We are pleased to highlight some of the USP of DETECTOMAT Fire Alarm System as such,

DETECTOMAT, Germany is one of the most qualified manufacturer for a complete Fire Detection and Alarm System which has built over 600,000 industrial detectors, installed at many countries as because sensor alarming system and the fire-fighting system is more sensitive, more accurate and more intelligent."

The DETECTOMAT detectors are famous for their robust engineering design, stylish look and daily prove their quality and efficiency. It has highly touted VdS mark and complies EN 54 Standard & LPCB approved. Intelligent Detectors Detectors with inbuilt - microprocessor DETECTOMAT Addressable Fire Alarm System has the capacity for 126 devices per loop with an overall loop length of 3,500 meters. DETECTOMAT Network devices can configure networks with up to 20 control panels. DETECTOMAT Detectors have Integrated T-branch and short circuit isolator DETECTOMAT Conventional Fire Alarm System has the capacity for 25- 30 devices per zone. Redundant host processor , Redundant loop card , Redundant Power Supply Detectors with Ambient Temperature of 60 Deg. C

German is world known for its meteorology. We can provide After Sales Support as having trained man power for the Installation, Testing, Commissioning & Programming, as training is provided by DETECTOMAT. In house Product demonstration & training center for Programming and Installation, After sales service support. Product protocol matches to APOLLO protocol

DETECTOMAT Fire Alarm System & Equipments are Approved By BHEL, NTPC- ANTA, RRVUNL, MAHAGENCO, Reliance, ADANI, KPCL, ABB, VA Tech, DCPL, Desein, Fichtner , GSPL , NTPC- KAWAS

DETECTOMAT FIRE ALARM SYSTEM INSTALLATIONS IN INDIA

INDUSRIAL & POWER PLANT PROJECTS AREVA T&D LTD. - Kotambi, Baroda. AREVA RRVPNL- Indiranagar substation. NTPC-Anta, Rajasthan. MAHAGENCOs 1x 250 MW Paras TPS ( Unit 2) RRVUNLs 1x250 MW Suratgarh Super Thermal power Project ADANI Power LTD - 4 x 330 MW Mundra, TPS. KPTCLs 2 x 115 MW Varahi Hydroelectic Power Project Tata Nano Project-Sanand , Gujarat through ABB-Baroda MAHAGENCOs 1X500 MW Khaperkheda TPS through BGR -Chennai HI-TECH SILONG-Meghalaya State Electricity Board

COMMERCIAL PROJECT Reliance Industries Ltd. Reliance PCS Center Naroda,Ahmedabad & Reliance PCS Center Gurgoan , Delhi. GSPL Paguthan Terminal Bharuch K. RAHEJA Aquiline Properties IT SEZ at KOBA , near Gandhinagar NTPC-KAWAS

EXPORT PROJECTS Addressable Fire Alarm system for Anjelique Internation Delhi for their Anjelique Internation Zambia office. Conventional Fire Alarm system for Areva T & D Noida for their client Kenya Electricity Board Kenya

Product-Information Sheet
Fire control panel detect 3004 , deep housing, language kit English plus Type detect 3004 M GB Order No. 32551
editing status: 2009-07-16

plus

Description: Microprocessor controlled modular fire control panel for the use with the Loop 3000 fire detection system components. Approved according to EN 54 - 2 A1 2006, EN 54 - 4 A1 2002, A2 2006 and VdS for the use according to VdE 0833.

Properties: Large LCD, 160 x 80 with backlight. Integrated display and control panel according to DIN EN 54 - 2 A1 2006. 2 slots for 2 loop - interfaces for the connection of up to 4 loops each with a maximum of 126 loop 3000 devices per loop and a maximum loop length of up to 3.500 m. Option for 2 conventional interface cards for controlling up to 16 conventional zones. Extinguishing interface for controlling extinguishing and gas suppression systems in accordance to EN 12094. Integrated control of extinguishing systems via the standard extinguishing interface in accordance to VdS.
Connections for a fire brigade interface for controlling the panels outputs, key deposit and transmission units.

Integrated interface connection for up to 63 additional network components. Integrated RS 232 - interface for the dpt software and the connection of printers and other peripheral equipment. Integrated power supply 72W according to EN54 with 1 output for external devices rated at 24VDC/800 mA. Monitored power supply unit and battery charging according to EN 54-4 A1 2002 and A2 2006 via the MC 3004 monitoring card. 1 external output 24 V / 400 mA monitored for sounding/signalling devices. 3 potential free relais for fire and fault. 3 inputs for collective signals. Emergency power supply via 2 batteries 12 V / up to 26 Ah. Integrated ground fault monitoring. Segmented front door allowing the quick assembly of LED indicator modules and printers. Option for customised front logos. In accordance to EN 61000 - 6 - 3 class B for emissions, so suitable for the use in sensitive areas. Possibility for complete system redundancy with the CPU and loop interfaces. Up to 128 programmable detector zones. Up to 42 T-branches per loop possible. Event log memory of up to 500 messages. Programming of control logics and time dependent functions for the components of series Loop 3000. Customized customer texts allowing up to a maximum of 20 characters. Simple menu structure in accordance to EN 54 - 2 A1 2006. Integrated alarm buffer and 2 detector / zone dependencies. Time controlled changeovers of sensitivity levels of Loop 3000 detectors by day/night modes. Software controlled disablements for zones and individual detectors via external inputs. Ability to change and edit inspection and reaction times along with all delays. Programming options for different alarm modes. Different access levels with password protection. Integrated "one-man-revision mode" with clear protocols and a revision counter. Visual diagnostics and remote-control operations via the visualization software "Visual detect". Commissioning and service tool for analyzing and fault finding functions with "I-check" software. Incl. English language kit for control and programming.

Technical data

Supply voltage Power supply Emergency supply Quiescent current Alarm current Interfaces Display

Outputs Inputs Ambient temperature Humidity Protection class Colour Material Dimensions (H x W x D) Weight Standards VdS approval System approval CPD-Number Further approvals General remarks detectomat GmbH An der Strusbek 5 D-22926 Ahrensburg / Germany

230 V AC (-15%/+10%) 24 V DC / 72 W / 3,5 A 1 output 24 V DC / 800 mA for external devices 2 x 12 V / 26 Ah 250 mA 400 mA RS 232 Bitbus (RS 485 based) LC-Display 160 x 80 points, backlight 20 LED-displays for status signal 1 x 24 V / 400 mA monitored for sounding/signalling devices up to 4 loop 140 mA / 3500 m for up to 126 Loop 3000 elements each 3 relais outputs 250 V / 5 A for alarm and fault 8 open collector outputs 30 V DC / 90 mA 3 inputs for collective signal -5 bis +40 C C 5 - 95 % (non-condensing) IP 30 light grey, RAL 7035 sheet steel 490 mm x 420 mm x 210 mm 12,5 kg, without batteries EN 54-2:1997 A1:2006 EN 54-4:1997 A1:2002 A2:2006 G 203068 S 295054 0786-CPD-20817 EN 12094 for 1 area extinguishing systems international approvals on request Scope of delivery without loop cards, network interfaces and batteries utilization of integrated standard extinguishing interface requires 1 optional LED indicator module in the front to ensure the indication according to EN 54 - 2. info@detectomat.com www.detectomat.com - Subject to alterations and errors Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

Product-Information Sheet
Fire control panel detect 3004 , shallow housing, language kit English plus Type detect 3004 S GB Order No. 32553
editing status: 2009-07-16

plus

Description: Microprocessor controlled modular fire control panel for the use with the Loop 3000 fire detection system components. Approved according to EN 54 - 2 A1 2006, EN 54 - 4 A1 2002, A2 2006 and VdS for the use according to VdE 0833.

Properties: Large LCD, 160 x 80 with backlight. Integrated display and control panel according to DIN EN 54 - 2 A1 2006. 2 slots for 2 loop - interfaces for the connection of up to 4 loops each with a maximum of 126 loop 3000 devices per loop and a maximum loop length of up to 3.500 m. Option for 2 conventional interface cards for controlling up to 16 conventional zones. Extinguishing interface for controlling extinguishing and gas suppression systems in accordance to EN 12094. Integrated control of extinguishing systems via the standard extinguishing interface in accordance to VdS.
Connections for a fire brigade interface for controlling the panels outputs, key deposit and transmission units

Integrated interface connection for up to 63 additional network components. Integrated RS 232 - interface for the dpt software and the connection of printers and other peripheral equipment. Integrated power supply 72W according to EN54 with 1 output for external devices rated at 24VDC/800 mA. Monitored power supply unit and battery charging according to EN 54-4 A1 2002 and A2 2006 via the MC 3004 monitoring card. 1 external output 24 V / 400 mA monitored for sounding/signalling devices. 3 potential free relais for fire and fault. 3 inputs for collective signals. Emergency power supply via 2 batteries 12 V / up to 12 Ah. Integrated ground fault monitoring. Segmented front door allowing the quick assembly of LED indicator modules and printers. Option for customised front logos. In accordance to EN 61000 - 6 - 3 class B for emissions, so suitable for the use in sensitive areas. Possibility for complete system redundancy with the CPU and loop interfaces. Up to 128 programmable detector zones. Up to 42 T-branches per loop possible. Event log memory of up to 500 messages. Programming of control logics and time dependent functions for the components of series Loop 3000. Customized customer texts allowing up to a maximum of 20 characters. Simple menu structure in accordance to EN 54 - 2 A1 2006. Integrated alarm buffer and 2 detector / zone dependencies. Time controlled changeovers of sensitivity levels of Loop 3000 detectors by day/night modes. Software controlled disablements for zones and individual detectors via external inputs. Ability to change and edit inspection and reaction times along with all delays. Programming options for different alarm modes. Different access levels with password protection. Integrated "one-man-revision mode" with clear protocols and a revision counter. Visual diagnostics and remote-control operations via the visualization software "Visual detect". Commissioning and service tool for analyzing and fault finding functions with "I-check" software. incl. English language kit for control and programming.

Technical data

Supply voltage Power supply Emergency supply Quiescent current Alarm current Interfaces Display

Outputs Inputs Ambient temperature Humidity Protection class Colour Material Dimensions (H x W x D) Weight Standards VdS approval System approval CPD-Number Further approvals

General remarks

230 V AC (-15%/+10%) 24 V DC / 72 W / 3,5 A 1 output 24 V DC / 800 mA for external devices 2 x 12 V / 12 Ah 250 mA 400 mA RS 232 Bitbus (RS 485 based) LC-Display 160 x 80 points backlight 20 LED-displays for status signal 1 x 24 V /400 mA monitored for sounding/signalling devices up to 4 loop 140 mA / 3500 m for up to 126 Loop 3000 elements each 3 relais outputs 250 V / 5 A for alarm and fault 8 open collector outputs 30 V DC / 90 mA 3 inputs for collective signal -5 bis +40 C C 5 - 95 % (non-condensing) IP 30 light grey, RAL 7035 sheet steel 490 mm x 420 mm x 150 mm 12,5 kg, without batteries EN 54-2:1997 A1:2006 EN 54-4:1997 A1:2002 A2:2006 G 203068 S 295054 0786-CPD-20817 EN 12094 for 1 area extinguishing systems international approvals on request Scope of delivery without loop cards, network interfaces and batteries utilization of integrated standard extinguishing interface requires 1 optional LED indicator module in the front to ensure the indication according to EN 54 - 2. info@detectomat.com www.detectomat.com - Subject to alterations and errors Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

detectomat GmbH An der Strusbek 5 D-22926 Ahrensburg / Germany

Product-Information Sheet
Fire control panel detect 3004, deep housing, language kit English Type detect 3004 M GB Order No. 32421
editing status: 2009-12-15

Description: Microprocessor controlled modular fire control panel for the use with the Loop 3000 fire detection system components. Approved according to EN 54 and VdS for the use according to VdE 0833.

Properties: 4 alphanumeric lines LC-displaywith backlight Integrated display and control panel according to DIN EN 54 2 slots for 2 loop - interfaces for the connection of up to 4 loops each with a maximum of 126 loop 3000 devices per loop and a maximum loop length of up to 3.500 m. Option for 2 conventional interface cards for controlling up to 16 conventional zones. Extinguishing interface for controlling extinguishing and gas suppression systems in accordance to EN 12094. Option for control of extinguishing systems via the standard extinguishing interface in accordance to VdS.
Connection option for a fire brigade interface for controlling the panels outputs, key deposit; transmission units.

Integrated interface slot for the connection for up to 63 additional network components. Integrated RS 232 - interface for the dpt software and the connection of printers and other peripheral equipment. Integrated power supply 72W according to EN54 with 1 output for external devices rated at 24VDC/800 mA. 1 external output 24 V / 400 mA monitored for sounding/signalling devices. 3 potential free relais for fire and fault. 3 inputs for collective signals. Emergency power supply via 2 batteries 12 V / up to 26 Ah. Integrated ground fault monitoring. Segmented front door allowing the quick assembly of LED indicator modules and printers. Option for customised front logos. Possibility for complete system redundancy with the CPU and loop interfaces. Up to 128 programmable detector zones. Up to 42 T-branches per loop possible. Event log memory of up to 500 messages. Programming of control logics and time dependent functions for the components of series Loop 3000. Customized customer texts allowing up to a maximum of 20 characters. Integrated alarm buffer and 2 detector / zone dependencies. Time controlled changeovers of sensitivity levels of Loop 3000 detectors by day/night modes. Software controlled disablements for zones and individual detectors via external inputs. Ability to change and edit inspection and reaction times along with all delays. Programming options for different alarm modes. Different access levels with password protection. Visual diagnostics and remote-control operations via the visualization software "Visual detect". Commissioning and service tool for analyzing and fault finding functions with "I-check" software. Incl. English language kit for control and programming.

Technical data

Supply voltage Power supply Emergency supply Quiescent current Alarm current Interfaces Display

Outputs Inputs Ambient temperature Humidity Protection class Colour Material Dimensions (H x W x D) Weight Standards VdS approval System approval CPD-Number Further approvals General remarks detectomat GmbH An der Strusbek 5 D-22926 Ahrensburg / Germany

230 V AC (-15%/+10%) 24 V DC / 72 W / 3,5 A 1 output 24 V DC / 800 mA for external devices 2 x 12 V / 26 Ah 86 mA 146 mA RS 232 RS485 and Bitbus as option for network 4 alphanueric lined LC-Display Backlight 7 20 LED Displays for status signal 1 x 24 V / 400 mA monitored for sounding/signalling devices up to 4 loop 140 mA / 3500 m for up to 126 Loop 3000 elements each 3 relais outputs 250 V / 5 A for alarm and fault 8 open collector outputs 30 V DC / 90 mA 3 inputs for collective signal -5 bis +40 C C 5 - 95 % (non-condensing) IP 30 light grey, RAL 7035 sheet steel 490 mm x 420 mm x 210 mm 12,5 kg, without batteries EN 54-2:1997 EN 54-4:1997 G 203068 S 295054 0786-CPD-20817 EN 12094 for 1 area extinguishing systems international approvals on request Scope of delivery without loop cards, network interfaces and batteries

info@detectomat.com www.detectomat.com - Subject to alterations and errors -

Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

Product-Information Sheet
Fire control panel detect 3004, shallow housing, language kit English Type detect 3004 S GB Order No. 32424
editing status: 2009-12-15

Description: Microprocessor controlled modular fire control panel for the use with the Loop 3000 fire detection system components. Approved according to EN 54 and VdS for the use according to VdE 0833.

Properties: 4 alphanumeric lines LC-display with backlight Integrated display and control panel according to DIN EN 54 2 slots for 2 loop - interfaces for the connection of up to 4 loops each with a maximum of 126 loop 3000 devices per loop and a maximum loop length of up to 3.500 m. Option for 2 conventional interface cards for controlling up to 16 conventional zones. Extinguishing interface for controlling extinguishing and gas suppression systems in accordance to EN 12094. Option for control of extinguishing systems via the standard extinguishing interface in accordance to VdS.
Connection option for a fire brigade interface for controlling the panels outputs, key deposit, transmission units.

Integrated interface slot for the connection for up to 63 additional network components. Integrated RS 232 - interface for the dpt software and the connection of printers and other peripheral equipment. Integrated power supply 72W according to EN54 with 1 output for external devices rated at 24VDC/800 mA. 1 external output 24 V / 400 mA monitored for sounding/signalling devices. 3 potential free relais for fire and fault. 3 inputs for collective signals. Emergency power supply via 2 batteries 12 V / up to 12 Ah. Integrated ground fault monitoring. Segmented front door allowing the quick assembly of LED indicator modules and printers. Option for customised front logos. Possibility for complete system redundancy with the CPU and loop interfaces. Up to 128 programmable detector zones. Up to 42 T-branches per loop possible. Event log memory of up to 500 messages. Programming of control logics and time dependent functions for the components of series Loop 3000. Customized customer texts allowing up to a maximum of 20 characters. Integrated alarm buffer and 2 detector / zone dependencies. Time controlled changeovers of sensitivity levels of Loop 3000 detectors by day/night modes. Software controlled disablements for zones and individual detectors via external inputs. Ability to change and edit inspection and reaction times along with all delays. Programming options for different alarm modes. Different access levels with password protection. Visual diagnostics and remote-control operations via the visualization software "Visual detect". Commissioning and service tool for analyzing and fault finding functions with "I-check" software. Incl. English language kit for control and programming.

Technical data

Supply voltage Power supply Emergency supply Quiescent current Alarm current Interfaces Display

Outputs Inputs Ambient temperature Humidity Protection class Colour Material Dimensions (H x W x D) Weight Standards VdS approval System approval CPD-Number Further approvals General remarks detectomat GmbH An der Strusbek 5 D-22926 Ahrensburg / Germany

230 V AC (-15%/+10%) 24 V DC / 72 W / 3,5 A 1 output 24 V DC / 800 mA for external devices 2 x 12 V / 12 Ah 86 mA 146 mA RS 232 RS485 and Bitbus as option for network 4 alphanumeric lined LC-Display Backlight / 20 LED-displays for status signal 1 x 24 V / 400 mA monitored for sounding/signalling devices up to 4 loop 140 mA / 3500 m for up to 126 Loop 3000 elements each 3 relais outputs 250 V / 5 A for alarm and fault 8 open collector outputs 30 V DC / 90 mA 3 inputs for collective signal -5 bis +40 C C 5 - 95 % (non-condensing) IP 30 light grey, RAL 7035 sheet steel 490 mm x 420 mm x 150 mm 12,5 kg, without batteries EN 54-2:1997 EN 54-4:1997 G 203068 S 295054 0786-CPD-20817 EN 12094 for 1 area extinguishing systems international approvals on request Scope of delivery without loop cards, network interfaces and batteries

info@detectomat.com www.detectomat.com - Subject to alterations and errors -

Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

Product-Information Sheet
Fire control panel detect 3016, wall mounted housing, language kit English Order No. 32422 - Type detect 3016 XL GB
editing status 20.01.2010

Description: Microprocessor controlled modular fire control panel for the use with the Loop 3000 fire detection system components approved according to EN 54 and VdS for the use according to VdE 0833

Properties: 4 alphanumeric lines LC-display with backlight Integrated display and control panel according to DIN EN 54 Basic version with 5 slots for 2 redundant loop-interfaces for the connection of up to 10 loops with a maximum of 126 loop 3000 devices per loop and a maximum loop lenght of 3500m Option for up to 11 slots for extension boards and the connection of up to 16 loops with 126 loop 3000 devices per loop Option for 8 conventional interface cards for controlling up to 64 conventional zones Extinguishing interface option for controlling extinguishing and gas suppression systems for 6 extinguishing areas in accordance to EN12094 Connection option for a fire brigade interface for controlling the panels outputs, key deposit and transmission units Integrated interface slot for the connection for up to 63 additional network components Integrated RS 232 - interface for the DPT programming software and the connection of printers and other peripheral equipment Integrated power supply 192 W according to EN 54 with 2 outputs for external devices rated at 24V DC/ 800mA 1 external output 24 V / 400 mA monitored for sounding/signalling devices 3 potential free relais for fire and fault 3 inputs for collective signals Emergency power supply via 2 batteries 12V / up to 45 Ah Segmented front door allowing the quick assembly of LED indicator Modules and printers. Option for customised front logos Possibility for complete system redundancy with redundant CPU and redundant loop interfaces Up to 196 programmable detector zones Additional up to 42 T-branches per loop possible Event log memory of up to 500 messages Programming of control logics and time dependent functions for the components of series Loop 3000 Customized customer texts allowing up to a maximum of 20 characters Integrated alarm buffer and 2 detector / zone dependencies Time controlled changeovers of sensitivity levels of Loop 3000 detectors by day/night modes Software controlled disablements for zones and individual detectors via external inputs Ability to change and edit inspection and reaction times along with all delays. Programming options for different alarm modes Different access levels with password protection Visual diagnostics and remote-control operations via the visualization software "Visual detect" Commissioning and service tool for analyzing and fault finding functions with "I-check" software. incl. English language kit for control and programming

Technical data

Supply voltage Power supply Emergency supply Quiescent current Alarm current Interfaces Display

Outputs Inputs
Ambient temperature

Humidity
Protection class Colour Material Dimensions (H x W x D) Weight Standards VdS approval System approval Further approvals

230 V AC (-15%/+10%) 24 V DC / 192 W / 8 A 1 output 24 V DC / 800 mA for external devices 2 x 12 V / 45 Ah ca. 190 mA ca. 250 mA 2 x RS 232 RS485 and Bitbus as option for network 4 alphanumeric lines LC-display Backlight 20 LED - displays for status signal 1 x 24 V /400 mA monitored for sounding/signalling devices up to 16 loops 140 mA / 3500 m for up to 126 Loop 3000 elements each 3 relais outputs 250 V / 5 A for alarm and fault 8 open collector outputs 30 V DC / 90 mA 3 inputs for collective signal - 5 up to + 40 C C 5 - 95 % (non-condensing) IP 30 Light grey, RAL 7035 Sheet steel 750 mm x 600 mm x 240 mm 13,5 kg, without batteries EN 54-2: 1997 EN 54-4: 1997 G 203067 S295054 EN 12094 EN 12094 for 1 area extinguishing systems Scope of delivery without loop cards, network interfaces and batteries Ground fault montoring via module EM (Art.Nb. 30927) Utilization of integrated standard extinguishing interface requires 1 optional LED indicator module in the front to ensure the indication according to EN 54 - 2 info@detectomat.com www.detectomat.com - Subject to alterations and errors Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

General remarks

detectomat GmbH An der Strusbek 5 D-22926 Ahrensburg / Germany

Product-Information Sheet
Optical smoke detector, with isolator, mesh design, silver Order No. 30488 - Type PL 3301 silver
editing status: 2009-08-26

Description: Optical smoke detector for loop 3000 with 2 optical and 1 thermal sensor for earliest fire detection and indication and with bidirectional isolator according to DIN EN 54-7. Silver mesh design. Properties: Exact pollution recognition by an additional independent measuring chamber. Detector sensitivities automatically calibrated and freely programmable. Fault monitoring of the measurement chamber signal and loop 3000-electronics. Periodic sensor test. Automatic and manual addressing on the loop 3000. Integrated isolator and T-branch option. Alarm output for the triggering of a LED indicators. Functions completely integrated via loop 3000 protocol. Disable and enable modes with individually adjustable sensitivities. Storage of last maintenance date. Self learning modes for the ambient conditions. Display of the temperature environments of the fire detection system by a second temperature measurement. Multicolour-LED for alarm- (red) and fault (yellow). Delivery including protective cover for installation phase.
Technical data

Operation voltage Quiescent current Alarm current OC-outputs Sensitivity Ambient temperature Humidity Air speed Protection class Colour housing Material Dimensions (H x ) Standards VdS approval System approval Further approvals CPD-Number detectomat GmbH An der Strusbek 5 D-22926 Ahrensburg / Germany

15 to 30 V loop powered 280 A 5 mA max. 10 mA for LED-indicator or piezo buzzer 5 levels adjustable -10 to +60 C C max. 93 % (+/-2%) <20 m/s IP 40 silver ABS, metal mesh 42 mm x 95 mm DIN EN 547 G 205046 S 295054 and S 208123 on request 0786-CPD-20037 info@detectomat.com www.detectomat.com - Subject to alterations and errors Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

Product information
Date: 03.08.2010 Brief description : Design changes to the PL 3300/3200 O outer casing, reduced 6mm in height TINr.: 0016

1: New PL 3300/3200 O with detector base

2 : New PL 3300/3200 O without detector base

Description; The Standard design of proven PL - series was in the wake of mechanical revision to be adapted to better accommodate todays market. With the 6mm reduction in height, we and users alike are able to optimise the detectors handling and storage.These advantages apply to internal production and testing along with the installation and commissioning by the end user. The original modern design has not been affected and only a slight change is noticeable. The following detector types are to be modified: Part No. 30011 32248 30009 32519 Description PL 3300 O PL 3300 O PL 3200 O PL 3200 O

The changes made to the outer casing, in no way effect the operation of the detector or the detector base. The design changes have been approved by the VdS and the respective approvals for this detector series have been amended. All dust covers for this detector range have also been changed to fit this new design. These changes will come into effect during the middle of August 2010.

Questions or queries

We will be happy to answer any questions you my have regarding this or any other detectomat products.

detectomat GmbH An der Strusbek 5 D-22926 Ahrensburg

info@detectomat.com www.detectomat.com - Subject to change (without notice); -

Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

Product-Information Sheet
Multi sensor detector optical - heat, without isolator Order No. 30007 - Type PL 3200 OT
editing status: 2009-08-25

Description: Optical and thermal multi sensor detector for loop 3000 with 2 optical and 2 thermal sensors for earliest fire detection and indication in all environments with difficult ambient conditions according to DIN EN 54-5/7 and CEA 4021.

Properties: Highest reliability by intelligent combination of thermal and optical sensor signals with via algorithms. Exact pollution recognition by an additional independent measuring chamber. Integrated temperature measurement as differential procedure and maximum value in accordance to EN 54-5 1A. Detector sensitivities automatically calibrated and freely programmable. Fault monitoring of the measurement chamber signal and loop 3000-electronics. Periodic sensor test. Automatic and manual addressing on the loop 3000. Alarm output for the triggering of a LED indicators. Functions completely integrated via loop 3000 protocol. Disable and enable modes with individually adjustable sensitivities. Storage of last maintenance date. Self learning modes for the ambient conditions. Display of the temperature environments of the fire detection system by a second temperature measurement. Multicolour-LED for alarm- (red) and fault (yellow). Delivery including protective cover for installation phase. Technical data Operation voltage 15 to 30 V DC loop powered Quiescent current 280 A Alarm current 5 mA OC-outputs max. 10 mA for LED-indicator or piezo buzzer Sensitivity 5 levels adjustable Ambient Temperature -10 to +60 C C Humidity max. 93 % (+/-2%) Air speed < 20m/s Protection class IP 40 Colour housing white (similar to RAL 9003) Material ABS Dimensions (H x ) 52 mm x 100 mm Standards DIN EN 547, EN 54-5, CEA 4021 VdS approval G 205052 System approval S 295054 and S 208123 Further approvals LPCB, BOSEC, PT (GOST), UNIVERZA V LJUBLJANI, EMI, Bahrain CPD-Number 0786-CPD-20197

detectomat GmbH info@detectomat.com An der Strusbek 5 www.detectomat.com D-22926 Ahrensburg / Germany - Subject to alterations and errors -

Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

Product-Information Sheet
Heat detector with fixed and rate of rise temperature settings, without isolator Order No. 30008 - Type PL 3200 T
editing status: 2009-10-05

Description: Heat detector with fixed and rate of rise temperature settings for loop 3000 with 1 thermal sensor for earliest fire detection and indication in all environments with difficult ambient conditions according to DIN EN 54-5. Properties: Integrated temperature measurement as rate of rise procedure and maximum value in accordance to EN 54-5 1A. Detector sensitivities automatically calibrated and freely programmable. Periodic sensor test. Automatic and manual addressing on the loop 3000. Alarm output for the triggering of a LED indicators. Functions completely integrated via loop 3000 protocol. Disable and enable modes with individually adjustable sensitivities. Storage of last maintenance date. Display of the temperature environments of the fire detection system by a second temperature measurement. Multicolour-LED for alarm- (red) and fault (yellow). Delivery including protective cover for installation phase.
Technical data

Operation voltage Quiescent current Alarm current OC-outputs Sensitivity Ambient temperature Humidity Air speed Protection class Colour housing Material Dimensions (H x ) Standards VdS approval System approval
Further approvals

CPD-Number

15 to 30 V DC loop powered 280 A 5 mA max. 10 mA for LED-indicator or piezo buzzer 5 levels adjustable -10C to +60C max. 93 % (+/-2%) < 20m/s IP 40 white (similar to RAL 9003) ABS 52 mm x 100 mm DIN EN 54-5 G 203038 S 295054 and S 208123 on request 0786-CPD-20043 info@detectomat.com www.detectomat.com - Subject to alterations and errors Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

detectomat GmbH An der Strusbek 5 D-22926 Ahrensburg / Germany

Product-Information Sheet
Optical smoke detector, without isolator Order No. 30009 - Type PL 3200 O
Stand: 2009-10-05

Description: Optical smoke detector for loop 3000 with 2 optical and 1 thermal sensor for earliest fire detection and indication according to DIN EN 54-7.

Properties: Exact pollution recognition by an additional independent measuring chamber. Detector sensitivities automatically calibrated and freely programmable. Fault monitoring of the measurement chamber signal and loop 3000-electronics. Periodic sensor test. Automatic and manual addressing on the loop 3000. Alarm output for the triggering of LED indicators. Functions completely integrated via loop 3000 protocol. Disable and enable modes with individually adjustable sensitivities. Storage of last maintenance date. Self learning modes for the ambient conditions. Display of the temperature environments of the fire detection system by a second temperature measurement. Multicolour-LED for alarm- (red) and fault (yellow). Delivery including protective cover for installation phase.
Technical data

15 to 30 V DC loop powered 280 A 5 mA OC-outputs max. 10 mA for LED-indicator or piezo buzzer Sensivity 5 levels adjustable C C Ambient temperature -10 to +60 Humidity max. 93 % (+/-2%) < 20m/s Air speed Protection class IP 40 white (similar to RAL 9003) Colour housing Material ABS Dimensions ( H x ) 44 mm x 100 mm Standards DIN EN 547 G 202003 VdS approval System approval S 295054 and S 208123 Further approvals on request CPD-Number 0786-CPD-20677
Operation voltage Quiescent current Alarm current

detectomat GmbH An der Strusbek 5 D-22926 Ahrensburg / Germany

info@detectomat.com www.detectomat.com - Subject to alterations and errors -

Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

Product-Information Sheet
Heat detector with fixed and rate of rise temperature settings, with isolator Order No. 30010 - Type PL 3300 T
Stand: 2009-08-25

Description: Heat detector with fixed and rate of rise temperature settings for loop 3000 with 1 thermal sensor for earliest fire detection and indication in all environments with difficult ambient conditions and with bidirectional isolator according to DIN EN 54-5. Properties: Integrated temperature measurement as rate of rise procedure and maximum value in accordance to EN 54-5 1A. Detector sensitivities automatically calibrated and freely programmable. Periodic sensor test. Automatic and manual addressing on the loop 3000. Integrated isolator and T-branch option. Alarm output for the triggering of a LED indicators. Functions completely integrated via loop 3000 protocol. Disable and enable modes with individually adjustable sensitivities. Storage of last maintenance date. Display of the temperature environments of the fire detection system by a second temperature measurement. Multicolour-LED for alarm- (red) and fault (yellow). Delivery including protective cover for installation phase.
Technical data

15 to 30 V DC loop powered 280 A 5 mA OC-outputs max. 10 mA for LED-indicator or piezo buzzer Sensivity 5 levels adjustable Ambient temperature -10C to +60C max. 93 % (+/-2%) Humidity < 20m/s Air speed IP 40 Protection class white (similar to RAL 9003) Colour housing ABS Material Dimensions (H x ) 52 mm x 100 mm DIN EN 54-5 Standards G 203037 VdS approval S 295054 and S 208123 System approval Further approvals on request CPD-Number 0786-CPD-20044
Operation voltage Quiescent current Alarm current

detectomat GmbH info@detectomat.com An der Strusbek 5 www.detectomat.com D-22926 Ahrensburg / Germany - Subject to alterations and errors -

Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

Product-Information Sheet
Optical smoke detector, with isolator Order No. 30011 - Type PL 3300 O
Stand: 2009-08-25

Description: Optical smoke detector for loop 3000 with 2 optical and 1 thermal sensor for earliest fire detection and indication and with bidirectional isolator according to DIN EN 54-7. Properties: Exact pollution recognition by an additional independent measuring chamber. Detector sensitivities automatically calibrated and freely programmable. Fault monitoring of the measurement chamber signal and loop 3000-electronics. Periodic sensor test. Automatic and manual addressing on the loop 3000. Integrated isolator and T-branch option. Alarm output for the triggering of a LED indicators. Functions completely integrated via loop 3000 protocol. Disable and enable modes with individually adjustable sensitivities. Storage of last maintenance date. Self learning modes for the ambient conditions. Display of the temperature environments of the fire detection system by a second temperature measurement. Multicolour-LED for alarm- (red) and fault (yellow). Delivery including protective cover for installation phase.
Technical data

15 to 30 V DC loop powered 280 A 5 mA OC-outputs max. 10 mA for LED-indicator or piezo buzzer Sensivity 5 levels adjustable Ambient temperature -10 to +60 C C Humidity max. 93 % (+/-2%) Air speed < 20m/s Protection class IP 40 Colour housing white (similar to RAL 9003) Material ABS Dimensions (H x ) 44 mm x 100 mm Standards DIN EN 54-7 VdS approval G 202002 System approval S 295054 and S 208123 Further approvals on request 0786-CPD-20679 CPD-Number
Operation voltage Quiescent current Alarm current

detectomat GmbH info@detectomat.com An der Strusbek 5 www.detectomat.com D-22926 Ahrensburg / Germany - Subject to alterations and errors -

Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

Product-Information Sheet
Multi sensor detector optical - heat, with isolator Order No. 30021 - Type PL 3300 OT
Stand: 2009-10-05

Description: Optical and thermal multi sensor detector for loop 3000 with 2 optical and 2 thermal sensors and bidirectional isolator for earliest fire detection and indication in all environments with difficult ambient conditions according to DIN EN 54-5/7 and CEA 4021. Properties: Highest reliability by intelligent combination of thermal and optical sensor signals with via algorithms. Exact pollution recognition by an additional independent measuring chamber. Integrated temperature measurement as rate of rise procedure and maximum value in accordance to EN54-5 1A. Detector sensitivities automatically calibrated and freely programmable. Fault monitoring of the measurement chamber signal and loop 3000-electonics. Periodic sensor test. Automatic and manual addressing on the loop 3000. Integrated Isolator and T-branch option. Alarm output for the triggering of LED indicators. Functions completely integrated via loop 3000 protocol. Disable and enable modes with individually adjustable sensitivities. Storage of last maintenance date. Self lerning modes for the ambient conditions. Display of the temperature environments of the fire detection system by a second temperature measurement. Multicolour-LED for alarm- (red) and fault (yellow). Delivery including protective cover for installation phase.
Technical data

15 to 30 V DC loop powered 280 A 5 mA OC-outputs max. 10 mA for LED-indicator or piezo buzzer Sensivity 5 levels adjustable C C Ambient temperature -10 to +60 max. 93 % (+/-2%) Humidity Air speed < 20m/s Protection class IP 40 white (similar to RAL 9003) Colour housing ABS Material Dimensions (H x ) 52 mm x 100 mm Standards DIN EN 547, EN 54-5, CEA 4021 VdS approval G 205051 S 295054 ans S 208123 System approval on request Further approvals 0786-CPD-20198 CPD-Number
Operation voltage Quiescent current Alarm current

detectomat GmbH An der Strusbek 5 D-22926 Ahrensburg / Germany

info@detectomat.com www.detectomat.com - Subject to alterations and errors -

Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

Product-Information Sheet
Multisensor carbon monoxide gas and heat, with isolator Order No. 30079 - Type PL 3300 COBT
Stand: 2009-08-25

Description: Intelligent multi sensor detector for the loop 3000 series featuring sensor technology for carbon monoxide detection in combination with two thermal detectors and an integrated isolator for all environments with difficult ambient conditions, in accordance to EN 54-5/7. For the earliest detection of smouldering fires of all kinds including electrical. The PL 3300 COBT continously monitors the temperature and the CO-concentration. Properties: Alarm evaluation with professional CO-sensor technology. Measurement of carbon monoxid with 2 alarm thresholds: Prealarm: 15 ppm in 15 min. Alarm: 30 ppm in 60 min. Integrated acoustic indication for CO-pre alarm and CO-alarm. Highest reliability by intelligent combination of thermal and CO sensor via algorithm. Integrated temperature measurement as differential procedure and maximum value in accordance to EN 54-5 1A. Periodic sensor test. Automatic and manual addressing on the loop 3000. Integrated isolator and T-branch option. Alarm output for the triggering of a LED indicators. Functions completely integrated via loop 3000 protocol. Disable and enable modes with individually adjustable sensitivities. Display of the temperature environments of the fire detection system by a second temperature measurement. Multicolour-LED for alarm- (red) and fault (yellow). Delivery including protective cover for installation phase.
Technical data

5 years Operation voltage 15 to 30 V DC loop powered Quiescent current 600 A Alarm current 5 mA OC-outputs max. 10 mA for LED-indicator or piezo buzzer CO - Alarm at 30 ppm, heat accord. to EN 54 - 5 1A Sensitivity Ambient temperature -10 to +60 C C Humidity max. 93 % (+/-2%) Protection class IP 40 Colour housing white (similar to RAL 9003) Material ABS Dimensions (H x ) 52 mm x 100 mm Standards DIN EN 54-5 VdS approval G 207005 System approval S 295054 and S 208123 Further approvals Bulgaria CPD - Number 0786-CPD-20582 The Carbon Monoxide detector requires calibrating once a year to ensure the General remarks high detection levels is maintained.

CO-Sensor lifetime

detectomat GmbH info@detectomat.com An der Strusbek 5 www.detectomat.com D-22926 Ahrensburg / Germany - Subject to alterations and errors -

Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

Technical data

15 to 30 V DC loop powered 280 A 5 mA OC-outputs max. 10 mA for LED-indicator or piezo buzzer Sensivity 5 levels adjustable Ambient temperature -10 to +60 C C Humidity max. 93 % (+/-2%) Air speed < 20m/s Protection class IP 40 Colour housing white (similar to RAL 9003) Material ABS Dimensions (H x ) 44 mm x 100 mm Standards DIN EN 547 VDS-Approval G 202107 System approval S 295054 and S 208123 Further approvals on request CPD-Number 0786-CPD-20036
Operation voltage Quiescent current Alarm current

Product-Information Sheet
Optical smoke detector, with isolator, round glass-design, silver Order No. 30568 - Type PL 3305 O silver
Stand: 2009-08-27

Description: Optical smoke detector for loop 3000 with 2 optical and 1 thermal sensor for earliest fire detection and indication and with bidirectional isolator according to DIN EN 54-7. Round glass design, silver colour. Properties: Exact pollution recognition by an additional independent measuring chamber. Detector sensitivities automatically calibrated and freely programmable. Fault monitoring of the measurement chamber signal and loop 3000-electronics. Periodic sensor test. Automatic and manual addressing on the loop 3000. Integrated isolator and T-branch option. Alarm output for the triggering of a LED indicators. Functions completely integrated via loop 3000 protocol. Disable and enable modes with individually adjustable sensitivities. Storage of last maintenance date. Self learning modes for the ambient conditions. Display of the temperature environments of the fire detection system by a second temperature measurement. Multicolour-LED for alarm- (red) and fault (yellow). Delivery including protective cover for installation phase. Operation voltage Quiescent current Alarm current OC-outputs Sensitivity Ambient temperature Humidity Air speed Protection class Colour housing Material Dimensions (H x ) Standards VdS approval System approval Further approvals CPD - Number Technical data 15 to 30 V DC loop powered 280 A 5 mA max. 10 mA for LED-indicator or piezo buzzer 5 levels adjustable -10 to +60 C C max. 93 % (+/-2%) <20 m/s IP 40 silver Glass, ABS 47 mm x 110 mm DIN EN 54-7 G 204089 S 295054 and S 208123 on request 0786-CPD-20041

detectomat GmbH info@detectomat.com An der Strusbek 5 www.detectomat.com D-22926 Ahrensburg / Germany

Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

- Subject to alterations and errors -

Product-Information Sheet
Optical smoke detector, with isolator, mesh design, white Order No. 30956 - Type PL 3301 O white
Stand: 2009-08-27

Description: Optical smoke detector for loop 3000 with 2 optical and 1 thermal sensor for earliest fire detection and indication and with bidirectional isolator according to DIN EN 54-7. White mesh design. Properties: Exact pollution recognition by an additional independent measuring chamber. Detector sensitivities automatically calibrated and freely programmable. Fault monitoring of the measurement chamber signal and loop 3000-electronics. Periodic sensor test. Automatic and manual addressing on the loop 3000. Integrated isolator and T-branch option. Alarm output for the triggering of a LED indicators. Functions completely integrated via loop 3000 protocol. Disable and enable modes with individually adjustable sensitivities. Storage of last maintenance date. Self learning modes for the ambient conditions. Display of the temperature environments of the fire detection system by a second temperature measurement. Multicolour-LED for alarm- (red) and fault (yellow). Delivery including protective cover for installation phase. Operation voltage Quiescent current Alarm current OC-outputs Sensitivity Ambient temperature Humidity Air speed Protection class Colour housing Material Dimensions (H x ) Standards VdS approval System approval Further approvals CPD - Number Technical data 15 to 30 V DC loop powered 280 A 5 mA max. 10 mA for LED-indicator or piezo buzzer 5 levels adjustable -10 to +60 C C max. 93 % (+/-2%) <20 m/s IP 40 white (similar to RAL 9003) ABS, metal mesh 42 mm x 95 mm DIN EN 54-7 G 205046 S 295054 and S 208123 on request 0786-CPD-20037

detectomat GmbH info@detectomat.com An der Strusbek 5 www.detectomat.com D-22926 Ahrensburg / Germany

Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

- Subject to alterations and errors -

Product-Information Sheet
Multi sensor optical - heat - intelligent Fusion Order No. 32149 - Typ PL 3300 OTi Fusion
editing status: 2009-10-05

Description: Intelligent optical and thermal multi sensor detector for loop 3000 with 2 optical and 2 thermal sensors and a bidirectional Isolator for earliest fire detection and indication in all enviroments with difficult ambient conditions, according to EN 54-5/7 and CEA 4021. Fusion-Technology for the detection of the smallest smoke particles and fires in the early stage by using the wavelengthsof the wide-band white light spectrum. Properties: Integrated measurement-System and algorithm for condensation recognition (Humitec) Intelligent analysis and disruption mode fr the elimination of false alarm (e.g. cigarette smoke) Highest reliability by intelligent combination of thermal and optical sensor signals via algorithms Exact pollution recognition by an additional independent measuring chamber Integrated temperature measurement as rate of rise procedure and max. value in accordance to EN54-5 1A Detector sensitivities automatically calibrated and freely programmable Fault monitoring of the measurement chamber signal and loop 3000-electronics Periodic sensor test Automatic and manual adressing on the loop 3000 Integrated Isolator and T-branch option Alarm output for the triggering of LED indicators Functions completely integrated via loop 3000 protocol Disable and enable modes with individually adjustable sensitivities Storage of last maintenance date Self learning modes for the ambient conditions Display of the temperature envirements of the fire detection system by a second temperature measurement Multicolour-LED for alarm- (red) and fault (yellow) Delivery including protective cover for installation phase
Technical data Operation voltage Quiescent current Alarm current OC-outputs Sensivity Ambient temperature Humidity Air speed Protection class Colour housing Material Dimensions (H x ) Standards VdS approval System approval further apporvals CPD-number Sensivity

15 to 30 V DC loop powered 250 A 5mA max. 10 mA for LED-indicator or piezo buzzer 5 levels adjustble -10 to +60 C C max. 93% (+/-2%) < 20m/s IP 40 white (similar to RAL 9003) ABS 52 mm x 100 mm DIN 54-7, EN 54-5, CEA 4021 G 208095 S 295054 and S 208123 on request 0786-CPD-20580

detectomat GmbH An der Strusbek 5 D-22926 Ahrensburg / Germany

info@detectomat.com www.detectomat.com - Subject to alterations and errors -

Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

Product-Information Sheet
Multi sensor detector optical - heat - intelligent Order No. 32150 - Type PL 3300 OTi
Stand: 2009-10-05

Description: Intelligent optical and thermal multi sensor detector for loop 3000 with 2 optical and 2 thermal sensors and a bidirectional isolator for earliest fire detection and indication in all environments with difficult ambient conditions, according to EN 54-5/7. Properties: Integrated measurement-system and algorithm for condensation recognition (Humitec). Intelligent analysis and disruption mode for the elimination of false alarms (e.g. cigarette smoke). Highest reliability by intelligent combination of thermal and optical sensor signals with via algorithms. Exact pollution recognition by an additional independent measuring chamber. Integrated temperature measurement as rate of rise procedure and maximum value in accordance to EN 54-5 1A. Detector sensitivities automatically calibrated and freely programmable. Fault monitoring of the measurement chamber signal and loop 3000-electronics. Periodic sensor test. Automatic and manual adressing on the loop 3000. Integrated isolator and T-branch option. Alarm output for the triggering of LED indicators. Functions completely integrated via loop 3000 protocol. Disable and enable modes with individually adjustable sensitivities. Storage of last maintenance date. Self learning modes for the ambient conditions. Display of the temperature environments of the fire detection system by a second temperature measurement. Multicolour-LED for alarm- (red) and fault (yellow). Delivery including protective cover for installation phase. Operation voltage Quiescent current Alarm current OC-outputs Sensitivity Ambient temperature Humidity Air speed Protection class Colour housing Material Dimensions (H x ) Standards VdS approval System approval Further approvals CPD-Number Sensitivity Technical data 15 to 30 V DC loop powered 250 A 5 mA max. 10 mA for LED-indicator or piezzo buzzer 5 levels adjustable -10 to +60 C C max. 93 % (+/-2 %) <20 m/s IP 40 white (similar to RAL 9003) ABS 52 mm x 100 mm) DIN EN 54-7, EN 54-5, CEA 4021 G 208096 S 295054 and S 208123 on request 0786-CPD-20578

detectomat GmbH An der Strusbek 5 D-22926 Ahrensburg / Germany

info@detectomat.com www.detectomat.com - Subject to alterations and errors -

Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

Product-Information Sheet
Optical smoke detector, with isolator, mesh design, black Order No. 30525 - Type PL 3301 O black
Stand: 2009-08-26

Description: Optical smoke detector for loop 3000 with 2 optical and 1 thermal sensor for earliest fire detection and indication and with bidirectional isolator according to DIN EN 54-7.

Properties: Exact pollution recognition by an additional independent measuring chamber. Detector sensitivities automatically calibrated and freely programmable. Fault monitoring of the measurement chamber signal and loop 3000-electronics. Periodic sensor test. Automatic and manual addressing on the loop 3000. Integrated isolator and T-branch option. Alarm output for the triggering of a LED indicators. Functions completely integrated via loop 3000 protocol. Disable and enable modes with individually adjustable sensitivities. Storage of last maintenance date. Self learning modes for the ambient conditions. Display of the temperature environments of the fire detection system by a second temperature measurement. Multicolour-LED for alarm- (red) and fault (yellow). Delivery including protective cover for installation phase. Operation voltage Quiescent current Alarm current OC-outputs Sensitivity Ambient temperature Humidity Air speed Protection class Colour housing Material Dimensions (H x ) Standards VdS approval System approval Further approvals CPD - Number Technical data 15 to 30 V DC loop powered 280 A 5 mA max. 10 mA for LED-indicator or piezo buzzer 5 levels adjustable -10 to +60 C C max. 93 % (+/-2%) <20 m/s IP 40 black ABS, metal mesh 42 mm x 95 mm DIN EN 54-7 G 205046 S 295054 and S 208123 on request 0786-CPD-20037

detectomat GmbH info@detectomat.com An der Strusbek 5 www.detectomat.com D-22926 Ahrensburg / Germany

Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

- Subject to alterations and errors -

Product-Information Sheet
Fire Control Panel, 2 Zones, Conventional, English Order No. 32638 - Type DCC 2
editing status 13.04.2010

Description: Compact microprocessor controlled fire control panel for the use with the CT 3000 fire detection system components. Approved according to EN 54-2:1997/A1 2006 and EN 54-4:1997/A2:2006.

Properties: Clear display and easy operation with LED displays and operation keys Connection possibility for 2 conventional zones for the use with the CT 3000 fire detection components with up to 20 detectors per zone Integrated power supply accord. to EN 54-4:1997/A2:2006 with 1 output for external devices rated at 24V DC 2 monitored outputs with 300 mA each for signalling devices 2 potentialfree relay outputs for alarm and fault Emergency power supply via 1 battery 12 V / up to 7 Ah Independent connection of detector and signalling device zones Integrated "one-man-revision mode" 2 access levels via key switch Manual control of signalling devices via seperate input Internal selftest for 8 potential faults Incl. programming option, e.g. alarm delay, fast modus
Technical data Supply voltage Power supply Emergency supply Quiescent current Alarm current Short circuit Conventional line broken wire/ fault Display Outputs Ambient temperature Humidity Stock temperature Protection class Colour Material Dimensions (H x W x D) Weight Standards Further approvals

230 V AC 10 % 24 V DC/300 mA 1 x 12 V/7 Ah 2 to 10 mA 10 to 110 mA 110 mA 0 to 2 mA 21 LEDs for status display, thereof 11 LEDs masked 6 keys for operation 2 x 24 V/300 mA monitored for signalling devices 2 relay outputs 60 V DC/120 V AC /3A for alarm and fault -5C to +40C 0 - 95 % (non condensing) -20C to +60C IP 30 Grey (similar to RAL 7035) ABS 288 mm x 340 mm x 98 mm 2,30 kg, without battery EN 54-2:1997/A1:2006 EN 54-4:1997/A2:2006 1293-CPD-0132 info@detectomat.com www.detectomat.com - Subject to alterations and errors Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

detectomat GmbH An der Strusbek 5 D-22926 Ahrensburg / Germany

Product-Information Sheet
Fire Control Panel, 4 Zones, Conventional, English Order No. 32639 - Type DCC 4
editing status 13.04.2010

Description: Compact microprocessor controlled fire control panel for the use with the CT 3000 fire detection system components. Approved according to EN 54-2:1997/A1:2006 and EN 54-4:1997/A2:2006.

Properties: Clear display and easy operation with LED displays and operation keys Connection possibility for 4 conventional zones for the use with the CT 3000 fire detection components with up to 20 detectors per zone Integrated power supply accord. to EN 54-4:1997/A2:2006 with 1 output for external devices rated at 24 V DC 2 monitored outputs with 300 mA each for signalling devices 2 potentialfree relay outputs for alarm and fault Emergency power supply via 1 battery 12 V / up to 7 Ah Independent connection of detector and signalling device zones Integrated "one-man-revision mode" 2 access levels via key switch Manual control of signalling devices via seperate input Internal selftest for 8 potential faults
Technical data Supply voltage Power supply Emergency supply Quiescent current Alarm current Short circuit Conventional line broken wire/ fault Display Outputs Ambient temperature Humidity Stock temperature Protection class Colour Material Dimensions (H x W x D) Weight Standards Further approvals

230 V AC 10 % 24 V DC/300 mA 1 x 12 V/7 Ah 2 to 10 mA 10 to 110 mA 110 mA 0 to 2 mA 25 LEDs for status display, thereof 11 LEDs masked 6 keys for operation 2 x 24 V/300 mA monitored for signalling devices 2 relay outputs 60 V DC/120 V AC /3A for alarm and fault -5C to +40C 0 - 95% (non condensing) -20C to +60C IP 30 Grey (similar to RAL 7035) ABS 288 mm x 340 mm x 98 mm 2,30 kg, without battery EN 54-2:1997/A1:2006 EN 54-4:1997/A2:2006 1293-CPD-0132 info@detectomat.com www.detectomat.com - Subject to alterations and errors Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

detectomat GmbH An der Strusbek 5 D-22926 Ahrensburg / Germany

Product-Information Sheet
Fire Control Panel, 8 - 16 Zones, Conventional, English Order No. 32640 - Type DCC 8 plus
editing status 28.04.2010

Description: Compact microprocessor controlled fire control panel for the use with the CT 3000 fire detection system components. Approved according to EN 54-2:1997/A1:2006 and EN 54-4:1997/A2:2006.

Properties: Clear display and easy operation with LED displays and operation keys Connection possibility for 8 conventional zones for the use with the CT 3000 fire detection components with up to 20 detectors per zone Extension option via 4 zone modules for up to 16 conventional zones for CT 3000 fire detection components Integrated power supply accord. to EN 54-4:1997/A2:2006 4 monitored outputs with 300 mA each for signalling devices 2 potentialfree relay outputs for alarm and fault Emergency power supply via 1 battery 12 V / up to 18 Ah Independent connection of detector and signalling device zones Integrated "one-man-revision mode" Manual control of signalling devices via seperate input Internal selftest for 8 potential faults Incl. programming option, e.g. alarm delay, fast modus Panel network of max. two fire control panels Accessories: 32653 - 4 zone extension module Type GE 4 32654 - 4 alarm zones extension Type SE 4 32655 - Relay-module, 8 Relays 1 A/12 V Type RM 8
Technical data Supply voltage Power supply Emergency supply Quiescent current / Zone Alarm current / Zone Short circuit Conventional line broken wire/ fault Display Outputs Ambient temperature Humidity Stock temperature Protection class Colour Material Dimensions (H x W x D) Weight Standards Further approvals

230 V AC 10 % 24 V DC/1 A 1 x 12 V/18 Ah 2 to 10 mA 10 to 110 mA 110 mA 0 to 2 mA 16 LED-displays for status display (+ 8 LEDs in case of extension) 6 keys for operation and programming 4 x 24 V/300 mA monitored for signalling devices 2 relay outputs 60 V DC/120 V AC/3A for alarm and fault -5C to +40C 0 - 93% (non condensing) -20C to +60C IP 30 Grey (similar to RAL 7035) ABS Outer dimensions 345 mm x 455 mm x 128 mm 4,26 kg, without battery EN 54-2:1997/A1:2006 EN 54-4:1997/A2:2006 1293-CPD-0133 info@detectomat.com www.detectomat.com - Subject to alterations and errors Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

detectomat GmbH An der Strusbek 5 D-22926 Ahrensburg / Germany

No. 30014

Heat detector

CT 3000 T

highly functional detection-system intelligent analysis of the thermal sensor

Technical data operating voltage quiescent current alarm current open collector output sensitivity operation temperature humidity protection class colour housing material EN approvals 9 up to 33 V DC 80 A 20 mA 15 mA for LED indicators 60C rate of rise -10C up to +60C max. 95 %/RH/40C IP 30 white ABS 54-7 further on request

Conventional heat detector according to EN 54-7:

No. 30015

Optical smoke detector

CT 3000 O

VdS G203036

Conventional optical smoke detector according to EN 54-7:

highly functional detection-system intelligent analysis of the measuring chamber signal

Technical data operating voltage quiescent current alarm current open collector output sensitivity operation temperature humidity protection class colour housing material DIN EN dimensions (H x ) approvals 9 up to 33 V DC 40 mA 20 mA 15 mA for LED indicators < 0,15 dB/m -10C up to +60C max. 95 %/RH/40C IP 30 white ABS 54-7 44 mm x 100 mm further on request

Product-Information Sheet
Detector standard base, white Order No.32242 Type SDB 3000
editing status: 2009-08-27

Description: Detector Base for all detectors of series CT and loop 3000.

Properties: Integrated connectors for LED indicator (Art. 31193) or piezo buzzer (Art. 32091). Space for additional connectors Type WAGO 243. Integrated connectors for the connection of one spur for the loop extension (T-branch). Mounting space for the piezo buzzer (Art 32091) and the detector labelling clip (Art 30479). Including transparent seal cover to protect the base against contaminents.
Technical data

Colour housing Material Dimensions (H x ) detectomat GmbH An der Strusbek 5 D-22926 Ahrensburg / Germany

white (similar RAL 9003) ABS 21 mm x 95 mm info@detectomat.com www.detectomat.com - Subject to alterations and errors Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

Product-Information Sheet
Input- / Output module, single I/O, signalling devices,with isolator Order No. 31640 - Type OMS 3301 mini
editing status 20.01.2010

Description: Intelligent Input- / Output module mini for the Loop 3000 for the control of external optical and acoustic signalling devices with bidirectional isolator for the integration in externally connected modules according to DIN EN 5418 including one monitored fault input and one open collector output for signalling devices

Properties: Integrated automatic switch function of the output at "external signal line on/off" signal by the fire control panel Connecting module with one freely programmable fault input and one output for the connection of signalling devices Programming of different switching variants of input and output also with time control Monitoring of the operating status via Loop 3000 Independent programming of Input and Output Automatic and manual addressing on the loop 3000 Integrated Isolator Functions completely integrated via loop 3000 protocol Completely encapsulated module for the integration in special applications with control by the loop 3000

Technical data Operation voltage Current consumption Output Input

Ambient temperature
Humidity Weight

Protection class
Colour housing Material Dimensions (H x W x D) Standards VdS approval System approval CPD - number

15 to 30 V DC loop powered 380 A 1 Open Collector 500 mA 1 10 mAparallelfor LED-status indication Low active monitored -10 to +60 C C max. 93% (+/-2%) Approx.20g IP 30 Blue ABS 27 mm x 73 mm x 15 mm DIN EN 54-18, 17 G 206047 S 295054 and S 208123 0786-CPD-20530 info@detectomat.com www.detectomat.com - Subject to alterations and errors Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

detectomat GmbH An der Strusbek 5 D-22926 Ahrensburg / Germany

Product-Information Sheet
Input- / Output module, single I/O, Relay, with Isolator Order No. 30200 - Type IOM 3311
editing status 20.01.2010

Description: Intelligent Input- / Output Module for the Loop 3000 with bidirectional isolator according to DIN EN 54-18 with one monitored input and one potentialfree relay output

Properties: Connecting module with one freely programmable Input and one freely programmable output Programming of different switching variants of input and output also with time control Monitoring of the operating status via Loop 3000 Independent programming of Input and Output Automatic and manual addressing on the loop 3000 Integrated Isolator and T-branch option Functions completely integrated via loop 3000 protocol Multicolour-LED for alarm (red) and fault (yelow) Aestethical robust wall mounted housing according with IP 54 Accessories: Possibility for monitoring of the output with UBW 3311 (Order No. 32073)

Technical data Operation voltage Quiescent current Alarm current Output Input

Ambient temperature
Humidity Weight

Protection class
Colour housing Material Dimensions (H x W x D) Standards VdS approval System approval CPD - number

15 to 30 V DC loop powered 460 A 460 A, 5 mA if alarm-LED is active Relay 1 change over contact 30 V DC/ 1A Low active monitored -10 to +60 C C max. 93% (+/-2%) Approx. 185 g IP 54 grey (similar to RAL 7035) ABS 93 mm x 93 mm x 55 mm DIN EN 54-18, 17 G 205029 S 295054 and S 208123 0786 - CPD-20459

detectomat GmbH An der Strusbek 5 D-22926 Ahrensburg / Germany

info@detectomat.com www.detectomat.com - Subject to alterations and errors -

Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

Product-Information Sheet
Input module, 1 conventional zone,with Isolator Order No. 30205 - Type TCM 3300
editing status 16.12.2009

Description: Intelligent Input module for the connection of one conventional detector zone to the loop 3000 with vidirectional isolator according to DIN EN 54-18 and for the connection of conventional detectors with 12V or 24V technology

Properties: Voltage selection for the detector zone supply via "jumper" on the module board External supply of conventional detector zones for the flexible use of different current consumptions and operation voltages Possibility for parametrization of short-circuit, wire break, prealarm and alarm thresholds Automatic and manual adressing on the loop 3000 Integrated Isolator and T-branch option Functions completely integrated via loop 3000 protocol Multicolour-LED for alarm (red) and fault (yellow) Aesthetical robust wall mounted housing according with IP 54

Technical data Operation voltage Quiescent current Alarm current Input Ambient temperature Humidity Weight Portection class Colour housing Material Dimensions (H x W x D) Standards VdS approval System approval CPD-Nummer

15 to 30 V DC loop powered External supply output 12V or 24V DC 560 A 560 A ; 5 mA if alarm-LED is active 1 monitored detector zone with up to 65 mA -10 to +60 C C max. 93% (+/-2%) Approx. 190g IP 54 grey (similarto RAL 7035) ABS 93 mm x 93 mm x 55 mm DIN EN 54-18, 17 G 206048 S 295054 and S 208123 0786-CPD-20373

detectomat GmbH An der Strusbek 5 D-22926 Ahrensburg / Germany

info@detectomat.com www.detectomat.com - Subject to alterations and errors -

Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

Product-Information Sheet
Input- / Output module, single I/O, signalling devices, with isolator Order No. 30211 - Type OMS 3301
editing status 20.01.2010

Description: Intelligent Input- / Output module for the Loop 3000 for the control of external optical and acoustic signalling devices with bidirectional isolator according to DIN EN 54-18 including one monitored fault input and one potentialfree relay output for signalling devices

Properties: Integrated automatic switch function of the output at "external signal line on/off" signal by the fire control panel Connecting module with one freely programmable fault input and one output for the connection of signalling devices Monitoring of the operating status via Loop 3000 Independent programming of Input and Output Automatic and manual addressing on the loop 3000 Integrated Isolator and T-branch option Functions completely integrated via loop 3000 protocol Multicolour-LED for alarm (red) and fault (yellow) Programming of different switching variants ofa input and output also with time control Aestethical robust wall mounted housing according with IP 54 General remarks The fault input can be used for the monitoring module UBW 3311 Accessories: Possibility for monitoring of the output with UBW 3311 (Art.Nb. 32073)

Technical data Operation voltage Current consumption Input Output

Ambient temperature
Humidity Weight

Protection class
Colour housing Material Dimensions (H x W x D) Standards VdS approval System approval CPD - number

15 to 30 V DC loop powered 460 A Relay 1 change over contact 30 V DC / 1A Low active monitored -10 to 60 C C max. 93% (+/-2%) Approx. 190 g IP 54 Grey (similar to RAL 7035) ABS 93 mm x 93 mm x 55 mm DIN EN 54-18, 17 G 205030 S 295054 and S 208123 07786-CPD-20460

detectomat GmbH An der Strusbek 5 D-22926 Ahrensburg / Germany

info@detectomat.com www.detectomat.com - Subject to alterations and errors -

Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670

Product-Information Sheet
Input- / Output module, single I/O, Open Collector with Isolator Order No. 30513 - Type AMD 3311
editing status 14.12.2009

Description: Intelligent Input- / Output module mini for the Loop 3000 with bidirectional isolator for the integration in special detectors and externally connected modules according to DIN EN 54-18 including one monitored input and one open collector output

Properties: Connecting module with one freely programmable Input and one freely programmable output Additional parallel alarm output (blinking) for the control of a status indicator (without series resistor) Programming of different switching variants of input and output also with time control Monitoring of the operating status via Loop 3000 Independent programming of Input and Output Automatic and manual addressing on the loop 3000 Integrated Isolator Functions completely integrated via loop 3000 protocol Completely encapsulated module for the integration in special applications with control by the loop 3000

Technical data Operation voltage Quiescent current Alarm Current Output Input Ambient temperature Humidity Weight Protecting class Colour Housing Material Dimensions (H x W x D) Standards VdS approval System approval CPD-Nummer

15 to 30 V DC loop powered 380 A 380 A ; 5 mA if alarm-LED is active 1 Open Collector 500 mA 1 10 mA parallel for LED-Status indication low active monitored -10 to +60 C C max. 93% (+/-2%) Approx. 20g IP 30 Blue ABS 27 mm x 73 mm x 15 mm DIN EN 54-1, 18 G 206047 S 295054 and S 208123 076-CPD-20530

detectomat GmbH An der Strusbek 5 D-22926 Ahrensburg / Germany

info@detectomat.com www.detectomat.com - Subject to alterations and errors -

Tel. +49(0)4102/2114-60 Tel. +49(0)4102/2114-670