STANDARDS AUSTRALIA/STANDARDS NEW ZEALAND Amendment No. 1 to AS/NZS 3008.1.1:2009 Electrical installationsSelection of cables Part 1.1: Cables for alternating voltages up to and including 0.6/1 kVTypical Australian installation conditions
CORRECTION The 2009 edition of AS/NZS 3008.1.1 is amended as follows; the amendments should be inserted in the appropriate places. SUMMARY : This Amendment applies to Clauses 3.3.2 and 4.4, Tables 3(1), 6, 7, 8, 9, 10, 12, 13, 15, 16 and 34, and Appendices A and D. Published on 15 August 2011. Approved for publication in New Zealand on behalf of the Standards Council of New Zealand on 29 July 2011.
AMDT No. 1 AUG 2011
Clause 3.3.2 Delete the Clause and replace with the following: 3.3.2 Flexible cords and cables 3.3.2.1 Used for installation wiring The determination of current-carrying capacity of flexible cords and cables used for installation wiring shall be as given in Tables 4 to 15 and 17. 3.3.2.2 Other than installation wiring The determination of current-carrying capacity of flexible cords and cables used for other than installation wiring shall be as follows: (a) General Except as provided in Item (b), the current-carrying capacity of flexible cords and cables not used as installation wiring shall be determined from Tables 16 and 17. The current-carrying capacity of flexible cables shall be determined from Tables 4 to 15. Connection of equipment Where a flexible cord is (i) (ii) used for the connection of equipment to the installation wiring by means of a plug and socket; and the equipment comes within the scope of associated Standards;
(b)
Table 3(1) Delete the heading of Column 6 and replace with Derating table.
Table 7 Delete the first sentence of Note 6 and replace with the following:
These ratings are based on 40C ambient air temperature and 25C ambient soil temperature. For other conditions, see Clause 3.5.3.
Table 16 In Note 3, delete the second and third sentences and replace with the following:
Where flexible cords are used as installation wiring, the current ratings are given in Tables 4 to 15 and 17. (Refer to Clause 3.3.2) .
Clause 4.4, Equation 4.4(1) Delete the notation to the equation and replace with the following: I0 = operating current, in amperes IR = rated current given in Tables 4 to 21, in amperes (For cable affected by the presence of certain external influences as detailed in Clauses 3.5.2 to 3.5.8, it will be necessary to correct the rated current given in Tables 4 to 21 by the application of an appropriate rating factor or factors obtained from Tables 22 to 29.) 0 = operating temperature of cable when carrying I0, in degrees Celsius R = operating temperature of the cable when carrying IR, in degrees Celsius A = ambient air or soil temperature, in degrees Celsius
Appendix A, Paragraph A1.2(a) 1. 2. Item (a), second line, delete 510 A and replace with 492 A. Delete 510 5 0.6 = 1530 A and replace with 492 5 0.6 = 1476 A.
Paragraph A1.2(b) 1. 2. Item (b), second line, delete 510 A and replace with 492 A. Delete 510 4 0.79 = 1611.6 A and replace with 492 4 0.79 = 1554.7.
Paragraph A1.2(c) 1. 2. Item (c), second line, delete 560 A and replace with 553 A. Delete 560 4 0.74 = 1657.6 A and replace with 553 4 0.74 = 1636.9 A.
Paragraph A1.2(d) 1. 2. Item (d), second line, delete 590 A and replace with 593 A. Delete 590 3 0.87 = 1540 A and replace with 593 3 0.87 = 1547.7 A.
Paragraph A2.2 1. 2. 3. Second paragraph, second line, delete 26 A and replace with 28 A and delete 30 A and replace with 32 A. Third paragraph, delete 26 0.65 = 16.9 A and replace with 28 0.65 = 18.2 A. Fourth paragraph, delete 30 0.57 = 17.1 A and replace with 32 0.57 = 18.2 A.
Appendix D, Table D1 Delete heading of Table D1 and replace with the following: LOAD CURRENT SHARING CONFIGURATION