PSC Inspection Common Deficiencies

Category 2 Fire Fighting Equipment 01- January-2000 to 31-December-2005 No


1 2 3 4 5 6 7 8 9 10 11

Fixed Fire Fighting System


Deficiencies with Action Code 30 (means 'Ground for Detention') Foam Monitors on catwalk seized and partly broken/damaged.(Tanker only) Deficiencies with Action Code 17 (means 'To rectify deficiencies before departure') CO2 system power failure alarm not working when activated - defective system. Fixed fire extinguishing system not serviced/checked as required on a yearly basis. Fixed fire extinguishers installation for CO2. Validity date of the certificate was expired. Some brackets of the fixed fire fighting system were not tightened and the bottles were not properly secured. Sand box found without shovel. Deficiencies with Action Code 16 (means 'To rectify deficiencies within 14 days') Foam monitor handle found broken and not freely moving. CO2 room pressure gauge on discharge line found defective. Deficiencies with Action Code 15 (means 'To rectify deficiencies at next port') CO2 bottle storage room - Various lights found broken, emergency lights were not operational and there was no signage warning to run the exhaust fan prior entry. Deficiencies with Action Code 99 (means 'Other') CO2 piping to cargo hold found damaged by corrosion. Paint locker was not provided with fixed fire extinguishing system.

No
1 2 3 4 5 6 7 8

Fire Detection System


Deficiencies with Action Code 30 (means 'Ground for Detention') Fire detection system found not operative Deficiencies with Action Code 17 (means 'To rectify deficiencies before departure') Crew need to familiarize with the fire detection system. Malfunction and fault of fire detection panel - many zone found isolated. (under repair) Some areas in fire detector panel were isolated. Smoke detectors were found loose, taken out and some were covered up by plastic bag. Deficiencies with Action Code 16 (means 'To rectify deficiencies within 14 days') Fire detectors do not have any IMO symbols/stickers. Deficiencies with Action Code 15 (means 'To rectify deficiencies at next port') Fire detection control panel - common fault on activation and unable to reset. Manufacturer's representative to verify the accuracy and operability of gas detection system and temperature sensing system. Provide manufacturer's certification of accuracy and operability to Class for approval and verification prior to next port.(LNG only) Deficiencies with Action Code 99 (means 'Other') Cargohold smoke detection system on wheelhouse - top suction line clamps found damaged; Fan casing found damaged by corrosion. Fire Detection System - to cargo hold found faulty.

9 10

No
1 2 3

Fire & General Alarms


Deficiencies with Action Code 30 (means 'Ground for Detention') Main fire alarm sensor on bridge found defective. Several fire alarm units observed found defective. Deficiencies with Action Code 17 (means 'To rectify deficiencies before departure') Fire Alarm System found indicating faults.

Page 1 of 6

ZIZA ZERO INCIDENT ZERO ACCIDENT

PSC Inspection Common Deficiencies


Category 2 Fire Fighting Equipment 01- January-2000 to 31-December-2005

No
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Emergency Fire Pump


Deficiencies with Action Code 30 (means 'Ground for Detention') Emergency fire pump not properly working .There is no pressure at the fire line .To check under supervision of class. Emergency fire pump not operable. Emergency fire pump non return valves found defective. Deficiencies with Action Code 17 (means 'To rectify deficiencies before departure') Remote control valve from emergency pump was not working. Emergency fire pump found with no suction/air in hydraulic line. Emergency fire pump extension spindle universal joint pins found loose. Emergency fire pump - priming pump inoperative. No water supply to emergency fire pump. Emergency fire pump - leaking of sea water from pump shaft. Fuel Oil of Emergency Fire Pump Engine found not enough. Fire protective material for bulkhead in emergency fire pump room was partly missing and damaged. Fire pump - emergency fire pump's discharge pressure was inadequate. The IMO symbol was not be posted at the emergency fire pump room. Deficiencies with Action Code 16 (means 'To rectify deficiencies within 14 days') Emergency fire pump - discharge valve found not operating. Emergency fire pump - suction and discharge pressure gauges found faulty and defective. Deficiencies with Action Code 15 (means 'To rectify deficiencies at next port') Ensure current design of emergency fire pump will operate under all conditions of list and trim.

No
1 2 3 4 5 6

Fireman's Outfit
Deficiencies with Action Code 30 (means 'Ground for Detention') Fireman's outfit/lantern was missing from the inventory. Deficiencies with Action Code 17 (means 'To rectify deficiencies before departure') Fireman's outfit safety lights, batteries were found flat/dead. Fireman's out fit stowage room on main deck - safety light and EEBD were found missing. Fireman's Outfit was not provided with fireproof lifelines. Deficiencies with Action Code 16 (means 'To rectify deficiencies within 14 days') Fireman's Outfit not stowed as per Fire Control Plan position. Deficiencies with Action Code 99 (means 'Other') Firema'n outfit torchlight found not functioning.

No
1 2 3 4 5 6 7

Self Contained Breathing Apparatus (SCBA)


Deficiencies with Action Code 17 (means 'To rectify deficiencies before departure') SCBA sets - some bottles found with low preasure. Breathing apparatus minimum pressure alarm not working. Breathing Apparatus. Validity date of the certificate was expired. Breathing Apparatus found without proof of maintenance and some with inspection date expired. Deficiencies with Action Code 16 (means 'To rectify deficiencies within 14 days') Air breathing apparatus to be renewed to approved type. Deficiencies with Action Code 99 (means 'Other') Breathing Apparatus mask hoses perished in corrugations. Annual inspection by shore based service station on SCBA cylinder bottles were not carried out.

Page 2 of 6

ZIZA ZERO INCIDENT ZERO ACCIDENT

PSC Inspection Common Deficiencies


Category 2 Fire Fighting Equipment 01- January-2000 to 31-December-2005

No
1 2 3 4 5 6 7 8 9 10 11 12 13

Fire & Gastight Doors


Deficiencies with Action Code 30 (means 'Ground for Detention') Accommodation fire doors (including entrance to E/R) found not closed. E/R cannot be closed properly in case of fire (Electrical cables were passing through the deck opening & Eng. Control room door). Deficiencies with Action Code 17 (means 'To rectify deficiencies before departure') Fire doors were not self closing (not closed automaticaly) and not closing properly. Various fire doors were lashed open and numerous self-close devices of fire doors were not in good condition. Self-closing fire doors found with hold back hook. Back hooks to be removed and "Keep Door Close" sign is recommended. Self closing device for fire door room found missing. Self closing device of the fire door was taken off. Self closing device on (Class A) fire door to E/R on upper deck was not provided. Deficiencies with Action Code 16 (means 'To rectify deficiencies within 14 days') Fire proof door in accommodation was unable to close tightly. Engine room fire door closing device found broken. Steering gear room entrance door from deck, the fire door seal found defective. Deficiencies with Action Code 99 (means 'Other') Galleys doors (Class A fire division) found not working and the other door was badly corroded at bottom. Ensure complete closure is possible for all fire doors in stair towers, accommodation space and machinery space access (Solas 74 amended II-2/46-77). A-O class fire doors between E/room and steering room differed from fire control plan (used combustible gasket).

No
1 2 3 4 5 6 7 8 9

Ventilators, Fire Dampers & Flaps


Deficiencies with Action Code 30 (means 'Ground for Detention') Engine room ventilation fan dampers found frozen and remote air closing inoperative. Machinery spaces (means of control) - inoperative. Funnel fire damper stucked/inoperative. Deficiencies with Action Code 17 (means 'To rectify deficiencies before departure') Fire dampers found seized and unable to close - inoperative and did not close properly from remote location. Engine room ventilation damper operating handle found broken. Fire dampers tight, stiff and not sealing properly. Fire damper, the open/close position was painted over. All fire flaps to be marked according to their function, flaps have to be regularly greased and moved to keep them working smoothly. No "Open / Close" marks for part of ventilators. Deficiencies with Action Code 18 (means 'To rectify deficiencies within 3 months') Cargo hold mushroom vents mechanical fan safety grills secure found wasted/broken. Deficiencies with Action Code 16 (means 'To rectify deficiencies within 14 days') CO2 room ventilator cover, securing bolts found missing. Several fire dampers & ventilation flaps to be marked. Fire/Ventilation dampers found with no marking "open" & "close". Deficiencies with Action Code 15 (means 'To rectify deficiencies at next port') Fire fighting measures: Ventilation/fire dampers, quick closing devices means of control, quick closing valves on M/E LO settling tank found not operating. Galley vent on funnel deck found with excess of grease that has been build up. Deficiencies with Action Code 99 (means 'Other') Ventilation in CO2 room found not operational. Engine room ventilator fire dampers were unable to be closed from outside fan duct room space. Several fire dampers (cargo hold) found not operating properly (not opening).

10 11 12 13 14

Page 3 of 6

ZIZA ZERO INCIDENT ZERO ACCIDENT

PSC Inspection Common Deficiencies


Category 2 Fire Fighting Equipment 01- January-2000 to 31-December-2005

No
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Fire Extinguishers
Deficiencies with Action Code 17 (means 'To rectify deficiencies before departure') Portable foam applicator unit in engine room found foam tank was empty. Portable foam applicator nozzle and fire hose coupling in E/R - not connected well. Chemical foam fire extinguishers in pump room not suitable for chemical fire. Portable fire extinguisher malfunction. Portable fire extinguishers. Validity date of the certificate was expired. Position of portable fire extinguisher at upper deck - interfere with daily operation. Portable fire extinguisher not checked/inspected as required. Fire extinguisher was not accessible for immediate use due to obstacles. Fire extinguisher inside forcastle not properly secured. Deficiencies with Action Code 16 (means 'To rectify deficiencies within 14 days') Portable fire extinguisher at entrance to machinery space was not provided. Portable fire extinguisher in emergency generator room was not provided near the entrance. No records found on Annual Inspection of Portable Fire Extinguishers by a"competent person ". Dry powder fire extinguisher was not filled up. Deficiencies with Action Code 15 (means 'To rectify deficiencies at next port') Annual inspection by shore based service station on fire extinguishers were not carried out. Portable fire extinguishers to be provided with devices indicate whether they have been used (SOLAS amendments 2000 Chapter - 2 Regulation 10.3.2.4).

No
1 2 3 4 5 6 7 8 9 10 11 12 13 14

Fire Hoses, Hydrants, Nozzles & Attachments


Deficiencies with Action Code 30 (means 'Ground for Detention') Fire-fighting appliances - nozzles were not of dual-purpose type. Deficiencies with Action Code 17 (means 'To rectify deficiencies before departure') Fire hydrant access was blocked by oil drums. Fire nozzle found with seal joint damaged. Dual purpose fire nozzles found seized. Fire nozzles and fire hose's coupling are not connected well. Fire hoses / nozzles are found with rubber washers missing. Fire hoses / nozzles are not at designated position and some are missing. Fire hydrants & hoses gaskets need to be replaced. Deficiencies with Action Code 16 (means 'To rectify deficiencies within 14 days') All rubber hoses for non portable fire extinguisher adjacent boiler were perished. Fire hydrant in accommodation found leaking. Fire hydrant hose retaining clip not operable. Fire hose/nozzle also missing. Fire hydrant valves not operable need to be maintained. Fire hose nozzles of jet type only. Almost all fire nozzles in E/R are not dual purpose type (jet/spray/shutoff). Deficiencies with Action Code 15 (means 'To rectify deficiencies at next port') Fire hose box on main deck found damaged.

No
1 2 3 4

International Shore Connection (ISC)


Deficiencies with Action Code 17 (means 'To rectify deficiencies before departure') International shore connection gasket need to be renewed. International shore connection - not kept in designated location & found with insufficient washers Deficiencies with Action Code 16 (means 'To rectify deficiencies within 14 days') International Shore Connection was not found in designated location. Deficiencies with Action Code 99 (means 'Other') Update ship's Fire Control Plan to reflect proper location of International Shore Connection.

Page 4 of 6

ZIZA ZERO INCIDENT ZERO ACCIDENT

PSC Inspection Common Deficiencies


Category 2 Fire Fighting Equipment 01- January-2000 to 31-December-2005

No
1 2 3 4 5 6 7 8 9 10 11 12 13 14

Fire Main & Isolating Valve


Deficiencies with Action Code 30 (means 'Ground for Detention') Fire main isolating valve found not operational. Deficiencies with Action Code 17 (means 'To rectify deficiencies before departure') Fire main isolation valves found to be frozen. Fire main isolating valves found tight to operate and stiff to operate. Main fire line securing cleats at main deck found broken. Main fire line on main deck found corroded and leaking. Fire line expansion joint/sleeve and pipe fitting found leakage. Fire line found holed and drain valves were leaking. Deficiencies with Action Code 16 (means 'To rectify deficiencies within 14 days') Main Isolation Valve between accommodation/deck to be marked on bulkhead. Fire main on deck in some areas heavily corroded. Fire lines found wasted. Fire line expansion joint found leaking at drain plug. Deficiencies with Action Code 15 (means 'To rectify deficiencies at next port') Fire main on main deck holed and leaking. Fire main expansion joint found leaking excessively. Deficiencies with Action Code 99 (means 'Other') Temporary repairs made on fire line main deck and line to be pressure tested.

No
1 2

Quick Closing Valve


Deficiencies with Action Code 30 (means 'Ground for Detention') Means of closure found not operative - quick closing valves inoperative. Deficiencies with Action Code 17 (means 'To rectify deficiencies before departure') Air bottle for engine room quick closing valve operation was not charged.

No
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Others Deficiency Details


Deficiencies with Action Code 30 (means 'Ground for Detention') Self-closing blanking devices for sounding pipes in E/R found defective. Deficiencies with Action Code 17 (means 'To rectify deficiencies before departure') Safety instruction at outside paint locker illegible. Standard IMO safety signals to be displayed where required. Emergency escape from engine room to deck - found lights not working and door hinges are not free. Steering gear room - Poor housekeeping, oil at floorboard and the door was kept opened by ropes. Accumulation of used paint drums with half filled paint (without cover) at steering gear flat. Main engine unit no.1,2,3,4,5 and 6 exhaust outlet trunking to main exhaust manifold were not insulated. Leak oil alarm from running generators inoperative due to open drain. Air bottle for Self-Operated Safety (SOS) valves kept at too low pressure and it is below required bar due to or suspected to unknown leakage. Means of control - In engine room shaft tunnel; sounding cap was missing. Fire screens were in poor condition. Filters (grease trap) above cooking plate in galley found with full of grease. Waste receptacles are not constructed from non-combustible materials. Safety equipment was not used during cargo operations. Fire call button on forecastle damaged. Updated List of Crew & Cargo plan were not available with Fire Control Plans.

Page 5 of 6

ZIZA ZERO INCIDENT ZERO ACCIDENT

PSC Inspection Common Deficiencies


Category 2 Fire Fighting Equipment 01- January-2000 to 31-December-2005

No
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35

Others Deficiency Details


Deficiencies with Action Code 16 (means 'To rectify deficiencies within 14 days') One oxygen detector's certificate found out of date. Diesel generator engines - fuel pipings (high pressure) were not shielded/enclosed. No fire screen in place for oil tank air pipe. The lamp cover is missing over the atomiser of the boiler in Eng.Room. Fire prevention - waste receptacles are not made of non-combustible material. Waste receptacles made from plastic Paint locker spray notice was partially blocked. Bosun store was kept as paint store. Graphical symbols for fire control plan was not posted/or marked. Fire control plan found without an Class approved. Fire control plan deferred from actual site. Some plans are unreadable. Deficiencies with Action Code 15 (means 'To rectify deficiencies at next port') Bilge holding double bottom tank (in E/R) self closing device on sounding pipe found defective. Deficiencies with Action Code 99 (means 'Other') Fire control plans - to be colour coded. International Code of Fire Safety System publication found not available on board. Alarm of high pressure fuel delivery lines between high pressure fuel pumps and fuel injectors of emergency generator engine: not provided. Main & Auxiliay engines high pressure fuel pipe leakage alarms found not fitted. Emergency generator - High pressure fuel oil line was not provided with protective enclosures. Closure of air intake for emergency generator room found missing. All waste receptacles must be constructed by non-combustible material. Joints of fuel oil lines are without protection to avoid oil spray.

Page 6 of 6