You are on page 1of 4

1728EX Quick Setup for Pre-Programmed Systems

Step 1:

Connecting Hardware

If you are using EOL resistors, refer to Hardwire Zone Connection Using EOL Resistors on page 4.

Step 2:

How to Program
2.1 2.2 [ENTER] [INSTALLER CODE] (default: 0000) [SECTION] [DATA] Press [CLEAR] at any point to exit and then enter a new section. [ENTER] to save.

Step 3:
Section [143]

Minimum Programming for Central Station Reporting


Description Partition 1 Account Number (press the [FORCE] key if less than 4 digits; to enter hexadecimal values refer to the Decimal and Hexadecimal Programming Table on page 4) Data ____/____/____/____

[151]

Central Station Telephone Number 1 (press the [ENTER] key if less than 32 digits)

__________________________________
Maximum: 32 digits

[153]

Backup Central Station Telephone Number (press the [ENTER] key if less than 32 digits)

__________________________________
Maximum: 32 digits

Step 4:

Optional Programming with Defaults and Pre-Programmed Settings

If a hardware reset is performed, the control panel will reset to factory defaults (refer to the Spectra Programming Guide) and the pre-programmed settings will be lost.
= pre-programmed setting Section Description
Zone Definitions Empty slot [FORCE] - Disabled 1 - Entry Delay 1 Additional definitions for on2 - Entry Delay 2 board terminals: 3 - Follow 7 - Keyswitch 4 - Instant 8 - Standard 24Hr Fire 5 - 24Hr Buzzer 9 - Delayed 24Hr Fire 6 - 24Hr Burglary Partition Assignment Empty - Zone disabled 1 - Partition 1 2 - Partition 2 3 - Both partitions

Data
Zone Options [6] - Intellizone [7] - Delay before transmission [8] - Force Zone Keyswitch Options [1] - OFF = Maintained / ON = Momentary [2] - OFF = Regular arm / ON = Stay arm

[1] - Auto-zone Shutdown Enabled [2] - Bypass Enabled [3] - Stay Zone [4] OFF OFF ON ON [5] OFF ON OFF ON

Zone Alarm Type Steady Alarm Pulsed Alarm Silent Alarm Report Only

[001] [002] [003] [004] [005] [006]

Zone 1: Delayed 24Hr Fire zone Zone 2 : Follow zone Zone 3 : Instant zone (Stay Zone enabled) Zone 4 : Instant zone Zone 5 : Instant zone Zone 6 (keypad zone 1): Entry Delay 1 zone

9 1 ____ /____ ( 1 2 * * * * * *) 3 1 ____ /____ ( 1 2 * * * * * *) 4 1 ____ /____ ( 1 2 3 * * * * *) 4 1 ____ /____ ( 1 2 * * * * * *) 4 1 ____ /____ ( 1 2 * * * * * *) 1 1 ____ /____ ( 1 2 * * * * * *)

[066]

PGM1 Timer

0 3 0 ____/____/____ seconds 0 4 5 ____/____/____ seconds 0 4 5 ____/____/____ seconds 0 3 0 ____/____/____ seconds 0 3 0 ____/____/____ seconds 0 0 4 ____/____/____ minutes

[069] [070] [071] [072] [073]

Entry Delay 1 Entry Delay 2 Exit Delay 1 Exit Delay 2 Bell Cut-off Timer Partition 1

[077]

Answering Machine Override Delay (000 to disable)

0 3 2 ____/____/____ seconds

Event Group # [120]

Sub-group # 0 1 _____/_____

Partition # 0 1 _____/_____

PGM1 Activation Event ([PG]/[FNC1] was pressed; smoke reset)

0 5 _____/_____

[126]

PGM1 Normal State

Option [4]

OFF = N.O.

ON = N.C.

[127]

Lock System Master Code

Option [4] Option [6]

OFF = Disabled OFF = Disabled

ON = Enabled ON = Enabled

User Code 048 is a Duress Code

[128]

Panic 1 (keys [1] and [3]) Panic 2 (keys [4] and [6]) Panic 3 (keys [7] and [9])

Option [1] Option [2] Option [3]

OFF = Disabled OFF = Disabled OFF = Disabled

ON = Enabled ON = Enabled ON = Enabled

Panic 1 alarm type Panic 2 alarm type Panic 3 alarm type

Option [4] Option [5] Option [6]

OFF = Silent Alarm OFF = Silent Alarm OFF = Silent Alarm

ON = Audible Alarm ON = Audible Alarm ON = Fire Alarm

[129]

Wireless Module Low Battery Supervision

Option [6]

OFF = Disabled

ON = Enabled

[130]

One-touch Regular Arming One-touch Stay Arming One-touch Force Arming One-touch Bypass Programming

Option [1] Option [2] Option [3] Option [4]

OFF = Disabled OFF = Disabled OFF = Disabled OFF = Disabled

ON = Enabled ON = Enabled ON = Enabled ON = Enabled

[131]

No exit delay beeps and no bell squawk when Stay arming

Option [5]

OFF = Disabled

ON = Enabled

[132]

EOL (End-of-line) resistors

Option [4]

OFF = No EOL

ON = with EOL

[133] [135]

Switch to Stay Arming if no entry delay is opened

Option [4] Option [3]

OFF = Disabled OFF = Disabled

ON = Enabled ON = Enabled

Dialer

[137]

Call Telephone #1 for Arming/Disarming Report Codes

Option [1]

OFF = Disabled

ON = Enabled

[140]

Reporting formats for telephone numbers 1 and 2. Enter a number from 1 to 6. (1 = ADEMCO slow; 2 = Silent Knight fast; 3 = SESCOA; 4 = ADEMCO Express; 5 = ADEMCO Contact ID; 6 = Pager)

5 5 _____ /_____
Tel.# 1 Format Tel.# 2 Format

[302] [303] [304]

Master Code 1 Master Code 2

( 1 * 3 4 5 * * *) ( 1 * 3 4 5 * * *) ( 1 * 3 4 5 * * *) User Options [5] Force Arming [1] Partition 1 access [6] Arm only [2] Partition 2 access [7] PGM activation only [3] Bypass programming [8] Future use [4] Stay arming

User Code 004

[348]

User Code 048

( 1 * 3 4 5 * * *)

Buttons Section

+
[711] [712] [713] [714] [715] [716] [717] [718]

+
_____ _____ _____ _____ _____ _____ _____ _____

+
_____ _____ _____ _____ _____ _____ _____ _____

+
_____ _____ _____ _____ _____ _____ _____ _____

4 5 Remote control # 1 _____ _____ _____ _____ 4 5 Remote control # 2 _____ _____ _____ _____ 4 5 Remote control # 3 _____ _____ _____ _____ 4 5 Remote control # 4 _____ _____ _____ _____ 4 5 Remote control # 5 _____ _____ _____ _____ 4 5 Remote control # 6 _____ _____ _____ _____ 4 5 Remote control # 7 _____ _____ _____ _____

_____ _____ _____ _____ _____ _____ _____ _____

4 5 Remote control # 8 _____ _____ _____ _____

Button Options Empty slot [FORCE] = Button disabled 1 - Regular arming 2 - Stay arming 3 - Instant arming 4 - Force arming 5 - Disarm 6 - Disarm when no alarm 7 - Regular arm and disarm 8 - Panic 1 9 - Panic 2 A - Panic 3 B - PGM activation (Event group # 07) C - PGM activation (Event group # 08) D - PGM activation (Event group # 09)

Step 5:

Testing
Arm the system with [MASTER CODE] (default: 1234) Trigger zones to verify operation

Decimal and Hexadecimal Programming Table


What Do I See?

Value or Action

What Do I Press?
1686V 1686H 1689 1641 1640

10-Zone LED
Values 1 to 9 A (HEXA ONLY) B (HEXA ONLY) C (HEXA ONLY) D (HEXA ONLY) E (HEXA ONLY) F (HEXA ONLY) Exit Without Saving In Programming Mode / Waiting for a Section Enter a Space / Erase Current Digit Save Data (HEXA
ONLY)

16-Zone LED
[1] to [9] [10] [11] [12] [13] [14] [15] [ARM1] & [STAY1] flash [ARM1] & [STAY1] flash

LCD
[1] to [9] 0 B C D E F
PROGRAMMING MODE [ ] SECTION PROGRAMMING MODE [ ] SECTION

Icon LCD
[1] to [9] 0 B C D E F SECTION SECTION

[1] to [9] [0] [STAY] / [BYP] / [MEM] / [TBL] / [TRBL] / [PG] / [FNC1] / [CLEAR] / __ [FORCE] / [ENTER] /

[1] to [9] [0 (10)] [STAY] [BYP] [MEM] [TBL] [PG] [ENTER] flashes [ENTER] flashes Displays next digit or next section Advances to the next section

Installer Quick Keys


To access the installer quick keys, press the [ENTER] key, enter your [INSTALLER CODE] and then press: [TBL] or [TRBL] (Installer Test Mode): The Installer Test Mode will allow you to perform walk tests. [MEM] (Test Report): Sends the Test Report report code programmed in section [211] to the central station. [BYP] (Call WinLoad): Dials the PC telephone number (section [150]) to initiate communication with WinLoad. [STAY] (Cancel Communication): Cancels all communication with WinLoad or central station until next reportable event. [FORCE] (Answer WinLoad): Will force the control panel to answer an incoming call from WinLoad.

Hardwire Zone Connection Using EOL Resistors

Printed in Canada - 03/2004

1728EX-EQ01