Professional Documents
Culture Documents
{L1R)si
(1)
where L, C and R are flter inductor, flter capacitor and
load resistance, respectively. The power stage is a typical
resonance system, so proporional plus derivative
compensator with a non-zero pole is applied to control the
close-loop system, and the transfer fnction of the
compensator is:
CMCE 2010
(2)
where is the root locus gain, Y_ is zero to counteract one
pole of the power stage (1), w_ is high fequency pole to
restrain high fequency noise existing in the loop.
The discretization methods by which the s-domain
transfer fnction is mapped to z-domain include Euler
method, root-matchig method and equal-effect holder
method [10]. The difference of these methods for the gross
system performance can be ignored as the sampling rate
(switching fequency) achieves mega-level in low-voltage
converters, so backward Euler method which is relatively
simple is applied, and its transfer equation is:
l
j
-
]
(3)
where Ts is sampling cycle, and equal to switching cycle
for switching dc-dc converters. From (2) and (3), the
transfer difference equation of the digital compensator is
obtained:
d(k)- ad(k-l) oe(k) .e(k-l). (4.a)
l
a=
l W
]
I_
o-
K
'
l W_] )
l W
]
]
K
.-
l W
]
]
(4.b)
(4.c)
(4.d)
Equation (4) is the discrete time-domain control law of
D-PD controllers for dc-dc converters.
D. Steady-State Analysis
When the digitally controlled dc-dc converters gets
stable, digital cycle duty d[k} and digital error e[k} will
keep constant, so steady-state control law of D-PD
controller can be obtained fom (4):
d k |-
o .
e k|
ia
(5)
Digital error e[k} must never be equal to zero in the
steady state; otherwise d[k} is equal to zero, so this steady
state control law is different fom D-PID compensator that
the input digital error is equal to zero, and output cycle
duty is unlimited by the input error in the steady state. The
following equation is obtained based on the DPWM
operation for buck dc-dc converters:
1 -
|
-
dk|
| ,
^
'
(6)
where D is the steady cycle duty of the square wave,
^,is the DPWM resolution. From (5) and (6), the error
limit equation is obtained:
O1
(ia)|
ek|-
'
,
^
(o .)|
(7)
Equation (7) is the steady-state condition which digital
error e[k) must follow for D-PD controller.
C. Error-Shi Technique
Although the close-loop converter system shown in
Fig.l is zero-type system for D-PD controller [11], steady
state error can be eliminated by error-shif technique. Fig.2
(a) shows the transfer curve of the conventional ADC, |,
is LSB size, and the zero error-bin of dc-dc converters is
fom |.,,[ to |.,,+ | 2. The horizontal axis is
expressed as |.,,|,`,because the ADC input is equivalent
to the error between reference voltage and output voltage.
The ADC encodig fnction can be abstracted:
ek |-
1
..''
'
)
(8)
When steady-state error of the converter system is
equal to zero (} [|.,,| 2, |.,,+ | 2 ], e[k} also
becomes zero shown in Fig.2 (a), but this situation violates
the steady-state condition obtained in the above content.
Therefore, we must modif the ADC encoding fnction to
shif output eror as shown in Fig.2 (b), and then defne the
following equation:
(ia)|
e -
C
,
^
''J
(o .)|
(9)
where eshii is the shifed error. The modifed encoding
fnction is obtained based on Fig.2 (b), (8) and (9):
ek|-
1
(| |)
'
l-a)
'
,
^
(10)
.. C
(o.)|
1 Z J (11)
S
From (4.b) and (11), coeffcient a is equal to 1I2N, so
coeffcient a look-up table can be replaced by one shifer.
The shifing number ^ should not be too big in order that
pole w_ can effectively restrain high-fequency noise
existing in the loop. FigA depicts the block diagram of D
PD compensator which mainly includes two look-up tables,
one adder and one shifer. Comparing to D-PID
compensator [8], the number ofJook-up tables is decreased
form three to two, and the adder input is decreases fom
four to three.
IV. SIMULATION
This section presents the simulation results by
30|O
I|O|00Ol
O|!0UO
- e[\]
Figure 3. block diagram of delay-line window-ADC with error-shif
technique.
O1O
Figure 4. block diagram of digital compensator.
TLAB/Simulink to verif the validity of the proposed
D-PD controller. We choose the following circuit
parameters for continuous conduction mode (CCM) based
on the buck dc-dc converters shown in Fig.l :
/=l.OMHz, L=l.OjH C=22.0jF R=2.7Q, Vg=6.0V
Vo=Vre.2.7V, Vq=25.0mV
We set w,equal to 3wn14, w,is the comer fequency of
the power stage LC flter, and set ^ equal to two, so w_ is
equal to 3/. Adjusting root locus gain , the phase margin
of the open-loop converter system can be set to 60 as
shown in Fig. 5, and then the control law coeffcients are
obtained based on (4):
a=0.25, b=19.00, c=-16.00
It should be noted that the c-LUT can also be replaced
by another shifer because coefcient L is an exponential
fnction of two, but this does not always happen. The
ADC resolution should be 8 bit according to the LSB size
Vq, so the DPWM resolution is set to 9 bit in order to avoid
limit cycles [12]. The zero eror-bin of the dc-dc converter
is fom 2.6875V to 2.7125V which the ideal output with
zero steady-state error should be located in.
Fig. 6 shows the load transient characteristics of the
buck dc-dc converters for the proposed D-PD controIler
and D-PID controller, with the load step change fom 2A
to lA at 1.3ms and back to 2A at 2.3ms, the circuit
parameters of two converters are same. The two curves are
both located in the zero eror-bin of dc-dc converters afer
the stabilization of the systems, so this indicates that the
proposed D-PD controller has the same effectiveness as D
PID controller to eliminate steady-state error. However, for
the proposed D-PD controlled converter, overshoot is 3%,
and transitional time is 0.3ms afer the load step change,
40 .
~ 40
"
_ t:
_ '
-10
-20
= - . .. l
Pha c:ag 0
r-
_ _ _ _
|rcqucocy(rad/scc)
Figure 5. bode diagram of the open-loop converter system
t
t
^ll
.
~l-1
/
J
j
''\\\\' \
!'
!
!t
!
t
!
., .\_ ......,.
.
~
-+
' `r
4
.. . /.,
!
.2 .4 .6 .S 2 2.2 2.4 2.6 2.S J J.2
timc,ms)
Figure 6. Load transient waveforms obtained by M TLAB/Simulink
simulation for load step change fom 2A to lA and back to 2A
while overshoot is 6%, and transitional time is O.5ms for
the D-PID controlled converter, so the proposed D-PD
contoller is better than D-PID controllers for the dynamic
performance of dc-dc converter.
V. CONCLUSION
This paper introduces digital proportional plus
derivative (D-PD) controller which can signifcantly
decrease the layout area of digital compensator in contrast
with D-PID controller for switching dc-dc converters.
Error-shif technique which can be easily implemented in
delay-line window-AC is proposed to eliminate steady
state eror for the proposed D-PD controller. Simulation
shows that the proposed D-PD controller can achieve the
same steady-state performance and better dynamic
performance than D-PID controller for switching dc-dc
converters.
O1U
REFERENCES
[I] J. Li, F. C. Lee, "Digital current mode control achitecture with
improved performance for DC-DC converters," in Proc. IEEE
APEC'08 Conf, 2008, pp. 10871092
[2] S. Chattopadhyay and S. Das, "A digital currentmode control
technique for dc-dc converters," IEEE Trans. Power Electronics,
vo1.21, no.6, Nov. 2006, pp. 1718-1726
[3] J. Chen, A. Prodic, R. Erickson, and D. Maksimovic, "Predictive
digital current programmed control," IEEE Trans. Power
Electronics, vol. 18, no. I, Jan. 2003, pp. 411-19
[4] A. G. Perry, G. Feng, Y-F. Liu, P.C. Sen, "A Design Method for PI
Like Fuzzy Logic Controllers for DC-DC Converter" IEEE
Transactions on Industrial Electronics, vol. 54, no. 5, October 2007,
pp. 2688-2696
[5] K. Wei, Q. Sun, B. Liang, "The Research of Adaptive Fuzzy PID
Control Algorithm Based on LQR Approach in DC-DC Converter"
2008 IEEE Pacifc-Asia Workshop on Computational Intelligence
and [ndustrial Application, pp. 139143
[6] A. G. Perry, G Feng, Y-F Liu, "A New Design Method for PI-like
Fuzzy Logic Controllers for DC-to-DC Converters", 2004 3SIh
Annual IEEE Power Elecrronics Sperialisls Conference, pp. 375[-
3757
[7] Y. Duan, H. Jin,"Digital Controller Design for Switch mode Power
Converters", IEEE Applied Power Electronics Conference (APEC),
1999, pp. 967-973
[8] B.J. Patella, A. Prodic, A. Zirger, D. Masimovic,"High-Frequency
Digital PWM Controller IC for DC-DC Converters", IEEE
Transactions on Power Electronics, vol. 18, no. [, January 2003, pp.
438446
[9] Sanjaya Maniktala, "Switching power supplies A to Z",
Amsterdam: Elsevier/Newnes, 2006, pp. 170-217
[10] G. F. Franklin and J. D. Powell, "Digital Control of Dynamic
Systems", Reading, M. AddisonWesley, [998, pp. 73-101
[II] Showsong Hu, "Theory of automatic control", 5th ed. Beijing:
Science Publishers, 2007, pp. 98121
[12] A. V. Peterchev and S. R. Sanders, "Quantization resolution and
limit cycle in digitally controlled PWM converters", in Proc. IEEE
PESC Conf, 2001, pp. 465-471