Network solutions for PROFIBUS
according to IEC 61158/61784
Brochure March 2010
BR_Netzloesungen_PROFIBUS_EN.book Seite 1 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
PROFIBUS system overview 2
PROFIBUS system overview
Introduction
PROFIBUS is the successful open fieldbus that can be used
for fast and cost-effective production in a wide area of
applications.
Distributed automation structures are the prerequisite for
such flexible manufacturing. Connecting production areas
with local networks secures the information flow necessary
for this.
PROFIBUS is a bus system for process and field communication
in cell networks with few stations and with field devices, as
well as for data communication in accordance with
IEC 61158/61784.
Automation devices such as PLCs, PCs, HMI devices, sensors or
actuators can communicate via a standardized bus.
This allows the use of a wide range of PROFIBUS products from
Siemens and other manufacturers for solving automation
tasks. These products can be operated together in a PROFIBUS
network.
PROFIBUS thus offers openness for connecting standard com-
ponents from other manufacturers.
Part of TIA
Totally Integrated Automation (TIA) stands for an integrated
range of products and systems for automation in all areas
from incoming goods, through the production process to the
dispatch of goods, from the field level, through the produc-
tion control level to the connection to the corporate manage-
ment level:
An integrated software tool set supports all project phases,
from the selection of hardware, programming and opera-
tion, to diagnostics and maintenance.
The tools access a common database.
This saves input costs and ensures project-wide consis-
tency.
Outstanding features
PROFIBUS is a powerful, open, and rugged bus system that
offers trouble-free communication.
The system is fully standardized, which enables simple con-
nection of standardized components from a variety of
manufacturers.
Configuration, commissioning, and troubleshooting can
be carried out from any location. This results in user-
defined communication relationships that are very versa-
tile, simple to implement, and easy to change.
Investment security through continuous compatible
further development.
Network components for use in harsh industrial environ-
ments.
Fast assembly and startup on site with the help of the
FastConnect wiring system.
Continuous monitoring of network components through a
simple and effective signaling concept.
High security of investment since existing networks can be
extended without any adverse effects.
High availability through ring redundancy with the active
OLM network component.
Fail-safe communication with PROFIsafe.
High levels of operational reliability and plant availability
thanks to different diagnostics options.
BR_Netzloesungen_PROFIBUS_EN.book Seite 2 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
PROFIBUS system overview 3
Contents
Communication functions
Process or field communication (PROFIBUS PA, PROFIBUS DP)
is used to link field devices to a programmable controller,
HMI system or control system.
Interfacing is performed over integrated interfaces on the CPU
or through interface modules (IMs) and communications pro-
cessors (CPs).
With modern high-performance automation systems it is
often more effective to link more than one PROFIBUS DP line
to one automation system, not just to increase the number
of I/O stations that can be connected, but also to enable indi-
vidual production areas to be handled independently
(segmentation).
PROFIBUS standardized to IEC 61158/61784 is a high-perfor-
mance, open, and rugged fieldbus system with short response
times and the following protocols:
PROFIBUS DP (distributed I/O)
is used to connect distributed I/Os, e.g. SIMATIC ET 200,
with extremely fast response times in accordance with the
IEC 61158/61784 standard.
PROFIBUS PA (Process Automation)
extends PROFIBUS DP with intrinsically safe transmission
technology in accordance with the standard IEC 61158-2.
Text
PROFIBUS system overview
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Possible applications. . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Networking options . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
electrical networks. . . . . . . . . . . . . . . . . . . . . . . . . . . 8
optical networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
hybrid networks. . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Network selection criteria. . . . . . . . . . . . . . . . . . . . . . 12
FastConnect for electrical bus cables . . . . . . . . . . . . . 13
SpliTConnect for PROFIBUS PA . . . . . . . . . . . . . . . . . . 14
FastConnect for optical bus cables . . . . . . . . . . . . . . . 15
Passive network components
Electrical bus cables . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Optical bus cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Active network components
Electrical network . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Optical network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Network transitions . . . . . . . . . . . . . . . . . . . . . . . . . 22
Communications processors for SIMATIC
CPs for SIMATIC S7 . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
CPs for SIMATIC S7: Function overview . . . . . . . . . . . 26
Communications processors for PG/PC
CPs for PG/PC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
CPs with internal microprocessor . . . . . . . . . . . . . . . . 28
CPs without internal microprocessor . . . . . . . . . . . . . 29
Possible applications with OPC
(Openness, Productivity & Collaboration) . . . . . . . . . 30
CPs for PG/PC: Function overview . . . . . . . . . . . . . . . 32
Connection options
Electrical and optical networking. . . . . . . . . . . . . . . . 33
Technology components for PROFIBUS . . . . . . . . . 35
Advantages at a glance . . . . . . . . . . . . . . . . . . . . . . 35
BR_Netzloesungen_PROFIBUS_EN.book Seite 3 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
PROFIBUS system overview 4
PROFIBUS system overview
Introduction
General overview of PROFIBUS
PROFIBUS is used to connect field devices, such as distributed
I/O devices or drives, to automation systems such as SIMATIC
S7 and S7mEC, PC-based controllers, WinAC, SIMOTION,
SINUMERIK, or SIMATIC IPCs.
PROFIBUS is standardized in accordance with IEC 61158/
61784 and is a powerful, open and rugged fieldbus system
with short response times. PROFIBUS is available in different
forms for various applications.
PROFIBUS DP
(distributed I/O)
PROFIBUS DP is used for connecting distributed field devices,
e.g. SIMATIC ET 200, or drives with extremely fast response
times. PROFIBUS DP is used when sensors/actuators are dis-
tributed at the machine or in the plant (e.g. field level).
The actuators and sensors are connected to the field devices.
The field devices are supplied with output data in accordance
with the master/slave technique and transfer input data to the
controller or industrial PC.
Openness all along the line
Thanks to the openness of PROFIBUS DP, standard-compliant
components from different manufacturers can also be con-
nected.
The IEC 61158/61784 standards provide future protection for
your investment.
Member companies worldwide offer the most diverse prod-
ucts with PROFIBUS DP interface for the field area.
Siemens has a full product range of standard and fail-safe con-
trollers, network components, communication software, and
field devices.
And for field device manufacturers we offer everything to do
with the PROFIBUS DP interface, such as ASICs, training, certi-
fication, and much more.
PROFIsafe
permits standard and safety-related communication on one
and the same bus cable. It is an open solution for safety-
related communication over standard buses and uses the
PROFIBUS services.
G
_
I
K
1
0
_
X
X
_
5
0
0
2
6
MSS
SIMOREG SINAMICS
SIMOCODE
PRO
ET 200L
PROFIsafe
ET 200pro
SIMOTION C/P/D
SIMATIC S7
Notebook
Multi Panel
SINUMERIK
PROFIBUS DP
SIMOVERT
MASTER-
DRIVES
MICRO-
MASTER
ET
200M
AS-Interface
ET
200eco
Field PG M
DP/AS-i
LINK
Advanced
DP/AS-i
F-Link
DP/AS-
Interface
Link 20E
Sensors IO modules
Code
reading
systems
RFID systems
SIMATIC RF
Compact
feeder
arrangement
ET 200M with
F-IO
S7-300F with standard
and F I/Os
IO-Link
module
Field devices
BR_Netzloesungen_PROFIBUS_EN.book Seite 4 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
PROFIBUS system overview 5
Isochronous mode
The CPU, I/O and user program are synchronized with the
PROFIBUS cycle. The "isochronous mode" function is
supported by the CPUs of SIMATIC S7-400, SIMOTION,
SINUMERIK and servo drives. The drives are controlled using
the PROFIdrive profile.
PROFIBUS PA
(process automation)
PROFIBUS PA extends PROFIBUS DP with intrinsically safe
transmission of data and power (e.g. transducers in the food
processing industry) in accordance with the international
standard IEC 61158-2 (same protocol, different physical
properties).
PROFIBUS FMS
(Fieldbus Message Specification)
PROFIBUS FMS is used for data communication between auto-
mation systems of different manufacturers. This enables pre-
cise, distributed implementation of general closed-loop con-
trol and measuring tasks.
Example of a PROFIBUS FMS configuration
SIMATIC
PDM
Intrinsically safe area
DP/DP
coupler
SIMATIC PC with WinAC
DP/PA
Coupler/
Link
RS 485iS coupler
Customized
solutions with
ASICs
Customized
solutions with
ASICs
* PDM is a parameterization tool for intelligent field devices
Vision Sensor
VS 120
DP slave
G
_
I
K
1
0
_
X
X
_
5
0
0
2
7
*
PROFIBUS PA PROFIBUS DP
SIMATIC TDC
Power Rail
Booster
SIMATIC HMI
SIPART PS2
SITRANS FM
SITRANS P
Mobile
Panel
ET 200iSP
SIMATIC C7
non-Siemens
device
G
_
I
K
1
0
_
X
X
_
5
0
0
2
9
PROFIBUS-FMS
S7-300
S7-400
SIMATIC HMI
Field PG M
BR_Netzloesungen_PROFIBUS_EN.book Seite 5 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
PROFIBUS system overview 6
PROFIBUS system overview
Application options
Factory automation
It is possible to use PROFIBUS DP in, for example, the food
and beverages industry, to implement production lines with
variable speeds or options for controlling the plant during
operation.
Many variables have to be flexible in order to allow fault-free pro-
duction. Plant availability is becoming increasingly important.
Downtimes caused by repairs are usually more expensive than
the appropriate monitoring of systems for wear or possible
faults.
With the aid of high-performance components in the communi-
cation, for example, errors can be located and reported quickly.
Process automation
Process automation has high performance and reliability re-
quirements and demands simple and safe operation of plants.
PROFIBUS PA uses the intrinsically safe transmission techno-
logy specified in the international IEC 61158-2 standard. This
allows field devices to be integrated into the hazardous zone.
The basis for this is PROFIBUS DP that has been expanded for
intrinsically-safe operation. The acyclic communication servic-
es of PROFIBUS DP/PA allow online access to device parame-
ters, that is, the process control systems have direct access to
the actual status of the field device data and to the status and
diagnostics messages.
Using PROFIBUS DP/PA, the field devices become an integral
component of the company-wide automation concept from
open-loop and closed-loop control right up to asset manage-
ment, including spare parts management and warehouse
management.
Building automation
The networking of large buildings or parts of buildings allows
centralized or distributed access to all stations.
Electrical installation systems are found not only in residential
and non-residential buildings but also in every industrial plant.
Most devices and also many building systems such as lighting,
heating, air conditioning, fans, blinds, or access controls are
operated almost without exception with electric power.
These systems, just like those in industrial automation, must
be regulated, controlled, and monitored.
Factory automation
Process automation
Building automation
BR_Netzloesungen_PROFIBUS_EN.book Seite 6 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
PROFIBUS system overview 7
Networking options
Electrical PROFIBUS network configuration
Siemens offers a comprehensive range of PROFIBUS network
components for electrical, optical, and wireless transmission
technology.
PROFIBUS is standardized in accordance with IEC 61158/
61784 for universal automation (PROFIBUS FMS and
PROFIBUS DP), and in accordance with IEC 61158-2 for pro-
cess automation (PROFIBUS PA).
PC with
CP 5613 A2/
CP 5621
S7-400 with
CP 443-5 Extended
Intrinsically safe area
Repeater
Repeater
Drive
PC/IPC with
CP 5614 A2
RS 485iS
coupler
DP/PA
coupler/link
ET 200pro with motor starter
G
_
I
K
1
0
_
X
X
_
5
0
0
1
2
ET 200pro
PROFIBUS DP
ET 200M
ET 200S
PROFIBUS PA
ET 200iSP
PROFIBUS DP
BR_Netzloesungen_PROFIBUS_EN.book Seite 7 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
PROFIBUS system overview 8
PROFIBUS system overview
Networking options electrical networks
The electrical network uses a shielded, twisted pair cable.
The RS485 interface works with voltage differences. It is
therefore less sensitive to interference than a voltage or cur-
rent interface.
With PROFIBUS, the stations are connected to the bus via a bus
terminal or a bus connector (max. 32 stations per segment).
The electrical network can be configured as a bus or tree struc-
ture. The individual segments are connected via repeaters.
The transmission rate can be set in steps from 9.6 Kbit/s to
12 Mbit/s in accordance with IEC 61158/61784.
The maximum segment length depends on the transmission
rate.
For applications in the intrinsically-safe area the transmission
technology compliant with IEC 61158-2 is used with
PROFIBUS PA. The transmission rate in this case is 31.25 Kbit/s.
Features of the electrical network
Transmission method in accordance with IEC 61158/61784
for universal automation (PROFIBUS FMS/DP), and in accor-
dance with IEC61158-2 for the intrinsically-safe area
(PROFIBUS PA)
Shielded 2-wire cable
Transmission method: RS485 (in accordance with EIA)
Bus topology with bus terminals and bus connectors for
connecting PROFIBUS stations
Network is immune to interference thanks to double-
shielded cables and a simple, uniform installation and
grounding concept
Simple and fast connector assembly with FastConnect
The DP transmission system of RS485 (bit coding by means
of differential voltage signals) is converted to IEC 61158-2
(bit coding by means of current signals) using the network
components (DP/PA coupler or DP/PA link)
PROFIBUS cables with cable connectors
PROFIBUS FastConnect stripping tool
BR_Netzloesungen_PROFIBUS_EN.book Seite 8 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
PROFIBUS system overview 9
Networking options optical networks
Network configuration of optical PROFIBUS with OLMs
The optical network uses fiber-optic cables as the transmis-
sion medium. The fiber-optic cable is provided with a coating.
The term "fiber" is often also used for fiber-optic cables (FOC).
Optical networks are especially suitable for long ranges. There
is a choice between plastic, PCF or glass fiber-optic cables.
Fiber-optic standard cable with connector
Features of the optical network
The transmission link is insensitive to electromagnetic
influences
It is suitable for long ranges
Galvanic isolation is implemented
You can choose between plastic, PCF or glass fiber-optic
cables
It is tap-proof since no radiation is emitted from the line
It is easy to lay since the cable is light-weight and pre-
assembled, and there are no grounding problems
No additional lightning protection concept is required in
the outdoor area
Rugged construction of the fiber-optic cable for industrial
applications both indoors and outdoors
The fiber-optic cables galvanically isolate the modules.
S7-400 with
CP 443-5 Extended
PC/lPC with CP 5611/
CP 5621/CP 5613 A2/
CP 5614 A2
S7-300
with CP 342-5
PROFlBUS electrical
PROFlBUS optical
(PROFlBUS
FC standard cable)
Drive
Cabinet
(FO standard
cable 50/125)
ET 200pro
with motor starter G
_
l
K
1
0
_
X
X
_
5
0
1
3
5
OLM/G12 OLM/G12
ET 200S
ET 200pro
OLM/G12 OLM/G12
OP170B
ET 200M
Optical Link Module
(OLM/G12)
BR_Netzloesungen_PROFIBUS_EN.book Seite 9 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
PROFIBUS system overview 10
PROFIBUS system overview
Networking options optical networks
Network configuration of optical PROFIBUS DP with PROFIBUS OBT
Optical PROFIBUS with OLMs
Using optical link modules (OLMs) it is possible to construct an
optical network in a linear, ring, or star topology. A network
topology for increased availability requirements can be estab-
lished using the redundant ring structure.
The maximum distance between two OLMs is 15 km. The
transmission rate can be set in steps from 9.6 Kbit/s to
12 Mbit/s.
Optical PROFIBUS with integral interface and OBT
The optical PROFIBUS with integral interface and OBT is con-
structed in a linear topology. A cost-optimized solution is
available for this in the form of devices with integral optical
interface. Terminal equipment with an RS485 interface can be
connected via an Optical Bus Terminal (OBT). The maximum
distance between two stations is 50 m in the case of plastic
fiber-optic cable.
To cover distances of up to 300 m, special fiber-optic cables
are offered.
PC/IPC/OP
with 5613 FO
S7-300
with CP 342-5 FO
ET 200S
with IM 151 FO
ET 200M
with IM 153-2 FO
DP node
without integrated optics
Individual link lengths: plastic up to 50 m,
PCF up to 300 m
Connecting cable
830-1T
Other
nodes
PROFIBUS (Fiber Optic)
PROFIBUS (RS485)
G
_
I
K
1
0
_
X
X

5
0
1
0
7
OBT
PROFIBUS
BR_Netzloesungen_PROFIBUS_EN.book Seite 10 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
PROFIBUS system overview 11
Networking options mixed networks
Electrical and optical PROFIBUS in star topology
Hybrid electrical and optical networks are possible. The transi-
tion between both media is implemented by the OLM.
In station-to-station communication on the bus, there is no
difference between two-wire technology and fiber-optic tech-
nology. A maximum of 127 stations may be connected to one
PROFIBUS network.
PROFIBUS OLM
Glass fiber-optic cables for PROFIBUS
Bus
connector
with terminating
resistor
Bus
connector
with terminating
resistor
S7-400
with CP 443-5
Extended
PC/lPC with
CP 5611 A2/
CP 5621/
CP 5613 A2/
CP5614 A2
S7-300
with CP 342-5
PROFlBUS electrical (PROFlBUS FC Standard Cable)
G
_
l
K
1
0
_
X
X
_
5
0
0
5
0
ET 200M
OLM/G11 OLM/G11
OLM/G11
OLM/G11 OLM/G11 OLM/G11
ET 200S
ET 200S
OLM/G12
OLM/G11 OLM/G11
OLM/G12
PROFlBUS optical
(FO standard
cable 50/125)
BR_Netzloesungen_PROFIBUS_EN.book Seite 11 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
PROFIBUS system overview 12
PROFIBUS system overview
Network selection criteria
Criteria Electrical network Optical network
RS 485 con-
forming to IEC
61158/ 61784
IEC 61158-2
(PA)
Plastic PCF Glass
EMC


Inter-building networking

1)

5)

5)
Operating distance

2)


Suitability for high transmission rate

4)
-

Simple plug fitting

3)

3)
Simple cable laying

Equipotential bonding measures required Yes Yes No No No


Performance spectrum for special applications

Used for moving nodes


6)

6)

6)
Use in intrinsically safe area
-

- - -
1) Lightning protection measures required
2) Depending on transmission rate
3) Trained personnel and special tools necessary
4) Careful cable laying necessary
5) Outdoor cable required
6) Trailing cable required

suitable


partly suitable

-
not applicable
G
_
I
K
1
0
_
X
X
_
5
0
0
1
0
BR_Netzloesungen_PROFIBUS_EN.book Seite 12 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
PROFIBUS system overview 13
FastConnect for electrical bus cables
The FastConnect stripping technology facilitates swift and
simple connection of PROFIBUS connectors to the PROFIBUS
cables.
The special design of the FastConnect bus cables permits the
use of the FastConnect stripping tool, with which the outer
sheath and the braided shield can be removed to measure in
one operation. Cables prepared in this way are attached to the
FastConnect bus connectors using the insulation displace-
ment method.
The system comprises three components that are coordinated
with one another:
FastConnect bus cables for quick assembly
FastConnect stripping tool
FastConnect bus connector for PROFIBUS
The PROFIBUS FastConnect bus cables can also be connected
to the conventional bus connectors.
Advantages of the FastConnect system
Reduction of the connection times of terminals by
removing the outer sheath and braided shield in one
operation
Assembly errors such as short-circuit between shield
and core are prevented
Simple assembly operations thanks to preset FC strip-
ping tool
Contact assignment can be checked in the closed
state by means of the transparent cover on the insu-
lation piercing connecting devices and color coding
FastConnect connecting system available for degrees
of protection IP20 and IP65.
Initial position of the stripping tool
(FCS) in the right hand
Measuring the cable length by
placing the cable on the template.
End stop with the index finger of
the left hand.
Inserting the measured end of the
cable into the tool as far as the in-
dex finger of the right hand.
Clamping end of cable in FCS as far
as end stop.
Turn FCS four times in direction of
arrow.
Pull FCS off end of cable while still
closed.
Cable off-cuts remain in the FCS.
After unclamping the FCS,
the off cuts can be removed.
Insert cores into the connector
according to color coding, press
the interlock down and tighten the
strain relief screw.
Finished! PB FC M12 PlugPRO pre-assembled
BR_Netzloesungen_PROFIBUS_EN.book Seite 13 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
PROFIBUS system overview 14
PROFIBUS system overview
SpliTConnect for PROFIBUS PA
SpliTConnect for fieldbus systems is used for constructing
fieldbus segments as per IEC 61158-2 (e.g. PROFIBUS PA) with
field device interface points.
The bus cable is easy to assemble thanks to the FastConnect
system (FastConnect stripping tool, FC Process Cable compli-
ant with IEC 61158-2).
The FC Process Cable is stripped as with FastConnect.
Additional grounding of the SpliTConnect Tap can be imple-
mented using a contacting screw.
The terminal devices can be connected using the FC Process
Cable in accordance with IEC 61158-2 or the SpliTConnect
M12 Outlet/M12 Jack. The SpliTConnect Coupler can be used
to construct a PROFIBUS PA hub by connecting SpliTConnect
Taps in series.
By replacing the contacting screw with the SpliTConnect
Terminator, the SpliTConnect Tap can be used as a bus termi-
nating element.
Advantages of SpliTConnect
The connection times of terminals are reduced by
fast and easy removal of the outer sheath and
braided shield in one operation
Simple assembly operations thanks to preset FC
stripping tool
Connection of the terminal device is facilitated by use
of the FastConnect system
Widely diverse uses possible thanks to the modular
SpliTConnect system
Reduction in number of types and parts thanks to uni-
form connection system for PROFIBUS PA
SpliTConnect Tap and Terminator SpliTConnect Coupler
SpliTConnect M12 Outlet SpliTConnect M12 Jack
BR_Netzloesungen_PROFIBUS_EN.book Seite 14 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
15
FastConnect for optical bus cables
FastConnect for glass fiber-optic cables
For the FastConnect FOC system, fiber-optic cables with
glass core (62.5/200/230) are offered. They are suitable for
easy assembly in the field;
FC glass FOC: Duplex cable for fiber-optic networks indoors
and outdoors
FastConnect glass fiber-optic cables are assembled on-site
using the FC FO termination kit. The termination kit per-
mits the stripping and the "cleaving" of the fiber in the as-
sembled connector.
FastConnect SC and FastConnect BFOC connectors are
available for the assembly of glass fiber-optic cables
Assembly with FastConnect for glass fiber-optic cables
BR_Netzloesungen_PROFIBUS_EN.book Seite 15 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
Passive network components 16
Passive network components
Electrical bus cables
The following applies for all PROFIBUS connecting cables:
Due to the double shielding, they are particularly suitable
for laying in industrial environments subject to electro-
magnetic interference.
A consistent grounding concept can be implemented
via the outer sheath and the ground terminals of the
bus terminal.
The printed meter marks simplify assembly.
Cable type Designation Features Fields of application
For the construction of PROFIBUS net-
works, the following different types of
silicon-free cable are offered for the dif-
ferent applications:
Bus cables
with
FastConnect
technology
Quick and easy connector
assembly with the aid of
the stripping tool. Shielded
twisted-pair cables con-
structed with radial sym-
metry.
PROFIBUS
FC standard cable GP
Standard cable for universal applica-
tions
FC robust cable Special cable for chemically and me-
chanically demanding environments
FC food cable Special cable for the food and
beverages industry
FC ground cable Special cable for routing under-
ground
FC flexible cable Special cable for use in cable carriers
FC trailing cable Trailing cable for moving machine
parts (stranded)
FC FRNC cable GP Halogen-free and flame-retardant
cable
FC process cable GP Bus cable for fieldbus systems compli-
ant with IEC 61158-2
(hazardous and non-hazardous areas)
Bus cables
without
FastConnect
technology
Shielded, twisted-pair ca-
ble with circular cross-sec-
tion; sold by the meter
PROFIBUS
Festoon cable GP
Special cable for festoon suspension
Torsion cable Special cable for use on machine
parts where the cable is subject to tor-
sion (stranded)
ECOFAST hybrid cable GP Hybrid cable for data transmission
and voltage supply to ECOFAST sta-
tions (stranded)
SIENOPYR marine cable Halogen-free, tread-resistant, flame-
retardant and marine approved cable
for permanent laying in ships and off-
shore installations
BR_Netzloesungen_PROFIBUS_EN.book Seite 16 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
Passive network components 17
1)
For special lengths with 180 or 90 cable outlet, see
http://support.automation.siemens.com/ww/view/en/26999294
Cable type Designation Features Fields of application
Connecting
cables
PROFIBUS
connecting cable 830-1T
Twisted-pair conductors
(cores of stranded copper)
with a braided shield and a
9-pin sub D connector at
each end. Both ends of the
cable are terminated with a
resistor combination
(not switched).
The PROFIBUS connecting cable 830-1T
can be used to establish the connection
between an electrical PROFIBUS inter-
face and a PROFIBUS station (OLM, OBT
and end station) at up to 12 Mbit/s.
PROFIBUS
connecting cable 830-2
PROFIBUS standard bus
cable pre-assembled with
two 9-pin connectors
(angled at 90). One con-
nector of the pre-assem-
bled connecting cable is
equipped with a program-
ming device interface.
The connecting cable 830-2 is used for
connecting PROFIBUS stations
(e.g. HMI) to PLCs at transmission rates
of up to 12 Mbit/s.
PROFIBUS
M12 connecting cable
1)
Pre-assembled connecting
cable (PROFIBUS FC Trail-
ing Cable) with two 5-pin
M12 plugs/sockets
The PROFIBUS M12 connecting cable is
used for connecting PROFIBUS stations
(e.g. SIMATIC ET 200) with IP65 degree
of protection
7/8" connecting cable
1)
Pre-assembled connecting
cable with two 5-pin 7/8"
plugs/sockets
The 7/8" connecting cable is used for
supplying energy to PROFIBUS stations
(e.g. SIMATIC ET 200) with IP65 degree
of protection
Hybrid Hybrid cable with two en-
ergy cores (1.5 mm),
sold by the meter
The hybrid cable is used for supplying
data and energy to the ET 200pro
PROFIBUS hybrid stan-
dard cable GP
Cable versions:
Standard cable for universal applica-
tions
PROFIBUS
hybrid robust cable
Rugged, trailing-type and weld
spatter-proof hybrid cable, e.g. for
use in welding cells
BR_Netzloesungen_PROFIBUS_EN.book Seite 17 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
Passive network components 18
Passive network components
Optical bus cables
Cable type Designation Features Fields of application
Fiber-optic
cable with
FastConnect
technology
Glass fiber with green
outer sheath, sold by the
meter
For indoor and outdoor
installation
FC FO standard cable GP
(62.5/200/230)
Cable versions:
Robust round cable for permanent
installation
FC FO trailing cable
(62.5/200/230)
Robust round cable for use in trailing
cables and moving applications
Fiber-optic
cable
without
FastConnect
technology
Glass fiber, sold by the
meter or pre-assembled
with 4 BFOC or SC connec-
tors
For indoor and outdoor
installation
FO standard cable GP
(50/125)
Cable versions:
Rugged standard cable
for universal applications
FO ground cable
(50/125)
Cable protected against the ingress of
water lengthwise and transversely for
installation outdoors; with non-me-
tallic rodent protection;
underground laying possible
FO trailing cable GP
(50/125)
FO trailing cable (50/125)
Cable for use in cable carriers
SIENOPYR marine-duplex
fiber-optic cable
(62.5/125)
Halogen-free, tread-resistant, flame-
retardant and marine-approved cable
for laying in ships and offshore units
ECOFAST fiber-optic
hybrid cable (DESINA-
compatible)
Sold by the meter or pre-
assembled with DESINA
connectors
Hybrid cable for data transmission and
voltage supply
PROFIBUS plastic
fiber-optic
Plastic, PCF fiber-optic ca-
ble; sold by the
meter or pre-assembled
with Simplex connectors
Plastic and PCF fiber-optic cables are
used for the construction of optical
PROFIBUS DP networks in indoor appli-
cations.
Duplex core Up to 80 m
with low mechanical loads,
e.g. laboratory structures
Standard cable Up to 50 m,
with Kevlar tension elements
PROFIBUS PCF
plastic fiber optic
standard cable
Up to 400 m,
with Kevlar tension elements
Standard cable GP 200/230
Trailing cable 200/230
Trailing cable GP 200/230
Up to 300 m,
with Kevlar tension elements
BR_Netzloesungen_PROFIBUS_EN.book Seite 18 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
Passive network components 19
Active network components
Electrical network
Bus connector
The RS485 bus connectors for PROFIBUS are used for connect-
ing a PROFIBUS station or a PROFIBUS network component to
the bus cable for PROFIBUS.
There are different versions of the bus connectors in sub D,
RJ45 or M12 connection technology that are optimized for the
devices to be connected.
Bus terminals
The PROFIBUS bus terminals enable connection of a bus node
to a PROFIBUS network.
Different versions are available:
Up to 1.5 Mbit/s: RS485 bus terminal
Up to 12 Mbit/s: 12M bus terminal
The bus terminals have a prepared device connection for
PROFIBUS stations. Stations are connected to PROFIBUS net-
works by simply connecting sub D connectors to the spur line.
Multi-point connections can be implemented by directly lining
up several bus terminals (up to 32 stations per segment) at
bus terminal 12M.
Active terminating element
The active RS485 terminating resistor is used to terminate bus
segments. Power supply is independent of the bus stations.
Separately from the other I/O components, the terminating
resistor is supplied with a permanent voltage or with a voltage
switched from the I/O. By terminating the bus system, the sta-
tions (e.g. ET 200M/S) can be freely connected and discon-
nected without malfunctions.
Repeater RS485
The RS485 repeater with IP20 connects two PROFIBUS or MPI
bus segments in RS485 technology with up to 32 stations, in-
cluding repeaters. It enables transfer rates from 9.6 Kbit/s to
12 Mbit/s (including 45.45 Kbit/s for PROFIBUS PA).
The repeater is used for:
Increasing the number of stations (up to 127) and
expansion
Galvanic isolation of segments
Regeneration of the signals in amplitude and time
PROFIBUS bus connector PROFIBUS FC M12 Plug PRO
PROFIBUS bus terminal Active terminating element
Repeater RS485
BR_Netzloesungen_PROFIBUS_EN.book Seite 19 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
Active network components 20
Active network components
Electrical network
Diagnostics repeater
STEP 7 or COM PROFIBUS prompts the diagnostics repeater to
determine the topology of the bus system and saves it in the
internal diagnostics memory.
If a fault occurs, the repeater automatically transmits a stan-
dard diagnostic message to the bus master with the following
information:
Affected segment
Fault location (e.g. between station X and Y)
Distance of the fault location from station X or Y as well as
from the repeater in meters
Type of fault
The following faults are diagnosed:
Break in data lines A, B
Data-line-to-shield short circuit
Bus terminating resistor missing
Sporadic errors are also detected. The error messages are
displayed graphically in STEP 7. They are completely inte-
grated into the SIMATIC system diagnostics (e.g. overview
diagnostics, "Report system error" function).
Power Rail Booster
The Power Rail Booster enables a PROFIBUS DP connection via
contact conductors as used, for example, on suspended
monorail conveyors or high-bay storage and retrieval systems.
The diverse PROFIBUS DP system capabilities, such as diagnos-
tics and PROFIsafe safety engineering over the bus, can con-
tinue to be used.
BT 200 hardware tester
The PROFIBUS line can be tested during the installation phase
with the BT 200 tester. Installation errors are found quickly
and simply and the installation engineer requires no special
knowledge of PROFIBUS.
Even before commissioning of the plant it is possible to test
the RS485 interface of the PROFIBUS DP slave with the BT 200.
Outputting a list of accessible slaves on the pre-wired bus is
also possible, and this without a master on PROFIBUS DP.
Diagnostics repeater Power Rail Booster
BT 200 hardware tester
BR_Netzloesungen_PROFIBUS_EN.book Seite 20 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
Active network components 21
Optical network
Optical Link Module OLM
With the PROFIBUS OLM (Optical Link Modules), optical
PROFIBUS networks can be established in linear, star and re-
dundant ring topologies. The transfer rate of a fiber-optic line
is independent of the distance and can be up to 12 Mbit/s.
Possible applications for OLMs include:
System buses based on PROFIBUS
Networking between buildings using glass fiber-optic cable
Mixed networks with electrical and optical segments
Networks covering a wide area
(road tunnels, traffic control systems)
Networks with high availability requirements
(redundant ring networks)
OLM/G12-EEC for outdoor use at temperatures as low
as -20 C
OBT optical bus terminal
The OBT (Optical Bus Terminal) is used to connect a
PROFIBUS DP station without integral optical interface or an
existing RS485 bus segment to an optical line. It thus opens
up the benefits of optical data transfer for existing DP devices
or network segments in combination with devices possessing
an integral optical interface (e.g. ET 200S FO).
The OBT is also used as the "socket outlet" for connecting
mobile devices (e.g. programming devices) without interrupt-
ing the bus.
The PROFIBUS DP station is connected to the RS485 interface
of the OBT via a cable terminated at both ends, e.g. 830-1T
connecting cable . The OBT is integrated into the optical line
using two optical interfaces.
The following optical transmission media can be connected to
the OBT:
Plastic fiber-optic cable
pre-assembled with 2 2 Simplex connectors, max. 50 m
PCF fiber-optic cable
pre-assembled with 2 2 Simplex connectors, max. 300 m.
Benefits
Automatic detection of all PROFIBUS data rates:
9.6 Kbit/s to 12 Mbit/s including 45.45 Kbit/s
(PROFIBUS PA).
High availability due to media redundancy.
The distance between two OLMs in the redundant ring
is only limited by the optical range of the modules.
RS485 interface with segment capability
(sub D socket)
Unrestricted multi-master operation:
Expanded segmentation functions for localization of
faults on fiber-optic and RS485 segments
Fast localization of faults:
Indication of module status through floating
signaling contact
Checking the fiber-optic cable route quality:
Measurement output for optical receiver for log-
ging and validity checking of the fiber-optic
path attenuation with a voltmeter
Signaling of the fault at its location of origin, no
indication of secondary faults
High cascading depth: Line and redundant ring up to
124 OLM (only limited by monitoring times)
Large range due to use of glass fiber-optic cables in
lengths of up to 15 km
PROFIBUS OLM PROFIBUS OBT
Benefits
Existing devices with electrical interface can be con-
nected to new optical networks, as can existing bus
segments
Low-cost solution for simple optical networking
Time savings thanks to simple and fast assembly of
the fiber-optic cable connectors directly on-site.
BR_Netzloesungen_PROFIBUS_EN.book Seite 21 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
Network transitions 22
Network transitions
Network transitions between the bus systems
PC with
SlMATlC
WinAC
(proxy)
PC with
PN OPC server
WirelessHART
field device
lWLAN
RCoax Cable
lWLAN/PB
Link PN lO
(Proxy)
lE/WSN-PA
LlNK
lE/PB
Link PN lO
(Proxy)
S7-1200
lE/AS-i
LlNK
PN lO
S7-300
S7-300
S7-200
DP/AS-i F-Link
SlMOTlON C
DP/AS-lnterface Link 20E
DP/AS-i LlNK Advanced
SlNUMERlK
S7-300
S7-300
S7-400
S7-400
S7-300
PC
lndustrial
Ethernet
PROFlNET
PG
WinAC
PROFlBUS
G
_
l
K
1
0
_
X
X
_
1
0
1
3
9
AS-lnterface
Access Point
SCALANCE
W-780
BR_Netzloesungen_PROFIBUS_EN.book Seite 22 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
Network transitions 23
Network transitions between one bus system and another are
implemented using links, controllers (PLCs) or PCs.
In the case of PLCs or IPCs, this takes place via integrated in-
terfaces and communications processors (CPs). Links pass the
data through from one network to another without additional
links.
Links are independent components that form the seamless
transition between the various bus systems, e.g. between
Industrial Ethernet and PROFIBUS. For example, HMI systems
can gain easy access from Industrial Ethernet to field devices
on the PROFIBUS or on the AS-Interface.
This enables implementation of vertical integration from the
control level to the field level.
The following links are available:
IE/PB Link PN IO
for the transition from Industrial Ethernet to PROFIBUS
IWLAN/PB Link PN IO
for the transition from IWLAN to PROFIBUS
DP/AS-i LINK Advanced, DP/AS-i F LINK and DP/AS Interface
Link 20E for the transition from PROFIBUS to AS-Interface
The proxy concept simplifies integration of existing fieldbus
systems with high transparency.
On Industrial Ethernet, the proxy represents one or more
fieldbus devices (e.g. on PROFIBUS). It ensures transparent
conversion of the communication between the networks
(no tunneling of the protocols), and forwards the cyclic data,
for example, to the fieldbus devices.
As PROFIBUS master, the proxy coordinates data exchange
between the PROFIBUS stations. At the same time, it is an
Ethernet station with PROFINET communication. Proxies can
be implemented as controllers or purely as network transi-
tions. The same principle is applied when integrating
AS-Interface systems.
As well as wired proxies on Industrial Ethernet, SIMATIC NET
also offers proxies with Industrial Wireless LAN connection.
IWLAN/PB Link PN IO IE/PB Link PN IO
DP/AS-i LINK Advanced DP/AS-Interface Link 20E
BR_Netzloesungen_PROFIBUS_EN.book Seite 23 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
Communications processors for SIMATIC 24
Communications processors for SIMATIC
CPs for SIMATIC S7
The SIMATIC NET communications processors can be used for
applications in factory or process automation. Thanks to their
openness in accordance with international standards,
different components are able to work with each other. They
are characterized in particular by their ruggedness in the in-
dustrial environment.
Effectiveness and efficiency are essential in the case of solu-
tion concepts for plant components of automation tasks. This
means that very high demands are imposed on the communi-
cation performance with regard to data rates. Thanks to their
protocol preprocessing, the communications processors
maintain a constant data throughput. At a stable high level,
they offer fast response times and rule out any fluctuations in
communication performance.
The CPs perform communication tasks for the terminals and
only take up few of their resources.
The PLC as an element of communication
Programmable logic controllers (PLCs) are of key importance
in the world of automation. And industrial communication
forms the nerve center in this respect. The CPs for PLCs adopt
a key role in industrial communication.
SIMATIC NET increases availability by means of modular, net-
worked subsystems, as in the case of electrical supply, which
also takes place in individual circuits.
Communications processors for SIMATIC S7
The communications processors are all designed for use in
rough industrial environments with a wide range of tempera-
tures. The communications processors are also certified for
marine use (e.g. ABS), enabling them to be used on ships or
offshore installations.
The CPs feature S7 communication (client, server, multi-
plexing), open communication (SEND/RECEIVE) and PG/OP
communication as standard.
The CPs offer the following advantages
CPs for SIMATIC, e.g. SIMATIC S7-300/-400
By means of open communication with standards,
SIMATIC can communicate with any other device.
STEP 7
For the protocols
DP
PG/OP communication
S7 communication
Open communication
(SEND/RECEIVE)
FMS
Clock synchronization
1)
Multiprotocol:
- all protocols of a CP simultaneously operable
- several CPs operable in one S7-300 or S7-400
1)
for CP 443-5 Extended and CP 443-5 Basic
S7-400
CP 342-5
CP 342-5 FO
CP 343-5
CP 443-5 Extended
CP 443-5 Basic
SIMATIC S7-300/S7-400
S7-300
G
_
I
K
1
0
_
X
X
_
5
0
1
8
5
BR_Netzloesungen_PROFIBUS_EN.book Seite 24 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
Communications processors for SIMATIC 25
CPs for S7-300 and S7-400
The CP 342-5, CP 342-5 FO and CP 343-5 communications
processors connect SIMATIC S7-300 to PROFIBUS and
CP 443-5 Basic and Extended connect SIMATIC S7-400 to
PROFIBUS. They are PROFIBUS DP masters or slaves, or
PROFIBUS FMS masters with an electrical or optical interface
up to 12 Mbit/s.
The communications processors are easy to configure and can
be programmed using PROFIBUS.
They offer cross-network PG communication using S7 routing,
and can be replaced with the need for a programming device.
The PROFIBUS communications processors for SIMATIC
offer the following advantages:
Expansion of the process I/O to SIMATIC S7-300 using
several PROFIBUS interfaces
Flexible use of the process I/O by means of dynamic activa-
tion of DP slaves
Sub-process-oriented design of an automation solution
through the use of several CPs
Optimization of applications and a host of possible applica-
tions thanks to transmission of data with S7 communica-
tion
Extensive operator control and monitoring thanks to multi-
plex function with OP communication
Suitable for closed-loop control tasks thanks to
SYNC/FREEZE and equidistant bus cycle
Comprehensive diagnostics are provided via NCM S7,
including operating status of the CP, general diagnostics
and statistics functions, connection diagnostics, and diag-
nostics buffer. Configuration is carried out using STEP 7
Time-of-day synchronization is supported for CP 443-5
Basic and Extended
Increased plant availability thanks to redundant connec-
tion of the process I/O (e.g. ET 200M) in the SIMATIC
S7-400 H system (on CP 443-5 Basic and Extended)
Addition of distributed I/O during operation
(CP 443-5 Extended)
CP 342-5/CP 342-5 FO for S7-300 CP 443-5 for S7-400
CP 343-5 for S7-300
BR_Netzloesungen_PROFIBUS_EN.book Seite 25 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
Communications processors for SIMATIC 26
Communications processors for SIMATIC
CPs for SIMATIC S7: Overview of functions
Function overview for SIMATIC S7
PROFIBUS configuration for SIMATIC and PG/IPC
suitable
not applicable
D
P

m
a
s
t
e
r
C
l
a
s
s

2
R
e
c
e
i
v
i
n
g

s
t
a
t
i
o
n
s
S
e
n
d
i
n
g

s
t
a
t
i
o
n
s
S
e
n
d
/
R
e
c
e
i
v
e

1
)
H
i
g
h
-
a
v
a
i
l
a
b
i
l
i
t
y

c
o
m
m
u
n
i
c
a
t
i
o
n
S
t
a
n
d
a
r
d

s
y
s
t
e
m
I
n
f
o
.

/

R
e
p
o
r
t
W
r
i
t
e
R
e
a
d
D
P

s
l
a
v
e
D
P

m
a
s
t
e
r
C
l
a
s
s

1
S7 communica-
tion
Open
commu-
nication
Time
1) SDA and SDN services of PROFIBUS Layer 2 (FDL)
2) DP master or DP slave
3) S7 server only
G
_
I
K
1
0
_
X
X
_
5
0
1
0
0
2) 2)
3)
PG/OP PROFlBUS FMS PROFlBUS DP Hardware
SIMATIC S7-300
SIMATIC S7-400
CP 443-5 Basic
CP 443-5 Extended
CP 343-5
CP 342-5/
CP 342-5 FO
S7-400 with
CP 443-5 Extended
(DP master)
S7-300 with CP 342-5
(DP master)
PC with CP 5613 A2/
CP 5623
and DP Base
(DP master)
PG with STEP 7/
STEP 5 and
CP 5711
Third-party device
S5 with
IM 308-C
G
_
I
K
1
0
_
X
X
_
5
0
0
0
7
ET 200S
ET 200pro
PROFIBUS DP
BR_Netzloesungen_PROFIBUS_EN.book Seite 26 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
Communications processors for PG/PC 27
Communications processors for PG/PC
CPs for programming device/PC
For the implementation of flexible production, PCs and
programming devices (PGs) are becoming increasingly impor-
tant in the industrial sector, in addition to programmable
controllers.
Thanks to their flexible programming capability, the produc-
tion system can be quickly adapted to the automation task.
With powerful communication structures, automation
projects today can be implemented economically and with the
necessary flexibility.
PC as an element of communication
The PC assumes an important role in industrial communica-
tion. Combined with real-time applications, such as in a
Windows environment, it forms an ideal basis for visualization
(e.g. WinCC).
Together with SoftControl software the PC handles communi-
cations tasks that could only previously be solved using a pro-
grammable controller.
Note:
The necessary configuration tools for the SIMATIC NET communications
processors for PGs/PCs are included in all software packages.
The software that runs under Windows can be found on the SIMATIC NET
CD for Windows operating systems, including the associated manuals in
PDF format and comprehensive additional information on SIMATIC NET
products and communication.
Communications processors for PG/PC
Benefits
CPs for PCI, PCIe, PCMCIA, PCI 104 format or with
USB port
They offer flexibility depending on the resource
requirements in the PC
CPs with or without an internal microprocessor
Simple integration into the system environment and
office applications using open and standardized
interfaces, e.g. with the OPC server.
You will find software for the PC
products running under Windows
with the corresponding authorization
diskettes on the SIMATIC NET
software CD.
Development Kits are available for
use in various operating system
environments (e.g. for CP 5613 A2
or CP 5614 A2).
As a rule, the necessary
configuration tools are included in
the software packages.
Manuals in PDF format and
extensive supplementary
information on SIMATIC NET
products and communication can be
found in the SIMATIC NET Manual
Collection which is enclosed with
the software products.
CPs without an internal
microprocessor
CPs with an internal
microprocessor
G
_
I
K
1
0
_
X
X
_
5
0
1
8
4
CP 5512
(PC-Card,
CardBus)
CP 5613 A2
(PCI)
CP 5623
(PCIe)
CP 5611 A2 (PCI)
CP 5621 (PCIe)
CP 5613 FO
(PCI)
CP 5614 A2
(PCI)
CP 5624
(PCIe)
SIMATIC NET
Manual Collection
Software Hardware
CP 5711
(USB V2.0)
CP 5603
BR_Netzloesungen_PROFIBUS_EN.book Seite 27 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
Communications processors for PG/PC 28
Communications processors for PG/PC
CPs with an internal microprocessor
The CPs with an internal microprocessor are PCI cards and per-
mit the connection of PCs and SIMATIC PG/PCs to PROFIBUS at
up to 12 Mbit/s. This provides high-performance support for
control tasks on the PC (PCbased control, numeric control,
robot control).
These CPs can be used as:
DP master and DP slave:
CP 5614 A2 (PCI 32-bit)
CP 5624 (PCIe x1)
DP master or DP slave:
CP 5603 (PCI-104)
CP 5613 A2 (PCI 32-bit)
CP 5623 (PCIe x1)
DP master with additional optical interface
CP 5613 FO (PCI 32-bit)
In connection with the corresponding software, the CPs
support the following communication services:
PROFIBUS DP master Class 1 and 2 or DP slave according to
IEC 61158/61784
PG/OP communication with STEP 5 or STEP 7
S7 communication with S7-5613 software package
Open communication (SEND/RECEIVE) based on the FDL
interface
PROFIBUS FMS according to IEC 61158/61784 with
FMS-5613 software package
System interface for PG/PC
Benefits
Fast access to process data by means of direct access
to the dual port RAM of the hardware
Saving of slots through parallel operation as DP
master and DP slave (CP 5614 A2/CP 5624)
High computing performance in the PG/PC;
reduces workload of host CPU by preprocessing the
communication on the hardware
Use of different operating system environments;
driver as source code for porting to the operating
system environment
Use also in motion control applications;
real-time capable data exchange through constant
bus cycle time
Preventive maintenance measures
(CP 5623 A2/CP 5624);
deriving of measures by evaluating system runtime
and ambient temperature
System Hardware Software
packages
Description
SIMATIC
IPC/PG
CP 5603
(PCI-104)
CP 5613 A2
(PCI 32-bit)
CP 5613 FO
(PCI 32-bit)
CP 5614 A2
(PCI 32-bit)
CP 5623
(PCIe x1)
CP 5624
(PCIe x1)
DP-Base;
DP-5613
S7-5613
FMS-5613
For the control
application
For multiprotocol;
more than 8 stations,
several CPs in one PC
CP 5603 CP 5623/CP 5613 A2/CP 5613 FO
CP 5624/CP 5614 A2
BR_Netzloesungen_PROFIBUS_EN.book Seite 28 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
Communications processors for PG/PC 29
CPs without an internal microprocessor
The CPs without an internal microprocessor permit the con-
nection of SIMATIC PGs/PCs and PCs to PROFIBUS and to the
multipoint interface (MPI) of the SIMATIC S7.
They can be used as a DP master or DP slave:
CP 5512 (CardBus 32-bit)
CP 5611 A2 (PCI 32-bit)
CP 5621 (PCIe x1)
CP 5711 (USB V2.0)
In connection with the corresponding software, the CPs
support the following communication services:
PROFIBUS DP master Class 1 and 2 according to
IEC 61158/61784 with SOFTNET-DP software package
PROFIBUS DP slave with SOFTNET-DP Slave software
package
PG/OP communication with STEP 7
S7 communication with SOFTNET-S7 software package
Open communication (SEND/RECEIVE) on basis of the FDL
interface with SOFTNET-DP or SOFTNET-S7 software pack-
age
Communication for PG/IPC with SOFTNET for PROFIBUS
Benefits
Portability and flexibility;
Connection for portable PCs, e.g. for diagnostics and
commissioning
Easy installation and commissioning due to plug &
play technology
Economical PROFIBUS controllers and device solu-
tions
System Hardware Software
packages
Description
SIMATIC
IPC/PG/PC
CP 5512
(CardBus
32-bit)
CP 5611 A2
(PCI 32-bit)
CP 5621
(PCIe x1)
CP 5711
(USB V2.0)
SOFTNET-S7
SOFTNET-DP
SOFTNET-DP
slave
STEP 7
Monoprotocol;
up to 8 stations
For parameterizing
the existing plant
with SIMATIC S7;
for configuring the
S7-CPs
CP 5512
CP 5621
CP 5611 A2 CP 5711
PROFlBUS
PC/lPC with
CP 5611 A2/CP 5621/CP 5512
and SOFTNET for PROFlBUS
S7-300
with CP 342-5
or CP 343-5
S7-400 with
CP 443-5
S5-115U to S5-155U
with CP 5431 FMS/DP
G
_
l
K
1
0
_
X
X
_
5
0
0
3
9
BR_Netzloesungen_PROFIBUS_EN.book Seite 29 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
Communications processors for PG/PC 30
Communications processors for PG/PC
Options for use with OPC (Openness, Productivity & Collaboration)
System Integration with OPC Server
OPC is a standardized, open, and vendor-independent inter-
face that is widely used in automation.
As a rule, OPC communication consists of a server and one or
several clients. These clients can be located on the same PC or
also on other PCs in the Ethernet network.
OPC servers are available for a wide variety of protocols,
such as PROFINET, SNMP and networks, such as Ethernet.
OPC servers from SIMATIC NET have the following
functions:
Connection of automation solutions of various manufac-
turers to SIMATIC PLCs, field devices and Ethernet network
components
Servers for OPC DA, OPC DA-XML and OPC A&E-capable
clients
Configuration with STEP 7 or alternatively in free NCM PC
Programming interface for the OPC server via the Custom
Interface (C++) and "Automation Interface" (VB)
Optimized communication between OPC client and server
by grouping of variables (items)
Application examples and documentation
OPC XML DA
as Web service
SIMATIC S5
(SEND/RECEIVE only)
SNMP
OPC server
PN IO OPC server S/R OPC server
DP OPC server
FMS OPC server
DP protocol
FMS protocol
S7 OPC server
S7 communication
Open
communication
(SEND/RECEIVE)
PC/Windows PC
SIMATIC NET
OPC-Scout
WinCC
OPC-Client
Microsoft Office
OPC-Client
OPC XML
Webclient
G
_
I
K
1
0
_
X
X

5
0
7
0
0
Internet
Intranet
Industrial Ethernet
PROFINET
S7-400
S7-300
SIMATIC S5
ET 200pro
PROFIBUS
SNMP PROFINET
COM/DCOM
OPC UA
PC
PC
BR_Netzloesungen_PROFIBUS_EN.book Seite 30 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
Communications processors for PG/PC 31
OPC server for PROFIBUS:
S7 OPC server
The S7 OPC server permits communication with SIMATIC
S7-300/400 systems via the S7 protocol and with SIMATIC S5
systems via SEND/RECEIVE protocol.
DP OPC server
The DP OPC server permits access to process and diagnostics
data of the distributed IO.
FMS OPC server
The FMS OPC server offers simple communication with
FMS-capable field devices.
OPC servers for Industrial Ethernet und PROFINET:
S7 OPC server
The S7 OPC server permits communication with SIMATIC
S7-300/400 systems via the S7 protocol and with SIMATIC S5
systems via SEND/RECEIVE.
PN CBA OPC server
The PN CBA OPC server implements access to variables from
PROFINET CBA components such as the IE/PB Link.
Components created with the SIMATIC iMap engineering tool
can be used with variables and symbols defined in STEP 7.
PN IO OPC server
The PN IO OPC server permits communication with the
PROFINET IO devices via the PROFINET protocol.
This allows PROFINET functionality to be added even to
existing installations.
SNMP OPC server
The SNMP OPC server permits the diagnosis and parameteriza-
tion of any Ethernet devices, such as switches, that have
SNMP functionality (Simple Network Management Protocol).
SNMP is an open and widely used protocol for the administra-
tion of TCP/IP networks. Products with SNMP functionality
have an "SNMP agent" that makes information available in a
structured form.
www.siemens.com/snmp-opc-server
BR_Netzloesungen_PROFIBUS_EN.book Seite 31 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
Communications processors for PG/PC 32
Communications processors for PG/PC
CPs for PG/PC: Overview of functions
Function overview for PG/PC
H
a
r
d
w
a
r
e
S
o
f
t
w
a
r
e
O
p
e
r
a
t
i
o
n

s
y
s
t
e
m

(
3
2

B
i
t
)
O
P
C
P
R
O
F
I
B
U
S

D
P

5
)
P
R
O
F
I
B
U
S

F
M
S
P
G
/
O
P
S
7

c
o
m
m
u
n
i
c
a
t
i
o
n
O
p
e
n

c
o
m
m
u
n
i
c
a
t
i
o
n

7
)
W
i
n
d
o
w
s

X
P

P
r
o
W
i
n
d
o
w
s

2
0
0
3

S
e
r
v
e
r

/

2
0
0
3

R
2

S
e
r
v
e
r
W
i
n
d
o
w
s

V
i
s
t
a

B
u
s
i
n
e
s
s

/

U
l
t
i
m
a
t
e
o
t
h
e
r

o
p
e
r
a
t
i
n
g

s
y
s
t
e
m
s
D
P

M
a
s
t
e
r
C
l
a
s
s

1
D
P

M
a
s
t
e
r
C
l
a
s
s

2
D
P

s
l
a
v
e
R
e
a
d
W
r
i
t
e
I
n
f
o
/
R
e
p
o
r
t
CP 5603
(PCI-104)
CP 5613 A2
CP 5613 FO
CP 5614 A2
(PCI 32 Bit)
CP 5623
CP 5624
(PCIe x1)
CP with DP-Base
1) 4)

2)

DP-5613
4)

S7-5613
FMS-5613
DK-5613
6)

6)

6)

6)

2)
CP 5611 A2
(PCI 32 Bit)
CP 5621
(PCIe x1)
CP 5512
(CardBus 32 Bit)
CP 5711
(USB V2.0)
SOFTNET-DP
2)3)

2)3)

SOFTNET-DP Slave
2)
SOFTNET-S7
STEP 7
You can find more information on the Internet
http://www.siemens.com.simatic-net/ik-info
If you have questions on LINUX projects
please contact I&S
E-mail: it4industry@siemens.com
1) Included in scope of supply of the hardware
2) DP master and DP slaves cannot be operated simultaneously
3) Master Class 1 and Master Class 2 cannot be operated simultaneously
on one CP
4) DP-Base and DP-5613 cannot be operated simultaneously
5) DP master and DP slave only possible with CP 5614/CP 5624
6) With porting via DK-5613
7) SEND/RECEIVE based on the FDL interface
on SIMATIC NET-
CD Edition 2008
suitable
not applicable
BR_Netzloesungen_PROFIBUS_EN.book Seite 32 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
Connection options 33
Connection options
Electrical and optical networking
The options for connecting an electrical or optical network to a
CP are implemented with the different network components.
Typical connection for electrical networking with OBT
Typical connection for electrical networking with
PROFIBUS FastConnect RS485 bus connector
PROFIBUS module
e.g. CP 5613 A2
PROFIBUS FC
Bus connector
RS 485 plug 180
12M bus terminal
For loop through
of bus nodes
to PROFIBUS
PROFIBUS FC
Bus cable
PROFIBUS FC
Bus cable
G
_
I
K
1
0
_
X
X

5
0
0
5
5
PROFIBUS FC
Bus connector
RS 485
G
_
I
K
1
0
_
X
X
5
0
1
7
0
SIMATIC S7-300
PROFIBUS FC
Standard Cable
CP 342-5
BR_Netzloesungen_PROFIBUS_EN.book Seite 33 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
Connection options 34
Connection options
Electrical and optical networking
Typical connection for optical networking with PROFIBUS OLM
Typical connection for optical networking Typical connection for optical networking
with plastic fiber-optic cable and Simplex connector with fiber-optic cable and BFOC connector
Typical connection for an intrinsically-safe network
PROFIBUS module
e.g. CP 5613 A2
PROFIBUS FC
Bus connector
RS 485 plug 180
PROFIBUS FC
RS 485 bus connector
Preassembled
glass FOC
G
_
I
K
1
0
_
X
X

5
0
0
5
6
PROFIBUS FC
Standard Cable
PROFIBUS OLM
PROFIBUS-
module, e.g.
CP 5613 FO
FOC with Simplex connector
PROFIBUS PCF
or plastic fiber-optic cable
CP 342-5 FO
(IM 153-2 FO,
IM 151,
BM 143 DESINA)
G
_
I
K
1
0
_
X
X

5
0
0
6
1
Fiber-optic cable with BFOC connector
G
_
I
K
1
0
_
X
X

5
0
0
1
4
OLM OLM
DP/PA coupler Coupler
FC Process
Cable
G
_
I
K
1
0
_
X
X

5
0
0
5
7
TAP TAP TAP
PROFIBUS PA
SITRANS P SITRANS F SITRANS P
BR_Netzloesungen_PROFIBUS_EN.book Seite 34 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
PROFIBUS 35
PROFIBUS

Technology components
ASICs for PROFIBUS
enable third-party manufacturers to connect their devices and
systems simply to the PROFIBUS fieldbus.
ASICs enable, for example, the short response times on
PROFIBUS DP that are required at transfer rates of up to
12 Mbit/s.
Different ASICs and connections are available for the different
functional requirements such as master devices, or simple or
intelligent slaves.
Advantages of the PROFIBUS components at a glance
Integrated use in factory and process automation
(PROFIBUS PA)
Problem-free connection of components from
different manufacturers, standardized in accordance
with IEC 61158/61784 and GB/T 20540.1-2006 /
GB/T 20540.6-2006 (Chinese national standard)
Investment security due to compatible developments
High degree of investment protection:
existing systems can be extended and integrated into
new PROFINET systems
Connection to AS-Interface and IO-Link
Flexible use
Line, tree and ring topologies
Configuration, commissioning, and troubleshooting
can be carried out from any location.
This results in user-defined communication relation-
ships that are very versatile, simple to implement, and
easy to change.
High availability through ring redundancy with OLM
WLAN interfacing of PROFIBUS to PROFINET
Fail-safe communication with PROFIsafe
Industrial compatibility
Rugged design
Modular design for standard rail mounting
Diagnostics with network components
Fast fault localization by means of signaling contact,
LEDs, measuring sockets, and test devices
Continuous monitoring of network components
through a simple and effective signaling concept
Permanently secure and quick-assembly
plug-in connectors
Fast assembly and startup on site with the help of the
FastConnect wiring system
Plug-in connectors for degree of protection IP20 and
IP65
Different bus cables for different applications
Time savings when commissioning thanks to pre-
assembled cables
Fiber-optic networking (plastic/glass) for short and
long distances
BR_Netzloesungen_PROFIBUS_EN.book Seite 35 Montag, 22. Mrz 2010 11:36 11
Siemens AG 2010
The information provided in this brochure contains descriptions
or characteristics of performance which in case of actual use do
not always apply as described or which may change as a result
of further development of the products. An obligation to provide
the respective characteristics shall only exist if expressly agreed
in the terms of contract. Availability and technical specifications
are subject to change without notice.
All product designations may be trademarks or product names
of Siemens AG or supplier companies whose use by third
parties for their own purposes could violate the rights of
the owners.
Get mor information
SIMATIC NET:
www.siemens.com/automation/simatic-net
Information material available for downloading:
www.siemens.com/simatic/printmaterial
SIMATIC Guide Manuals:
www.siemens.com/simatic-docu
Service & Support:
www.siemens.com/automation/service&support
SIMATIC NET contacts:
www.siemens.com/automation/partner
Industry Mall for electronic ordering:
www.siemens.com/industrymall
Siemens AG
Industry Sector
Sensors and Communication
Postfach 48 48
90327 NRNBERG
GERMANY
Subject to change without prior notice
Order No.: 6ZB5530-0AQ02-0BB3
3P.8201.48.02 / Dispo 26000
BR 0310 3.0 WEN 36 En
Printed in Germany
Siemens AG 2010
www.siemens.com/automation