Professional Documents
Culture Documents
(User Manual)
MiCOM
I> I>> I<
PTC
L1 L2 L3
P 211
[%] [S]
MiCOM
I> I>> I<
PTC
L1 L2 L3
P 211
[%] [S]
Vx PTC A1 A2 13 14 23 24 T1 T2
S2 S1
Vx PTC A1 A2 13 14 23 24 T1 T2
S2 S1
Fig. 1 MiCOM P211 connection for motor currents IBmin < In < IBmax.
3 4 5 6 7
MiCOM
I> I>> I<
PTC
L1 L2 L3
P 211
[%] [S]
Vx PTC A1 A2 13 14 23 24 T1 T2
S2 S1
10
11
1 2 3 4 5 6 7 8 9 10 11
- keyboard - LED display - I> overload and I>T overload trip indicator - I>> short circuit fault trip indicator - I< undercurrent start and I<T undercurrent trip indicator - indicator of unbalance or loss of phase and trip T - indicator of excessive temperature inside the motor - auxiliary power supply terminals - output contact terminals: 13 - 14: P1 relay; 23 - 24: P2 relay - PTC sensor terminals - control input terminals
1 2 3
L1 L2 L3
4 5
LED indicator will be restored to the status before the voltage interruption. To start the motor the tripped protection must be reset following the procedures described in section 7. b) Using the menu diagram (fig. 5) and relay keypad, select the menu item to be changed. c) Press : If a password has been input before, the LED displays 'P000' with the last digit blinking. Now select the correct password number with or keys. Use the key to go to the second password digit, and then repeat the described procedure. Press . Setting edit mode is now accessible. If no password has been input before, the rightmost digit of the display starts blinking. The setting values should now be entered, following the steps described above. After all the setting values have been input, press , to accept the setting. Go to the next menu setting to be changed and repeat the above procedure. If a password has been entered, then after completing the changes of settings, go to item and press . All the new settings are now accepted and edit mode is exited (the password must be re-entered to change any setting when out of the edit mode). 5.4 Entering a password Note: A three-digit password can be used to provide security. The settings can then only be read unless the password is entered. a) Choose menu item and press . The third digit of the display (password) starts flashing. Input the password number with b) or keys.
d) e)
Use key to go to the second digit of the password, input the password number and then repeat the procedure with the first digit of the password. Press saved. to accept the password which should next be
c)
5.5 Settings 5.5.1 Overload Protection I>: The following parameters should be entered: Current value IB in [A] (within the relay current range) Time delay t at I = 6 IB (1 - 40 s, step 1 s). For tripping times at other IB multiplies at 0% and 50% of the motor thermal state - see table 1. Reset options: 1 - manual, 0 - self-reset (see section 7 for detailed description) P1 relay operation 0 - output state remains unchanged (13-14 contact closed) after a protection trip 1 - output contact (13-14) opens after a protection trip P2 relay operation 0- output contact is not influenced by a protection start or trip, the status remains the same as chosen in setting 1 - output contact is not influenced by a protection start, but after tripping they change over from the state chosen 2 - every protection start (I>, I<, , Zf) changes the state of the contact from the state chosen in setting 5.5.2 Short Circuit Protection I>>: Current value as a multiple of IB (5 - 12, step 1) P1 relay operation - see the description above P2 relay operation - see the description above 5.5.3 Undercurrent protection I<: Current value as a percentage of IB (30 - 90%, step 10%) Time delay t (0 - 60s, step 1 s) P1 relay operation - see the description above P2 relay operation - see the description above 5.5.4 Loss of phase protection: Time delay t (0 - 10s, step 0.1 s) P1 relay operation - see the description above P2 relay operation - see the description above 5.5.5 Unbalance protection: Unbalance value in [%] (15% - 50%, step 1 %) Time delay t (0 - 25 s, step 0.1 s) P1 relay operation - see the description above P2 relay operation - see the description above 5.5.6 Temperature Protection: Reset option: 1 - manual, 0 - self-reset (incl. LED reset) P1 relay operation - see the description above P2 relay operation - see the description above 5.5.7 MiCOM P211Configuration Select mode of operation by means of S1 - S2 terminals: 0 - P1 relay trip is latched, if S1-S2 are shorted 1 - all protection trips are reset by shorting the S1-S2 input, providing the cause of the fault has ceased 2 - immediate motor trip (break of P1 contacts: 13 - 14) by shorting S1-S2 intput 3 - P2 output contacts (23 - 24) change state, when S1-S2 are shorted Selection of P2 contact operating mode when the auxiliary supply voltage Vx is applied in setting
5.5.10 Default Settings Overload Protection I> IB = minimum setting in [A], t = 10 s, manual reset (1), P1 contacts open (1) and P2 contacts change state (1) after a protection trip Short Circuit Protection I>> I>> = 10 IB , P1 and P2: as above Undercurrent Protection I< I< = 30 % of IB , t = 9.5 s, P1 and P2: as above Loss-of-Phase Protection t = 0.5 s, P1 and P2: as above
Unbalance Protection
Menu navigation
Protection settings Overload I> Short circuit (IB setting) I>> Undercurrent Loss of phase I< Zf Unbalance Description Temperature PTC Configuration Description Accept / Cancel
Description
Description
Configuration option
Current settings
5
Fig. 5 Menu diagram with the default settings
Unbalance setting
Change of password
P1 Programming
Key:
P2 Programming
6.9 The following indications occur when the auxiliary voltage Vx is applied to the relay:
- I>, I>>, I<, , PTC LEDs flash for a moment - depending on the relay current range, one of symbols: PR1, PR2, PR3, PR4, or PR5 is displayed for about 1 second - L1 indicator comes on and the '0.0' symbol appears The status of any protecion trip is memorised in case of auxiliary supply voltage interruption. Therefore the respective LED indicators will return after the Vx auxiliary supply is restored. To put the relay into stand-by, the tripped protection must be reset following the procedure described in section 7. The MiCOM P211 is then ready to operate.
100.0
MiCOM
I> I>> I<
PTC
L1 L2 L3
P 211
[%] [S]
75.0
Vx PTC A1 A2 13 14 21 22 T1 T2
S2 S1
6.10 The LEDs and display being off indicate the auxiliary supply voltage Vx has been switched off. Resetting is possible when the cause of the protection trip has ceased. 7.1 Reset by shorting terminals S1 - S2 (remotely or locally). If the menu option has been selected, a temporary shorting of the S1 - S2 terminals will reset all tripped protection and their LED indications. 7.2 Reset from the keypad. Select menu item and press
32.5
7. Resetting
key. All tripped protection and their LED indications will be reset. For I> and PTC protection the reset will only take place, if reset option is chosen. 7.3 Self-reset (only for I> overload and PTC temperature protection). If option has been selected from the menu all tripped protection and their LED indications are reset automatically, after the casue of tripping has ceased. 7.4 Reset of motor thermal state To quickly reset the motor thermal state the keys should be pressed simultaneously. NOTE: Absence of auxiliary supply voltage Vx for the period of time longer than the reset time of the output relays, will make the motor thermal state reset.
5.0 111.0 103.0
Fig 6. Dimensions of MiCOM P211 Table 1. Time delays for overload protection
Motor thermal state [%] 0 50 0 50 0 50 0 50 0 50 0 50 1 0,54 1,44 0,72 2,34 1,2 4,32 2,28 10,7 5,88 23,1 13,7 2 1,09 2,98 1,96 4,70 2,49 8,80 4,73 22,0 12,4 47,0 28,9 3 1,50 4,44 2,28 7,02 3,60 12,9 6,72 32,3 17,6 68,7 40,8 4 2,10 5,96 3,06 9,42 4,80 17,3 8,94 43,3 23,6 92,5 55,0 5 2,58 7,40 3,4 11,7 5,94 21,5 11,1 54,0 29,4 116 69,3 6 3,12 9,00 4,56 14,3 7,32 26,3 13,6 65,5 35,7 141 84,2 Time settings for I = 6 x IB
IB
multiple
7 3,54 10,3 5,22 16,6 8,28 29,8 15,5 74,4 40,5 159 94,7
8 4,14 11,9 6,06 18,8 9,66 34,6 17,9 86,0 46,9 188 112
9 4,74 13,5 6,84 21,4 10,9 39,2 20,3 97,7 53,2 210 125
10 5,06 14,8 7,48 23,5 11,9 43,1 22,3 108 58,8 233 139
15 7,90 22,7 11,5 36,2 18,4 66,3 34,3 166 90,5 360 214
20 10,3 29,6 15,0 47,8 24,0 87,0 45,0 216 118 449 265
25 12,9 37,2 18,8 58,8 30,0 107 55,5 276 150 572 340
30 14,8 42,4 21,5 67,0 34,2 124 64,2 311 170 664 396
35 17,2 49,5 25,0 78,9 4,02 143 74,0 357 194 791 472
40 20,6 59,7 30,2 94,5 48,2 174 90,4 418 228 978 540
1,5
Technical data
IB base current settings 4 - 6 A in steps of 0.2 A 5 - 10 A in steps of 0.5 A 10 - 20 A in steps of 0.5 A 20 - 40 A in steps of 1 A 40 - 80 A in steps of 1 A Max. rated voltage of a motor directly connected to MiCOM P211 (without external CT's) 1000 V Frequency range 10 - 1000 Hz Auxiliary supply voltage options 24, 110/127, 230 V 50/60 Hz, 24 - 230 V AC/DC Auxiliary supply voltage tolerance (0.8 - 1.1) Vx Current accuracy 10 % Protection setting ranges short-circuit (5 - 12) x IB ; in steps of 1 undercurrent 30 - 90 % of IB; in steps of 10% unbalance 15 - 50 %, in steps of 1 % Time accuracy 10 % Time setting ranges overload at I=6 x IB 1 - 40 s, in steps of 1 s undercurrent element 0 - 60 s, in steps of 1 s unbalance element 0 - 25 s, in steps of 0.1 s loss of phase element 0 - 10 s, in steps of 0.1 s Tripping time I<T, T, ZfT < 250 ms I>>, PTC < 100 ms
Reset time of output relays on aux. supply voltage Vx interruption 0.08 s (Vx=24, 110, 230 V 50/60 Hz) 2.2/1.3 s (Vx=230 V AC/DC) 0.6/0.3 s (Vx=110 V AC/DC) 0.03/0.02 s (Vx=24 V AC/DC) PTC sensor input max. resistance in cold state 1500 trip resistance 3700 - 4000 reset resistance 1900 - 2100 Burden ~ 4.5 VA Output contacts 2 NO (programmed independently) Contact rating make: 5 A carry: 5 A (continuous break: 5 A (220 V AC, cos 0.4) Durability Unloaded contact 10 operations min. Loaded contact 10 operations min.
5 7
Emission tests Conducted emissions EN 55011, class A Radiated emissions EN 55011, class A Immunity tests Conducted immunity EN 61000-4-6, class 3 Radiated immunity EN 61000-4-3, level 2 Radiated immunity from digital radio telephones ENV 50204, level 3 Surge immunity EN 61000-4-5, level 3 Fast transients EN 61000-4-4, level 3 High Frequency Disturbance IEC 1000-4-12, level 3 Impulse immunity IEC 255-5 Electrostatic Discharge EN 61000-4-2, level 3 Voltage dips EN 61000-4-11 Voltage interruptions EN 61000-4-11
Dielectric withstand IEC 60255-5: 1997 2 kV rms for 1 minute between all terminals of independent circuit with teminals on each independent circuit connected together 1 kV rms for 1 minute across the open contacts of normally open output contacts Temperature IEC 60255-6: 1998 operating - 5 C - + 55 C storage and transit - 25 C - + 70 C Enclosure protection class IEC 60529:1989 housing terminals Weight 0.5 kg IP 40 IP 20
0 0 0 0
Your contact:
Strzegomska 23/27, 58-160 Swiebodzice, Poland Sales Dept. Tel.: +48 (74) 854 84 25 Fax: +48 (74) 854 85 48 www.alstom.com e-mail: pcb-gee.poland@tde.alstom.com
ALSTOM T&D SA
abcd
TRANSMISSION & DISTRIBUTION Protection & Control, HQ, 60 Route de Sartrouville, BP58, F78230 Le Pecq Cedex. Tel: +33 (0) 134 80 79 00 Fax: +33 (0) 134 80 79 13 Email: protection.control@tde.alstom.com Internet: www.tde.alstom.com
2000 ALSTOM. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM. Other names mentioned, registered or not, are the property of their respective companies. Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it. We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice. Publication: 506.066.00.1.GB Printed in Poland
France