10MY1B RXYQ10MY1B RXYQ10MY1B RXYQ12MY1B RXYQ14MY1B RXYQ16MY1B RXYQ10MY1B RXYQ10MY1B RXYQ12MY1B RXYQ14MY1B RXYQ16MY1B RXYQ16MY1B RXYQ16MY1B RXYQ16MY1B
3 phase, 380 - 415V, 50Hz 45,000 178,000 52.0 50.4 48,500 193,000 56.5 7-100 50,000 197,000 57.8 56.0 54,000 216,000 63.0 7-100 55,000 217,000 63.5 61.5 59,300 236,000 69.0 7-100 60,500 240,000 70.2 68.0 65,700 262,000 76.5 6-100 65,000 256,000 74.9 72.5 70,000 279,000 81.5 6-100 70,000 275,000 80.5 78.0 75,300 299,000 87.5 6-100 75,500 298,000 87.2 84.5 81,700 325,000 95.0 5-100 80,000 314,000 91.9 89.0 86,000 342,000 100.0 5-100 Heating capacity (*3) kW kcal/h Btu/h kW Capacity control Casing color Compressor Motor output kW Air flow rate Dimensions(HXW XD) 9.6+14.4 (1.9+1.6)+(1.9+1.6+1.6) 15.9 (Flare) 34.9 (Brazing) 6.4 (Flare) 19.1 (Brazing) 34.9 (Brazing) 6.4 (Flare) 19.1 (Brazing) 34.9 (Brazing) 6.4 (Flare) 11.4+14.4 12.9+14.4 14.4+14.4 Sound level (380V) (*4) Refrigerant (1.9+1.6+1.6)+(1.9+1.6+1.6) 19.1 (Brazing) 34.9 (Brazing) 6.4 (Flare) 19.1 (Brazing) 34.9 (Brazing) 6.4 (Flare) Refrigerant oil Refrigerant oil charge Piping connections Liquid mm Suction gas mm Discharge gas mm Oil mm 1.9+1.6 9.5 (Flare) 19.1 (Brazing) 15.9 (Flare) 1.9+1.6 9.5 (Flare) 22.2 (Brazing) 19.1 (Brazing) m3/min mm dB(A) 57 (1.2+4.5)X1 175 1,600X930X765 58 60 R410A Synthetic (ether) oil 1.9+1.6 12.7 (Flare) 28.6 (Brazing) 19.1 (Brazing) 1.9+1.6+1.6 12.7 (Flare) 28.6 (Brazing) 22.2 (Brazing) 1.9+1.6+1.6 12.7 (Flare) 28.6 (Brazing) 22.2 (Brazing) (2.7+4.5)X1 180 % 210+210 260+300 63 210+210 300+300 63 210+210 300+300 63 Power supply Cooling capacity kcal/h(*1) Btu/h(*1) (*1) (*2) 20,000 78,900 23.1 22.4 21,500 85,400 25.0 14-100 25,000 98,700 28.9 28.0 27,000 108,000 31.5 14-100
REYQ14MY1B
35,500 141,000 41.3 40.0 38,700 154,000 45.0 10-100
REYQ16MY1B
40,000 157,000 45.9 44.5 43,000 171,000 50.0 10-100
(*1) (*2)
Ivory white (5Y7.5/1) Hermetically sealed scroll type (1.2+4.5)+(2.7+4.5) 175+180 230+230 61 (2.7+4.5)X2 180+180 230+230 61 (2.7+4.5)+(4.2+4.5) (2.7+4.5)+(2.0+4.5+4.5) (2.7+4.5)+(3.0+4.5+4.5) (4.2+4.5)+(3.0+4.5+4.5) (2.0+4.5+4.5)+(3.0+4.5+4.5) (3.0+4.5+4.5)+(3.0+4.5+4.5) 180+210 230+260 62 180+210 230+300 62 R410A Synthetic (ether) oil 180+210 230+300 62 (1,600X930X765)+(1,600X1,240X765) (1,600X1,240X765)+(1,600X1,240X765)
(1,600X930X765)+(1,600X930X765)
210 1,600X1,240X765 60
210 60
Note : Specifications are based on the following conditions; Cooling : (*1) Indoor temp. of 27 CDB, 19.5CWB, and outdoor temp. of 35.0 CDB. (*2) Indoor temp. of 27 CDB, 19.0CWB, and outdoor temp. of 35.0 CDB. Heating : (*3) Indoor temp. of 20 CDB, and outdoor temp. of 7CDB, 6CWB. (*1)(*2)(*3) Equivalent piping length : Heat pump type 7.5m, level difference 0m. Heat recovery type 7.5m, level difference 0m.
Sound level : (*4) Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions. Use C1220T-1/2H for over 19.1
Note : Specifications are based on the following conditions; Cooling : (*1) Indoor temp. of 27 CDB, 19.5CWB, and outdoor temp. of 35.0 CDB. (*2) Indoor temp. of 27 CDB, 19.0CWB, and outdoor temp. of 35.0 CDB. Heating : (*3) Indoor temp. of 20 CDB, and outdoor temp. of 7CDB, 6CWB. (*1)(*2)(*3) Equivalent piping length : Heat pump type 7.5m, level difference 0m. Heat recovery type 7.5m, level difference 0m.
Sound level : (*4) Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions. Use C1220T-1/2H for over 19.1
43
44
MODEL
Power supply Total capacity of connectable indoor units Casing Dimensions (HXW XD) mm Liquid mm Indoor Unit Gas mm Piping Liquid mm connections Outdoor Suction gas mm Unit Discharge gas mm Machine weight kg
BSVQ100MV1
100 or less 185X310X280 9.5 (Flare) 15.9 (Flare) 9.5 (Flare) 15.9 (Flare) 12.7 (Flare) 9.0
BSVQ160MV1
BSVQ250MV1
REYQ8MY1B REYQ10MY1B REYQ10MY1B REYQ10MY1B REYQ10MY1B REYQ12MY1B REYQ14MY1B REYQ16MY1B REYQ10MY1B REYQ10MY1B REYQ12MY1B REYQ14MY1B REYQ16MY1B REYQ16MY1B REYQ16MY1B REYQ16MY1B
3 phase, 380 - 415V, 50Hz 45,000 50,000 55,000 60,500 65,000 70,000 75,500 80,000 178,000 197,000 217,000 240,000 256,000 275,000 298,000 314,000 52.0 57.8 63.5 70.2 74.9 80.5 87.2 91.9 72.5 78.0 84.5 89.0 50.4 56.0 61.5 68.0 70,000 75,300 81,700 86,000 48,500 54,000 59,300 65,700 279,000 299,000 325,000 342,000 193,000 216,000 236,000 262,000 63.0 81.5 87.5 95.0 100.0 56.5 69.0 76.5 6-100 6-100 5-100 5-100 7-100 7-100 7-100 6-100 Ivory white(5Y7.5/1) Hermetically sealed scroll type (2.7+4.5)+ (4.2+4.5)+ (2.0+4.5+4.5)+ (1.2+4.5)+ (2.7+4.5)+ (2.7+4.5)+ X (3.0+4.5+4.5) 2 (2.7+4.5)X2 (2.7+4.5) (4.2+4.5) (2.0+4.5+4.5) (3.0+4.5+4.5) (3.0+4.5+4.5) (3.0+4.5+4.5) 180+210 210+210 210+210 210+210 175+180 180+180 180+210 180+210 (1,600X930X765)+(1,600X930X765) (1,600X930X765)+(1,600X1,240X765) (1,600X1,240X765)+(1,600X1,240X765) 62 63 63 63 61 61 62 62 R410A Synthetic (ether) oil (1.9+1.6)+(1.9+1.6) (1.9+1.6)+(1.9+1.6+1.6) (1.9+1.6+1.6)+(1.9+1.6+1.6) 15.9 (Flare) 15.9 (Flare) 15.9 (Flare) 15.9 (Flare) 19.1 (Brazing) 19.1 (Brazing) 19.1 (Brazing) 19.1 (Brazing) 28.6 (Brazing) 28.6 (Brazing) 28.6 (Brazing) 34.9 (Brazing) 34.9 (Brazing) 34.9 (Brazing) 34.9 (Brazing) 34.9 (Brazing) 22.2 (Brazing) 28.6 (Brazing) 28.6 (Brazing) 28.6 (Brazing) 28.6 (Brazing) 28.6 (Brazing) 28.6 (Brazing) 28.6 (Brazing) 6.4 (Flare) 6.4 (Flare) 6.4 (Flare) 6.4 (Flare) 6.4 (Flare) 6.4 (Flare) 6.4 (Flare) 6.4 (Flare)
V1: 1 phase, 220-240V, 50Hz More than 100 but 160 or less 160 or more but less than 250 Galvanized steel plate 185X310X280 185X590X435 9.5 (Flare) 9.5 (Flare) 15.9 (Flare) 22.2 (Flange) 9.5 (Flare) 9.5 (Flare) 15.9 (Flare) 22.2 (Flange) 12.7 (Flare) 19.1 (Flare) 11.0 21.0
Motor output kW Air flow rate Dimensions(HXW XD) Sound level (380V) (*4) Refrigerant Refrigerant oil Refrigerant oil charge Piping connections m3/min mm dB(A)
FXCQ25M FXCQ32M
FXCQ40M
FXCQ50M
2
REYQ34MY1B REYQ36MY1B REYQ38MY1B REYQ40MY1B REYQ42MY1B REYQ44MY1B REYQ46MY1B REYQ48MY1B MODEL Constituent Model REYQ10MY1B REYQ10MY1B REYQ10MY1B REYQ10MY1B REYQ10MY1B REYQ12MY1B REYQ14MY1B REYQ16MY1B REYQ10MY1B REYQ10MY1B REYQ12MY1B REYQ14MY1B REYQ16MY1B REYQ16MY1B REYQ16MY1B REYQ16MY1B REYQ14MY1B REYQ16MY1B REYQ16MY1B REYQ16MY1B REYQ16MY1B REYQ16MY1B REYQ16MY1B REYQ16MY1B
85,500 338,000 99.1 96.0 92,700 370,000 108.0 4-100 90,000 354,000 104 101 97,000 387,000 113.0 4-100 95,000 374,000 109 106 102,000 407,000 119.0 4-100 3 phase, 380 - 415V, 50Hz 101,000 105,000 397,000 413,000 117 121 117 113 113,000 109,000 433,000 450,000 127 132 4-100 4-100 Ivory white(5Y7.5/1) Hermetically sealed scroll type 110,000 432,000 127 123 118,000 470,000 138 4-100 116,000 455,000 133 129 125,000 496,000 145 3-100 120,000 471,000 138 134 129,000 513,000 150 3-100
Note:
Filter related
BYBC32GJW1 BYBC32G-W1 2 High efficiency filter 65% KAFJ532G36 2 High efficiency filter 90% KAFJ533G36 Filter chamber bottom suction KDDFJ53G36 Long life replacement filter KAFJ531G36
1 BYBC-GJW1: Without origin, BYBC-G-W1: With origin 2 Filter chamber is required if installing high efficiency filter.
Item
(2.7+4.5)X2+ (2.7+4.5)X2+ (2.7+4.5)+(4.2+4.5)+(2.7+4.5)+(2.0+4.5+4.5)+ (2.7+4.5)+ (4.2+4.5)+ (2.0+4.5+4.5)+ X X X X (3.0+4.5+4.5) 2 (3.0+4.5+4.5) 2 (3.0+4.5+4.5) 2 (3.0+4.5+4.5) 3 (2.0+4.5+4.5) (3.0+4.5+4.5) (3.0+4.5+4.5) (3.0+4.5+4.5) Air flow rate m3/min 180+180+210 180+180+210 180+210+210 180+210+210 180+210+210 210+210+210 210+210+210 210+210+210 Dimensions(HXW XD) (1,600X930X765)+(1,600X930X765)+ (1,600X930X765)+(1,600X1,240X765)+ (1,600X1,240X765)+(1,600X1,240X765)+ mm (1,600X1,240X765) (1,600X1,240X765) (1,600X1,240X765) dB(A) Sound level (380V) (*4) 64 65 65 65 64 64 64 64 R410A Refrigerant Refrigerant oil Synthetic (ether) oil (1.9+1.6)+(1.9+1.6+1.6)+(1.9+1.6+1.6) (1.9+1.6+1.6)+(1.9+1.6+1.6)+(1.9+1.6+1.6) Refrigerant oil charge (1.9+1.6)+(1.9+1.6)+(1.9+1.6+1.6) Liquid mm 19.1 (Brazing) 19.1 (Brazing) 19.1 (Brazing) 19.1 (Brazing) 19.1 (Brazing) 19.1 (Brazing) 19.1 (Brazing) 19.1 (Brazing) Piping connections Suction gas mm 34.9 (Brazing) 41.3 (Brazing) 41.3 (Brazing) 41.3 (Brazing) 41.3 (Brazing) 41.3 (Brazing) 41.3 (Brazing) 41.3 (Brazing) Discharge gas mm 28.6 (Brazing) 28.6 (Brazing) 34.9 (Brazing) 34.9 (Brazing) 34.9 (Brazing) 34.9 (Brazing) 34.9 (Brazing) 34.9 (Brazing) Oil mm 6.4 (Flare) 6.4 (Flare) 6.4 (Flare) 6.4 (Flare) 6.4 (Flare) 6.4 (Flare) 6.4 (Flare) 6.4 (Flare) Motor output kW
Note : Specifications are based on the following conditions; Cooling : (*1) Indoor temp. of 27 CDB, 19.5CWB, and outdoor temp. of 35.0 CDB. (*2) Indoor temp. of 27 CDB, 19.0CWB, and outdoor temp. of 35.0 CDB. Heating : (*3) Indoor temp. of 20 CDB, and outdoor temp. of 7CDB, 6CWB. (*1)(*2)(*3) Equivalent piping length : Heat pump type 7.5m, level difference 0m. Heat recovery type 7.5m, level difference 0m. Sound level : (*4) Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions. Use C1220T-1/2H for over 19.1
5 6 7 8
Decoration Panel Sealing Member of air discharge outlet Panel spacer High efficiency filter unit 65% High efficiency filter unit 90% Replacement high efficiency filter 65% Replacement high efficiency filter 90% Filter related Filter chamber Long life replacement filter Non-woven type Ultra long-life filter Replacement ultra long-life filter Without T shape and fan Chamber type With T shape without fan Fresh air intake kit Direct installation type Branch duct chamber Chamber connection kit Insulation kit for high humidity
KDP55D160 KDT-55D160
Item
Type
FXZQ20M
FXZQ25M
FXZQ32M
BYFQ60BW1 KDBHQ44B60 KDBQ44B60 KAFQ441B60 KDDQ44X60
FXZQ40M
FXZQ50M
Decoration panel Sealing member of air discharge outlet Panel spacer Replacement long-life filter Fresh air intake kit Direct installation type
Item
Panel related Air inlet and air discharge outlet related
Type
Decoration Panel Panel Spacer Long life replacement filter Air discharge grill Air discharge blind panel Flexible duct (with shutter)
FXKQ25M,FXKQ32M,FXKQ40M
BYK45FJW1 KPBJ52F56W KAFJ521F56 K-HV7AW KDBJ52F56W KFDJ52F56
FXKQ63M
BYK71FJW1 KPBJ52F80W KAFJ521F80 K-HV9AW KDBJ52F80W KFDJ52F80
45
46
Item
Decoration Panel Access panel 1 Auxiliary Model 240V/220V electric heater kW Capacity 2 High efficiency filter 65% 2 High efficiency filter 90% Filter related Long life replacement filter For bottom suction Filter chamber For rear suction Air suction canvas Air inlet and air Screening door discharge outlet Air suction flange related Air discharge adaptor Natural evaporating pan type humidifier 1 Panel related
FXSQ40M FXSQ50M
BYBS45DJW1 KTBJ25K56W KEA25K50VE 1.2 KAFJ252L56 KAFJ253L56 KAFJ251K56 KAJ25L56D KAJ25L56B KSA-25K56 KBBJ25K56 KDJ2507K56 KDAJ25K56 KNM25K50V1
FXSQ63M
BYBS71DJW1 KTBJ25K80W KEA25K63VE 1.4 KAFJ252L80 KAFJ253L80 KAFJ251K80 KAJ25L80D KAJ25L80B KSA-25K80 KBBJ25K80 KDJ2507K80 KDAJ25K71 KNM25K63V1
FXSQ80M FXSQ100M
FXSQ125M
No.
1 1-1 2 3 4 5 6
Name of Options
Cool/Heat Selector Fixing box REFNET header REFNET joint Kit of air discharge duct Central drain pan kit Refrigerant leak detector kit
RXYQ5MY1B
RXYQ8MY1B RXYQ10MY1B
KRC19-26A KJB111A KHRP26M22H (Max. 4branch) KHRP26M33H (Max. 8branch)
5
Note:
BYBS125DJW1 KTBJ25K160W KEA25K100VE KEA25K125VE 2.1 2.8 KAFJ252L160 KAFJ253L160 KAFJ251K160 KAJ25L160D KAJ25L160B KSA-25K160 KBBJ25K160 KDJ2507K160 KDAJ25K140 KNM25K125V1
KHRP26M22H (Max. 4branch),KHRP26M33H (Max. 8branch) KHRP26M72H (Max. 8branch) KHRP26M22T, KHRP26M33T, KHRP26M72T KPF26B450 KWC26B450 KPF26B280 KWC26B280
KHRP26M22T, KHRP26M33T
KFLD26A,KHLD26A
No.
1 1-1
Name of Options
Cool/Heat Selector Fixing box REFNET header Distributive REFNET joint piping Outdoor unit multi connection piping kit Pipe size reducer Kit of air discharge duct Central drain pan kit Refrigerant leak detector kit
RXYQ22MY1B RXYQ44MY1B RXYQ18MY1B RXYQ30MY1B RXYQ34MY1B RXYQ38MY1B RXYQ40MY1B RXYQ24MY1B RXYQ28MY1B RXYQ46MY1B RXYQ20MY1B RXYQ32MY1B RXYQ36MY1B RXYQ42MY1B RXYQ26MY1B RXYQ48MY1B
KRC19-26A KJB111A KHRP26M22H (Max. 4branch), KHRP26M33H (Max. 8branch), KHRP26M72H (Max. 8branch), KHRP26M73H (Max. 8branch) KHRP26M22T, KHRP26M33T, KHRP26M72T, KHRP26M73T BHFP22M90 KHRP26M73TP, KHRP26M73HP, BHFP22M90P KPF26B280X2 KWC26B280 X2 KPF26B280 KPF26B450 KWC26B280 KWC26B450 KPF26B450X2 KWC26B450 X2 KPF26B450X2 KWC26B450 X2 BHFP22M135 KHRP26M73TP, KHRP26M73HP, BHFP22M135P KPF26B280X2 KPF26B450 KWC26B280 X2 KWC26B450 KPF26B280 KPF26B450X2 KWC26B280 KWC26B450 X2 KPF26B280 KPF26B450X2 KWC26B280 KWC26B450 X2 KPF26B450X3 KWC26B450 X3
1 One adaptor for wiring (KRP1B61) per indoor unit is required if installing an electric heater or a natural evaporating pan type humidifier. An electric heater cannot be used for VRV system cooling only. 2 If installing a high filter in the ceiling mounted built-in type, an assembly chamber for either bottom or rear suction is required.
Item
Drain pump kit High efficiency filter Filter chamber Long life replacement filter
4 5 6
KFLD26A, KHLD26A
REYQ8MY1B REYQ10MY1B
KHRP25M33H (Max. 8branch) KHRP25M22T, KHRP25M33T
Item
Drain pump kit Replacement long-life filter (Resin net) L-type piping kit (for upward direction)
Type
FXHQ32M
KDU50M60VE KAFJ501D56 KHFP5M35
FXHQ63M
KDU50M125VE KAFJ501D80 KHFP5M63
FXHQ100M
KAFJ501D112
1 2 3 4 5 6
KPF26B280 KWC26B280
Item
Drain pump kit
FXAQ32M
FXAQ40M
FXAQ50M
FXAQ63M
No.
1 2 3 4
Name of Options
REFNET header REFNET joint Outdoor unit multi connection piping kit Pipe size reducer Kit of air discharge duct Central drain pan kit Refrigerant leak detector kit
REYQ22MY1B REYQ44MY1B REYQ18MY1B REYQ30MY1B REYQ34MY1B REYQ38MY1B REYQ40MY1B REYQ24MY1B REYQ28MY1B REYQ46MY1B REYQ20MY1B REYQ32MY1B REYQ36MY1B REYQ42MY1B REYQ26MY1B REYQ48MY1B
KHRP25M33H (Max. 8branch), KHRP25M72H (Max. 8branch), KHRP25M73H (Max. 8branch) KHRP25M22T, KHRP25M33T, KHRP25M72T, KHRP25M73T BHFP26M90 KHRP25M72TP, KHRP25M72HP, KHRP26M73TP, KHRP26M73HP, BHFP26M90P KPF26B280X2 KWC26B280 X2 KPF26B280 KPF26B450 KWC26B280 KWC26B450 KPF26B450X2 KWC26B450 X2 KPF26B450X2 KWC26B450 X2 KPF26B280X2 KPF26B450 KWC26B280 X2 KWC26B450 BHFP26M135 KHRP25M72TP, KHRP25M72HP, KHRP26M73TP, KHRP26M73HP, BHFP26M135P KPF26B280 KPF26B450X2 KWC26B280 KWC26B450 X2 KPF26B280 KPF26B450X2 KWC26B280 KWC26B450 X2 KPF26B450X3 KWC26B450 X3
K-KDU572BVE
Item
Long life replacement filter
Type
FXLQ20M
FXLQ25M
FXLQ32M
5 6 7
KAFJ361K28
KAFJ361K45
KFLD26A, KHLD26A
Item
Long life replacement filter
Type FXNQ20M
FXNQ25M
FXNQ32M
For BS Units
No.
1 2 Fixing box
KAFJ361K28
KAFJ361K45
Name of Options
Cool/Heat selector
BSVQ100MV1
BSVQ160MV1
KRC19-26A KJB111A
BSVQ250MV1
47
48
FXCQ-M
BRC7C62 BRC7C67
FXFQ-M
BRC7E61W BRC7E65
FXZQ-M
BRC7E530W BRC7E531W
FXSQ-M
BRC4C62 BRC4C64
FXMQ-M
BRC4C62 BRC4C64
FXHQ-M
BRC7E63W BRC7E66
FXAQ-M
BRC7E618 BRC7E619
FXLQ-M FXNQ-M
BRC4C62 BRC4C64 BRC1A62
No.
1
Part name
Without PPD
intelligent Touch Controller
Model No.
DCS601B51 DCS601B51 DCS002A51
KJB411A 128 units DAM602A52 DAM602A53 DAM602A51 DAM602A51 x2 DAM602A51 x3 DAM602A51 x4 DMS502A51 DMS504B51 DAM411A1 DAM412A1 DPF201A51 DPF201A52 DPF201A53 DCS302A52 KRP2A61 KRP2A62 KRP4A51-53 DTA104A61 DTA104A62 PPD: Power Proportional Distribution function
Function
Air-Conditioning management system that can be controlled by a compact all-in-one unit. New Functions : Auto cool / heat change-over Temperature limitation Multilingual (English, French, German, Spanish, Italian, or Chinese) Wall embedded switch box.
H/P C/O
With PPD
1-1 Electrical box with earth terminal (4blocks)
BRC1A61
BRC1A62 BRC15A61
BRC1A61
192 units 2 intelligent Manager ECO 21 Number of units to be connected 256 units 512 units 768 units 1024 units BACnet Gateway
Air conditioner management system (featuring minimized engineering) that can be controlled by personal computers.
Interface unit to allow communications between VRV and BMS. Operation and monitoring of airconditioning systems through BACnet communication. Interface unit to allow communications between VRV and BMS. Operation and monitoring of airconditioning systems through LONWORKS communication. Expansion kit, installed on the BACnet Gateway (DMS502A51), to provide 3 more DIII-NET communication ports. Not usable independently. Expansion kit, installed on the BACnet Gateway (DMS502A51), to provide 16 more wattmeter pulse input points. Not usable independently. Enables ON/OFF command, operation and display of malfunction; can be used in combination with up to 4 units. Enables temperature measurement output for 4 groups; 0-5VDC. Enables temperature setting input for 16 groups; 0-5VDC. Interface between the central monitoring board and central control units. Simultaneously controls air-conditioning control computer and up to 64 groups of indoor units. To control the group of indoor units collectively, which are connected by the transmission wiring of remote controller. Cooling/Heating mode change over. Demand control and Low noise control are available between the plural outdoor units.
KRP1B96
KRP1D98
Note 3
KRP1C93
KRP4A93
4 5 6 7
LONWORKS Network compatible LON Gateway DMS-IF Optional DIII board Optional Di board Parallel interface Basic unit
Contact/analog signal
Temperature measurement units Temperature setting units Unification adaptor for computerized control Wiring adaptor for electrical appendices (1) Wiring adaptor for electrical appendices (2) External control adaptor for outdoor unit
DTA104A61
DTA104A62
DTA104A61
DTA104A62
DTA104A61 DTA104A61
9 10 11-1
Note: 1. Installation box is necessary for each adaptor marked 2. Up to 2 adaptors can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit. 4. Installation box is necessary for second adaptor.
Various PC boards
No.
1 Adaptor for wiring D -NET Expander adaptor
11-2
Part name
Model No.
KRP1B61 KRP1B59 KRP1B3 DTA109A51
Function
PC board when equipped with auxiliary electric heater in the indoor unit. Up to 1024 units can be centrally controlled in 64 different groups. Wiring restrictions (max. length : 1000m, total wiring length : 2000m, max. number of branches : 16) apply to each adaptor.
12
System configuration
No.
1 2 3 4 5 6 7 Central remote controller Unified ON/OFF controller Schedule timer Unification adaptor for computerized control Interface adaptor for SkyAir-series Central control adaptor kit
(Y)M-FA, FDY-KA For SkyAir, FD FDYB-KA, FDY-KA, FVY(P)J-A For UAT(Y)-K(A),FD-K
Part name
Model No.
DCS302B61 DCS301B61 DST301B61 DCS302A52 DTA102A52 DTA107A55 DTA103A51
Function
Up to 64 groups of indoor units(128 units) can be connected, and ON/OFF, temperature setting and monitoring can be accomplished individually or simultaneously. Connectable up to 2 controllers in one system. Up to 16 groups of indoor units(128 units) can be turned, ON/OFF individually or simultaneously, and operation and malfunction can be displayed. Can be used in combination with up to 8 controllers. Programmed time weekly schedule can be controlled by unified control for up to 64 groups of indoor units (128 units). Can turn units ON/OFF twice per day. Interface between the central monitoring board and central control units.
Adaptors required to connect products other than those of the VRV System to the high-speed DIII-NET communication system adopted for the VRV System.
* To use any of the above optional controllers, an appropriate adaptor must be installed on the product unit to be controlled.
Up to 1024 units can be centrally controlled in 64 different groups. DTA109A51 Wiring restrictions (max. lengh : 1,000m, total wring lengh : 2,000m, max. number of branches : 16) apply to each adaptor. Fixing plate for DTA109A51
KRP4A92
49
50
Daikin's HRV (Heat Reclaim Ventilation) recovers heat energy lost through ventilation and holds down room temperature changes caused by ventilation, thereby maintaining a comfortable and clean environment. This also curbs the load on the air conditioning system and conserves energy. In addition, the HRV is interlocked to Daikin's VRV system, SkyAir and other air conditioning systems an d automatically switches over ventilation mode, further increasing the effects of energy conservation. HRV operation has been centralized on the air conditioner remote controller allowing total control over air conditioning and ventilation with a simple configuration.
ON/OFF signal Cooling/Heating mode signal Set temperature signal Ventilation signal Humidifier ON/OFF signal
24.5-26.5/22 25.5-27.5/24
Casing
Galvanized steel plate Self-extinguishable polyurethane foam mm kg 269X760X509 24 285X812X800 33 348X988X852 48 348X988X1,140 710X1,498X852 710X1,498X1,140 61 132 158
Indoor unit
Insulation Material
Air to air cross flow total heat (Sensible heat + latent heat) exchange Specially processed nonflammable paper Multidirectional fibrous fleeces Sirroco fan Ultra-High 150/150 150/150 110/110 69/98 39/54 20/24 0.030X2 100 150 250/250 250/250 155/145 64/98 39/54 20/20 350/350 350/350 230/210 98/142 70/85 25/15 0.090X2 500/500 500/500 350/300 98/147 54/54 25/20 650/650 650/650 500/440 93/162 39/69 25/34 0.140X2 200 -15C to +50CDB, 80% RH or less 800/800 800/800 670/660 137/225 98/118 49/69 0.230X2 250 1,000/1,000 1,000/1,000 870/800 157/196 98/108 78/69 1,500/1,500 1,500/1,500 1,200/1,200 137/206 98/118 49/69 0.230X4 350 2,000/2,000 2,000/2,000 1,400/1,400 137/196 78/88 59/69
High Low
Fan External Static Pressure (Pa) [50Hz/60Hz] Motor Output Connection Duct Diameter Unit ambient condition
Note: 1. Sound level is measured at 1.5m below the center of the body. 2. Air flow rate can be changed over to Low mode or High mode. 3. Sound level is measured in an anechoic chamber. Sound level generally become greater than this value depending on the operating conditions, reflected sound, and peripheral noise. 4. The sound level at the air discharge port is about 8 dB higher than the unit's sound level. 5. Even when the outdoor temperature is below -15C, the system is operable down to -20C with the preheater installed at the outdoor air intake side.
50CDB
285 mm
-15CDB
51
52
R410A
Precautions
System/ Precautions on
Refrigerant Refrigeration oil Condensing pressure R22 Mineral oil (Suniso) 1.84MPa (18.8kg/cm 2) R410A Synthetic (ether) oil 2.97MPa (30.3kgf/cm 2)
(Single-component refrigerant) (Quasi-azeotropic mixture refrigerant)
Installation
Tools
Several dedicated tools are required for the installation work of R410A models. Some of conventional tools can be used except tools actually used to the installation work for R22 models.
R410A applies higher pressure than R22 and uses refrigeration oil different from R22. Therefore, piping works and tools are also different from those for R22 refrigerants.
Work process / Usage Pipe cutting Pipe flaring Applying to flared section Flare nut jointing Pipe expanding in connection of pipe Pipe bending Air tight test Oxidation proof for inside pipe Pipe brazing
Interchangeability with conventional tool Interchangeable and can be used. Dedicated flaring tool is required due to flaring dimension change. Use dedicated ether oil, ester oil, alkyl-benzene oil or mixture of these oils. Dedicated torque wrench is required due to different size of 1/2 "and 5/8" flare nuts.
Flaring tool Piping assembling oil Refrigerant (Refrigerant oil) piping work Torque wrench Pipe expander Pipe bender Nitrogen Welder Gauge manifold Charging hose
(Unit : mm)
From air tight test Refrigerant charging using to refrigerant vacuum and operation check additional charging Vacuum drying
Dedicated gauge manifold and charge hose are required due to high pressure and prevention of intoroduction of impurities. Interchangeable and can be used. (Be strictly sure that oil does not flow in reverse to the unit during pump stop.) Previous tool cannot be used due to different refrigerant characteristics. (Measuring instrument must be used.)
Type Copper tube O.D. 6.4 Copper tube W.T. ( minimum ) 0.40 requirement
O type 9.5 0.60 12.7 0.80 15.9 0.99 19.1 0.66 22.2 0.77 25.4 0.88 28.6 0.99 1.10
1/2H type 31.8 34.9 1.21 38.1 1.32 41.3 1.43 44.5 1.54 50.8 1.76 54.1 1.87
Vacuum pump Charging cylinder Weighing scale for refrigerant charging Gas leakage detector
* The table shows the requirements of Japanese High Pressure Gas Control low. The thickness and material shall be selected in a ccordance with local code.
Refrigerant additional charging Interchangeable and can be used. Gas leakage check Dedicated detector is required (Use detector for R410A).
Prior to work
Check the refrigerant to be used Preparing of working drawing Mounting sleeves and inserts Installing indoor unit Refrigerant piping work Drain piping work Duct work Insulation work Electric work (Connection wiring / Power supply) Setting various items
(1) Check wall thickness of copper tube (Refer to the table "Wall thickness of refrigerant pipe") (2) Maintain cleanliness inside of pipe. (3) Make sure to conduct N 2 blowing when brazing is required. (4) Pay attention on pipe flaring and oil to be coated on flared section. (5) Be sure to use torque wrench.
Flaring
Make sure to conduct chamfering (filing) at cut section, since a large wall thickness of pipe results large burr. Be aware of no cutting chips left inside pipe. Apply appropriate amount of refrigeration oil on outer / inner surface of flared section to prevent leakage. Make sure to use synthetic oil (ether oil, ester oil, archi-benzene oil or mixture of those oils) as refrigeration oil.
(1) Make sure to conduct air tight test. (2) Confirm the pressure of 3.8 MPa does not decrease for 24 hours. (In case the design pressure of 3.8 MPa)
* Specifications vary depending on model types. Confirm by referring to the installation manual.
Refrigerant charging
Charge R410A from service port at liquid side stop value of outdoor unit in liquid phase. At that time, conduct vacuum drying using vacuum pump.
Air-tightness test
Make sure to conduct air-tightness test.
Work
Foundation work for outdoor unit Installation of outdoor unit Air tight test Vacuum drying Refrigerant additional charging Test run / Adjustment Preparing documents required before delivery Delivery / Operation instruction
(1) Vacuum grade is -755 mmHg or lower (2) Use dedicated vacuum pump
(1) Confirm the correct amount of refrigerant. (2) Be sure to charge refrigerant in liquid phase. (3) Use the dedicated gauge manifold and charging hose. (4) The refrigerant amount to be charged is shown in the installation manual. (5) Record the added refrigerant amount to the record sheet.
Preparation of documents and drawings in accordance with local codes and standard.
Conduct installation work for R410A model following above mentioned piping work procedure. Otherwise, unit may have trouble. Refer to the "Work execution and control for R410A model" for the details on handling of R410A, installation works and tools.
53
54