Product Specification

37258G

Genset Control
for Multiple
Unit Operation

DESCRIPTION
The easYgen-3000 Series are control units for genset management applications. The numerous inputs and
outputs, along with a modular software structure, permit you to use the easYgen-3000 Series for a wide range
of applications with only a single part number. This includes stand-by, AMF, peak shaving, import-export, cogeneration or distributed generation, among others. Also the easYgen-3000 Series is compatible for island, island
parallel, mains parallel and multiple unit mains parallel operations.
The easYgen-3000 Series is able to control up to 32 gensets connected in a network with automatic sequencing.
The easYgen-3000 Series is available in two variants, the easYgen-3100 for cabinet back panel installation,
and the easYgen-3200 with graphical display and soft keys for front panel mounting.
FlexAppTM This feature provides the tools to easily configure the number of operated breakers: None, GCB,
GCB and MCB.
LogicsManagerTM Woodward's LogicsManager software enables to change the operation sequences and
adapt them to specific needs. The LogicsManager accomplishes this by monitoring a range of measuring values and internal states, which are combined logically with Boolean operators and programmable timers. This
enables to create and/or modify control and relay functions.
FlexInTM The analog inputs are configurable to operate with VDO, resistive, and/or 0 to 20 mA senders.
Flexible Outputs Speed and voltage bias outputs are configurable to function with all speed governors and
voltage regulators. The outputs can also be used as freely scalable outputs (e.g. for driving external meters).

Peak shaving operation


Stand-by operation
AMF operation
Cogeneration (CHP)
Isolated & mains parallel
operation
Import/export control
Soft loading features
Open/closed transition

FlexCANTM Advanced network interfaces ensure unsurpassed control performance from engine control up
to total plant operation. The easYgen-3000 Series is capable of working with all common industrial interfaces,
including CAN, RS-232, and RS-485. The multiple communication protocols permit the easYgen-3000 Series to
communicate with a vast majority of engine control units (ECUs), external I/O boards, PLCs, and modems.
CANopen, J1939, Modbus RTU, and Modem protocols are supported.

Load sharing and loaddependent start/stop for


up to 32 units

DynamicsLCDTM The adaptive and interactive 5.7", 320x240 pixel graphical LC display with soft keys and a
clear menu structure ensures intuitive user operation and navigation.

Programmable operation
sequences

Features
Operation modes: Auto, Stop, Manual, and Load/No Load test modes via discrete input possible
Breaker control: Slip frequency / phase matching synchronization, open-close control, breaker monitoring
Load transfer features: open / closed transition, interchange, soft loading / soft unloading, mains parallel
Process and load-dependent start/stop logic for diesel and gas engines programmable for spinning or system
reserve with fixed or dynamic priorities.
Real and reactive power load sharing with up to 32 units
Remote control via interface and discrete/analog inputs for adjusting speed, frequency, voltage, power, reactive
power, and power factor set points
Complete integrated engine and generator protection as well as mains monitoring features
Freely configurable PID controllers for various control purposes, such as heating circuit control (CHP applications), water level, fuel level, or pressure and/or other process values
Special Scania S6, MTU ADEC, Volvo EMS2 & EDC4, Deutz EMR2, MAN MFR/EDC7, SISU EEM, Cummins
and Woodward EGS02 ECU support (depending on Package)
Counters for operating hours / engine starts / maintenance / active energy / reactive energy
Configurable trip levels / delay timers / alarm classes for monitoring and protective functions
Clear text display and evaluation of up to 100 J1939 analog values
Discrete and analog I/O expansion board connectivity (Woodward IKD 1 or Phoenix Contact IL series)
Front panel and PC configurable (ToolKit software)
Multi-level password protection for access via HMI or interface
Multi-lingual capability !"#$%&'()*+,-."()/,+"0'()12."%&'()3'%"+&+()4.2."+&+()56.$%."()78,69#9+&+():9,;%&'()<9&&%."()78$%&'=
Event recorder (300 events, FIFO) with real time clock

Multi-lingual capability
CANopen / J1939 ECU
Control
Modbus RTU Protocol
CE marked
UL/cUL Listing
LR & ABS Marine

SPECIFICATIONS
78?+,)&922$@)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)BCDCE)FG0) H)68)EI)FG0=)
5"6,%"&%0)08"&9-26%8")AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)-.JA)BK)L)
M-N%+"6)6+-2+,.69,+) 82+,.6%8"=)AAAAAAAAAAAAAAAAAAAAAAA)OCI)68)KI)P3)D)OE)68)BQH)P/)
M-N%+"6)6+-2+,.69,+) &68,.#+=)AAAAAAAAAAAAAAAAAAAAAAAA)ORI)68)HI)P3)D)OCC)68)BKS)P/)
M-N%+"6)'9-%G%6@AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)TQ)U()"8"O08"G+"&%"#)
Voltage)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)) D"=
100 Vac [1])
<.6+G) F,.6+G=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)STDBCI)F.0)
)
V.JA)W.$9+) F-.J=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)HSDBQI)F.0)
)
) <.6+G)&9,#+)W8$6A F&9,#+=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)CAQ);F)
and 400 Vac [4] <.6+G) F,.6+G=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)CKKDEHI)F.0)
)
V.JA)W.$9+) F-.J=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)RESDSII)F.0)
)
) <.6+G)&9,#+)W8$6A F&9,#+=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)EAI);F)
M009,.0@)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)3$.&&)B)
V+.&9,.N$+).$6+,".68,)?%"G%"#&)AAA)R2OR?()R2OE?()R2OE?)XY()B2OC?()B2OR?)
1+66%"#),."#+)AAAAAAAAAAAAAAAAAAAAA)2,%-.,@)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAQI)68)SQI(III)F.0)
Z%"+.,)-+.&9,%"#),."#+)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)BACQ[F,.6+G)
V+.&9,%"#)\,+]9+"0@AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)QIDSI)^_) EI)68)HQ)^_=)
^%#')5-2+G."0+)5"296`)<+&%&6."0+)2+,)2.6')AAAAAAA)aBb)IAETH)V#()aEb)CAI)V#)
V.JA)28?+,)08"&9-26%8")2+,)2.6')AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)c)IABQ)L)
Current (Isolated)) <.6+G) 5,.6+G=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)aBb)AADB)M)8,)aQb)AADQ)M)
Z%"+.,)-+.&9,%"#),."#+)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)5#+")d)RAI[5,.6+G)
)
5-.%"&D#,89"G)d)BAQ[5,.6+G)
1+66%"#),."#+)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)B)68)RC(III)M)
e9,G+")AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)c)IABQ)FM)
<.6+G)&'8,6O6%-+)09,,+"6) B)&=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAaBb)QI[5,.6+G()aQb)BI[5,.6+G)
Power)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA))
1+66%"#),."#+)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)IAQ)68)TT(TTTAT);LD;W.,)
Discrete inputs)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)%&8$.6+G)
5"296),."#+)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)BCDCE)FG0) H)68)EI)FG0=)
5"296),+&%&6."0+)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA).22,8JA)CI);X'-&)
)
)
)

Relay outputs)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)%&8$.6+G)
38"6.06)-.6+,%.$)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)M#3GX)
Z8.G) *7=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)CAII)M.0fCQI)F.0)
)
CAII)MG0fCE)FG0)D)IARS)MG0fBCQ)FG0)D)IABH)MG0fCQI)FG0)
7%$86)G96@) 7Y=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA))
)
BAII)MG0fCE)FG0)D)IACC)MG0fBCQ)FG0)D)IABI)MG0fCQI)FG0)
Analog inputs (none isolated))AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA\,++$@)&0.$+.N$+)
:@2+)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)I)68)QII)X'-&)D)I)68)CI)-M)
<+&8$96%8")AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)BB)e%6)
Analog outputs (isolated))AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA\,++$@)&0.$+.N$+)
:@2+)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)g)BI)F)D)g)CI)-M)D)7LV)
5"&9$.6%8")W8$6.#+) 08"6%"989&$@=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)BII)F.0)
5"&9$.6%8")6+&6)W8$6.#+) B&=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)QII)F.0)
<+&8$96%8")AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)BBDBC)e%6) G+2+"G%"#)8").".$8#)896296=)
g)BI)F) &0.$+.N$+=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)%"6+,".$),+&%&6."0+)hB);X'-&)
g)CI)-M) &0.$+.N$+=)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)-.J%-9-)$8.G)QII)X'-&)
Housing) RCII=) ) /,8"6)2."+$)\$9&')-89"6%"#)AAAAAAAAAAAAAAAAAA)7$.&6%0)'89&%"#)
Y%-+"&%8"&)
) LJ^JY)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)CHC)[)CBK)[)TT)--)
/,8"6)096896)
) LJ^)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)CET)aiBABb)[)BHR)aiBAIb)--)
38""+06%8")AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)&0,+?D2$9#)6+,-%".$&)CAQ)--j)
/,8"6)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)%"&9$.6%"#)&9,\.0+)
1+.$%"#)
) /,8"6)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)57SS) ?%6')&0,+?)\.&6+"%"#=)
)
) /,8"6)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)57QE) ?%6')0$.-2)\.&6+"%"#=)
)
) e.0;)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)57CI)
L+%#'6)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA).22,8JA)B(HQI)#)
Housing) RBII=) ) 1?%60')0.N%"+6)N.0;)-89"6%"#)AAAAA)1'++6)-+6.$)'89&%"#)
Y%-+"&%8"&)
) LJ^JY)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)CQI)[)CCH)[)HE)--)
38""+06%8")AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)&0,+?D2$9#)6+,-%".$&)CAQ)--j)
7,86+06%8")&@&6+-)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)57)CI)
L+%#'6)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA).22,8JA)C(BQI)#)
Disturbance test) 3!=)AAAAAAAAAAAA)6+&6+G).008,G%"#)68).22$%0.N$+)!k)#9%G+$%"+&)
Listings)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)lZ()0lZ) 0lZ)8"$@)\8,)+.&m#+"ORBII=)
Marine)AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA)Z<) :@2+)M22,8W.$=()Me1) Y+&%#")M&&+&&-+"6=)

DIMENSIONS
Plastic housing for front panel mounting (3200)

Metal housing for cabinet mounting (3100)

216 mm 181 mm

227 mm

282 mm
247 mm

84 mm

87 mm

99 mm

250 mm

TERMINAL DIAGRAM

)
International

L88G?.,G))
7X)e8J)BQBT)
/8,6)38$$%"&)3X()l1M)
HIQCCOBQBT)
BIII)!.&6)Y,.;+)<8.G)
/8,6)38$$%"&)3X)HIQCQ)
7'n)iB) TKI=)EHCOQHBB)
/.Jn)iB) TKI=)ETHORIQH)
)

Europe

L88G?.,G)*-N^)
^."G?+,;&6,.&&+)CT)
KIQSQ)16966#.,6()*+,-."@)
7'n)iET) I=)KBB)KHT)QEOI)
/.Jn)iET) I=)KBB)KHT)QEOBII)
+-.%$n)&6#6O%"\8f?88G?.,GA08-)
)

Distributors & Service

For more information contact:

L88G?.,G)'.&).")%"6+,".6%8".$)
"+6?8,;)8\)G%&6,%N968,&)."G)
&+,W%0+)\.0%$%6%+&A)/8,)@89,)
"+.,+&6),+2,+&+"6.6%W+()0.$$)6'+)
/8,6)38$$%"&)2$."6)8,)&++)6'+)
L8,$G?%G+)Y%,+068,@)8")89,)
?+N&%6+A
)
)
)
)
www.woodward.com/power)

19No+06)68)6+0'"%0.$)-8G%\%0.6%8"&A)
:'%&)G809-+"6)%&)G%&6,%N96+G)\8,)
%"\8,-.6%8".$)29,28&+&)8"$@A)56)%&)"86)
68)N+)08"&6,9+G).&)0,+.6%"#)8,)
N+08-%"#)2.,6)8\)."@)L88G?.,G)
*8W+,"8,)38-2."@)08"6,.069.$)8,)
?.,,."6@)8N$%#.6%8")9"$+&&)+J2,+&&$@)
&6.6+G)%").)?,%66+")&.$+&)08"6,.06A)
L+).22,+0%.6+)@89,)08--+"6&)
.N896)6'+)08"6+"6)8\)89,)29N$%0.O
6%8"&A)7$+.&+)&+"G)08--+"6&)
%"0$9G%"#)6'+)G809-+"6)"9-N+,)
N+$8?)68)
&6#6OG80f?88G?.,GA08-)

Woodward
All Rights Reserved
)
RKCQH*)O)CIBIDIQD16966#.,6

FEATURES OVERVIEW
easYgen-3000 Series
V8G+$)
7.0;.#+)

RBII)
7B)

RCII)
7C)

) )

) )

7B)

) )

7C)

Measuring
*+"+,.68,)W8$6.#+) RO2'.&+DEO?%,+=)
*+"+,.68,)09,,+"6) RJ)6,9+),A-A&A=
V.%"&)W8$6.#+) RO2'.&+DEO?%,+=)
V.%"&)8,)#,89"G)09,,+"6) BJ)6,9+),A-A&A=)pB)
e9&N.,)W8$6.#+) BO2'.&+DCO?%,+=)

)
)
)
)
)

Control
e,+.;+,)08"6,8$)$8#%0) 82+")."G)0$8&+G)6,."&%6%8"=)
M968-.6%0()V."9.$()1682()."G)6+&6)82+,.6%"#)-8G+&)
1%"#$+)."G)-9$6%2$+O9"%6)82+,.6%8")
V.%"&)2.,.$$+$)-9$6%2$+O9"%6)82+,.6%8") 92)68)RC)9"%6&=)
MV/) .968)-.%"&)\.%$9,+=)."G)&6."GON@)82+,.6%8"
3,%6%0.$)-8G+)82+,.6%8")
*3e)."G)V3e)&@"0',8"%_.6%8") &$%22%"#)D)2'.&+)-.60'%"#=)
5"6+,0'."#+) %-28,6)D)+J28,6)08"6,8$=)
Z8.GOG+2+"G+"6)&6.,6D&682)
"D\()F()7()q()."G)7/),+-86+)08"6,8$)W%.).".$8#)%"296)8,)%"6+,\.0+)
Z8.GDW.,)&'.,%"#)\8,)92)68)RC)#+"&+6&)
/,++$@)08"\%#9,.N$+)75Y)08"6,8$$+,&)

FlexAppTM)

C)

O)

)
)
)
)
)

)
)
)
)
)

)
)
)
)
)

)
)
)
)
)

)
)
)
)
)

)
)
)
)
)

)
)
)
)
)

)
)
)
)
)

)
)
)
)

)
)
)
)

)
)
)
)

)
)
)
)

)
)
)
)

)
)
)
)
)
)
)

)
)
)
)
)
)
)

)
)
)
)
)
)
)

C)
)
)
)
)
)
)
)
)
)
)
O)

)
)
)
)

)
)
)
)
)
)
)

C)
)
)
)pC)
)
)
)
)
)
)
)
R)

)
)
)
)
)
)
)

)
)
)
)
)
)
)

O)

) )
) )

)
)
)
)
)
C
)
)
)pC)
)
)
)
)
)
)
)
R

HMI

18\6);+@&) .GW."0+G)Z3)G%&2$.@=)
DynamicsLCDTM)
16.,6D&682)$8#%0)\8,)G%+&+$)D)#.&)+"#%"+&)
389"6+,&)\8,)82+,.6%"#)'89,&)D)&6.,6&)D)-.%"6+"."0+)D).06%W+D,+.06%W+)+"+,#@
38"\%#9,.6%8")W%.)73)pR)
!W+"6),+08,G+,)+"6,%+&)?%6'),+.$)6%-+)0$80;) N.66+,@)N.0;92=)
Protection
Mk15p
*+"+,.68,n)W8$6.#+)D)\,+]9+"0@)
QT)D)CK)D)HBX)D)HBl)
*+"+,.68,n)8W+,$8.G(),+W+,&+D,+G90+G)28?+,)
RC)D)RC<)D)RC/)
*+"+,.68,n)9"N.$."0+G)$8.G)
ES)
*+"+,.68,n)%"&6."6."+89&)8W+,09,,+"6)
QI)
*+"+,.68,n)6%-+O8W+,09,,+"6) 5!3)CQQ)08-2$%."6=)
QB)
*+"+,.68,n)#,89"G)\.9$6)pE)
QI*)
*+"+,.68,n)28?+,)\.068,
QQ)
*+"+,.68,n),86.6%8")\%+$G)
)
!"#%"+n)8W+,&2++G)D)9"G+,&2++G)
BC)D)BE)
!"#%"+n)&2++G)D)\,+]9+"0@)-%&-.60')
)
!"#%"+n)Yi).9J%$%.,@)+J0%6.6%8")\.%$9,+)
)
V.%"&n)W8$6.#+)D)\,+]9+"0@)
QT)D)CK)D)HBX)D)HBl)
V.%"&n)2'.&+)&'%\6)D),86.6%8")\%+$G)
KH)D)

O)

RII)

) )
) )

)
)
)
RII)

) )
) )
)
)
)
)
)
)
)
)
)
)
)
)
)

)
)
)
)
)
)
)
)
)
)
)
)
)

)
)
)
)
)
)
)
)
)
)
)
)
)

) )
) )
)
)
)
)
)
)
)
)
)
)
)
)
)

)
)
)
)
RII)

)
)
)
)
)
)
)
)
)
)
)
)
)

)
)
)
)
)
)
)
)
)
)
)
)
)

) )
) )
) )
) )
)
)
)
)
)
)
)
)
)
)
)
)
)

)
)
)
)
RII)

)
)
)
)
)
)
)
)
)
)
)
)
)

)
)
)
)
)
)
)
)
)
)
)
)
)

I/Os
)
)
)
12++G)%"296) -.#"+6%0)D)&?%60'%"#`)7%0;92=)
) )
) )
) )
Y%&0,+6+).$.,-)%"296&) 08"\%#9,.N$+=)
BI)
) )
BI)
) )
BI)
) )
BI)
Y%&0,+6+)896296&) 08"\%#9,.N$+=)
LogicsManagerTM) -.JA)BC) ) ) -.JA)BC) ) ) -.JA)BC) ) ) -.JA)BC)
!J6+,".$)G%&0,+6+)%"296&)D)896296&)W%.)3Mk82+") -.J%-9-=)
BS)D)BS) ) ) RC)D)RC) ) ) BS)D)BS) ) ) RC)D)RC)
M".$8#)%"296&)pQ) 08"\%#9,.N$+=))
FlexInTM)
R)
) )
R)
) )
R)
) )
R
M".$8#)896296&) iDO)BIF()iDO)CI-M()7LV`)08"\%#9,.N$+=))
C)
) )
C)
) )
C)
) )
C
!J6+,".$).".$8#)%"296&)D)896296&)W%.)3Mk82+") -.J%-9-=)
O)
) ) BS)D)E ) )
O)
) ) BS)D)E)
Y%&2$.@)8\)4BTRT).".$8#)W.$9+&) "9-N+,)8\)17k&=)
BS)
) )
O)
) )
BS)
) )
O)
Y%&2$.@)."G)+W.$9.6%8")8\)4BTRT).".$8#)W.$9+&) &9228,6+G)17k&=
O)
) ) BII) ) )
O)
) )
BII)
3Mk)N9&)08--9"%0.6%8")%"6+,\.0+&)pS)
FlexCANTM)
C)
) )
C)
) )
C)
) )
C
<1OCRCDEHQ)V8GN9&)<:l)1$.W+)%"6+,\.0+ &=)
B)D)B)
) ) B)D)B) ) ) B)D)B) ) )
B)D)B)

Listings/Approvals
lZ)Z%&6%"#)
0lZ)Z%&6%"#)
Z<)r)Me1)V.,%"+)
3!)V.,;+G

)
)
)
)

) )
) )
) )

) )
) )
) )

)
O)
)
)

) )
) )
) )

)
O)
)
)

Part Numbers
BM)3:)%"296&)D)\,8"6)2."+$)-89"6%"#)?%6')G%&2$.@))pK)
QM)3:)%"296&)D)\,8"6)2."+$)-89"6%"#)?%6')G%&2$.@))pK)
BM)3:)%"296&)D)0.N%"+6)N.0;)-89"6%"#)?D8)G%&2$.@)
QM)3:)%"296&)D)0.N%"+6)N.0;)-89"6%"#)?D8)G%&2$.@)
12.,+)08""+068,);%6)
)

7Dk)HEEIO)
7Dk)HEEIO)
7Dk)HEEIO)
7Dk)HEEIO)
7Dk)HTCRO)

O)
O)
BTRB)
BTRI)
BRBE)

)
)
)
)
)

)
)
)
)
)

O)
O)
BTRR)
BTRC)
BRBE)

) )

)
)
)
)

)
)
)
)

BTCC)
BTCR)
O)
O)
BRBE)

) )

)
)
)
)

)
)
)
)

BTCE)
BTCQ)
O)
O)
BRBE)

pB) -.%"&)8,)#,89"G)09,,+"6)&+$+06.N$+))
pQ) &+$+06.N$+)G9,%"#)08"\%#9,.6%8")N+6?++")FYX) I)68)BHI)X'-()I)68)Q)N.,=()FYX) I)68)BHI)X'-()I)68)BI)N.,=()FYX)
pC) ,+\+,)68)6'+)M22$%0.6%8")V."9.$)RKEKB)\8,)
I)68)RHI)X'-()EI)68)BCIP3=()FYX) I)68)RHI)X'-()QI)68)BQIP3=()76BII()<+&%&6%W+)%"296) 8"+O)8,)6?8O28$+()C26A)
.22$%0.6%8"&)?%6')-8,+)6'.")H)2.,.$$+$)#+"&+6&)
$%"+.,)8,)T26A)9&+,)G+\%"+G)=()8,)CI)-M) IDE)68)CI -M()\,++$@)08"\%#9,.N$+=
N+0.9&+)8\)N9&)$8.G)$%-%6&)
pS) \,++$@)&+$+06.N$+)G9,%"#)08"\%#9,.6%8")N+6?++")3Mk82+")8,)4BTRT`),+]9+&6)%"\8,-.6%8"))
pR) W%.)&+,%.$)08""+06%8")."G):88$s%6)&8\6?.,+) %"0$9G+G=) pK) .)&0,+?)."G).)0$.-2);%6).,+)G+$%W+,+G)?%6')6'+)9"%6)\8,)\.&6+"%"#
pE) -+.&9,+G)#,89"G)09,,+"6)

SIRCOVER and

Manual Changeover Switches

appli_114_a

svr_059_a_1_cat

svr_099_b_1_cat

SIRCOVER BY-PASS

Changeover switches with fully visualised breaking


from 125 to 3200 A
Function

General characteristics

SIRCOVER products are manually


operated multipolar changeover switches.
They provide changeover, source inversion
or switching under load between two low
voltage power circuits, as well as their
safety isolation.

3 stable positions, (I, 0, II) or overlapping


contacts (I, I+II, II), and on load
changeover switching (AC-22 and AC-23).
Fully visualized breaking.
IP20 devices and accessories.

SIRCOVER BY-PASS are manually


operated changeover switches.
They are a combination of three interlocked
switches enabling the use with 3 + 6 pole
or 4 + 8 pole. They insulate by providing
simultaneous safety isolation top and
bottom and by passing loads of low
voltage circuits mainly during maintenance
operations.

274

C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:274 Sec1:274

Conformity
to standards

Devices 6 or 8 pole
Devices with oversized neutral ex.:
3 x 250 A + N 400 A.
Devices with
advanced neutral.

Approvals and
certifications (1)

IEC 60947-3
IS 14947-3
EN 60947-3
VDE 0660-107
(1992)
NBN EN 60947-3
BS EN 60947-3

Available
on request

Bureau Vritas
BBJ Poland
(Attestaion of
verification)
(1) Product reference on
request.

General Catalogue 2011-2012 SOCOMEC

15/11/10 16:28:11

Manual Changeover Switches

SIRCOVER and SIRCOVER BY-PASS

What you need to know


SIRCOVER with 3 stable positions (I, O, II) are 3 or 4 pole devices from 125 A
to 3200 A. They are available enclosed in a steel or polyester enclosure from
125 to 1600 A.
SIRCOVER with overlapping contacts (I-I+II-II) are 3 or 4 pole devices
available from 125 to 1800A. They are available enclosed in a steel enclosure
from 125 to 1600 A.
SIRCOVER BY-PASS with 3 stable positions (I, O, II) are a combination of
three interlocked switches enabling the use with 3+6 poles or 4+8 poles from
125 to 1600 A. They are available in steel enclosure from 125 to 1600 A and
with overlapping contacts (I, I+II, II).

svr_136_a_1_x_cat

appli_114_a

SIRCOVER and SIRCOVER BY-PASS can be used with a direct or external


handle.

A connection kit for copper bars allows the link between the 2 connection
terminals of one pole (fig 1 and 2) and the bridging of the upstream and
downstream link for ratings 2000, 2500 and 3200A (fig 3).

Top or bottom flat


connection

Edgewise connection
Top or bottom

SOCOMEC General Catalogue 2011-2012

C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:275 Sec1:275

Fig 3

acces_231_a_1_cat

Fig 2

acces_229_b_2_cat

acces_226_c_2_cat

Fig 1

Top or bottom bridging


connection

275

15/11/10 16:29:07

SIRCOVER and SIRCOVER BY-PASS - References

svr_051_a_1_cat

SIRCOVER I-0-II

Rating
(A)

No. of
poles

Switch body

3P

4100 3013(1)

4P

4100 4013(1)

3P

4100 3016(1)

4P

4100 4016(1)

3P

4100 3019

4P

4100 4019

3P

4100 3025(1)

Direct handle

External
handle

Shaft for
external
handle

Bridging bar*

Terminal
shrouds

Terminals
protection
screen

3P
2694 3014(5)(6)

3P
1509 3012(7)

4P
2694 4014(5)(6)

4P
1509 4012(7)

3P
2694 3021(5)(6)

3P
1509 3025(7)

4P
2694 4021(5)(6)

4P
1509 4025(7)

1st/2nd contact
3P
NO/NC
(5)(6)
4109 0021(4) 2694 3051

3P
1509 3063(7)

4P
2694 4051(5)(6)

4P
1509 4063(7)

Auxiliary
contacts

125 A

160 A

4109 0019

200 A

250 A
4P

4100 4025(1)

3P

4100 3039(1)

4P

4100 4039

(1)

3P

4100 3050(1)

Type S2
Black
4199 5012(2)

Black IP55
1421 2113
Black IP65
1423 2113(2)

400 A

200 mm
1400 1020

4109 0025

320 mm
1400 1032(2)
4109 0039

500 A

4109 0050

4P

4100 4050(1)

3P

4100 3063(1)

630 A

4109 0063

4P

4100 4063(1)

3P

4100 3080(1)

4P

4100 4080(1)

3P

4100 3120(1)

4P

4100 4120

(1)

3P

4100 3160(1)

4P

4100 4160(1)

3P

4100 3180

4P

4100 4180

3P

4100 3200

4P

4100 4200

3P

4100 3250

4P

4100 4250

3P

4100 3320

4P

4100 4320

800 A

3P
1509 3080(7)

4109 0080

1 250 A
Black
2799 7052(2)

S4 type
Black IP65
1443 3113(2)

1 600 A

200 mm
1401 1520

4P
1509 4080(7)

4109 0120

320 mm
1401 1532(2)

3P
1509 3160(7)
4109 0160

4P
1509 4160(7)

1 800 A

2 000 A

2 500 A

Black
2799 7012(2)

Black IP65
2799 7146(2)

3 200 A

320 mm
2799 3018(2)

1st contact
NO/NC
included
included

(3)

2nd contact
NO/NC
4409 0022(4)

* 1 piece required per pole.


(1) Available enclosed (see pages 498 and 500 "Enclosed changeover switches").
(2) Standard.
(3) See page 281 "Copper bars connection kits".
(4) 2 pieces: one for position I and one for position II.
(5) To shroud front switch top and bottom 2 references required.
(6) To fully shroud front, rear, top and bottom 4 references required.
(7) 2 pieces: one for top side and another for bottom side.

276

C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:276 Sec1:276

General Catalogue 2011-2012 SOCOMEC

15/11/10 16:29:43

Manual Changeover Switches

SIRCOVER and SIRCOVER BY-PASS

svr_051_a_1_cat

SIRCOVER I - I+II - II

Rating (A)

No. of
poles

Switch body

3P

4190 3013(1)

4P

4190 4013(1)

3P

4190 3016(1)

Direct handle

External
handle

Shaft for
external
handle

Bridging bar*

Auxiliary
contacts

Terminal
shrouds

Terminal
screens

125 A

160 A

3P
3P
2694 3014(4)(5) 1509 3012(6)
4P
4P
2694 4014(4)(5) 1509 4012(6)

4109 0019

4P

4190 4016(1)

3P

4190 3019

4P

4190 4019

3P

4190 3025(1)

4P

4190 4025(1)

3P

4190 3039(1)

4P

4190 4039(1)

3P

4190 3050(1)

4P

4190 4050(1)

3P

4190 3063(1)

4P

4190 4063(1)

3P

4190 3080(1)

4P

4190 4080(1)

3P

4190 3120(1)

4P

4190 4120(1)

3P

4190 3160(1)

4P

(1)

200 A

250 A

Black
4199 5012(2)

S2 type
Black IP65
1423 2114(2)

200 mm
1400 1020
320 mm
1400 1032(2)

400 A

4109 0025

3P
3P
2694 3021(4)(5) 1509 3025(6)
4P
4P
2694 4021(4)(5) 1509 4025(6)

4109 0039

500 A

4109 0050

630 A

4109 0063

800 A

4109 0080

1 250 A
Black
2799 7052(2)

S4 type
Black IP65
1443 3114(2)

1 600 A

200 mm
1401 1520

4109 0120

320 mm
1401 1532(2)

4190 4160

4109 0160

3P

4190 3180

4P

4190 4180

1 800 A

1st/2nd contact
NO/NC
4109 0021(3)

3P
3P
2694 3051(4)(5) 1509 3063(6)
4P
4P
2694 4051(4)(5) 1509 4063(6)

3P
1509 3080(6)
4P
1509 4080(6)

3P
1509 3160(6)
4P
1509 4160(6)

* 1 piece required per pole.


(1) Available enclosed (see pages 498 and 500 "Enclosed changeover switches").
(2) Standard.
(3) 2 pieces: one for position I and one for position II.
(4) To fully shroud front, rear, top and bottom 4 references required.
(5) To shroud front switch top and bottom 2 references required.
(6) 2 pieces: one for top side and another for bottom side.

SOCOMEC General Catalogue 2011-2012

C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:277 Sec1:277

277

15/11/10 16:29:46

SIRCOVER and SIRCOVER BY-PASS - References (continued)

svr_059_a_4_cat

SIRCOVER BY-PASS

Rating (A)

No. of
poles

Switch body
I-0-II

3+6P

4100 7013(1)

4+8P

4100 9013(1)

3+6P

(1)

4100 7016

4+8P

4100 9016(1)

Direct handle

External
handle

Shaft for
external
handle

Bridging bar

Auxiliary
contacts

Terminal
shrouds

Terminal
screens

125 A

160 A

S2 type
Black
4199 5012(2)

Black IP55
1421 2113(2)
Black IP65
1423 2113

3P
2694 3014(4)(5)

200 mm
1400 1020
4109 0019

4P
2694 4014(4)(5)

320 mm
1400 1032(2)

3+6P

4100 7019

4+8P

4100 9019

3+6P

4100 7025(1)

4+8P

4100 9025(1)

3P
2694 3021(4)(5)

3+6P

4100 7039(1)

4P
2694 4021(4)(5)

3P
1509 3012(6)
4P
1509 4012(6)

200 A

250 A

4109 0025

400 A

200 mm
1401 1520

4109 0039

1st/2nd
contact
NO/NC
4109 0021(3)

4+8P

4100 9039(1)

3+6P

4100 7050(1)

4+8P

4100 9050(1)

3P
2694 3051(4)(5)

3+6P

4100 7063(1)

4P
2694 4051(4)(5)

Black
2799 7052(2)

S3 type
Black IP65
1433 3113(2)

500 A

320 mm
1401 1532(2)

630 A

4109 0050

4109 0063

4+8P

4100 9063(1)

3+6P

4100 7080(1)

4+8P

4100 9080(1)

3+6P

4100 7120(1)

800 A

4109 0080

1 250 A
4+8P

4100 9120(1)

3+6P

4100 7160

4+8P

4100 9160

Black
Black IP65
2799 7012(2) 4199 7146(2)

1 600 A

200 mm
2799 3015

4109 0120

3P
1509 3025(6)
4P
1509 4025(6)

3P
1509 3063(6)
4P
1509 4063(6)

3P
1509 3080(6)
4P
1509 4080(6)

450 mm
2799 3019(2)
3P
1509 3160(6)
4109 0160

4P
1509 4160(6)

* For By-Pass 2 pieces are required per pole.


(1) Available enclosed (see pages 498 and 500 "Enclosed changeover switches").
(2) Standard.
(3) 2 pieces: one for position I and one for position II.
(4) To shroud front switch top and bottom 3 references required.
(5) To fully shroud front, rear, top and bottom 6 references required.
(6) 2 pieces: one for top side and another for bottom side.

278

C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:278 Sec1:278

General Catalogue 2011-2012 SOCOMEC

15/11/10 16:29:49

Manual Changeover Switches

SIRCOVER and SIRCOVER BY-PASS


Accessories

Direct handle

SIRCOVER
Rating (A)
125 630
800 1800
2000 3200

Handle color
Black
Black
Black

Handle type
Single lever
Single lever
Double lever

Reference
4199 5012
2799 7052
2799 7012

Handle type
Single lever
Single lever
Double lever

Reference
4199 5012
2799 7052
2799 7012

acces_153_a_2_cat

acces_129_b_1_cat

SIRCOVER BY-PASS
Rating (A)
125 200
250 630
800 1600

External operation handle

Handle color
Black
Black
Black

Use
The door interlocked external operation handle includes one padlockable handle, one
escutcheon and must be utilised with a shaft extension.
SIRCOVER
S4 type handle

S3 type handle

acces_152_a_2_cat

acces_151_a_1_cat

acces_150_a_1_cat

S2 type handle

Rating (A)
125 630
125 630
125 630
800 1800
800 1800
2000 3200

Switching
type
I - 0 - II
I - 0 - II
I - I+II - II
I - 0 - II
I - I+II - II
I - 0 - II

External
IP(1)
IP55
IP65
IP65
IP65
IP65
IP65

Handle
S2 type
S2 type
S2 type
S4 type
S4 type

Reference
1421 2113
1423 2113
1423 2114
1443 3113(2)
1443 3114(2)
2799 7146(2)

(1) IP: Degree of protection according to standard IEC 60529.


(2) Double lever handle.

SIRCOVER BY-PASS
Switching
Rating (A)
type
125 200
I - 0 - II
125 200
I - 0 - II
250 ... 630
I - 0 - II
800 1600
I - 0 - II

External
IP(1)
IP55
IP65
IP65
IP65

Handle
S2 type
S2 type
S3 type

Reference
1421 2113
1423 2113
1433 3113
4199 7146

(1) IP: Degree of protection according to standard IEC 60529.

acces_198_a_2_cat

Alternative S-type handle cover colours

Use
For single lever handles S1, S2, S3 type and for double lever handle S4 type.
Other colours: Consult us.
Color
Light grey
Dark grey
Light grey
Dark grey

To be ordered
in multiples of
50
50
50
50

Handle
S2, S3 type
S2, S3 type
S4 type
S4 type

Reference
1401 0001
1401 0011
1401 0031
1401 0041

S type handle adapter

acces_187_a_1_cat

Use
Enables S type handles to be fitted in place
of existing older style Socomec handles.
Adapter can also be utilised as a spacer to
increase the distance between the panel
door and the handle lever.

Color
Black

To be ordered
in multiples of
10

Dimensions
Adds 12 mm to the depth.

External IP(1)
IP65

Reference
1493 0000

(1) IP: Degree of protection according to standard IEC 60529.

SOCOMEC General Catalogue 2011-2012

C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:279 Sec1:279

279

15/11/10 16:29:53

SIRCOVER and SIRCOVER BY-PASS - References (continued)

Shaft guide for external operation

acces_260_a_2_cat

Use
To guide the shaft extension into the external handle.
This accessory enables handle to engage extension shaft with a misalignment of up to 15 mm.
Required for a shaft lenght over 320 mm.

Description
Shaft guide

Shaft for external handle

Reference
1429 0000

acces_143_b_1_cat

Use
Standard lengths:
- 200 mm,
- 320 mm,
- 450 mm.
Other lengths: Consult us.
SIRCOVER
Shaft length
(mm)
200 mm
320 mm
200 mm
320 mm
200 mm
320 mm
320 mm

Dimension X
(mm)
210 310
210 430
280 390
280 510
425 577
425 697
653 923

Reference
1400 1020
1400 1032
1400 1020
1400 1032
1401 1520
1401 1532
2799 3018(1)

SIRCOVER BY-PASS
Shaft length
Rating (A)
(mm)
200 mm
125 200
125 200
320 mm
250 400
200 mm
250 400
320 mm
500 630
200 mm
500 630
320 mm
800 1600
200 mm
800 1600
450 mm

Dimension X
(mm)
320 450
320 570
298 420
298 540
417 539
417 659
550 680
550 800

Reference
1400 1020
1400 1032
1401 1520
1401 1532
1401 1520
1401 1532
2799 3015(1)
2799 3019(1)

acces_144_b_1_cat

Rating (A)
125 400
125 400
500 630
500 630
800 1800
800 1800
2000 3200

acces_202_a_1_cat

(1) Extension shaft.

(1) Extension shaft.

Bridging bars

svr_068_a_1_x_cat

acces_208_a_2_cat

SIRCOVER BY-PASS

Use
Creation of a common link, on the top or
bottom side of the switch, in order to feed
load with either power supply I or/and II. For
SIRCOVER BY-PASS, two sets of bridging
bars are needed as the switch is composed
of three basic switch frames.
Rating (A)
125 200
250
400
500
630
800
1250
1600 ... 1800

Position I: 6 or 8 poles
Position II: 3 or 4 poles

Section (mm)
20 x 2.5
25 x 2.5
32 x 5
32 x 5
50 x 5
50 x 6
60 x 8
90 x 10

Reference
4109 0019
4109 0025
4109 0039
4109 0050
4109 0063
4109 0080
4109 0120
4109 0160

svr_124_a_1_cat

acces_041_a_1_cat

acces_205_a_2_cat

SIRCOVER

280

C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:280 Sec1:280

General Catalogue 2011-2012 SOCOMEC

15/11/10 16:30:07

Manual Changeover Switches

SIRCOVER and SIRCOVER BY-PASS

Copper bars connection kits for 2000 to 3200 A SIRCOVER


Fig.1

acces_226_b_1_x_cat

Use
Enables:
- To allow connection between the two
power terminals from a same pole for
2000 to 3200A ratings (Fig. 1 and Fig 2).
- Top or bottom bridging connection (Fig. 3).

For 3200 A rating, the connection pieces


(part A) are delivered bridged from factory.
Bolt sets must be ordered separately.
Technical notice for these specific
accessories is downloadable from
www.socomec.com

252
74
37 60

Fig. 2

155

Top or bottom flat connection - Fig. 1


129

acces_232_a_1_cat

74
37

Rating (A)
2 000 2 500
2 000 2 500

Piece
Connection - part A
Bolt set - part B

Quantity to order
per pole(1)
2
2

Reference
2619 1200
2699 1200

3 200
3 200

Connection - part A
Bolt set - part B

included
2699 1200

acces_228_b_1_x_cat

(1) Example for 3 pole device equipped upstream only: order 3 times the indicated quantities.

Top or bottom edgewise connection - Fig. 2

132

30303030 22

210

acces_233_a_1_cat

30303030

Rating (A)
2 000 2 500
2 000 2 500
2 000 2 500

Piece
Connection - part A
T piece - part C
Right angle - part D

Quantity to order
per pole(1)
2
2
2

Reference
2619 1200
2629 1200(2)
2639 1200(2)

3 200
3 200
3 200

Connection - part A
T piece - part C
Right angle - part D

2
2

included
2629 1200(2)
2639 1200(2)

(1) Example for 3 pole device equipped upstream only: order 3 times the indicated quantities.
(2) Bolt set is provided with the accessories.

Fig. 3

Top or bottom bridging connection -Fig. 3

acces_230_b_1_x_cat

148

225

acces_234_a_1_cat

30303030

svr_058_a_1_cat

Auxiliary contacts

Rating (A)
2 000 2 500
2 000 2 500
2 000 2 500
2 000 2 500

Piece
Connection - part A
Bolt set - part B
Bar - piece E
T piece - part C

Quantity to order
per pole(1)
2
2
1
1

Reference
2619 1200
2699 1200
4109 0250(2)
2629 1200(2)

3 200
3 200
3 200
3 200

Connection - part A
Bolt set - part B
Bar - piece E
T piece - part C

2
1
1

included
2699 1200
4109 0320(2)
2629 1200(2)

(1) Example for 3 pole device equipped upstream only: order 3 times the indicated quantities.
(2) Bolt set is provided with the accessories.

Use
Pre breaking and positions I and II
signalling: 1 or 2 NO/NC auxiliary contacts
in each position.
Low level auxiliary contacts: Consult us.

Connection to the control circuit


By 6.35 mm fast-on terminal.
Electrical characteristics
30 000 operations.

NO/NC changeover contact

acces_065_a_1_cat

Rating (A)
125 1800
2000 3200
2000 3200

Contact(s)
1st/2nd
1st
2nd

Reference
4109 0021
included
4409 0022

Characteristics
Operating current Ie (A)
Rating (A)
125 3200

SOCOMEC General Catalogue 2011-2012

C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:281 Sec1:281

Nominal
current (A)
16

A - 250
-13VAC
12

400 VAC
AC-13
8

24 VDC
DC-13
14

48 VDC
DC-13
6

281

15/11/10 16:30:17

SIRCOVER and SIRCOVER BY-PASS - References (continued)

Terminal shrouds
Use
Protection against direct contact with
terminals or connecting parts.

acces_206_a_2_cat

Rating (A)
125 200
125 200
250 400
250 400
500 630
500 630

No. of
poles
3P
4P
3P
4P
3P
4P

Advantage
Perforations allowing remote
thermographic inspection without removal.

Position
top / bottom / front (I) / rear (II)
top / bottom / front (I) / rear (II)
top / bottom / front (I) / rear (II)
top / bottom / front (I) / rear (II)
top / bottom / front (I) / rear (II)
top / bottom / front (I) / rear (II)

Reference
2694 3014(1)(2)
2694 4014(1)(2)
2694 3021(1)(2)
2694 4021(1)(2)
2694 3051(1)(2)
2694 4051(1)(2)

(1) To shroud front switch top and bottom 4 references required for a SIRCOVER and 6
references for a SIRCOVER BY-PASS.
(2) To shroud front switch top and bottom 2 references required for a SIRCOVER and a
SIRCOVER BY-PASS.

Terminal screens

acces_207_a_2_cat

Use
Top or bottom protection against direct contact with terminals or connection parts.
Rating (A)
125 ... 200
125 ... 200
250 ... 400
250 ... 400
500 ... 630
500 ... 630
800 ... 1 250
800 ... 1 250
1 600 ... 1 800
1 600 ... 1 800
2 000 ... 3 200

No. of poles
3P
4P
3P
4P
3P
4P
3P
4P
3P
4P
3/4P

Position
top / bottom
top / bottom
top / bottom
top / bottom
top / bottom
top / bottom
top / bottom
top / bottom
top / bottom
top / bottom
top / bottom

Reference
1509 3012
1509 4012
1509 3025
1509 4025
1509 3063
1509 4063
1509 3080
1509 4080
1509 3160
1509 4160
included

Inter phase barriers

acces_036_a_1_cat

Use
Safety isolating separation between the terminals, essential for use at 690 VAC
or in a polluted or dusty atmosphere.
The terminal shrouds also provide phase separation from 125 to 630 A.

282

C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:282 Sec1:282

Rating (A)
125 200
125 200
250 ... 400
250 ... 400
500 ... 630
500 ... 630
800 ... 3200

No. of poles
3P
4P
3P
4P
3P
4P
3/4P

Reference
2998 0033 (1)
2998 0034(1)
2998 0023(1)
2998 0024(1)
2998 0013(1)
2998 0014(1)
included

(1) Use 2 sets per side.

General Catalogue 2011-2012 SOCOMEC

15/11/10 16:30:47

Manual Changeover Switches

SIRCOVER and SIRCOVER BY-PASS

Handle key interlocking accessories

Fig. 2

Lockable in position I, 0 or II
Rating (A)
SIRCOVER
125 630

acces_061_a_1_x_cat

acces_001_a_1_x_cat

Fig. 1

Operation
external

Figure Reference
1
1423 2813

Locking using RONIS EL11AP lock in position 0 (not included)


Rating (A)
SIRCOVER
125 630

Fig. 3

Rating (A)
SIRCOVER
BY-PASS
125 200

800 1800
2000 3200
125 1800
2000 3200

Fig. 4

Rating (A)
SIRCOVER
BY-PASS
125 200
250 ... 630
800 1600
125 630
800 1600

Operation
direct
direct
direct
direct
external
external

Figure
2
3
3
3
4
4

Reference
4109 1006(1)
consult us
4109 1004(2)
4109 2007
1499 7701
2799 7002

acces_158_a_1_x_cat

acces_132_a_1_x_cat

(1) Specific handle included.


(2) This locking facility can be configured by the user in the 3 positions.

Locking using RONIS EL11AP lock in position I, 0, II (not included)


Rating (A)
SIRCOVER
BY-PASS
Operation
Figure Reference
125 200
direct
2
4109 1002(1)
250 630
direct
3
consult us
800 1800
800 1600
direct
3
4109 1004(2)
2000 3200
direct
3
4109 2007
125 1800
125 630
external
4
1499 7701
800 1600
external
4
2799 7002
Rating (A)
SIRCOVER
125 630

Use
using padlock (not supplied), this device is factory mounted in the direct or
external operation handle and allows using up to 3 padlocks (Fig.1).
Locking:
- using lock (not supplied)
- using undervoltage coil.
The interlocking positions are either determined as standard or configured by the
user, removing pre-formed tabs.
Padlocking and locking can be combined.

(1) Specific handle included.


(2) This locking facility can be configured by the user in the 3 positions.

Locking using 230 VAC undervoltage coil in position 0 (factory fitted)


Rating (A)
SIRCOVER
800 3200

Rating (A)
SIRCOVER
BY-PASS
800 1600

Operation
direct

Figure
3

Reference
consult us

Locking using CASTELL type K lock (not included)


Rating (A)
SIRCOVER
125 1800
2000 3200

Rating (A)
SIRCOVER
BY-PASS
125 630
800 1600

Operation
external
external

Figure
4
4

Reference
1499 7702
2799 7003

Other specific accessories

bd_03_04_01

Customised protection screens (for specific dimensions or high ambiant temperatures).


Inter phase barrier.
Connection accessories.
Low level auxiliary contacts.

SOCOMEC General Catalogue 2011-2012

C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:283 Sec1:283

283

15/11/10 16:30:52

SIRCOVER and SIRCOVER BY-PASS - Characteristics according to IEC 60947-3

125 to 500 A
Thermal current Ith (40C)
Rated insulation voltage Ui (V)
Rated impulse withstand voltage Uimp (kV)

125 A

160 A

200 A

250 A

400 A

500 A

800
8

800
8

800
8

800
8

800
8

1000
12

Rated operational currents Ie (A)


Rated voltage
Load duty category
400 VAC
AC-21 A / AC-21 B
400 VAC
AC-22 A / AC-22 B
400 VAC
AC-23 A / AC-23 B
690 VAC(2)
AC-20 A / AC-20 B
(2)
690 VAC
AC-21 A / AC-21 B
(2)
AC-22 A / AC-22 B
690 VAC
(2)
690 VAC
AC-23 A / AC-23 B
220 VDC
DC-20 A / DC-20 B
220 VDC
DC-21 A / DC-21 B
220 VDC
DC-22 A / DC-22 B
220 VDC
DC-23 A / DC-23 B
440 VDC
DC-20 A / DC-20 B
440 VDC
DC-21 A / DC-21 B
440 VDC
DC-22 A / DC-22 B
440 VDC
DC-23 A / DC-23 B

A/B(1)
125/125
125/125
125/125
125/125
125/125
125/125
63/80
125/125
125/125
125/125
125/125
125/125
125(3)/125(3)
125(3)/125(3)
125(4)/125(4)

A/B(1)
160/160
160/160
160/160
160/160
160/160
125/125
63/80
160/160
160/160
160/160
125/125
160/160
125(3)/125(3)
125(3)/125(3)
125(4)/125(4)

A/B(1)
200/200
200/200
160/160
200/200
160/160
125/125
63/80
200/200
160/160
160/160
125/125
200/200
125(3)/125(3)
125(3)/125(3)
125(4)/125(4)

A/B(1)
250/250
250/250
250/250
250/250
200/250
125/160
100/125
250/250
250/250
250/250
200/200
250/250
200(3)/200(3)
200(3)/200(3)
200(4)/200(4)

A/B(1)
400/400
400/400
250/250
400/400
200/250
125/160
100/125
400/400
250/250
250/250
200/200
400/400
200(3)/200(3)
200(3)/200(3)
200(4)/200(4)

A/B(1)
500/500
500/500
500/500
500/500
400/400
250/315
160/200
500/500
500/500
400/500
400/400
500/500
400(3)/400(3)
315(3)/400(3)
400(4)/400(4)

Operational power in AC-23 (kW)


At 400 VAC without pre-break in AC(1)(5)
At 690 VAC without pre-break in AC(1)(5)

63/63
55/75

80/80
55/75

80/80
55/75

132/132
90/110

132/132
90/110

280/280
150/185

Reactive power (kvar)


At 400 VAC (5)

55

75

90

115

185

230

Fuse protected short-circuit withstand (kA rms prospective)


100
Prospective short-circuit (kA rms)(6)
Associated fuse rating (A) (6)
125

100
160

50
200

50
250

18
400

100
500

Overload capacity
Rated short-time withstand current 0.3 s. ICW (kA eff.)
Rated peak withstand current (kA peak) (6)

15
20

15
20

15
20

17
30

17
30

25
45

Connection
Minimum Cu cable section (mm2)
Minimum Cu busbar section (mm2)
Maximum Cu cable section (mm2)
Maximum Cu busbar width (mm)
Tightening torque min (Nm)

35

50

50

95

185

240

50
25
9

95
25
9

95
25
9

150
32
20

240
32
20

240
40
20

Mechanical characteristics
Durability (number of operating cycles)(7)
Weight of 3 P switch (kg)
Weight of 4 P switch (kg)

10 000
1.5
1.6

10 000
1.6
1.7

10 000
1.8
1.9

10 000
2
2.1

10 000
3
3.5

5 000
3.5
4

(1) Category with index A = frequent operation - Category with index B = infrequent operation.
(2) With terminal shrouds or phase barrier.
(3) 3-pole device with 2 pole in series for the "+" and 1 pole for the "-".
(4) 4-pole device with 2 pole in series by polarity.
(5) The power value is given for information only, the current values vary from one manufacturer to another.
(6) For a rated operational voltage Ue = 400 VAC.
(7) Increased endurances: please consult us.

284

C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:284 Sec1:284

General Catalogue 2011-2012 SOCOMEC

15/11/10 16:30:53

Manual Changeover Switches

SIRCOVER and SIRCOVER BY-PASS

630 to 3200 A
Thermal current Ith (40C)
Rated insulation voltage Ui (V)
Rated impulse withstand voltage Uimp (kV)

630 A

800 A

1250 A

1600 A

1800 A

2000 A

2500 A

3200 A

1000
12

1000
12

1000
12

1000
12

1000
12

1000
12

1000
12

1000
12

Rated operational currents Ie (A)


Rated voltage
Load duty category
400 VAC
AC-21 A / AC-21 B
400 VAC
AC-22 A / AC-22 B
400 VAC
AC-23 A / AC-23 B
690 VAC(2)
AC-20 A / AC-20 B
(2)
AC-21 A / AC-21 B
690 VAC
690 VAC(2)
AC-22 A / AC-22 B
(2)
690 VAC
AC-23 A / AC-23 B
220 VDC
DC-20 A / DC-20 B
220 VDC
DC-21 A / DC-21 B
220 VDC
DC-22 A / DC-22 B
220 VDC
DC-23 A / DC-23 B
440 VDC
DC-20 A / DC-20 B
440 VDC
DC-21 A / DC-21 B
440 VDC
DC-22 A / DC-22 B
440 VDC
DC-23 A / DC-23 B

A/B(1)
630/630
630/630
500/500
630/630
500/500
315/315
160/200
630/630
630/630
500/500
500/500
630/630
500(3)/500(3)
500(3)/500(3)
500(4)/500(4)

A/B(1)
800/800
800/800
800/800
800/800
800/800
800/800
200/250
800/800
800/800
800/800
800/800
800/800
800(3)/800(3)
800(3)/800(3)
800(3)/800(3)

A/B(1)
1250/1250
1250/1250
1250/1250
1250/1250
800/800
800/800
200/250
1250/1250
1250/1250
1250/1250
1250/1250
1250/1250
1250(3) /1250(3)
1250(3)/1250(3)
1250(3)/1250(3)

A/B(1)
1600/1600
1600/1600
1250/1250
1600/1600
1000/1000
1000/1000
500/500
1600/1600
1250/1250
1250/1250
1250/1250
1600/1600
1250(3)/1250(3)
1250(3)/1250(3)
1250(3) /1250(3)

A/B(1)
1800/1800
1800/1800
1250/1250
1800/1800
1000/1000
1000/1000
500/500
1800/1800
1250/1250
1250/1250
1250/1250
1800/1800
1250(3) /1250(3)
1250(3)/1250(3)
1250(3)/1250(3)

A/B(1)
2000/2000
2000/2000
1600/1600
2000/2000
2000/2000
1000/1000
800/800
2000/2000
2000/2000
1250/1600
1250(3)/1250(3)
2000/2000
2000/2000
1250(3) /1250(3)
1000(3)/1000(3)

A/B(1)
2500/2500
2000/2500
1600/1600
2500/2500
2000/2500
1000/1000
800/800
2500/2500
2000/2500
1250/1600
1250(3)/1250(3)
2500/2500
2000/2000
1250(3) /1250(3)
1000(3)/ 1000(3)

A/B(1)
3200/3200
2500/3200
1600/1600
3200/3200
2000/2500
1000/1000
800/800
3200/3200
2000/2500
1250/1600
1250(3)/1250(3)
3200/3200
2000/2000
1250(3) /1250(3)
1000(3) /1000(3)

Operational power in AC-23 (kW)


At 400 VAC without pre-break in AC(1)(5)
At 690 VAC without pre-break in AC(1)(5)

280/280
150/185

450/450
185/220

710/710
185/220

710/710
475/475

710/710
475/475

710/710
750/750

710/710
750/750

710/710
750/750

Reactive power (kvar)


At 400 VAC (5)

290

365

575

Fuse protected short-circuit withstand (kA rms prospective)


Prospective short-circuit (kA rms)(6)
70
50
Associated fuse rating (A) (6)
630
800

100
1250

100
2 x 800

100
2 x 800

100
2 x 1000

100
2 x 1250

Overload capacity
Rated short-time withstand current 0.3 s. ICW (kA eff.)
Rated peak withstand current (kA peak) (6)

25
45

50
55

65
80

100
110

100
110

100
110

100
110

110
120

Connection
Minimum Cu cable section (mm2)
Minimum Cu busbar section (mm2)
Maximum Cu cable section (mm2)
Maximum Cu busbar width (mm)
Tightening torque min (Nm)

2 x 150
2 x 30 x 5
2 x 300
50
20

2 x 185
2 x 40 x 5
2 x 300
63

2 X 60 X 5
4 X 185
63
20

2 x 80 x 5
6 x 185
100
40

2 x 80 x 5
6 x 185
100
40

3 x 100 x 5

4 x 100 x 5

4 x 100 x 5

125
40

125
40

125
40

Mechanical characteristics
Durability (number of operating cycles)(7)
Weight of 3 P switch (kg)
Weight of 4 P switch (kg)

5 000
3.5
4

3 000
17.5
21

3 000
22.5
27.5

4 000
34
42

4 000
34
42

3 000
50
60

3 000
50
60

3 000
50
60

(1) Category with index A = frequent operation - Category with index B = infrequent operation.
(2) With terminal shrouds or phase barrier.
(3) 3-pole device with 3 pole in series for the "+" and 1 pole for the "-".
(4) 4-pole device with 2 pole in series per polarity.
(5) The power value is given for information only, the current values vary from one manufacturer to another.
(6) For a rated operational voltage Ue = 400 VAC.
(7) Increased endurances: please consult us.

SOCOMEC General Catalogue 2011-2012

C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:285 Sec1:285

285

15/11/10 16:30:54

SIRCOVER and SIRCOVER BY-PASS - Dimensions

SIRCOVER 125 to1800 A


Direct front operation

External front operation


Z1

A
M

II

10

8.5

CA

350

125

CA

svr_072_i_1_x_cat

L1

AC
AA
BA

II

HA

H
T

T
J

E min.

A. S2 type handle for external operation: 125 to 630 A


B. S4 type handle for external operation: 800 to 1800 A

Rating
(A)

Overall dimensions
A
A
3p.
4p. C
E min

125
160
200
250
400
500
630
800
1250
1600
1800

221
221
221
262
262
319
319
386
386
478
478

251
251
251
312
312
379
379
466
466
598
598

218
218
218
218
218
295
295
375
375
375
375

Terminal
shrouds

208 ... 436


208 ... 436
208 ... 436
208 ... 436
208 ... 436
285 ... 513
285 ... 513
425 ... 577
425 ... 577
425 ... 577
425 ... 577

45

60

18

1. Terminal shrouds
2. Direct handle operation:
- 125 to 630 A: L1 = 140 mm,
- 800 to 1800 A: L1 = 210 mm.

AC

Switch body
J
H
HA 3p.

J
4p.

Switch mounting
M
M
3p.
4p.
N

X
3p.

X
4p.

Z1

AA

BA

AC

235
235
235
280
280
401
400
459
459
461
461

148
148
148
148
148
225
225
298
298
298
298

212
212
212
273
273
332
332
386.5
386.5
388.5
518.5

156
156
156
196
196
246
246
255
255
347
347

36
36
36
50
50
65
65
80
80
120
120

20
20
20
25
35
32
45
50
60
90
90

25
25
25
30
35
37
50
60.5
65
43.5
43.5

8.5
8.5
8.5
11
11
13
13
15
16x11
12.5x5
12.5x5

56
56
56
61
61
70.5
70.5
48
48
54
54

50
50
50
61
61
65.5
65.5
48
48
54
54

3,5
3,5
3,5
3,5
3,5
5
5
7
7
8
8

28
28
28
30
30
43
43
66.5
66.5
66.5
66.5

124
124
124
124
124
180
180
253.5
255.5
255.5
255.5

135
135
135
160
170
235
260
321
330
288
288

115
115
115
130
140
205
220

10
10
10
15
15
15
20
26.5
29.5
15
15

25
25
25
25
25
25
25
29
29
29
29

182
182
182
223
223
272
272
306.5
306.5
306.5
388.5

186
186
186
246
246
306
306
336
336
467
467

101
101
101
116
116
176
176
250
250
250
250

Connection

SIRCOVER 2000 to 3200 A


Direct front operation

A
436.5

51.5

svr_128_c_1_x_cat

330

330

380

461
258
250

120

120

120

425

425

53.5

103
653

Rating (A)

Overall dimensions
A
3p.

A
4p.

Switch mounting
M
3p.

M
4p.

2000 3200

478

598

347

467

286

C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:286 Sec1:286

General Catalogue 2011-2012 SOCOMEC

15/11/10 16:30:55

Manual Changeover Switches

SIRCOVER and SIRCOVER BY-PASS


SIRCOVER BY-PASS 125 to 1600 A
Direct front operation

Z2

A
10

M
II

Z1
Y

CA

Z
8.5

II

CA

L1

AA
BA

AC

H
C

18

External front operation

svr_070_i_1_x_cat

210

125

330

HA

A. S2 type handle for external operation:


125 to 200 A
B. S3 type handle for external operation:
250 to 630 A
C. External double lever handle: 800 to 1600 A
1. Terminal shrouds
2. Direct handle operation:
- 125 to 200 A: L1 = 140 mm,
- 250 to 630 A: L1 = 210 mm,
- 800 to 1600 A: L1 = 330 mm.

45
103

E min.
61

Terminal
shrouds Switch body

Overall dimensions
A
A
Rating (A) 3+6p. 4+8p. C

E
min AC

125
160
200
250
400
500
630
800
1250
1600

320
320
320
298
298
417
417
550
550
550

243
243
243
243
243
362
362
479
479
479

221
221
221
262
262
319
319
386
386
478

251
251
251
312
312
379
379
466
466
598

313
313
313
313
313
432
432
560
560
560

235
235
235
280
280
401
400
459
459
461

Switch mounting

Connection

HA

J
J
M
3+6 p. 4+8 p. 3+6 p.

M
4+8 p. N

X
3+6p.

X
4+8p.

Z1

Z2

AA

BA

AC

25
25
25
25
25
25
25
29
29
29

182
182
182
223
223
272
272
306.5
306.5
388.5

186
186
186
246
246
306
306
335
335
467

36
36
36
50
50
65
65
80
80
120

20
20
20
25
35
32
45
50
60
90

25
25
25
30
35
37
50
60.5
65
43.5

8,5
8,5
8,5
11
11
13
13
15
16x11
12.5x5

56
56
56
61
61
70.5
70.5
48
48
54

50
50
50
61
61
65.5
65.5
48
48
54

3.5
3.5
3.5
3.5
3.5
5
5
7
7
8

28
28
28
30
30
43
43
66.5
66.5
66.5

124
124
124
124
124
180
180
253.5
253.5
253.5

219
219
219
219
219
317
317
439.5
439.5
439.5

135
135
135
160
170
235
260
321
320
288

115
115
115
130
140
205
220

10
10
10
10
15
15
20
26.5
29.25
15

212
212
212
273
273
332
332
386.5
386.5
518.5

156
156
156
196
196
246
246
255
255
347

101
101
101
116
116
176
176
250
250
250

Connection terminals
SIRCOVER and SIRCOVER BY-PASS 800 A

SIRCOVER and SIRCOVER BY-PASS 1250 A

SIRCOVER 1600 to 3200 A


SIRCOVER BY-PASS 1600 A

16 x 11

33

8.5

50

SOCOMEC General Catalogue 2011-2012

C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:287 Sec1:287

15.75

28.5
60

15.75

12.5
5

15

12.5
svr_098_a_1_x_cat

8.5

15 28.5

svr_077_a_1_x_cat

15

svr_078_b_1_x_cat

10 33

25 25
30
30
45
45
90

287

15/11/10 16:30:56

Dimensions for external handles

SIRCOVER 125 to 630 A

Front operation
Direction of operation

Door drilling
With lock
RONIS EL11AP

0
o
I+II

S2 type

20 20
26

37

4 5.5

47

2 6.5

28

37

37

47

47

79

14 14

73
.5

svr_138_a_1_gb_cat

D (1)

45

5
3.
45

45

26

14 14

24

II

1414

125

.5
28

90

90

78

With lock
CASTELL K

22

Handle type

20 20

20 20

(1) 31 to 37: rear screw mounting


37: front clip mounting.

SIRCOVER 800 to1800 A

Front operation
Door drilling

Direction of operation
0
or
I+II

With lock
RONIS EL11AP

20 20

26

4 7 (2)

1414

37
47

24
.5

26

14 14

73

45

5
3.
45
20 20

60

22

90
350

.5

2 6.5

37
47

II
D (1)

svr_139_a_1_gb_cat

28

37

4 5.5

90

28

78

With lock
CASTELL K

79

S4 type

14 14

Handle type

20 20

(1) 31 to 37: rear screw mounting


37: front clip mounting.
(2) 6 to 7: fast fixing.

SIRCOVER 2000 to 3200 A

Front operation
Handle type

Direction of operation

Door drilling
With lock
CASTELL K

C type
50

50

II

96
28

4 6.5

svr_140_a_1_gb_cat

50

C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:288 Sec1:288

90

288

25

0
50

300

90

31

4 x 6.5

31

3 x 6.5

General Catalogue 2011-2012 SOCOMEC

15/11/10 16:30:58

Manual Changeover Switches

SIRCOVER and SIRCOVER BY-PASS

SIRCOVER BY-PASS 125 to 200 A

Front operation
Direction of operation

Door drilling
With lock
RONIS EL11AP

0
20 20

26

37

37

47

24

47

26
73
.5

5
3.
45

D (1)

45

svr_141_a_1_gb_cat

14 14

125

1414

37

45

.5
28

II

2 6.5

28

4 5.5

47

22

90

90

78

With lock
CASTELL K

79

S2 type

14 14

Handle type

20 20

20 20

(1) 31 to 37: rear screw mounting 37: front clip mounting.

SIRCOVER BY-PASS 250 to 630 A

Front operation
Handle type

Direction of operation

S3 type

Door drilling
With lock
RONIS EL11AP

90

90

With lock
CASTELL K

20 20

78

26

37

37

47

22

14 14

20 20

61

79

73

D (1)

45

.5

26

14 14

24

47

5
3.
45

svr_142_a_1_gb_cat

210

1414

37

.5

2 6.5

28

4 5.5

II

28

47

20 20

(1) 31 to 37: rear screw mounting 37: front clip mounting.

SIRCOVER BY-PASS 800 to 1600 A

Front operation
Handle type

Direction of operation

Door drilling
With lock
CASTELL K

C type
50

50

II

96
28

4 6.5

50

25

0
50

300

90

svr_143_a_1_gb_cat

90

SOCOMEC General Catalogue 2011-2012

C0112A_GB_SIRCOVER_BP_b_bat.inddSec1:289 Sec1:289

31

4 x 6.5

31

3 x 6.5

289

15/11/10 16:30:59

ANSI code 87

Differential current relays


uni-line

Type RMC-131D

4921240104G

Measurement of 3 phase currents

Non-stabilised measurement

LED indication of fault condition

Timer controlled tripping

LED indication for activated relay

Extra change-over relay contact for


signalling

35 mm DIN rail or base mounting

Application

Relay output

The protective differential current relay type RMC-131D


forms part of a complete DEIF series of relays for
protection and control of generators, and is primarily
designed for marine applications. Also available are
short circuit relays (RMC-111D), combined short circuit
and overcurrent relays (RMC-122D) and double
overcurrent relays (RMC-132D).

The RMC-131D is provided with one relay coil with 2


maximum contacts. The relay can be configured either
to normally energised or normally de-energised. The
contacts may be set to open or to close on activation
(same function on both contacts).

The RMC-131D is type approved by major classification


societies and is applied for protection of e.g. generators
in 3-phase networks against leakage currents.

Measuring principle

Normally energised contact


Recommended for marine installation for warning and
alarm purposes.
In case of an auxiliary supply drop-out, the contact is
immediately activated.

The relay compares the differential current of each of


the 3 phases, providing an RMS measurement at
sinusoidal currents.

Normally de-energised contact


Recommended for marine installations for regulating
and control purposes.

In order to obtain a short response time on a fault


condition, the measurement is based on peak values.

An auxiliary supply failure will not result in an unwanted


activation of the contact.

The differential currents are obtained by connecting the


external current transformers for each winding in
parallel with inverse polarity.

Latch circuit
The contact can then be locked in its warning position,
even if the input currents return to normal (add L to
contact type in order specifications, if this is required).

The measurement is not stabilized, implying that the


relay contact is activated for disconnection of the
supervised unit when the differential current of the
individual phases exceeds its set point, irrespective of
the amperage of these.

DEIFA/S

RMC-131D

The 3 differential currents are measured by the relay


and the highest of these is selected. If this exceeds the
set point, the output is activated.
The set point value is set on the front of the relay by
means of a potentiometer. If exceeded, a fault signal is
generated, and the associated yellow LED is lit.

Timer function
When the set point has been exceeded, the associated
timer starts and will run as long as the fault condition
prevails.
The delay (3 ranges) does not depend on the exceeding
of the set point. If the fault disappears, the timer is
reset. When the timer expires, the contact is activated
and the associated red LED is lit.

The latch circuit is reset by disconnecting the auxiliary


supply.
Hysteresis
In order to avoid chatter on the relay contacts the
contact functions are provided with a hysteresis, i.e. a
difference of 2% of full scale between energising and
de-energising of the relay.
Power-up/power-down circuits
The RMC-131D is provided with a 200 ms power-up
circuit, ensuring the correct function of the relay on
connection of the auxiliary voltage.
Note: Normally energised contacts are not activated
(contact does not open/close) until 200 ms after
connection of the auxiliary voltage.
Likewise, the RMC-131D is provided with a 200 ms
power-down circuit, ensuring supervision and
maintenance of any set point exceedings for 200 ms
after disconnection of the auxiliary voltage.

Type RMC-131D
Settings and indication

Technical specifications
Meas. range (In):

0.3-0.4-0.5-0.6-0.8-1.0-1.3-1.5-2.02.5-3.0-4.0-5.0A AC

Adjusted range:

75...100% of In (e.g. 0.4, 0.45, etc.).


(lowest meas. range: 0.3A)

Frequency range:

40...45...65...70Hz.

Differential current:

0.04...0.4 x In.

Max. input current:

4 x
20 x
80 x

Load:

Max. 0.3VA per phase.

Output:

1 maximum contact.

Contact type:

Contact B, contact C:
Normally energised (NE), or
normally de-energised (ND)
with or without latch circuit (L)

Relay contact:

2 sets of change-over switches

Contact ratings:

250V-8A-2000VA (AC)
24V-8A-200W (DC)
3
(200 x 10 change-overs at resistive
load)

Contact voltage:

Max. 250V (AC). Max. 150V (DC).

Hysteresis:

2% of full scale (F.S.).

Response time:

<50 ms.

Temperature:

-25...70C (operating).

Temperature drift:

Set points:
max. 0.2% of full scale per 10C.

Galvanic separation:

Between inputs, outputs and aux.


voltage: 3250V - 50Hz - 1 min.

Supply voltage (Un):

57.7-63.5-100-110-127-200-220-230240-380-400-415-440-450-660-690V
AC 20% (max. 3.5VA)

In, continuously,
In for 10 s (max. 75A)
In for 1 s (max. 300A).

24-48-110-220V DC -25/+30%
(max. 2W).
Climate:

HSE, to DIN 40040.

EMC:

To EN 50081-1/2, EN 50082-1/2,
SS4361503 (PL4) and IEC 255-3.

Connections:

Max. 4 mm (single-stranded).
Max. 2.5 mm (multi-stranded).

Materials:

All plastic parts are self-extinguishing


to UL94 (V1).

Protection:

Case: IP40. Terminals: IP20,


to IEC 529 and EN 60529.

Type approval:

The uni-line components are


approved by the major classification
societies. For current approvals see
www.deif.com or contact DEIF A/S.

Setting of
Differential current
set point:
(440%) of ln
Time delay:
(0T1) in seconds
01/05/010 s

LED/relay
l> yellow LED is lit when the set
point has been exceeded, but the
contact not yet activated.
Contact is activated and red LED lit
after the timer has expired.

The relay is furthermore equipped with a green LED marked


POWER for indication of power ON. Once the relay has been
mounted and adjusted, the transparent front cover may be
sealed, preventing unwanted change of the setting.

Connections/dimensions (in mm)


Note: Current transformers
with the same characteristics
must be used on both sides.
The cable burden must be the
same on both sides. Current
transformers must be used for
RMC-131D only.

Shown contact positions: auxiliary voltage not connected

Weight: approx. 0.650 kg

Order specifications
Type Measuring current (ln) Relay Time delay (T1)
Supply voltage
Example:
RMC-131D 5A AC NEL - 5 s 440V AC

Due to our continuous development we reserve the right to


supply equipment which may vary from the described.

DEIF A/S, Frisenborgvej 33


DK-7800 Skive, Denmark
Tel.: +45 9614 9614, Fax: +45 9614 9615
E-mail: deif@deif.com, URL: www.deif.com

MK203A
Microprocessor based numerical relay
Current measurement based on
fundamental frequency

Technical Data
RATINGS
: 5A
: 50 Hz
: < 0.3 VA at In
: 4 x In continuous

Rated current ( In )
Rated frequency
Burden
Thermal withstand

Low-set inverse definite minimum time


( IDMT ) relay

High-set instantaneous relay


Separate low-set and high-set trip
indicators

Option to disable high-set relay


Front panel access to test function
Complies with IEC 60255-26 standard

AUXILIARY SUPPLY
Model MK203A-240A
Model MK203A-110A
Supply frequency
VA rating

: 198 ~ 265 V AC
: 94 ~ 127V AC
: 50 Hz
: 3 VA typical

SETTING RANGES
Low-set ( I > )

: 2.0 A to 6.0 A
: 40% to 120%
Time multiplier ( TM ) : 0.05 to 1.0
High-set ( I >> )
: I > to 10 x I > or disable
High-set delay time (t >>) : Instantaneous

TIME CURRENT CHARACTERISTIC CURVE


- Normal Inverse

CONTACTS
Trip contact (R1)
: Manual reset type
Contact Arrangement : Change-over
Contact rating
: 5 A, 250 V AC ( cosJ= 1 )
: Silver alloy
Contact material
Expected electrical life : 100,000 operations at
rated current
Expected mechanical life: 5 x 106 operations

INDICATORS
Auxiliary supply
Pick-up
Trip

: Green indicator
: Red indicator
: Red indicator

PERFORMANCE
Adjustable accuracy : Less than 5%.
Repeatability
: Less than 0.5% of full scale.

MECHANICAL
Mounting
Front panel

: Panel mounting
: Standard DIN
96 mm x 96 mm
Approximate weight : 0.7 kg

ENVIRONMENTAL CONDITIONS
Temperature
Humidity

: -5C to +55C
: 56 days at 93% RH and
40C non-condensing

MK203A Overcurrent Relay

Features

TYPICAL APPLICATION DIAGRAM


Aux

MK 203A
NO

NORMAL INVERSE

NC COM
4

14

15

16

R1
10

11

12

13

L1
L2
L3
N

COMBINED IDMT OVERCURRENT & EARTH FAULT RELAYS


AUX

MK 203A
NO

AUX

NC COM

10

11

12

MK 202A
NO

NC COM

14

15

16

10

11

12

13

14

15

16

R1

R1

13

L1
L2
L3
N

96 mm

110 mm
100 mm

91.0 p 0.5 mm

Front

Side

Panel Cutout

Ordering Information
MODEL

DESCRIPTION

MK203A - 240A
MK203A - 110A

For 50 Hz system, auxiliary voltage 198 ~ 265 V AC


For 50 Hz system, auxiliary voltage 94 ~ 127 V AC

91.0 p 0.5 mm

CASE DIMENSIONS

96 mm

MK203A Overcurrent Relay

HLC Sleeve Anchor


Features:
- for concrete, solid brick, sand limestone
- force controlled expansion
- setting mark for choosing the right anchor le
- fire test report
Material:
HLC, -EO,EC:
HLC-H,SK,L,T:

HLC
- min. tensile strength 500MPa
- steel galvanized to min. 5 microns
- Bolt steel grade 8.8
- steel galvanized to min. 5 microns

Basic loading data (for Single anchor) in concrete:HLC, HLC-H, HLC-EC/EO, HLC-L, HLC-SK, HLC-T

Characteristic resistance, R k [kN]: fc,cube

25 N/mm2

Anchor Size

6.5

10

12

16

20

Tensile NRk

kN

2.1

3.5

4.5

7.2

10.0

13.2

Shear VRk

kN

3.8

7.0

8.8

14.4

20.0

20.0

6.5

10

12

16

20

Design resistance, Rd [kN]: fc,cube

25 N/mm2

Anchor Size
Tensile NRd

kN

1.2

2.0

2.5

4.0

5.5

7.4

Shear VRd

kN

2.1

3.9

4.9

8.0

11.1

11.1

Recommended load, Lrec [kN]: fc,cube

25 N/mm2
6.5

10

12

16

20

Tensile NRec

kN

0.8

1.4

1.8

2.8

4.0

5.2

Shear VRec

kN

1.5

2.8

3.5

5.7

7.9

7.9

Anchor Size

Page 1

Issue 2008

HLC Sleeve Anchor


Basic loading data (for Single anchor) in solid brick 1,2,3: HLC, HLC-H, HLC-EC/EO, HLC-L, HLC-SK, HLC-T

MZ 12-2,0-2DF Recommended load, Lrec [kN]: fbrick

19 N/mm2

Anchor Size
Tensile NRec

kN

6.5
0.3

8
0.5

10
0.6

12
0.7

16
0.8

Shear VRec

kN

0.45

1.0

1.2

1.4

1.6

KS 12-2,0-2DF Recommended load, Lrec [kN]: fbrick

29 N/mm

Anchor Size
Tensile NRec

kN

6.5
0.4

8
0.5

10
0.6

12
0.8

16
0.8

Shear VRec

kN

0.65

1.0

1.2

1.6

1.6

1)

The technical data for the HLC sleeve anchors are reference loads for MZ 12 and KS 12. Due to the large variation of natural stone solid bricks,
on site anchor testing is recommended to validate technical data.
2)
For brick walls where anchor position in brick can not be determined, 100% anchor testing is recommended.
3)
The HLC anchor was installed and tested in center of solid bricks as shown. The HLC anchor was not tested in the mortar joint between solid
bricks or in hollow bricks, however a load reduction is expected.

Setting Details
Anchor position in concrete

Anchor position in Solid masonry brick

Anchor position in Brick


ccr

5.5 cm

scr
11 cm
5.5 cm
5.5 cm

11 cm

5.5 cm

5.5 cm
24 cm

Edge distance and anchor spacing given in setting details

Page 2

distance to free edge for solid masonry units is 30 cm


distance to horizontal and vertical mortar joint 5.5 cm

Issue 2008

HLC Sleeve Anchor


HLC, HLC-H, HLC-EC/EO, HLC-L

HLC-SK

Sw
d

20x150/95

20x115/60

20x80/25

16x140/90

16x100/50

16x60/10

12x100/60

12x75/35

12x55/15

10x100/65

10x80/45

10x60/25

10x50/15

10x40/5

8x85/55

8x70/40

8x55/25

8x40/10

6.5x60/40

6.5x40/20

Anchor Size

6.5x25/5

HLC, HLC-H, HLC-EC/EO, HLC-L

Setting details
M5

M6

M8

M10

M12

M16

mm

6.5 (1/4")

10

12

16

20

Min. Borehole depth

mm

30

40

50

65

75

85

Max. Borehole depth

mm

Min. Anchorage depth

mm

Total Anchor length

mm

30 45 65 46 61 76 91 48 58

68 88 108 65 85

110

72 112 152 95 130

165

lc

Anchor length under washer

mm

25 40 60 40 55 70 85 40 50

60 80 100 55 75

100

60 100 140 80 115

150

tfix

Max. Fixing length1

mm

5 20 40 10 25 40 55 5

25 45 65 15 35

60

10 50

95

Tinst

Tightening torque concrete

Nm

25

40

50

80

Tinst

Tightening torque masonry

Nm

2.5

13

20

25

Sw

Width across nut flats

10

13

19

24

Thread diameter

d0

Drill bit diameter

h1

hef

HLC

df

HLCH

h1,max = h (actual base material thickness) - 10mm -d0


16

31

26

15

33

41

41

90 25 60

15

mm

17

mm

Clearance hole

mm

11

13

17

21

hmin

Min. Thickness of the base


material2)

mm

60

70

80

100

100

120

ccr

Critical Edge Distance

mm

30

50

60

65

80

80

scr

Critical Spacing

mm

60

100

120

130

160

160

1)

When setting long anchors to achieve intermediate fixing length be advised of the base material thickness, use caution when drilling boreholes to
the maximum depth, to avoid back side blow out.
1)
For anchrors loaded in shear towards the edge the critiacl edge distance must be doubeled

Page 3

Issue 2008

HLC Sleeve Anchor

12x55/15

10x130/95

10x105/65

10x85/45

10x45/5

8x90/55

8x75/40

8x60/25

6.5x85/60

6.5x65/40

Anchor Size

6.5x45/20

HLC-SK

Setting details
M5

M6

M8

M10

mm

6.5 (1/4")

10

12

Min. Borehole depth

mm

30

40

50

65

Max. Borehole depth

mm

Min. Anchorage depth

mm

Total Anchor length

mm

45 65 85 60 75 90 45 85 105 130

80

tfix

Max. Fixing length1

mm

20 40 60 25 40 55 5 45 65

35

Tinst

Tightening torque concrete

Nm

25

40

Tinst

Tightening torque masonry

Nm

2.5

13

20

PZ 3

T 30

T 40

T 40

Thread diameter

d0

Drill bit diameter

h1

hef

Setting Driver

,max

= h (actual base material thickness) - 10mm 16

26

31

33

95

Min. Thickness of the base


60
80
mm
70
100
material
ccr
Critical Edge Distance
mm
30
50
65
60
scr
Critical Spacing
mm
60
100
120
130
1)
When setting long anchors to achieve intermediate fixing length be advised of the base material thickness, use caution when drilling boreholes to
the maximum depth, to avoid back side blow out.
hmin

Installation equipment
Rotary hammer ( TE2, TE6, TE6A, TE7, TE 7A, TE16, TE 16-C, TE 16-M, TE 35 ), a drill ( see table above), a
hammer and a torque wrench

Setting operations

Page 4

Issue 2008