Catalogue 1YMB612070-en
enabled
ABB
1. FEATURES
Unlimited breaking capacity Shortcircuit current limiting Small dimensions.
4.3 Indoor fusebases numbering system The numbering system for indoor fusebases has two alphanumerical sections as shown in the following diagram.
PBPM
6
Rated voltage 6 7,2 kV 10 12 kV 20 24 kV 30 36 kV
2. APPLICATIONS
The WBP fuselinks are used to protect switchgear equipment against shortcircuits in voltage transformers. Protection of switchgear equipment is very effective thanks to unlimited breaking capacity and short circuit current limitation. Thanks to very small dimensions WBP type fuselinks can be used in various types of switchgears, including flameproof types.
Fusebase type
PBPM
36
Rated voltage 36 kV
w.II1
Additional designation
Fusebase Kind of fuse type base I hanging type III standing type
The numbering system for outdoor fusebases have four double alphanumerical sections as shown in the folllowing diagram. A fuselink when mounted on a fusebase makes a complete fuse. For the available fusebases refer to Table 2.
Designations: N Normal climate T Tropical wet and dry climate 1 Outdoor installation 3 Indoor installation
5.1 Construction and operation of fuselinks A fuselink consists of an insulation tube1 whose both ends are terminated with end caps. Fuse elements are made from specially profiled silver wire. The fuse elements are helically wound on the porcelain stick. The resistance of the fuselinks is acc. to table 2. The fuse interior is tightly filled with arcquenching material, whose chemical composition and granularity have been appropriately chosen. The fuselink is sealed at its both ends. The fuse operation depends on automatic singletime interruption of fault current in the protected circuit by melting of its fuse element and quenching of the electric arc produced in the fuselink interior. The fuse links limit the peak value of shortcircuit currents and hence effectively protect circuits from thermal and electromagnetic effects of shortcircuits. A fuselink when mounted on its fusebase makes a complete fuse. For the availablebase refer to Table 2.Voltage transformers fuse links can be used as buildup version and in special bases with one contact installed on the voltage transformer and one on the post insulator. 5.2 Construction of the fusebases The fusebase consists of a steel beam fitted with protectiveearthing terminal. There are two indoor or outdoor support insulators on the beam. Contacts are mounted on the upper side of insulator. The set of contacts consists of contact spring, compression spring, and terminals.
WBP
Indoor Fuselink type
6
Rated Voltage 6 7,2 kV 10 12 kV 20 24 kV 30 36 kV
4.2 BRT outdoor instrument transforme fuselinks numbering system The numbering system for the BRT fuselinks has two alphanumerical sections as shown in the following diagram.
BRT
Outdoor Fuselink type
6
Rated voltage 6 7,2 and 12 kV 15 17,5 and 24 kV 30 36 kV
8. HOW TO ORDER
Order by specyfying the product name, type symbol, rated value, rated current and quantity. All additional demands which are not listed in this Catalogue should be agreed with the manufacturer by means of an Inquiry where the sources of requirements (regulations. standards, etc.) are to be apecified. 6.1 Order example 1.Type WBP6 fuselink for a rated voltage of 7.2 kV and rated current of 0,7 A 10pcs 2.Type PBPM6 Indoor fusebase for a rated voltage of 7,2 kV 20 pcs
1)
ABB
6. SPECIFICATIONS
6.1 Technical data of fuselinks Table 2
Rated Voltage Un kV WBP6 WBP10 WBP20 WBP30 BRT6 BRT15 BRT30 7,2 12 24 36 7.2 and 12 17.5 and 24 36 50 or 60 0,8 50 or 60 Rated current In A 0,7 0,6 0,5 0,4 Rated Breaking Current I ws kA 120 72 36 24 80 33
2 3
Fuselink Type
Frequency f Hz
Weight
Fusebase Type
W
42 62 135 225 57 144 290
W
52 72 165 275 63 156 310 PBPM6 PBPM10 PBPM20 PBPM30
>1500
>1000
16
The resistance are to be measured by an electrical bridge method or technical method using measuring instrument with accuracy class not worse than 0.5% at an ambient temperature of t = 20C 2C.
Note: Due to the introduction of improvements, the right is reserved to modify the products. Note: In case of installation of WBP fuses in closed housing and similar equipment characterised by heat exchange (stabilised ambient air temperature exceeds +40C) the value of nominal current In should be reduced by 0.1 A. 6.2 Technical data of fusebases Table 3
Rated voltage Un kV PBPM6 PBPM10 PBPM20 PBPM30 PBPN241 PBWMNI 36 w.II1 PBWMNIII 36 w.II1 7.2 12 24 36 24 36 36 50 or 60 Frequency f Hz Impulse withstand voltage of insulation to earth kV 60 75 125 170 125 170 170 in pole kV 70 85 145 200 145 195 195 50 Hz withstand voltage of insulation to earth kV 27 35 55 75 55 70 70 in pole kV 35 45 75 100 75 85 80 WBP6 WBP10 WPB20 WBP30 BRT15 BRT30
Type of fusebase
Type of fuselink
PBPM an indoor fusebase with resin insulators PBPN an outdoor suspended fusebase on 24 kV PBWMNI 36 w.II1 an outdoor suspended fusebase on 36 kV PBWMNIII 36 w.II1 an outdoor fusebase on 36 kV Note: Due to the introduction of improvements, the right is reserved to modify the products.
Recommendation of fuse links selection for MV voltage transformer protection
ABB Sp. z o.o. recommends using instrument transformers fuse elements type WBT from our production portfolio as protection for ABB's voltage transformers types UMZ and UDZ equipped with fuse holder. Using instrument transformer fuses has two main functions; to protect distribution equipment against results of internal voltage transformers short circuits and to reduce probability of explosion possibility in case of damage of internal isolation of voltage transformers. The selection of fuse element for protection of voltage transformer should be done mainly in dependence on rated primary voltage of voltage transformer*. The rated voltage of fuse element should be equal or higher of (phase to phase) rated voltage for primary winding of voltage transformer, for example for VT type UMZ 15-1 working with voltage 3 kV on primary winding, one should select fuse link type WBP-10 that rated voltage is 10 kV. The rated current of fuse links type WBP was reduced from 0,8A to 0,4-0,7A (depending on Un ) starting from January 2001. The reason of this change was to improve cooperation between fuse link and voltage transformers. Comparison of past voltage transformer fuse links type WBP with the new one is presented in the table below: ABB Sp. z o.o. recommends to use new fuse links with limited rated current (0,4- 0,7A) for protection voltage transformers type UMZ and UDZ instead of using former ones with rated current 0,8A.
7.2 12 24 36
0.8
ABB
DIMENSIONAL DRAWINGS
D L
Notes: Connections: silver-plated cooper. Deviations of dimensions with no tolerance specified shall be within 3%.
Dimensions (mm) A D 25 18 25 18 25 18 25 18
B 23 23 23 23
L
Notes: Connections: silver-plated cooper. Deviations of dimensions with no tolerance specified shall be within 3%.
Dimensions (mm) A B D 62 54 50 62 54 50 62 54 50
C 68 68 68
B C
ABB
A3 A2 A1
M5
2
M10
20
two 11 mm dia.holes
A4 A5
B2
A3
Notes: Earthing Terminal; tinned steel. Connections: silver-plated brass Contact Springs: silver-plated brass Deviations of dimensions with no tolerance specified shall be within 3%.
B1
Fuse base type PBPM-6 PBPM-10 Dimensions (mm) A2 A1 1702 2002 2102 2402 A3 245 285 A4 110 150 A5 95 95 A6 62,5 62,5 B1 165 190 B2 128 153 D 50 50 E 23 23
15 40
ABB
A3 A2 A1
2
M10
two 11 mm dia.holes
M5
20
A5 A6
A4
Notes: Earthing Terminal; tinned steel. Connections: silver-plated brass Contact Springs: silver-plated brass Deviations of dimensions with no tolerance specified shall be within 3%.
A3 415 490
25 60
B2 B1
B2 232 322
D 50 70
E 23 23
ABB
two 18 mm dia.holes
A5 A6
D 100
A4
B1
B2
26
M12
M12
A1 A2 A3
Notes: Earthing Terminal; tinned steel. Connections: silver-plated brass Contact Springs: silver-plated brass Deviations of dimensions with no tolerance specified shall be within 3%.
Dimensions (mm) A2 A1 2972 3572 4622 5522 A3 647 632 A4 127 205 A5 223 265 A6 159,5 159,5 B1 417 559 B2 336 476 D 145 175 E 62 62
40
ABB
A3 A2 A1 M12
M12
A5 A6
40
26
100
B2
A4
1YMB612070-en Publication 04.2004 1YMB612070-en Publication 09.2005
Notes: Earthing Terminal; tinned steel. Connections: silver-plated brass Contact Springs: silver-plated brass Deviations of dimensions with no tolerance specified shall be within 3%.
Dimensions (mm) A2 A1 4622 5522 A3 632 A4 205 A5 265 A6 159,5 B1 559 B2 476 D 175 E 62
ABB is working to continuous improve the products. Therefore we reserve the right to change design, dimension and data without prior notice. This product has been certified by ABB Group as Industrial IT Enabled - Information Level. All product information is supplied in interactive TM electronic format, based on ABB Aspect Object technology. The Industrial IT commitment from ABB ensures that every enterprise building block is equipped with the integral tools necessary to install, operate, and maintain it efficiently throughout the product lifecycle.