MW 33 POWER MANAGEMENT RELAY SETTINGS

Relay Programming Default Setting Variable Value Units


Tsyn Fn In Un TDR Fn 1f t1f R1f Fn 2f t2f R2f Un 1u t1u R1u Un 2u t2u R2u PF TPF RPF Q/P= tQ/P RQ/P ts 1p 1p 1p t1p R1p 2p 2p 2p t2p R2p 1q 1q 1q t1Q Dis 50 500 100 60 + 1.00 1.0 0.1 +/0.5 2.0 0.2 + 20 1.0 5 +/10 2.0 3 Lg 0.90 3.0 0.95 0.50 10.0 0.45 30 +/> 110 2 3 +/< 90 2 3 +/> 120 2 m Hz Ap V s 1f Hz s Hz 2f Hz s Hz 1u %Un s %Un 2u %Un s %Un s s s %Sn s %Sn %Sn s %Sn %Sn s

Description
Sync period of the internal clock calendar Mains Frequency Rated primary current of phase CTs Rated secondary phase-to-phase voltage of systems P.T.s Time interval for Demand Recording Operation mode of 1st frequency element (1f) Trip differential level of 1st frequency element Trip time delay of (1f) Reset differential of (1f) Operation mode of 2nd frequency element (2f) Trip differential level of 2nd frequency element Trip time delay of (2f) Reset differential of (2f) Operation mode of 1st voltage element (1u) Trip differential level of 1st frequency element Trip time delay of (1u) Reset differential of (1u) Operation mode of 2nd voltage element (2u) Trip differential level of 2nd frequency element Trip time delay of (2U) Reset differential of (2U) Operation mode of Power Factor control element (PF<) Operation level of (PF<) Trip time delay of (PF<) Reset level of (PF<) Operation level of the Q/P (tg ) element Q/P> (= 6 - 85) Trip time delay of (Q/P>) Reset level of (Q/P>) Start inhibition time Operation direction of the 1st Active Power element (1p) Operation mode of the (1p) element Operation level of (1p) Trip time delay of (1p) Reset differential of (1p) Operation direction of the 2nd Active Power element (2p) Operation mode of the (2p) element Operation level of (2p) Trip time delay of (2p) Reset differential of (2p) Operation direction of the 1st Reactive Power element (1q) Operation mode of the (1q) element Operation level of (1q) Trip time delay of (1q)

Actual Setting Variable Value Units


Tsyn Fn In Un TDR Fn 1f t1f R1f Fn 2f t2f R2f Un 1u t1u R1u Un 2u t2u R2u PF tPF RPF Q/P = tQ/P RQ/P ts 1p 1p 1p t1p R1p 2p 2p 2p t2p R2p 1q 1q 1q t1Q Dis 50 4000 110 1689 2.4 1 0.01 Dis 4 4.5 0.1 Dis 20 3 5 Dis 10 2 3 Dis 0.9 3 0.95 Dis 10 0.45 30 > 7 1 1 > 2 1 1 + Dis 120 2 m Hz Ap V s 1f Hz s Hz 2f Hz s Hz 1u %Un s %Un 2u %Un s %Un s s S %Sn s %Sn %Sn s %Sn %Sn s

R1Q 2q 2q 2q t2Q R2Q B1f B2f B1u B2u BPF BQ/P B1p B2p B1q B2q NodAd

5 + < 80 3 10 % OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF 1

%Sn %Sn s Sn -

Reset differential of (1q) Operation direction of the 2nd Reactive Power element (2q) Operation mode of the (2q) element Operation level of (2q) Trip time delay of (2q) Reset differential of (2q) Blocking Input at term. (1-2) BI blocks the output relay associated to the funct. 1f Blocking Input at term. (1-2) BI blocks the output relay associated to -the funct. 2f Blocking Input at term. (1-2) BI blocks the output relay associated to the funct. 1U Blocking Input at term. (1-2) BI blocks the output relay associated to the funct. 2U Blocking Input at term. (1-2) BI blocks the output relay associated to the funct. PF Blocking Input at term. (1-2) BI blocks the output relay associated to the funct. Q/P Blocking Input at term. (1-2) BI blocks the output relay associated to the funct. 1P Blocking Input at term. (1-2) BI blocks the output relay associated to the funct. 2P Blocking Input at term. (1-2) BI blocks the output relay associated to the funct. 1Q Blocking Input at term. (1-2) BI blocks the output relay associated to the funct. 2Q Identification number for connection on serial communication bus

R1Q 2q 2q 2q t2Q R2Q B1f B2f B1u B2u BPF BQ/P B1p B2p B1q B2q NodAd

5 Dis 200 3 10 OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF 1

%Sn %Sn s %Sn -

Value Units Description Variable Value Units

Configuration of output relays Default Setting Protective Output Element Relay


1u 2u 1f 2f PF> Q/P 1p 2p 1q 2q 1tr 2tr 3tr 4tr 1st voltage element operates relays 2nd voltage element operates relays 1st frequency element operates relays 2nd frequency element operates relays Power Factor element operates relays Q/P element operates relays 1st active power element operates relays 2nd active power element operates relays 1st reactive power element operates relays 2nd reactive power element operates relays Reset time delay of output relay R1 As above for relay R2 As above for relay R3 As above for relay R4

Actual Setting Protective Output Element Relay


1u 2u 1f 2f PF> Q/P 1p 2p 1q 2q 1tr 2tr 3tr 4tr 1 2 3 3 3 Aut. Aut. Aut. Aut. Aut. 4 -

3s Aut. Aut. Aut. Aut.

UFD 34 MULTIFUNCTION FREQUENCY RELAY SETTINGS


Relay Programming Default Setting Variable Valu Unit e
Fn UnP UnS Ncy Fn 1f 1t 1&f 1& Fn 2f 2t 2&f 2& Fn 3f 3t 3&f 3& Fn 4f 4t 4&f 4& 1df 1f 2df 2f E< 50 10 100 3 0.50 2 OFF 1 1 1.5 OFF 2 1.5 1 1f 0.75 1.50 0.75 2f 0.5 -/+ 0.2 -/+ 0.5 30 Hz kV V 1f Hz s s 2f Hz s s 3f Hz s s 4f Hz s s Hz/s Hz/s %En

Description
System frequency Rated primary phase-to-phase voltage of system's P.Ts. Rated secondary phase-to-phase voltage of system's P.Ts. Number of cycles evaluated for f and df/dt tripping Operation mode of the first frequency control element : Trip differential level of the 1st frequency control element Trip time delay of the first freq. element without df/dt control The first frequency element can be controlled Trip time delay of the first frequency element when df/dt control is operating Operation mode of the second frequency control element : Trip differential level of the 2nd frequency control element Trip time delay of the 2nd frequency element without df/dt control The second frequency element can be controlled Trip time delay of the second frequency element when df/dt control is operating Operation mode of the third frequency control element : Trip differential level of the 3rd frequency control element Trip time delay of the 3rd frequency element without df/dt control The third frequency element can be controlled Trip time delay of the third frequency element when df/dt control is operating Operation mode of the fourth frequency control element Trip differential level of the 4th frequency control element Trip time delay of the 4th frequency element without df/dt control The fourth frequency element can be controlled Trip time delay of the fourth frequency element when df/dt control is operating Operation mode of the first df/dt element Trip level of the first df/dt element Operation mode of the second df/dt element Trip level of the second df/dt element Undervoltage operation lock-out

Actual Setting Variable Value Unit


Fn UnP UnS Ncy Fn 1f 1t 1&f 1& Fn 2f 2t 2&f 2& Fn 3f 3t 3&f 3& Fn 4f 4t 4&f 4& 1df 1f 2df 2f E< 50 11 110 3 3 99.99 1f 1 2.4 2 OFF 99.99 2.4 3 OFF 99.99 Dis 1.5 0.75 OFF 0.5 0.8 2.5 30 Hz kV V 1f Hz s s 2f Hz s s 3f Hz s s 4f Hz s s Hz/s Hz/s %En

Un 1u t1u Un 2u t2u e de NodAd

-/+ 10 1.0 + 20 2.0 50 +/1

1u %Un s 2u %Un s Vs/s -

Operation mode of the 1st voltage control element Trip differential level of the 1st voltage control element Trip time delay of 1st voltage control element Operation mode of the 2nd voltage control element Trip differential level of the 2nd voltage control element Trip time delay of 2nd voltage control element Trip level of the element de/dt Operation of the function for de/dt Identification number for connection on serial communication bus

Un 1u t1u Un 2u t2u e de NodAd

Dis 10 1 Dis 20 2 50 Dis 1

1u %Un s 2u0 %Un s Vs/s -

Configuration of Output Relays Default Setting Protective Output Element Relays


1f 1t/& 2f 2t/& 3f 3t/& 4f 4t/& E< 1f 2f 1u t1u 2u t2u E 1tr 2tr 3tr 4tr Atr Btr Ctr Dtr Etr Ftr Gtr Htr Itr Jtr Ktr Ltr D1f D2f D2e 1 - - - 2 - - 3 - - - - - - 2 - 2 2 Aut. Aut. Aut. Aut. Aut. Aut. Aut. Aut. Aut. Aut. Aut. Aut. Aut. Aut. Aut. Aut. - - - 4 4 4 -

Description
Instantaneous element of 1st frequency As above, time delayed element. Instantaneous element of 2nd frequency level As above, time delayed element. Instantaneous element of 3rd frequency level As above, time delayed element. Instantaneous element of 4th frequency level 4 As above, time delayed element. Voltage lock-out element. Element of 1st df/dt level operates relays Element of 2nd df/dt level operates relays Instantaneous element of 1st voltage level As above, time delayed element instantaneous element of 2nd voltage level As above, time delayed element Element de/dt operates relays Reset time delay of output relay R1 As above for relay R2. As above for relay R3. As above for relay R4. As above for relay RA. As above for relay RB. As above for relay RC. As above for relay RD. As above for relay RE. As above for relay RF. As above for relay RG. As above for relay RH. As above for relay RI. As above for relay RJ. As above for relay RK. As above for relay RL. Blocking input D1 Blocking input D2 Blocking input D2

Actual Setting Protective Output Relays Element


1f 1t/& 2f 2t/& 3f 3t/& 4f 4t/& E< 1f 2f 1u t1u 2u t2u e 1tr 2tr 3tr 4tr Atr Btr Ctr Dtr Etr Ftr Gtr Htr Itr Jtr Ktr Ltr D1f D2f D2e 1 1 1 Aut. Aut. Aut. Aut. Aut. Aut. Aut. Aut. Aut. Aut. Aut. Aut. Aut. Aut. Aut. Aut. 2 4 3 -

D3u

Blocking input D3

D3u