You are on page 1of 70

Packaged Rooftops

Voyager, R-410A
12-25 Tons 60 Hz

Packaged Cooling (TC*)

Packaged Gas/Electric (YC*)

July 2007

RT-PRC028-EN

Introduction Preface and Warnings and Cautions


Packaged Rooftop Air Conditioners
Through the years, Trane has designed and developed the most complete line of Packaged Rooftop products available in the market today. Trane was the first to introduce the Micromicroelectronic unit controlsand has continued to improve and revolutionize this design concept. The ReliaTel control platform offers the same great features and functionality as the original Micro, with additional benefits for greater application flexibility. Voyager continues to provide the highest standards in quality and reliability, comfort, ease of service, and the performance of Trane light commercial products. Trane customers demand products that provide exceptional reliability, meet stringent performance requirements, and are competitively priced. Trane delivers with Voyager. Voyager features cutting edge technologies: reliable compressors, Trane engineered ReliaTel controls, computer-aided run testing, and Integrated Comfort Systems. So, whether youre the contractor, the engineer, or the owner you can be certain Voyager Products are built to meet your needs. Its Hard To Stop A Trane.

Packaged Gas/Electric

Packaged Cooling

2006 American Standard Inc. All rights reserved

RT-PRC028-EN

Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Jobsite Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Typical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

RT-PRC028-EN

Features and Benefits


Standard Features
2 throwaway filters provided on 12-25 ton units 5-year Limited Compressor Warranty (12-17 tons); 1 year on 20 & 25 tons 5 year Limited Heat Exchanger (12 - 17 tons) 1 year on 20 & 25 tons) 1-year Limited Parts Warranty Anti-Short Cycle Timer Belt Drive Motors Colored and Numbered Wiring Crankcase Heaters Dedicated Airflow Easy Access Low Voltage Terminal Board (LTB) Foil-Faced and Edge Captured Insulation High Efficiency Drum and Tube Heat Exchanger High Efficiency Gas Heat with Hot Surface Ignition High Pressure Cutout IAQ Sloped Condensate Drain Pan Liquid Line Refrigerant Drier Low Ambient Cooling to 0F Operating Charge of R-410A Patented Hybrid Condenser Coil for easy cleaning Provisions for Through-the-Base Gas and Condensate Drain Connections Quick Access Panels Quick Adjust Idler Arm Pulley ReliaTel Microprocessor Controls Single Point Power Single Side Service Standardized Components U-shaped Airflow Pattern

Options
Factory Installed Options15* 2 Pleated Filters6 Black Epoxy Pre-Coated Coils6 Differential Pressure Switches High Efficiency Motors6 Hinged Access Doors Novar Return Air Sensor8 Novar Unit Controls7 Powered or Unpowered Convenience Outlet5 Stainless Steel Heat Exchanger with 10 year warranty8 Supply and/or Return Air Smoke Detector3,12 Through the Base Electrical Access Through the Base Electrical with Circuit Breaker13,14 Through the Base Electrical with Disconnect Switch9,13,14

*Most Factory Installed Options (FIOPS) available for Downflow Air Discharge units only. Please verify with ordering system for availability. Explanation of Notes 1-17 located on page following Model Number Description. Field Installed Options CO2 Sensing Digital Display Zone Sensor Dual Thermistor Remote Zone Sensor Economizer (Horizontal) High Altitude Kit High and Low Static Drive Kits Humidity Sensor Low Static Drive LP Conversion Kit Manual Outside Air Damper Motorized Outside Air Dampers Powered Exhaust Quick Start Kit ReliaTel Options Module11 Remote Potentiometer Roof Curb (Downflow Only) Thermostat Ventilation Override Accessory3 Zone Sensors and Remote Zone Sensors

Factory* or Field Installed Options15 Barometric Relief Clogged Filter/Fan Failure Switch3,6 Discharge Air Sensing Kit3,6 Economizer (Downflow)1 Electric Heaters6,10,14 LonTalk Communications Interface (LCI)6 Oversized Motors6 Phase Monitor Reference or Comparative Enthalpy4,6 Tool-less Hail Guards6 Trane Communications Interface (TCI)2,6

Other Benefits
Cabinet design ensures water integrity Ease of Service, Installation and Maintenance Mixed model build enables fastest in the industry ship cycle times Outstanding Airflow Distribution ReliaTel Controls benefits Unmatched Product Support

RT-PRC028-EN

Features and Benefits

Unmatched Support
Trane Sales Representatives are a Support Group that can assist you with: Product Application Service Training Special Applications Specifications Computer Programs and much more

Controls ReliaTel
ReliaTel microprocessor controls provide unit control for heating, cooling and ventilating utilizing input from sensors that measure indoor and outdoor temperature and other zone sensors. ReliaTel also provides outputs for building automation systems and expanded diagnostics. For a complete list of ReliaTel offerings, refer to the Other Benefits section within the Features and Benefits section of this catalog.

Foil Faced Insulation


All panels in the evaporator section of the unit have cleanable foilfaced insulation. All edges are either captured or sealed to ensure no insulation fibers get into the airstream.

Conversionless Units
The dedicated design units (either downflow or horizontal) require no panel removal or alteration time to convert in the field a major cost savings during installation. Horizontal units come complete with duct flanges so the contractor doesnt have to field fabricate them. These duct flanges are a time and cost saver.

Standard Features
Anti-Short Cycle Timer (Standard with ReliaTel)
Provides a 3 minute minimum ON time and 3 minute OFF time for compressors to enhance compressor reliability by assuring proper oil return.

Heat Exchanger - Drum and Tube


The cabinet features a drum and tube heat exchanger that is manufactured using aluminized steel with stainless steel components for maximum durability. The requirement for cycle testing of heat exchangers is 10,000 cycles by ANSI Z21.47. This is the standard required by both UL and AGA for cycle test requirements. Trane requires the design to be tested to 2 times this current standard. The drum and tube design has been tested and passed over 150,000 cycles, which is over 15 times the current ANSI cycling requirements.

Colored And Numbered Wiring


Save time and money tracing wires and diagnosing the unit.

Crankcase Heaters
These band or insertion heaters provide improved compressor reliability by warming the oil to prevent migration during off-cycles or low ambient conditions. These are standard on all Voyager models.

Compressors
Voyager contains the best compressor technology available to achieve the highest possible performance. Dual compressors are outstanding for humidity control, light load cooling conditions and system back-up applications. Dual compressors are available on all models.

Efficiencies
Standard or High Efficiency Cooling available.

Easy Access Low Voltage Terminal Board


Voyagers Low Voltage Terminal Board is external to the electrical control cabinet. It is extremely easy to locate and attach the thermostat wire and test operation of all unit functions. This is another cost and time saving installation feature.

Forced Combustion Blower Negative Pressure Gas Valve Hot Surface Ignitor Heat Exchanger

The negative pressure gas valve will not allow gas flow unless the combustion blower is operating. This is one of our unique safety features. The forced combustion blower supplies pre-mixed fuel through a single stainless steel burner screen into a sealed drum where ignition takes place. It is more reliable to operate and maintain than a multiple burner system. The hot surface ignitor is a gas ignition device which doubles as a safety device utilizing a continuous test to prove the flame. The design is cycle tested at the factory for quality and reliability. 5

Condenser Coil
Voyager boasts a patent-pending 1+1+1 condenser coil, permanently gapped for easy cleaning.

RT-PRC028-EN

Features and Benefits

Our gas/electric rooftops exceed all California seasonal efficiency requirements and perform even better than the California NOx emission requirements.

Single Side Service


Single side service is standard on all units.

reduces costs, assures proper mounting and provides the opportunity to upgrade to unit circuit breaker protection.

Sloped Drain Pans


Every Voyager unit has a noncorrosive, sloped drain pan made of pre-painted steel and standard on all units.

Hinged Access Doors


These doors permit easy access to the filter, fan/ heat, and compressor/ control sections. They reduce the potential roof damage from screws or sharp access door corners.

Low Ambient Cooling


All Voyager microprocessor units have cooling capabilities down to 0F as standard.

Low Voltage Connections


The wiring of the low voltage connections to the unit and the zone sensors is as simple as 1-1, 2-2, and 3-3. This simplified system makes it easy for the installer to wire.

Standardized Components
Components are placed in the same location on all Voyager units. Familiarize yourself with one Voyager and you are familiar with every Voyager. Due to standardized components throughout the Voyager line, contractors/owners can stock fewer parts.

Motors
Factory or field installed oversized motors available for high static applications are available. High Efficiency motors are also available with efficiency ratings from 86.5 up to 91.0. It is not available for all models.

Variety of Options*
Factory Installed Options
Black Epoxy Pre-Coated Coils Motors
All indoor fan motors are belt drive as standard. The pre-coated coils are an economical option for protection in mildly corrosive environments.

Novar Unit Controls


Novar 3051 and 2024 are available for Voyager Cooling and Gas/Electric models.

Pressure Cutouts
Low and high pressure cutouts are standard on all Voyager models.

Circuit Breaker (Required with Through- the-Base Electrical)


This option is a factory installed thermal magnetic, molded case, HACR Circuit Breaker with provisions for through the base electrical connections. Available on all models.

Powered or Unpowered Convenience Outlet


This option is a GFCI, 120v/15amp, 2 plug, convenience outlet, either powered or unpowered. This option can only be ordered when Through the Base Electrical with either the Disconnect Switch or Circuit Breaker option is ordered. This option is available on all models.

Quick-Access Panels
Remove three or more screws for access to the standardized internal components and wiring.

Disconnect Switch (Required with Through-the-Base Electrical)


Factory installed 3-pole, molded case, disconnect switch with provisions for through the base electrical connections are available. Available on all models. Codes require a method of assured unit shutdown for servicing. Fieldinstalled disconnects sometimes interfere with service access. Factory installation of unit disconnects

Stainless Steel Heat Exchanger


The optional stainless steel heat exchanger is constructed of 304 stainless steel. It is resistant to corrosion and oxidation and easy to clean. The high strength to weight ratio allows for high ventilation rates with gas units. With this option, a 10-year stainless steel heat exchanger warranty is standard.

QuickAdjust Slider Plate


With the Quick-Adjust Slider Plate, the belt and sheaves can be quickly adjusted without moving the mounted fan motor. The result is a major savings in time and money.

Single Point Power


A single electrical connection powers the unit.

RT-PRC028-EN

Features and Benefits

Supply and/or Return Air Smoke Detector


With this option installed, if smoke is detected, all unit operation will be shut down. Reset will be manual at the unit. Return Air Smoke Detectors require minimum allowable airflow when used with certain models.

unpowered means of relieving excess building pressure.

Phase Monitor
Phase monitor shall provide 100% protection for motors and compressors against problems caused by phase loss, phase imbalance, and phase reversal. Phase monitor is equipped with an LED that provides an ON or FAULT indicator.

Clogged Filter/Fan Failure Switch


A dedicated differential pressure switch is available to achieve active fan failure indication and/or clogged filter indication. These sensors allow a zone sensor service light or Integrated Comfort System to indicate a dirty filter or a fan thats not working. The field installation charges for these valuable feedback devices often eliminate them from consideration. Factory installation can make such features a good investment.

Reference or Comparative Enthalpy


Measures and communicates humidity while maximizing comfort control.

Thermal Expansion Valve


Available for a wider range of applications. This is available on high efficiency models.

Tool-less Hail Guards


Tool-less, hail protection quality coil guards shall be either factory or fieldinstalled for condenser coil protection. This option protects the condenser coil from vandalism and/ or hail damage.

Discharge Air Sensing Kit


Provides true discharge air sensing in heating models. The kit is functional only with the ReliaTel Options Module.

Through-the-Base Electrical Utility Access


An electrical service entrance shall be provided allowing electrical access for both control and main power connections inside the curb and through the base of the unit. Option will allow for field installation of liquid-tight conduit and an external field installed disconnect switch. Factory provided through the base openings simplify wiring and piping. Because these utility openings frequently minimize the number of roof penetrations, the integrity of roofing materials is enhanced.

Electric Heaters
Electric heat modules are available within the basic unit. If ordering the Through the Base Electrical option with an Electrical Heater, the heater must be factory installed.

Fresh Air Options Dampers and Economizer


0 - 25% manual or 0 - 50% motorized outside air hoods are available. Economizers are equipped with either dry bulb or reference or comparative enthalpy sensing. These economizers provide free cooling as the outdoor temperature and/or humidity decreases. Correctly installed, they offer a valuable energy savings. Factory-installed economizers save time and ensure proper installation.

Trane Communication Interface (TCI)


Available factory or field installed. This module when applied with the ReliaTel easily interfaces with Tranes Integrated Comfort System. *Refer to Model Number Description for option availability.

Two-Inch Pleated Filters


2 pleated media filters are offered as an option on all Voyager units for jobs with enhanced Indoor Air Quality (IAQ) requirements. *Refer to Model Number Description for option availability.

Field Installed Options*


CO2 Sensing
The CO2 sensor has the ability to monitor space occupancy levels within the building by measuring the parts per million of CO2 (Carbon Dioxide) in the air. As the CO2 levels increase, the outside air damper modulates to meet the CO2 space ventilation requirements. The CO2 sensor kit is available as a field installed accessory.

LonTalk Communications Interface


The LonTalk communications interface allows the unit to communicate as a TracerLCI-V device or directly with generic LonTalkNetwork Building Automation System Controls.

Factory or Field Installed Options*


Barometric Relief
Designed to be used on downflow units, barometric relief is an

Oversized Motors
Factory or field installed oversized motors available for high static applications.

RT-PRC028-EN

Features and Benefits

Digital Display Zone Sensor


The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone sensors. This sensor should be utilized with ReliaTel controls.

Static Drive Accessories


Available on many models, this high and low static drive accessories extend the capability of the standard motor. Avoid expensive motors and operating costs by installing this optimized sheave accessory.

features enhanced by a variety of factory and field installed options, multiple control options, rigorously tested proven designs and superior product and technical support.

ReliaTel Controls
ReliaTel controls provide unit control for heating, cooling and ventilating utilizing input from sensors that measure outdoor and indoor temperature.

Dual Thermistor Remote Zone Sensor


This sensor will reduce the total number of remote sensors to obtain space temperature averaging. This sensor should be utilized with ReliaTel controls.

Ventilation Override Accessory


With the Ventilation Override Accessory installed, the unit can be set to transition to up to 3 different pre-programmed sequences for Smoke Purge, Pressurization, and Exhaust. The transition occurs when a binary input on the RTOM is closed (shorted). This would typically be a hard wired relay output from a smoke detector or fire control panel. The ventilation override kit is available as a field installed accessory.

High Altitude Kit


Previously a Canadian Agency requirement for units applied about 2000 feet, it is not required by the U.S. Domestic contractors should consult with local authority on best practice. Devates gas orifices by 10%.

ReliaTel Control Logic Enhances Quality and Reliability prevents the unit from short cycling, considerably improving compressor life. ensures that the compressor will run for a specific amount of time which allows oil to return for better lubrication, enhancing the reliability of the compressor. Voyager with ReliaTel reduces the number of components required to operate the unit, thereby reducing possibilities for component failure. ReliaTel Makes Installing and Servicing Easy ReliaTel eliminates the need for field installed anti-shortcycle timer and time delay relays. ReliaTel controls provide these functions as an integral part of the unit. The contractor no longer has to purchase these controls as options and pay to install them.

Humidity Sensor/Humidistat
Used in conjunction with our Dehumidification (Hot Gas Reheat) units to provide outstanding humidity control and comfort. Humidity sensors can be wall or duct mounted and set for levels between 40% and 60%.

Zone Sensors/Thermostats
Available in programmable, automatic and manual styles. *Refer to Model Number Description for option availability.

Other Benefits
Airflow Distribution
Airflow is outstanding. The Voyager can replace an older machine with old ductwork and, in many cases, improve the comfort through better air distribution. The U-shaped airflow allows for improved static capabilities.

LP Conversion Kit
Provided for field conversion of gas/ electric units from Natural gas to Propane.

Powered Exhaust Option


This option is available on downflow units and provides exhaust of the return air, when using a downflow economizer, to maintain proper building pressurization. Great for relieving most building overpressurization problems.

Cabinet Integrity
For added water integrity, Voyager has a raised 1 1/8" lip around the supply and return of the downflow units to prevent water from blowing into the ductwork.

Remote Potentiometer
When properly installed in the economizer control circuitry, this accessory provides a remote variable resistance to enable the operator to adjust the minimum damper position.

Easy to Install, Service and Maintain


Because todays owners are very cost-conscious when it comes to service and maintenance, the Trane Voyager was designed with direct input from service contractors. This valuable information helped to design a product that would get the serviceman off the job quicker and save the owner money. Voyager does this by offering outstanding standard The wiring of the low voltage connections to the unit and the zone sensors is as easy as 1-1, 2-2, and 3-3. This simplified system makes wiring easier for the installer.

Roof Curbs
Available for downflow units. Only two roof curbs for the entire Voyager line simplifies curb selection.

RT-PRC028-EN

Features and Benefits

ReliaTel Makes Testing Easy ReliaTel requires no special tools to run the Voyager unit through its paces. Simply place a jumper between Test 1 and Test 2 terminals on the Low Voltage Terminal Board and the unit will walk through its operational steps automatically. The unit automatically returns control to the zone sensor after stepping through the test mode a single time, even if the jumper is left on the unit. As long as the unit has power and the system on LED is lit, ReliaTel is operational. The light indicates that the controls are functioning properly. ReliaTel features expanded diagnostic capabilities when utilized with Trane Integrated Comfort Systems. Some zone sensor options have central control panel lights which indicate the mode the unit is in and possible diagnostic information (dirty filters for example). Other ReliaTel Benefits The ReliaTel built-in anti-shortcycle timer, time delay relay and minimum on time control functions are factory tested to assure proper operation. ReliaTel softens electrical spikes by staging on fans, compressors and heaters. Intelligent Fallback is a benefit to the building occupant. If a component goes astray, the unit will continue to operate at predetermined temperature setpoint. Intelligent Anticipation is a standard ReliaTel feature. It functions continuously as ReliaTel and zone sensor(s) work together in harmony to provide much tighter comfort control than conventional electromechanical thermostats. The same ReliaTel Board fits all Voyager Packaged Gas/Electrics, Cooling, and Heat Pump models. This provides standardization of parts for contractors. Less money is tied up in inventory with ReliaTel.
VariTrac TM

VariTrac Building Automation System


When Tranes changeover VAV System for light commercial applications is coupled with Voyager, it provides the latest in technological advances for comfort management systems and can allow thermostat control in every zone served by VariTrac.

Every unit receives a 100% unit run test before leaving the production line to make sure it lives up to rigorous Trane requirements. Voyager units incorporate either a one piece top or the Trane-Tite-Top (T3). Each part of the top (either two or three pieces) overlaps in such a way that water cannot leak into the unit. These overlapped edges are gasketed and sealed to ensure superior water integrity.

Rigorous Testing
All of Voyagers designs were rigorously rain tested at the factory to ensure water integrity. Actual shipping tests were performed to determine packaging requirements. Units were test shipped around the country to determine the best packaging. Factory shake and drop tests were used as part of the package design process to help assure that the unit arrives at the job site in top condition. Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the lifting lugs and rails hold up under stress. We perform a 100% coil leak test at the factory. The evaporator and condenser coils are leak tested at 200 psig and pressure tested to 450 psig. All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected immediately.

RT-PRC028-EN

Features and Benefits Factory Installed Options

Figure 1.

Voyager Factory Installed Options

10

RT-PRC028-EN

Application Considerations
Application of this product should be within the cataloged airflow and cooling considerations.

Heating Operation
The heat exchanger is manufactured with aluminized steel. To prevent condensation within the heat exchanger, do not exceed 50% outside air or a minimum mixed air temperature of 40F .

Barometric Relief
This product line offers an optional barometric relief damper for use in conjunction with economizer option. This accessory consists of gravity dampers which open with increased pressure. As the building air pressure increases, the pressure in the unit return air section also increases, opening the dampers and relieving the conditioned space. Note: The effectiveness of barometric relief damper during economizing operation is system related. Pressure drop of the return air system should be considered to control building pressurization.

Optional Stainless Steel Heat Exchanger


The optional stainless steel heat exchanger is manufactured with 304 stainless steel. To prevent corrosion and prolong heat exchanger reliability, the minimum mixed air temperature allowed across the heat exchanger is 20F . The stainless steel heat exchanger option is an excellent option that compliments the dehumidification package. Whenever high outside air or outside applications exist, these options should be utilized.

Note:

Black Epoxy Coil


The coils are manufactured with a thermoset, vinyl coating that is bonded to the aluminum fin stock prior to the fin stamping process. These coils are an economical option for protection in mildly corrosive environments. Note: Not to be used where seacoast applications exist.

Low Ambient Cooling


The Voyager line features, with ReliaTel microprocessor controls, low ambient cooling down to 0F . The following options need to be included/considered when low ambient applications are required: continuous fan operation, crankcase heaters (standard), thermal expansion valves, frostat. Contact your local Trane Representative for more assistance with low ambient cooling applications.

Clearance Requirements
The recommended clearances identified with unit dimensions should be maintained to ensure adequate serviceability, maximum capacity and peak operating efficiency. Actual clearances which appear inadequate should be reviewed with the local Trane sales personnel.

Unit Pitch
These units have sloped condensate drain pans. Units must be installed level. Any unit slope must be toward access side of the unit.

Condensate Trap
The evaporator is a draw-thru configuration. A trap must be field provided prior to start-up on the cooling cycle.

RT-PRC028-EN

11

Selection Procedure
Cooling Capacity
Note: Cooling Capacity Procedure is the same for cooling (TC*) and gas/electric (YC*). Note: Extrapolation outside of the table conditions is not recommended.

Heating Capacity
Note: Heating capacity procedures DIFFER for cooling (TC*) and gas/electric (YC*) units.

Step 4. In order to select the correct unit which meets the buildings requirements, the fan motor heat must be deducted from the gross cooling capacity. The amount of heat that the fan motor generates is dependent on the effort by the motor - cfm and static pressure. To determine the total unit static pressure you add the external static pressure to the additional static related by the added features:
External Static Duct System 0.49 wg Standard Filter 1 in. from 0.10 wg Table 22 Economizer from Table 22 0.04 wg (100% Return Air) Electric Heater Size 36 kW 0.07 wg from Table 22 (reference "Heating Capacity" section on this page for determination of heater size). No additional static add for gas/heat exchanger. Total Static Pressure 0.60 wg

Step 1. Calculate the buildings total and sensible cooling loads at design conditions. Use the Trane calculation methods or any other standard accepted method. Factors used in unit selection: Total Cooling Load: 180 MBh Sensible Cooling Load: 126 MBh Airflow: 6000 cfm Electrical Characteristics: 460/60/3 Summer Design Conditions: Entering Evaporator Coil: 80 DB, 67 WB Outdoor Ambient: 95 DB External Static Pressure: 0.49 in. wg Rooftop - downflow configuration Accessories Roof curb Economizer Electric Heat

Step 1. Calculate the building heating load using the Trane calculation form or other standard accepted method. Step 2. Size the system heating capacity to match the calculated building heating load. The following are building heating requirements: TC* cooling units: 460 volt/3 phase Power Supply Total heating load of 115.0 MBH 6000 cfm The electric heat accessory capacities are listed in Table 24. From the table, a 36 kw heater will deliver 122.94 MBh at 480 volts. In order to determine capacity at 460 volts, the heater voltage correction factor from Table 25 must be used. Therefore, 122.94 MBh x .94 (voltage correction factor) = 115.6 MBh. YC* gas/electric: Fuel natural gas total heating load of 195 MBh. Table Table 23 shows 250 MBh and 350 MBh input models. The output capacities of these furnaces are 203 MBh and 284 MBh respectively. The low heat model with 203 MBh output best matches the building requirements.

Step 2. As a starting point, a rough determination must be made of the size of the unit. The final selection will be made after examining the performance at the given conditions. Divide the total cooling load by nominal BTUH per ton (12 MBh per ton); then round up to the nearest unit size. 180 MBh / 12 MBh = 15.0 tons Step 3. Table 5 shows that a TCD180E4 has a gross cooling capacity of 188 MBh and 133.2 MBh sensible capacity at 6000 cfm and 95 DB outdoor ambient with 80 DB, 67 WB air entering the evaporator. To Find Capacity at Intermediate Conditions Not in the Table. When the design conditions are between two numbers that are in the capacity table, interpolation is required to approximate the capacity.

Note:

The Evaporator Fan Performance Table 11 has already accounted for the pressure drop for standard filters and wet coils (see note below Table 11). Therefore, the actual total static pressure is 0.60 -0.10 (from Table 22 = 0.50 wg).

With 6000 cfm and 0.50 wg. Table 11 shows 2.03 bhp for this unit. Note below the table gives a formula to calculate Fan Motor Heat, 3.15 x bhp = MBh. 3.15 x 2.56 = 6.39 MBh. Now subtract the fan motor heat from the gross cooling capacity of the unit: Net Total Cooling Capacity = 188 MBh - 6.39 = 181.61 MBh. Net Sensible Cooling Capacity = 133.2 MBh - 6.39 = 126.81 MBh. Step 5. If the performance will not meet the required load of the building -total or sensible cooling load, try a selection at the next higher size unit.

Air Delivery Selection


Note: Air Delivery procedures is the same for cooling (TC*) and gas/electric (YC*) units.

External static pressure drop through the air distribution system has been calculated to be 0.50 inches of water. From Table 22 static pressure drop through the economizer is 0.04 and the 36 kw heater is 0.07 inches of water (0.49 + 0.04 + 0.07). Enter Table 22 for a TCD180E4 at 6000 cfm and 0.50 static pressure. The standard motor at 777 rpm will give the desired airflow at a rated bhp of 2.71.

12

RT-PRC028-EN

Model Number Description


TC 12 D 3 150 456 E 7 3 8 0 9 0 10 A 11 A 12

DIGIT 1,2 UNIT TYPE TC TF YC YF Packaged Cooling, Electric Heat With Factory Installed Options Packaged Gas/Electric With Factory Installed Options

DIGIT 9,10 FACTORY INSTALLED OPTIONS Note: 00 0A 0B 0C 0F 0G (Applicable to Digit 1, 2 T models only) No Factory-installed Options Factory-installed Economizer Oversized Motor Downflow Economizer and Oversized Motor Trane Communications Interface (TCI) Downflow Economizer and TCI

DIGIT 11 MINOR DESIGN SEQUENCE DIGIT 12 SERVICE SEQUENCE Note: Explanation of Model Number Notes located on the following page. Most Factory Installed Options (FIOPS) available for Downflow Air Discharge units only. Please verify with ordering system for availability.

Note:

DIGIT 3 AIRFLOW CONFIGURATION D H Downflow Horizontal

DIGIT 4,5,6 NOMINAL GROSS COOLING CAPACITY (MBh) 150 180 210 240 300 12 Tons Standard Efficiency 15 Tons Standard Efficiency 17 Tons Standard Efficiency 20 Tons Standard Efficiency 25 Tons Standard Efficiency

DIGIT 9 HEATING CAPACITY Note: L H (Applicable to Digit 1, 2 Y models only) Low Heat High Heat

DIGIT 10 FACTORY INSTALLED OPTIONS15 Note: 0 (Applicable to Digit 1, 2 Y models only)

DIGIT 7 MAJOR DESIGN SEQUENCE DIGIT 8 VOLTAGE SELECTION 3 4 W 208-230/60/3 460/60/3 575/60/3

Packed Stock, No Options

A Downflow Economizer1 B Oversized Motor6 C Downflow Economizer and Oversized Motor1 F Trane Communications Interface (TCI)2,6

G Downflow Economizer and TCI1,2

RT-PRC028-EN

13

Model Number Description

Options
*Factory Installed Options15 2" Pleated Filters6 Black Epoxy Pre-Coated Coils6 Differential Pressure Switches High Efficiency Motors6 Hinged Access Doors Novar Return Air Sensor8 Novar Unit Controls7 Powered or Unpowered Convenience Outlet5 Stainless Steel Heat Exchanger with 10-year warranty6 Supply and/or Return Air Smoke Detector12 Through the Base Electrical Access Through the Base Electrical with Circuit Breaker13,14 Through the Base Electrical with Disconnect Switch9,13,14

LP Conversion Kit Manual Outside Air Damper Motorized Outside Air Dampers Powered Exhaust Quick Start Kit ReliaTel Options Module11 Remote Potentiometer Roof Curb (Downflow Only) Thermostat Ventilation Override Accessory3 Zone Sensors and Remote Zone Sensors

11. ReliaTel Options Module is required when ordering the following accessories: Clogged Filter Switch, Fan Fail Switch, Discharge Air Sensing Kit, Frostat, Ventilation Override, Smoke Detector and Dehumidification. 12. Option cannot be ordered in conjunction with field installed economizer. Must be factory installed. The return air smoke detector may not fit up or work properly on the Voyager units when used in conjunction with 3rd party accessories (such as bolt on heat wheels, economizers, and power exhaust). Do not order the return air smoke detectors when using this type of accessory. 13. Unit mounted disconnect and circuit breakers are mutually exclusive of each other. 14. Through-the-base electrical option or Horizontal-Side Access must be ordered with either unit mounted disconnect or circuit breaker. When adding heat, must order Trane Electric Heat. 15. All Factory Installed Options are Built-to-Order. Check order services for estimated production cycle. Note: *Most Factory Installed Options (FIOPS) available for Downflow Air Discharge units only. Please verify with ordering system for availability.

Model Number Notes


1. 2. 3. 4. 5. Some field set up required. TCI is for use with non-VariTrac systems and VariTrac systems. Requires ReliaTel options module. Requires Economizer. Must be ordered with Throughthe-Base Electrical option or Horizontal-Side Access and either Unit Mounted Disconnect or Circuit Breaker. Available factory installed on downflow AND horizontal units. Verify with ordering system. The Novar control option includes the following factory installed and wired devices: Novar ETM-2024 or Novar 3051 rooftop controller, fan proving switch, clogged filter or unit shutdown switch, Cool 1, Cool 2, Heat switch and discharge air sensor (downflow only). Note: Option cannot be ordered in conjunction with FIOPS Smoke Detector option.

Factory* or Field Installed Options15 Barometric Relief Clogged Filter/Fan Failure Switch3,6 Discharge Air Sensing Kit3,6 Economizer (Downflow)1 Electric Heaters6,10,14 LonTalk Communications Interface (LCI)6 Oversized Motors6 Reference or Comparative4,6 Enthalpy Tool-less Hail Guards6 Trane Communications Interface (TCI)2,6 8. 7. 6.

Field Installed Options


14

CO2 Sensing Digital Display Zone Sensor Dual Thermistor Remote Zone Sensor Economizer (Horizontal) High Altitude Kit High and Low Static Drive Kits Humidity Sensor Low Static Drive 9.

This option consists of the Novar return air sensor (Novar #WTS10) that is wired and shipped in the return air section of the unit. The sensor ships with approximately 15' of extra wire for dropping down the return air duct (downflow only). Cannot be fused.

10. Must be factory installed when using Through-the-Base Options.

RT-PRC028-EN

General Data
Table 1. General Data 12-15 Tons
12 Tons Downflow & Horizontal Units T/YC*150E3,4,WL Cooling Performance(i) Gross Cooling Capacity EER (DF/HF) Nominal CFM / ARI Rated CFM ARI Net Cooling Capacity Integrated Part Load Value(ii) System Power (kW) Compressor Number/Type Sound Outdoor Sound Rating (BELS)(iii) Outdoor Coil Type Tube Size (in.) OD Face Area (sq. ft.) Rows/FPI Indoor Coil Type Tube Size (in.) OD Face Area (sq. ft.) Rows/FPI Refrigerant Control Drain Connection Number/Size (in.) Outdoor Fan Type Number Used/Diameter (in.) Drive Type/No. Speeds CFM Number Motors/HP Motor RPM Indoor Fan Type Number Used/Diameter (in.) Drive Type/Number Speeds Number Motors Motor HP (Standard/Oversized)(iv) Motor RPM (Standard/Oversized) Motor Frame Size (Standard/Oversized) Filters Type Furnished(v) Number Size Recommended Downflow Horizontal Refrigerant Charge Pounds of R-410A(vi) Downflow (circuit 1/circuit 2) Horizontal (circuit 1/circuit 2) 13.9/13.0 15.0/14.0 27.5/16.875 Throwaway (2)20x20x2,(4)20x25x2 (2)20x20x2,(4)20x25x2 Throwaway (4)20x20x2,(4)20x25x2 (8)20x25x2 FC Centrifugal 1/15x15 Belt/1 1 3.0/5.0 1,740/3,450 145T/145T FC Centrifugal 1/18x18 Belt/1 1 3.0/5.0 1,740/3,450 145T/145T Propeller 2/26 Direct/1 10,400 2/.50 1,100 Propeller 2/26 Direct/1 11,000 2/.50 1,100 Hi-Performance 0.375 17.50 4/15 Short Orifice 1/1.00 NPT Hi-Performance 0.375 26.00 3/15 Short Orifice 1/1.00 NPT Hi-Performance 0.375 27.12 3/16 Hi-Performance 0.375 35.30 3/16 9.2 9.2 2/Scrolls 2/Scrolls 158,000 11.0 5,000/4,400 148,000 11.5 13.45 189,000 11.0 6,000/5,300 178,000 12.6 16.18 T/YC*150E3,4,WH 15 Tons Downflow & Horizontal Units T/YC*180E3,4,WL T/YC*180C3,4,WH

RT-PRC028-EN

15

General Data (12,15 Tons Standard Efficiency)


Table 1.
Heating

(continued) General Data 12-15 Tons


12 Tons Downflow & Horizontal Units Performance(vii) 15 Tons Downflow & Horizontal Units

(Gas/Electric Only) Heating Models Heating Input (Btuh) 1st Stage (Btu) Heating Output (Btuh) 1st Stage (Btu) AFUE% (DF/HF)(viii) Downflow/Horizontal Steady State Efficiency% No. Burners No. Stages Gas Supply Line Pressure (in w.c.) Natural or LP (minimum/maximum) Gas Connection Pipe Size (in.)
(i)

Low 150,000 100,000 122,000 81,000

High 250,000 175,000 203,000 142,000

Low 250,000 175,000 203,000 142,000

High 350,000 250,000 284,000 203,000

81.0/81.0 81.0 1 2

80.7/79.9 81.0 1 2

80.7/79.9 81.0 1 2

80.1/79.1 81.0 1 2

2.5/14.0 1/2 1/2 1/2

2.5/14.0 3/4

Cooling Performance is rated at 95F ambient, 80F entering dry bulb, 67F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360-93. (ii) Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80F ambient, 80F entering dry bulb, and 67F entering wet bulb at ARI rated cfm. (iii) Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370. (iv) For 380V/60Hz units, the oversized motor (Indoor Fan) is used as the standard motor. Refer to oversized motor data. (v) An optional 2 inch pleated filter is also available. (vi) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. (vii) Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. (viii) AFUE is rated in accordance with DOE test procedures.

16

RT-PRC028-EN

General Data (17, 20 Tons Standard Efficiency)


Table 2. General Data 17 - 20 Tons
17 Tons Downflow & Horizontal Units T/YC*210E3,4,WL Cooling Performance(i) Gross Cooling Capacity EER (DF/HF)(ii) Nominal CFM / ARI Rated CFM ARI Net Cooling Capacity Integrated Part Load Value(iii) System Power (kW) Compressor Number/Type Sound Outdoor Sound Rating (BELS)(iv) Outdoor Coil Type Tube Size (in.) OD Face Area (sq. ft.) Rows/FPI Indoor Coil Type Tube Size (in.) OD Face Area (sq. ft.) Rows/FPI Refrigerant Control Drain Connection Number/Size (in.) Outdoor Fan Type Number Used/Diameter (in.) Drive Type/No. Speeds CFM Number Motors/HP Motor RPM Indoor Fan Type Number Used/Diameter (in.) Drive Type/Number Speeds Number Motors Motor HP (Standard/Oversized) Motor RPM (Standard/Oversized) Motor Frame Size (Standard/Oversized) Filters Type Furnished(v) Number Size Recommended Downflow Horizontal Refrigerant Charge Pounds of R-410A(vi) Downflow (Circuit 1/Circuit 2) Horizontal (Circuit 1/Circuit 2) 27.0/12.0 25.6/12.0 26.4/15.0 25.3/15.3 Throwaway (4)20x20x2,(4)20x25x2 (8)20x25x2 Throwaway (4)20x20x2,(4)20x25x2 (8)20x25x2 FC Centrifugal 1/18x18 Belt/1 1 5.0/7.5 3,450/3,470 145T/184T FC Centrifugal 1/18x18 Belt/1 1 5.0/7.5 3,450/3,470 145T/184T Propeller 2/26 Direct/1 12,800 2/1.0 1,125 Propeller 2/26 Direct/1 13,700 2/1.0 1,125 Hi-Performance 0.375 26.00 4/15 Short Orifice 1/1.0 NPT Hi-Performance 0.375 26.00 4/15 Short Orifice 1/1.0 NPT Hi-Performance 0.375 35.30 3/16 Hi-Performance 0.375 35.30 3/16 9.4 9.4 2/Scrolls 2/Scrolls 211,000 11.0 7,000/6,200 198,000 12.2 18.00 256,000 10.2 8,000/7,000 240,000 11.8 23.53 T/YC*210E3,4,WH 20 Tons Downflow & Horizontal Units T/YC*240E3,4,WL T/YC*240E3,4,WH

RT-PRC028-EN

17

General Data (17, 20 Tons Standard Efficiency)


Table 2.
Heating

(continued) General Data 17 - 20 Tons


17 Tons Downflow & Horizontal Units Performance(vii) 20 Tons Downflow & Horizontal Units

(Gas/Electric Only) Heating Models Heating Input (Btuh) 1st Stage (Btu) Heating Output (Btuh) 1st Stage (Btu) AFUE%(viii) Downflow/Horizontal Steady State Efficiency% No. Burners No. Stages Gas Supply Line Pressure (in w.c.) Natural or LP (minimum/maximum) Gas Connection Pipe Size (in.)
(i)

Low 250,000 175,000 203,000 142,000

High 350,000 250,000 284,000 203,000

Low 250,000 175,000 203,000 142,000

High 400,000 300,000 324,000 243,000

80.2/81.0 81.0 1 2

79.3/79.7 81.0 1 2

80.2/81.0 81.0 1 2

79.8/79.7 81.0 1 2

2.5/14.0 1/2 3/4 1/2

2.5/14.0 3/4

Cooling Performance is rated at 95F ambient, 80F entering dry bulb, 67F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360-93. (ii) EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360. (iii) Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80F ambient, 80F entering dry bulb, and 67F entering wet bulb at ARI rated cfm. (iv) Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370. (v) An optional 2 inch pleated filter is also available. (vi) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. (vii) Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. (viii) AFUE is rated in accordance with DOE test procedures. *Indicates both downflow/horizontal units.

18

RT-PRC028-EN

General Data (25 Tons Standard Efficiency)


Table 3. General Data - 25 Tons
25 Tons Downflow & Horizontal Units T/YC*300E3,E4,EWL T/YC*300E3,E4,EWH Cooling Performance(i) Gross Cooling Capacity EER (DF/HF)(ii) Nominal CFM / ARI Rated CFM ARI Net Cooling Capacity Integrated Part Load Value(iii) System Power (kW) Compressor Number/Type Sound Outdoor Sound Rating (BELS)(iv) Outdoor Coil Type Tube Size (in.) OD Face Area (sq. ft.) Rows/FPI Indoor Coil Type Tube Size (in.) OD Face Area (sq. ft.) Rows/FPI Refrigerant Control Drain Connection Number/Size (in.) Outdoor Fan Type Number Used/Diameter (in.) Drive Type/No. Speeds CFM Number Motors/HP Motor RPM Indoor Fan Type Number Used/Diameter (in.) Drive Type/Number Speeds Number Motors Motor HP (Standard/Oversized) Motor RPM (Standard/Oversized) Motor Frame Size (Standard/Oversized) Filters Type Furnished(v) Number Size Recommended Downflow Horizontal Refrigerant Charge Pounds of R-410A(vi) Downflow (Circuit 1/Circuit 2) Horizontal (Circuit 1/Circuit 2) 17.75/17.75 14.625/13.25 Throwaway (4) 20 x 20 x 2, (4) 20 x 25 x 2 (8) 20 x 25 x 2 FC Centrifugal 1 18 X18 Belt/1 1 7.5/NA 3470/NA 184T/NA Propeller 2/28 3.00 /15.00 Direct/1/1.00 /1.00 15,700 2/1.0 1125 1100 Hi-Performance 0.3125 26.00 4/15 3.00 /15.00 Short Orifice 1/1.0 NPT Hi-Performance 0.3125 35.20 3/16 3.00 /15.00 9.4 2/Scrolls 291,000 10.0 10,000/8,750 272,000 10.5 27.20

RT-PRC028-EN

19

General Data (25 Tons Standard Efficiency)


Table 3.
Heating

(continued) General Data - 25 Tons


25 Tons Downflow & Horizontal Units Performance(vii)

(Gas/Electric Only) Heating Models Heating Input (Btuh) 1st Stage (Btu) Heating Output (Btuh) 1st Stage (Btu) AFUE%(viii) Downflow/Horizontal Steady State Efficiency% No. Burners No. Stages Gas Supply Line Pressure (in w.c.) Natural or LP (minimum/maximum) Gas Connection Pipe Size (in.)
(i)

Low 250,000 175,000 203,000 142,000

High 400,000 300,000 324,000 243,000

80.2/81.0/81 81.4/81.0/81 1 2

79.8/79.7/81 80.8/81.0/81

2.5/14.0 1/2 3/4

Cooling Performance is rated at 95F ambient, 80F entering dry bulb, 67F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Large Equipment Certification Program, which is based on ARI Standard 340/360-93. (ii) EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360. (iii) Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80F ambient, 80F entering dry bulb, and 67F entering wet bulb at ARI rated cfm. (iv) Outdoor Sound Rating shown is tested in accordance with ARI Standard 270 or 370. (v) An optional 2 inch pleated filter is also available. (vi) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. (vii) Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. (viii) AFUE is rated in accordance with DOE test procedures. *Indicates both downflow/horizontal units.

20

RT-PRC028-EN

Performance Data
Table 4. Gross Cooling Capacities 12 Tons Three Phase Standard Efficiency T/YC*150E3,4,W
Ambient Temperature 85 Air Ent Flow DB 61 67 73 61 67 95 Entering Wet Bulb 73 61 67 73 61 67 73 105 115

CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
4000 75 130.7 104.9 158.7 79.3 171.2 42.5 113.2 96.9 147.7 75.8 164.0 40.8 97.2 89.7 133.7 69.8 154.5 39.2 83.7 83.1 118.3 63.7 143.1 35.4 80 133.7 128.3 160.0 101.7 173.6 65.9 118.7 118.7 148.8 97.3 166.0 63.8 108.3 108.3 134.4 91.8 156.0 61.3 98.7 98.7 119.6 85.8 144.6 57.6 85 145.4 145.4 161.6 123.9 176.0 89.0 134.5 134.5 150.6 119.9 168.0 86.4 124.3 124.3 136.0 114.2 158.0 83.6 114.7 114.7 122.9 108.8 146.1 79.8 90 158.0 158.0 163.5 146.9 178.2 111.3 148.9 148.9 152.8 142.8 170.1 109.3 139.0 139.0 140.4 137.8 159.2 106.1 129.6 129.6 129.2 129.2 147.6 102.0 4500 75 138.9 114.5 163.2 82.8 173.2 42.6 121.4 106.8 153.1 79.4 166.3 41.2 104.3 99.2 140.2 74.7 157.1 36.8 91.9 91.8 125.3 69.1 145.8 35.6 80 143.5 141.1 164.6 107.7 175.8 67.7 129.6 129.6 154.2 104.0 169.0 66.0 118.4 118.4 140.6 99.1 159.1 63.2 108.2 108.2 127.2 94.0 147.8 59.8 85 155.8 155.8 166.2 133.0 178.5 93.1 145.0 145.0 155.6 129.2 171.1 90.2 135.2 135.2 143.6 124.7 161.2 88.3 124.6 124.6 129.5 119.6 149.6 84.8 90 165.7 165.7 169.3 158.5 181.0 117.9 156.8 156.8 158.5 154.7 173.3 115.9 147.6 147.6 148.1 148.1 163.2 113.6 138.0 138.0 137.8 137.8 151.8 109.6 5000 75 146.2 123.8 166.0 85.4 173.7 42.8 129.2 116.4 156.6 82.5 168.0 38.8 111.3 108.6 144.4 78.9 159.1 37.4 98.3 98.3 130.2 73.6 147.8 34.4 80 151.1 150.8 167.9 113.4 177.8 70.0 138.7 138.7 158.1 110.2 170.9 69.0 127.5 127.5 146.3 106.3 161.7 65.4 116.6 116.6 131.9 101.3 150.4 61.8 85 161.9 161.9 170.2 141.6 180.1 97.4 153.1 153.1 159.8 138.3 173.4 95.6 143.2 143.2 148.1 134.3 163.9 93.1 132.6 132.6 135.2 129.8 152.3 90.1 90 171.6 171.6 173.4 168.8 182.3 124.7 163.3 163.3 163.4 163.2 176.1 122.9 154.1 154.1 153.9 153.9 166.2 120.9 144.3 144.3 144.2 144.2 154.3 117.9 5500 75 151.6 131.9 168.3 88.6 174.9 43.8 134.8 125.2 158.9 85.7 169.0 40.1 119.2 117.6 147.8 82.4 160.2 36.7 105.2 105.2 134.5 78.1 149.8 33.8 80 157.1 157.1 170.5 118.9 179.0 73.5 146.2 146.2 160.8 116.5 172.4 70.3 134.8 134.8 148.7 112.6 163.4 67.3 124.2 124.2 135.9 108.3 152.2 64.0 85 167.5 167.5 173.3 149.8 180.9 102.6 158.5 158.5 163.3 147.3 175.2 100.3 149.1 149.1 152.0 143.5 165.8 98.4 138.5 138.5 139.4 138.2 154.2 94.3 90 176.2 176.2 177.1 175.9 184.0 131.5 168.4 168.4 168.4 168.4 177.8 130.0 159.2 159.2 159.1 159.1 168.6 128.2 149.0 149.0 148.9 148.9 156.8 125.6 6000 75 155.9 139.4 169.9 91.2 175.7 44.2 141.3 133.9 161.1 89.0 170.4 40.3 124.1 123.9 149.8 86.1 161.4 36.5 112.4 112.4 137.1 81.9 151.2 35.0 80 161.4 161.4 172.4 124.5 179.2 75.8 152.3 152.3 163.5 122.4 173.4 72.8 141.8 141.8 151.7 119.1 164.8 70.7 129.8 129.8 139.2 115.0 153.4 67.2 85 171.3 171.3 175.9 157.6 182.7 107.2 163.0 163.0 166.4 155.3 176.6 104.6 153.3 153.3 154.8 151.4 167.2 103.7 142.9 142.9 142.9 142.9 156.2 100.4 90 179.8 179.8 179.4 179.4 185.0 136.8 172.4 172.4 172.3 172.3 179.4 137.0 163.6 163.6 163.5 163.5 170.0 135.0 153.3 153.3 153.2 153.2 158.9 133.2 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity *Indicates both downflow and horizontal units.

RT-PRC028-EN

21

Performance Data (15 Tons Standard Efficiency)


Table 5. Gross Cooling Capacities 15 Tons Three Phase Standard Efficiency T/YC*180E3,4,W
Ambient Temperature 85 Air Ent Flow DB 61 67 73 61 67 95 Entering Wet Bulb 73 61 67 73 61 67 73 105 115

CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
4800 75 160.6 128.3 188.9 95.0 200.3 46.2 138.4 118.5 177.0 90.7 193.5 43.4 120.9 111.0 161.3 85.4 183.9 46.2 105.2 103.2 145.2 79.0 170.5 42.5 80 165.4 157.6 191.0 122.1 203.5 74.9 147.9 147.9 179.1 117.7 196.8 72.1 134.0 134.0 164.0 112.4 186.3 72.7 122.6 122.6 145.6 105.2 172.8 70.1 85 177.5 177.5 192.3 149.3 207.0 103.6 164.7 164.7 180.9 145.1 199.4 99.5 152.8 152.8 166.0 139.7 188.8 101.6 140.8 140.8 149.2 133.2 174.1 97.1 90 190.8 190.8 195.2 176.7 210.1 131.6 180.3 180.3 183.6 173.4 202.1 127.5 169.3 169.3 170.1 169.0 190.7 127.8 158.3 158.3 158.1 158.1 176.3 123.8 5400 75 170.5 140.1 193.4 97.3 201.9 47.0 149.5 130.8 182.5 95.3 195.5 40.1 129.6 122.7 169.6 90.9 186.5 41.3 115.4 114.2 150.4 84.2 174.5 41.6 80 175.6 173.2 196.0 127.8 206.1 79.1 159.9 159.9 184.0 125.5 199.3 72.4 146.3 146.3 170.7 120.8 189.5 72.4 133.5 133.5 152.3 114.4 176.8 71.7 85 187.8 187.8 198.2 159.0 209.4 109.5 177.8 177.8 186.6 156.5 202.6 104.0 166.2 166.2 172.2 151.6 192.4 103.9 152.8 152.8 158.6 146.7 178.8 102.4 90 199.7 199.7 202.0 192.1 212.7 139.6 189.8 189.8 190.7 189.6 205.8 135.4 179.2 179.2 179.0 179.0 195.3 134.8 167.5 167.5 167.3 167.3 181.0 132.9 6000 75 178.1 150.5 196.7 100.6 203.9 44.4 159.2 142.8 186.3 99.4 197.1 42.9 138.5 134.8 172.8 95.1 188.1 35.7 122.7 122.7 155.2 89.4 175.4 28.7 80 183.0 183.0 199.3 134.8 207.9 77.4 170.9 170.9 188.8 133.2 201.2 78.4 156.4 156.4 175.5 129.1 191.6 71.9 143.7 143.7 159.1 123.5 179.1 71.8 85 195.7 195.7 202.4 168.1 211.4 109.8 185.9 185.9 191.5 167.3 204.7 113.2 173.6 173.6 178.0 163.6 194.7 107.0 162.5 162.5 163.8 159.7 181.9 106.3 90 206.6 206.6 207.5 205.1 215.0 143.5 198.3 198.3 198.0 198.0 208.3 147.4 186.8 186.8 186.6 186.6 198.2 141.1 174.8 174.8 174.8 174.8 184.8 140.6 6600 75 182.7 159.9 198.7 101.7 205.0 40.6 166.1 153.8 189.8 103.2 198.5 44.3 145.9 144.9 176.4 99.9 189.6 35.9 130.3 130.3 161.6 94.7 177.2 33.3 80 189.5 189.5 201.9 139.8 209.1 79.4 179.3 179.3 192.2 140.4 202.8 82.1 167.3 167.3 178.8 136.8 193.4 74.5 152.4 152.4 164.3 132.1 180.8 71.3 85 201.4 201.4 205.7 179.5 212.8 117.1 192.2 192.2 195.8 178.7 206.6 118.8 180.6 180.6 182.7 176.3 196.9 112.8 168.3 168.3 168.5 168.4 184.1 110.8 90 210.5 210.5 210.7 210.4 216.3 154.5 203.4 203.4 203.4 203.4 210.4 155.0 193.6 193.6 193.5 193.5 200.8 152.2 181.3 181.3 181.3 181.3 187.7 149.9 7200 75 186.7 169.0 200.3 107.7 205.7 44.7 173.4 165.0 191.8 103.8 199.7 43.6 153.0 153.0 179.2 104.1 191.1 39.3 138.0 138.0 164.2 99.3 178.6 32.2 80 195.1 195.1 203.9 149.2 209.8 87.9 184.1 184.1 195.0 145.5 204.1 83.0 172.9 172.9 181.8 144.6 194.8 80.8 159.9 159.9 167.1 140.0 182.6 76.4 85 205.4 205.4 207.9 189.3 213.8 126.4 197.6 197.6 199.6 189.8 208.1 121.8 186.1 186.1 187.0 186.3 198.5 122.3 173.5 173.5 173.3 173.3 186.0 116.4 90 213.2 213.2 213.1 213.1 217.6 163.5 207.1 207.1 207.1 207.1 212.0 160.1 197.9 197.9 197.8 197.8 202.9 164.4 185.9 185.9 185.8 185.8 190.5 161.0 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity *Indicates both downflow and horizontal units.

22

RT-PRC028-EN

Performance Data (17 Tons Standard Efficiency)


Table 6. Gross Cooling Capacities 17 Tons Three Phase Standard Efficiency T/YC*210E3,4,W
Ambient Temperature 85 Air Ent Flow DB 61 67 73 61 67 95 Entering Wet Bulb 73 61 67 73 61 67 73 105 115

CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
5600 75 179.4 148.9 214.2 111.9 231.8 58.6 158.5 139.6 200.1 107.1 222.3 57.4 138.2 131.0 180.2 100.0 208.8 57.4 119.6 119.6 161.2 92.8 193.6 54.5 80 182.9 181.2 214.7 143.1 235.0 92.4 167.0 167.0 200.4 138.1 224.5 91.3 153.1 153.1 181.0 131.0 211.3 89.1 138.5 138.5 162.2 124.1 194.5 85.1 85 199.1 199.1 214.7 174.7 237.4 125.1 185.5 185.5 201.3 169.3 226.3 123.3 172.7 172.7 182.7 162.3 211.6 120.4 159.5 159.5 164.6 155.7 195.7 116.1 90 214.4 214.4 217.6 206.9 239.6 156.0 202.8 202.8 204.7 200.9 228.2 155.0 190.3 190.3 190.1 190.1 213.1 151.9 177.0 177.0 176.7 176.7 196.1 147.0 6300 75 188.9 162.1 219.4 116.8 234.4 58.2 169.5 153.7 204.8 112.7 225.5 56.4 147.3 144.2 189.0 107.2 212.9 56.5 129.7 129.7 167.7 99.8 197.5 54.1 80 194.8 194.8 220.4 152.2 238.0 94.5 180.3 180.3 205.9 147.7 228.5 95.4 165.7 165.7 189.8 141.9 214.6 92.5 151.2 151.2 167.5 134.0 199.1 88.8 85 211.4 211.4 221.8 187.8 241.0 130.8 199.0 199.0 207.9 183.3 231.0 129.7 185.7 185.7 192.1 178.0 216.2 127.6 170.7 170.7 172.2 169.9 200.1 123.9 90 225.2 225.2 225.8 223.6 243.9 167.5 213.8 213.8 213.5 213.5 233.3 165.9 200.9 200.9 201.0 201.0 218.0 163.6 188.5 188.5 188.4 188.4 202.3 159.2 7000 75 196.6 174.3 223.6 120.9 235.9 60.5 178.4 167.0 209.6 118.1 227.9 56.0 155.7 155.5 194.4 113.3 215.8 54.5 139.5 139.5 173.6 106.5 200.2 52.4 80 205.9 205.9 224.6 161.0 240.1 100.3 191.4 191.4 211.5 157.4 231.3 96.5 177.9 177.9 196.0 152.3 217.8 94.5 162.3 162.3 175.4 145.4 202.7 91.9 85 220.5 220.5 227.4 201.3 243.4 139.7 208.0 208.0 212.9 197.0 234.2 136.8 195.8 195.8 198.7 192.1 220.4 135.0 181.5 181.5 181.5 181.5 204.0 131.3 90 233.3 233.3 234.0 234.0 246.7 179.4 222.3 222.3 222.0 222.0 237.1 177.0 209.5 209.5 209.3 209.3 223.3 175.7 196.5 196.5 196.3 196.3 206.2 171.3 7700 75 204.5 186.9 227.0 125.9 237.8 60.1 183.5 178.5 213.6 123.3 229.7 56.5 163.9 163.9 198.0 119.0 217.8 54.7 148.6 148.6 180.1 113.2 203.0 51.9 80 213.2 213.2 229.2 170.1 241.8 103.8 200.4 200.4 215.1 166.5 233.3 100.6 185.9 185.9 199.4 161.7 220.5 97.6 169.9 169.9 181.9 156.2 205.8 95.7 85 227.4 227.4 232.7 214.6 245.3 147.3 215.9 215.9 218.1 210.5 236.5 143.3 202.6 202.6 204.3 203.3 224.1 142.7 188.9 188.9 188.5 188.5 207.1 139.4 90 239.8 239.8 239.7 239.7 248.9 190.4 229.5 229.5 229.4 229.4 240.0 188.5 216.9 216.9 217.1 217.1 226.4 187.1 203.3 203.3 203.4 203.4 210.2 183.6 8400 75 208.7 197.9 229.4 129.9 239.0 59.6 190.2 188.9 216.8 128.0 231.3 56.2 172.8 172.8 200.8 124.2 219.3 53.1 156.6 156.6 183.7 118.8 205.0 46.6 80 219.0 219.0 232.1 178.5 243.0 106.8 207.7 207.7 218.8 175.8 234.9 105.2 194.0 194.0 203.0 171.5 222.8 101.3 178.0 178.0 185.8 166.4 207.1 98.2 85 233.6 233.6 236.2 225.6 246.6 153.2 222.4 222.4 223.3 220.9 238.3 151.8 209.3 209.3 208.5 208.5 225.6 150.0 194.8 194.8 194.7 194.7 209.4 146.8 90 244.2 244.2 244.1 244.1 250.5 199.3 235.0 235.0 234.9 234.9 242.4 199.9 223.1 223.1 222.9 222.9 229.6 198.2 208.9 208.9 209.2 209.2 213.3 195.1 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity *Indicates both downflow and horizontal units.

RT-PRC028-EN

23

Performance Data (20 Tons Standard Efficiency)


Table 7. Gross Cooling Capacities 20 Tons Three Phase Standard Efficiency T/YC*240E3,4,W
Ambient Temperature 85 Air Ent Flow DB 61 67 73 61 67 95 Entering Wet Bulb 73 61 67 73 61 67 73 105 115

CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
7200 75 237.5 198.3 266.1 139.9 284.5 71.5 210.9 186.0 248.0 135.0 272.4 71.4 183.4 173.7 227.3 127.0 255.7 69.9 158.7 156.0 201.2 117.2 234.7 63.6 80 242.6 239.1 268.3 183.0 289.4 115.4 219.9 219.9 250.1 177.5 275.8 115.4 201.5 201.5 228.8 169.4 258.1 111.9 181.5 181.5 203.1 159.2 236.0 105.0 85 256.7 256.7 270.8 226.4 293.6 158.6 241.4 241.4 251.6 220.0 279.0 157.5 222.1 222.1 232.4 212.6 260.3 153.7 203.4 203.4 207.0 199.9 238.1 147.2 90 273.3 273.3 276.3 269.6 297.9 202.5 258.3 258.3 259.2 257.1 282.3 201.1 241.8 241.8 241.5 241.5 262.7 196.5 224.0 224.0 223.7 223.7 240.1 189.4 6400 75 224.5 182.1 258.8 134.9 280.8 72.7 199.5 170.2 242.2 128.3 267.4 71.3 173.3 158.3 218.1 119.1 250.6 70.4 147.9 143.4 193.1 108.9 229.8 63.2 80 229.3 221.7 261.8 173.2 285.1 112.9 208.5 206.5 242.9 165.7 271.2 112.3 186.3 186.3 219.2 156.2 252.4 106.9 167.8 167.8 194.4 146.2 230.8 100.0 85 244.7 244.7 263.1 211.0 288.6 152.1 226.9 226.9 244.9 203.7 273.4 149.4 209.0 209.0 223.4 195.0 254.0 144.5 191.1 191.1 197.7 184.7 232.0 137.2 90 260.4 260.4 266.8 250.0 292.1 191.1 245.6 245.6 248.1 241.6 276.1 188.7 229.8 229.8 230.7 228.6 256.2 182.3 210.3 210.3 210.1 210.1 234.1 175.0 8000 75 244.6 211.7 271.1 146.5 287.7 71.0 219.6 200.8 253.5 141.5 275.7 69.7 192.2 186.0 233.0 134.0 258.5 67.1 167.0 166.8 206.9 124.6 238.5 63.7 80 251.1 250.6 273.6 192.9 292.7 119.1 233.2 233.2 255.5 188.4 279.7 117.7 212.6 212.6 234.9 181.0 261.9 115.4 193.3 193.3 209.4 171.6 240.4 109.6 85 267.0 267.0 277.3 241.9 297.4 167.1 251.4 251.4 258.4 236.2 283.4 165.6 234.9 234.9 238.8 228.8 265.0 162.5 215.2 215.2 216.5 213.1 242.7 156.5 90 283.6 283.6 284.5 282.2 302.2 215.7 268.8 268.8 268.6 268.6 287.6 213.9 251.8 251.8 251.4 251.4 268.1 209.6 233.2 233.2 232.8 232.8 245.4 204.0 8800 75 250.0 224.4 274.5 150.8 289.9 70.4 227.0 214.9 258.0 147.9 278.2 69.2 201.4 197.9 237.0 140.7 262.0 68.2 178.2 178.2 211.8 131.7 241.4 63.8 80 258.5 258.5 277.9 203.3 295.3 123.0 243.0 243.0 260.0 199.2 282.8 121.1 222.4 222.4 239.4 192.4 264.7 118.6 202.1 202.1 214.5 183.7 243.8 115.1 85 275.8 275.8 282.7 256.6 300.2 175.3 260.6 260.6 265.7 252.2 287.0 173.6 243.0 243.0 244.8 239.8 268.8 170.7 224.2 224.2 224.9 224.3 246.5 166.4 90 291.7 291.7 292.2 292.1 305.5 227.4 277.0 277.0 277.1 277.1 291.8 226.8 260.2 260.2 259.9 259.9 272.8 223.6 241.2 241.2 241.0 241.0 250.2 218.7 9600 75 254.5 236.8 277.5 156.3 291.8 72.7 234.6 227.7 261.4 154.1 280.1 68.2 209.4 208.1 240.6 147.3 264.1 66.1 186.6 186.6 216.9 139.3 243.9 63.7 80 265.7 265.7 281.3 213.2 297.4 128.0 249.5 249.5 264.2 209.8 285.2 124.7 232.0 232.0 243.5 203.7 267.9 122.5 210.2 210.2 220.5 196.0 246.7 119.7 85 282.7 282.7 287.0 269.8 302.5 183.3 267.4 267.4 269.8 263.0 289.9 181.8 250.1 250.1 251.0 249.2 271.8 180.5 230.7 230.7 230.5 230.5 249.4 175.5 90 298.0 298.0 297.8 297.8 308.4 239.7 284.0 284.0 283.6 283.6 295.1 239.1 267.5 267.5 267.5 267.5 276.6 237.5 248.3 248.3 248.0 248.0 254.1 232.7 Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity *Indicates both downflow and horizontal units.

24

RT-PRC028-EN

Performance Data 25 Ton Standard Efficiency

Table 8.

Gross Cooling Capacities 25 Ton Three Phase Standard Efficiency T/YC*300E3,4,W


Ambient Temperature 85 95 Entering Wet Bulb 61 67 73 61 67 73 61 67 73 61 67 73 105 115

Air Ent Flow DB


9000

CFM (F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 277.3 239.3 295.9 167.7 305.4 93.5 263.1 235.0 284.1 163.8 297.3 76.7 247.3 229.2 269.5 157.2 283.8 73.5 228.0 221.7 250.8 153.4 266.1 70.9 80 283.6 283.4 298.7 214.3 308.7 101.0 271.2 271.2 287.3 213.4 302.3 124.8 257.8 257.8 272.6 210.4 286.7 126.6 242.6 242.6 255.1 205.9 271.3 125.2 85 298.2 298.2 304.2 266.2 314.8 157.0 286.3 286.3 292.6 266.5 306.4 179.5 273.5 273.5 279.0 263.6 291.2 178.7 258.7 258.7 261.3 256.4 275.2 176.9 90 308.4 308.4 311.3 310.2 318.4 227.1 299.6 299.6 299.6 299.6 311.3 232.7 287.5 287.5 287.6 287.6 296.9 233.7 273.3 273.3 273.3 273.3 280.3 231.8 10000 75 282.4 255.1 298.5 169.8 309.2 74.9 268.5 250.2 287.4 166.3 296.9 51.0 251.8 243.7 271.5 167.9 286.0 73.8 234.4 234.0 254.6 161.1 268.2 61.3 80 289.7 289.7 301.4 221.1 313.1 125.8 278.7 278.7 290.9 224.5 305.1 127.2 265.2 265.2 276.5 223.6 290.5 136.7 249.6 249.6 259.2 219.7 272.7 122.2 85 302.3 302.3 307.7 279.1 315.5 178.4 292.5 292.5 296.8 283.0 309.0 187.3 280.1 280.1 285.6 280.8 294.0 185.9 265.2 265.2 266.4 266.2 278.0 188.2 90 313.1 313.1 315.4 315.4 322.1 242.8 305.2 305.2 302.7 341.4 312.3 246.6 293.9 293.9 294.7 294.7 300.8 250.0 278.1 278.1 278.2 278.2 283.2 248.2 10500 75 284.6 262.4 300.3 173.4 308.8 67.2 273.0 259.9 288.8 171.1 298.6 61.9 254.4 250.3 274.0 168.8 285.6 59.0 236.5 236.5 256.0 165.2 268.7 75.6 80 292.3 292.3 303.6 231.9 311.2 122.7 283.3 283.3 293.5 231.6 305.5 127.4 268.5 268.5 277.5 229.7 292.6 126.9 252.7 252.7 260.1 225.9 272.1 122.1 85 299.9 322.1 309.4 291.4 317.5 188.3 296.9 296.9 299.3 293.7 308.8 190.0 282.9 282.9 285.1 282.8 296.4 195.1 267.4 267.4 267.7 267.7 280.7 198.6 90 317.0 317.0 317.0 317.0 323.0 249.4 310.5 310.5 305.2 355.8 313.5 255.2 294.9 294.9 294.5 294.5 302.1 257.2 279.6 279.6 280.3 280.3 285.5 256.3 11000 75 287.6 268.7 300.6 172.2 306.6 53.1 273.1 264.3 290.2 176.3 298.6 58.2 256.3 255.0 274.8 171.4 285.4 42.6 239.1 239.1 258.0 167.2 268.8 55.9 80 296.5 296.5 304.7 234.8 312.8 123.7 286.2 286.2 293.2 233.6 304.6 112.0 271.1 271.1 279.0 236.2 290.3 108.6 255.3 255.3 263.5 233.1 274.6 129.2 85 305.5 324.4 311.3 292.8 317.9 190.5 299.3 308.1 300.8 292.7 308.8 202.5 285.0 285.0 287.4 287.1 296.9 192.7 271.0 271.0 269.4 269.4 279.9 196.2 90 318.5 318.5 319.1 319.1 324.8 259.9 309.0 309.0 309.6 309.6 315.7 262.2 296.3 296.3 297.4 297.4 301.8 263.8 281.0 281.0 281.3 281.3 285.9 262.3

Notes: 1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula, refer to appropriate airflow table notes. 2. MBH = Total Gross Capacity 3. SHC = Sensible Heat Capacity 4. Table is for 460 volt capacity. For capacity at 230 volt, multiply table capacity by 101%. *Indicates both downflow and horizontal units.

RT-PRC028-EN

25

Performance Data
Table 9. Evaporator Fan Performance 12 Tons TC*150E Downflow or Horizontal
External Static Pressure (Inches of Water) .10 CFM 4000 4500 5000 5500 6000 .20 .30 BHP 1.40 1.87 2.44 3.13 3.93 .40 RPM 727 785 846 908 972 BHP 1.55 2.03 2.61 3.32 4.15 .50 .60 BHP 1.86 2.37 2.98 3.70 .70 RPM 821 873 928 985 BHP 2.01 2.54 3.17 3.91 4.78 .80 RPM 850 901 954 1010 1068 BHP 2.17 2.71 3.37 4.13 5.01 .90 RPM 878 928 979 1033 1090 BHP 2.34 2.89 3.56 4.34 5.24 1.00 RPM 905 953 1004 1056 1112 BHP 2.50 3.07 3.75 4.54 5.47 RPM BHP RPM BHP RPM 618 686 755 824 894 1.11 1.54 2.07 2.71 3.47 656 720 786 853 921 1.26 1.71 2.26 2.91 3.70 692 753 816 881 947 RPM BHP RPM 759 815 874 935 996 1.71 2.20 2.79 3.51 791 844 902 960

3-HP Standard Motor & Drive w/Field Supplied Low Static Drive Fan Sheave

3-HP Standard Motor & Drive

3-HP Standard Motor & High Static Drive Accessory 4.36 1021 4.56 1044

5-HP Oversized Motor & Drive Continued External Static Pressure (Inches of Water) 1.10 CFM 4000 4500 5000 5500 6000 1.20 1.30 BHP 3.01 3.63 4.35 5.17 1.40 RPM BHP 1.50 1.60 BHP 1.70 RPM BHP 3.66 4.38 5.18 1.80 RPM 1090 1134 1180 BHP 3.82 4.57 5.40 1.90 RPM 1110 1154 1200 BHP 3.99 4.75 5.61 2.00 RPM 1132 1174 BHP 4.16 4.94 RPM BHP RPM BHP RPM 930 978 2.67 956 2.85 980 RPM BHP RPM

3-HP Standard Motor & High Static Drive Accessory 1003 3.17 1026 3.34 1047 3.50 1069 1049 3.83 1071 4.02 1093 4.21 1113 1096 4.55 1118 4.76 1140 4.98 1159 1146 5.40 1166 5.62 3.25 1002 3.44 1026

5-HP Oversized Motor & Drive

1028 3.94 1051 4.14 1074 1079 4.76 1102 4.97 1123 1133 5.70

5-HP Oversized Motor & Drive w/Field Supplied Fan Sheave


For Standard Evaporator Fan Speed (RPM), reference Table 19. For High Evaporator Fan Speed (RPM), reference Table 20. For Oversized Evaporator Fan Speed (RPM), reference Table 21. Fan motor heat (MBH) = 3.15 x Fan BHP. Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table 22 to determine additional static pressure drop due to other options/accessories. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.

26

RT-PRC028-EN

Performance Data (12 Tons Standard Efficiency)


Table 10. Evaporator Fan Performance 12 Tons with Gas Heat YC*150E Downflow or Horizontal
External Static Pressure (Inches of Water) .10 CFM 4000 4500 5000 5500 6000 .20 .30 BHP 1.39 1.85 2.42 3.11 3.93 .40 RPM 745 806 870 936 BHP 1.53 2.01 2.59 3.29 .50 .60 BHP 1.82 2.33 2.94 .70 RPM 835 891 950 BHP 1.97 2.49 3.12 3.87 4.74 .80 RPM 864 917 975 1035 1095 BHP 2.12 2.66 3.31 4.07 4.95 .90 RPM 891 944 998 1057 1117 BHP 2.27 2.83 3.49 4.26 5.16 1.00 RPM 916 969 1022 1079 1138 BHP 2.41 2.9 3.68 4.46 5.38 RPM BHP RPM BHP RPM 640 711 783 855 928 1.12 1.56 2.10 2.76 3.54 677 745 813 883 954 1.25 1.70 2.26 2.93 3.74 711 776 843 910 979 RPM BHP RPM 776 836 897 961 1.68 2.17 2.77 3.49 806 864 924 986

3-HP Standard Motor & Drive

3-HP Standard Motor & High Static Drive Accessory

3.67 1011

1003 4.12 1027 4.33 1050 4.54 1072 5-HP Oversized Motor & Drive

Continued External Static Pressure (Inches of Water) 1.10 CFM 4000 4500 5000 5500 6000 1.20 1.30 BHP 2.86 3.49 4.23 5.07 1.40 RPM BHP 1.50 1.60 BHP 1.70 RPM BHP 3.47 4.17 4.97 1.80 RPM 1098 1143 1190 BHP 3.62 4.34 5.15 1.90 RPM 1120 1163 1209 BHP 3.79 4.51 5.34 2.00 RPM 1140 1183 1228 BHP 3.95 4.68 5.53 RPM BHP RPM BHP RPM 940 994 2.56 964 2.71 987 RPM BHP RPM

3-HP Standard Motor & High Static Drive Accessory 1011 3.01 1034 3.16 1056 3.32 1077 1059 3.66 1080 3.83 1102 4.00 1122 1112 4.41 1133 4.60 1152 4.78 1172 1165 5.27 1186 5.48 1206 5.69 3.16 1016 3.32 1038

5-HP Oversized Motor & Drive

1046 3.86 1069 4.05 1091 1101 4.67 1122 4.87 1143 1159 5.60

5-HP Oversized Motor & Field Supplied High Static Drive(i)


For Standard Evaporator Fan Speed (RPM), reference Table 19. For High Evaporator Fan Speed (RPM), reference Table 20. For Oversized Evaporator Fan Speed (RPM), reference Table 21. Fan motor heat (MBH) = 3.15 x Fan BHP. Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table 22 to determine additional static pressure drop due to other options/accessories. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.
(i)

Field Supplied Fan Sheave BK120. Field Supplied Belt may be necessary.

RT-PRC028-EN

27

Performance Data (15 Tons Standard Efficiency)


Table 11. Evaporator Fan Performance 15 Tons TC*180E Standard Refrigeration System Downflow or Horizontal
External Static Pressure (Inches of Water) .10 CFM 4800 5400 6000 6600 7200 .20 .30 RPM 471 506 543 580 618 BHP 1.01 1.33 1.72 2.17 2.70 .40 RPM 503 536 571 606 643 BHP 1.14 1.47 1.87 2.35 2.91 .50 .60 BHP 1.44 1.78 2.19 2.69 3.27 .70 RPM 598 621 648 679 712 BHP 1.60 1.95 2.36 2.87 3.46 .80 RPM 629 648 673 702 734 BHP 1.77 2.12 2.55 3.05 3.65 .90 RPM 658 676 699 725 755 BHP 1.94 2.30 2.74 3.25 3.85 1.00 RPM 684 704 723 748 776 BHP 2.11 2.49 2.93 3.46 4.06 RPM BHP RPM BHP 399 445 479 519 560 0.76 1.04 1.38 1.79 2.28 437 474 513 552 591 0.89 1.19 1.55 1.98 2.49 RPM BHP RPM 535 564 597 632 667 1.29 1.62 2.03 2.52 3.09 566 592 623 656 690

3-HP Standard Motor & Field Supplied Extra Low Static Drive

3-HP Standard Motor & Field Supplied Low Static Drive(i)

3-HP Standard Motor & Drive Continued External Static Pressure (Inches of Water) 1.10 CFM 4800 5400 6000 6600 7200 1.20 1.30 RPM 760 778 798 816 839 BHP 2.68 3.07 3.56 4.09 4.74 1.40 RPM 785 800 821 839 860 BHP 2.88 3.28 3.77 4.32 4.96 1.50 1.60 BHP 3.29 3.71 4.20 4.80 5.45 1.70 RPM 854 867 884 904 923 BHP 3.49 3.94 4.43 5.03 5.70 1.80 RPM 876 889 904 924 BHP 3.69 4.17 4.66 5.27 1.90 RPM 898 910 924 943 BHP 3.90 4.40 4.90 5.51 2.00 RPM 919 931 944 961 BHP 4.10 4.62 5.15 5.75 RPM BHP RPM BHP 710 730 749 771 797 2.29 2.68 3.13 3.67 4.29 735 755 774 794 818 2.48 2.88 3.34 3.88 4.51 RPM BHP RPM 809 823 842 862 881 3.09 3.49 3.99 4.56 5.20 832 845 863 884 902

3-HP Standard Motor & Drive

3-HP Standard Motor & High Static Drive Accessory

5-HP Oversized Motor & Drive


For Standard Evaporator Fan Speed (RPM), reference Table 19. For High Evaporator Fan Speed (RPM), reference Table 20. For Oversized Evaporator Fan Speed (RPM), reference Table 21. Fan motor heat (MBH) = 3.15 x Fan BHP. Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table 22 to determine additional static pressure drop due to other options/accessories. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.
(i)

Field Supplied Fan Sheave BK120 Required. Field Supplied Belt may be necessary.

28

RT-PRC028-EN

Performance Data (15 Tons Standard Efficiency)


Table 12. Evaporator Fan Performance 15 Tons with Gas Heat YC*180E Standard Refrigeration System Downflow or Horizontal
External Static Pressure (Inches of Water) .10 CFM 4800 5400 6000 6600 7200 .20 .30 BHP 1.06 1.39 1.81 2.3 2.88 .40 RPM 515 549 585 624 663 BHP 1.20 1.54 1.96 2.46 3.06 .50 .60 BHP 1.50 1.87 2.29 2.81 3.42 .70 RPM 609 635 664 695 729 BHP 1.66 2.03 2.48 3.00 3.61 .80 RPM 640 662 689 719 751 BHP 1.83 2.21 2.67 3.20 3.82 .90 RPM 668 689 714 743 773 BHP 2.00 2.39 2.85 3.41 4.04 1.00 RPM 694 716 738 765 795 BHP 2.18 2.58 3.05 3.62 4.26 RPM BHP RPM BHP RPM 414 456 499 542 586 0.81 1.11 1.48 1.92 2.45 450 490 531 572 614 0.94 1.26 1.65 2.12 2.67 483 520 559 599 640 RPM BHP RPM 548 578 611 648 686 1.35 1.70 2.12 2.63 3.24 578 607 638 671 708

3-HP Standard Motor & Field Supplied Low Static Drive(i)

3-HP Standard Motor & Drive

5-HP Oversized Motor & Drive Continued External Static Pressure (Inches of Water) 1.10 CFM 4800 5400 6000 6600 7200 1.20 1.30 BHP 2.75 3.17 3.68 4.26 4.94 1.40 RPM 792 811 833 855 989 BHP 2.95 3.38 3.89 4.49 5.17 1.50 1.60 BHP 3.34 3.81 4.33 4.96 5.66 1.70 RPM 859 876 896 918 BHP 3.54 4.03 4.56 5.20 1.80 RPM 880 897 916 937 BHP 3.73 4.26 4.80 5.43 1.90 RPM 901 917 935 956 BHP 3.93 4.48 5.04 5.67 2.00 RPM 921 937 955 BHP 4.13 4.70 5.28 RPM BHP RPM BHP RPM 719 742 763 788 816 2.36 2.77 3.25 3.82 4.49 744 766 788 810 837 2.55 2.97 3.46 4.03 4.71 769 789 811 832 857 RPM BHP RPM 815 833 855 877 898 3.14 3.59 4.11 4.72 5.41 838 855 875 898 919

3-HP Standard Motor & Drive

3-HP Standard Motor & High Static Drive Accessory

5-HP Oversized Motor & Drive


For Standard Evaporator Fan Speed (RPM), reference Table 19. For High Evaporator Fan Speed (RPM), reference Table 20. For Oversized Evaporator Fan Speed (RPM), reference Table 21. Fan motor heat (MBH) = 3.15 x Fan BHP. Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table 22 to determine additional static pressure drop due to other options/accessories. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.
(i)

Field Supplied Fan Sheave BK120 required. Field Supplied Belt may be necessary.

RT-PRC028-EN

29

Performance Data (17 Tons Standard Efficiency)


Table 13. Evaporator Fan Performance 17 Tons TC*210E Standard Refrigeration System Downflow or Horizontal
External Static Pressure (Inches of Water) .10 CFM 5600 6300 7000 7700 8400 .20 .30 BHP 1.45 1.94 2.52 3.21 4.03 .40 RPM 547 588 631 675 720 BHP 1.60 2.10 2.71 3.43 4.27 .50 .60 BHP 1.91 2.43 3.07 3.84 4.73 .70 RPM 629 663 701 741 782 BHP 2.08 2.60 3.25 4.03 4.95 .80 RPM 656 687 723 761 802 BHP 2.26 2.79 3.44 4.23 5.16 .90 RPM 683 711 744 782 821 BHP 2.43 2.99 3.64 4.44 5.38 1.00 RPM 710 735 766 801 840 BHP 2.63 3.19 3.85 4.65 5.60 RPM BHP RPM BHP RPM 452 499 546 594 642 1.14 1.63 2.11 2.75 3.52 487 532 578 625 671 1.30 1.76 2.31 2.98 3.78 518 561 606 651 697 RPM BHP RPM 575 614 655 698 741 1.75 2.26 2.89 3.64 4.51 602 639 678 720 762

5-HP Standard Motor & Field Supplied Extra Low Static Drive(i) 5-HP Standard Motor & Field Supplied Low Static Drive(ii)

5-HP Standard Motor & High Static Drive Accessory Continued External Static Pressure (Inches of Water) 1.10 CFM 5600 6300 7000 7700 8400 1.20 1.30 BHP 3.23 3.82 4.51 5.34 6.30 1.40 RPM 807 830 852 881 912 BHP 3.43 4.04 4.74 5.59 6.55 1.50 1.60 BHP 3.86 4.49 5.22 6.07 7.08 1.70 RPM 872 894 917 939 967 BHP 4.09 4.72 5.47 6.32 7.34 1.80 RPM 893 913 937 958 984 BHP 4.32 4.95 5.72 6.58 7.60 1.90 RPM 914 933 957 978 1002 BHP 4.56 5.19 5.97 6.85 7.87 2.00 RPM 935 952 975 997 BHP 4.80 5.43 6.22 7.12 RPM BHP RPM BHP RPM 736 759 788 821 858 2.83 3.38 4.07 4.87 5.82 761 783 810 841 876 3.03 3.59 4.29 5.10 6.06 785 807 831 861 894 RPM BHP RPM 829 853 874 900 930 3.64 4.27 4.97 5.83 6.81 851 874 895 919 949

5-HP Standard Motor & Drive

5-HP Standard Motor & High Static Drive Accessory

7.5-HP Oversized Motor & Drive


For Standard Evaporator Fan Speed (RPM), reference Table 19. For High Evaporator Fan Speed (RPM), reference Table 20. For Oversized Evaporator Fan Speed (RPM), reference Table 21. Fan motor heat (MBH) = 3.15 x Fan BHP. Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table 22 to determine additional static pressure drop due to other options/accessories. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.
(i) (ii)

Field Supplied Fan Sheave 1B5V200 and Field Supplied Motor Sheave 1VP34 Required. Field Supplied Belt may be necessary. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary.

30

RT-PRC028-EN

Performance Data (17 Tons Standard Efficiency)


Table 14. Evaporator Fan Performance 17 Tons with Gas Heat YC*210E Standard Refrigeration System Downflow or Horizontal
External Static Pressure (Inches of Water) .10 CFM 5600 6300 7000 7700 8400 .20 .30 BHP 1.52 2.04 2.68 3.43 4.31 .40 RPM 561 604 650 697 745 BHP 1.67 2.20 2.85 3.64 4.55 .50 .60 BHP 2.00 2.54 3.20 4.02 4.98 .70 RPM 644 679 718 760 804 BHP 2.18 2.73 3.40 4.21 5.18 .80 RPM 670 704 740 780 823 BHP 2.35 2.93 3.60 4.42 5.39 .90 RPM 697 728 763 800 841 BHP 2.53 3.12 3.82 4.64 5.62 1.00 RPM 723 751 785 821 860 BHP 2.73 3.32 4.04 4.87 5.85(ii) RPM BHP RPM BHP RPM 521 571 622 674 1.69 2.27 2.96 3.80 551 600 650 700 1.88 2.48 3.20 4.05 533 579 626 674 723 RPM BHP RPM 589 629 673 719 765 1.83 2.36 3.03 3.83 4.77 617 654 695 739 785

5-HP Standard Motor & Field Supplied Low Static Drive(i)

5-HP Standard Motor & Drive

5-HP Standard Motor & High Static Drive Accessory Continued External Static Pressure (Inches of Water) 1.10 CFM 5600 6300 7000 7700 8400 1.20 1.30 BHP 3.33 3.96 4.70 5.59 6.61 1.40 RPM 818 844 870 900 934 BHP 3.54 4.18 4.93 5.83 6.87 1.50 1.60 BHP 3.98 4.64 5.41 6.32 7.40 1.70 RPM 882 907 932 958 988 BHP 4.20 4.87 5.66 6.57 7.66 1.80 RPM 903 926 952 977 BHP 4.43 5.10 5.92 6.84 1.90 RPM 923 945 971 996 BHP 4.66 5.35 6.17 7.11 2.00 RPM 943 964 990 BHP 4.89 5.60 6.42 RPM BHP RPM BHP RPM 749 775 806 841 878 2.93 3.52 4.26 5.11 6.09 773 798 828 861 897 3.13 3.74 4.48 5.35 6.34 796 822 849 881 916 RPM BHP RPM 840 866 891 920 953 3.75 4.41 5.17 6.07 7.14 861 887 912 939 971

5-HP Standard Motor & Drive

5-HP Standard Motor & High Static Drive Accessory

7.5-HP Oversized Motor & Drive


For Standard Evaporator Fan Speed (RPM), reference Table 19. For High Evaporator Fan Speed (RPM), reference Table 20. For Oversized Evaporator Fan Speed (RPM), reference Table 21. Fan motor heat (MBH) = 3.15 x Fan BHP. Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table 22 to determine additional static pressure drop due to other options/accessories. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.
(i) (ii)

Field Supplied Fan Sheave BK190 required. Field Supplied Belt may be necessary. 7.5 HP Oversized Motor & Drive

RT-PRC028-EN

31

Performance Data (20 Tons Standard Efficiency)


Table 15. Evaporator Fan Performance 20 Tons TC*240E Standard Refrigeration System Downflow or Horizontal
External Static Pressure (Inches of Water) .10 CFM 6400 7200 8000 8800 9600 .20 .30 BHP 2.03 2.72 3.56 4.55 5.74 RPM 595 646 696 747 799 .40 BHP 2.19(ii) 2.92 3.80 4.83 6.04 .50 .60 BHP 2.51 3.27 4.22 5.34 6.63 .70 RPM 669 711 759 808 859 BHP 2.69 3.45 4.41 5.56 6.90 .80 RPM 693 733 778 826 876 BHP 2.89 3.65 4.60 5.77 7.14 .90 RPM 717 755 797 844 893 BHP 3.09 3.86 4.81 5.98 7.37 1.00 RPM 741 777 817 861 909 BHP 3.29 4.08 5.03 6.20 7.59 RPM BHP RPM BHP RPM 506 560 616 671 728 1.64 2.28 3.07 4.04 5.19 540 592 645 698 753 1.84 2.50 3.31 4.29 5.46 570 620 672 724 776 RPM BHP RPM 620 668 719 769 820 2.34 3.10 4.02 5.10 6.34 644 690 739 790 840

5-HP Standard Motor & Field Supplied Extra Low Static Drive(i)

5-HP Standard Motor & Drive Continued

7.5-HP Standard Motor w/Field Supplied Motor Sheave(iii) External Static Pressure (Inches of Water)

7.5-HP Oversized Motor & Drive

1.10 CFM 6400 7200 8000 8800 9600

1.20

1.30 BHP 3.91 4.76 5.76 6.93 8.32

1.40 RPM 832 862 896 933 974 BHP 4.12 4.99 6.01 7.19 8.58

1.50

1.60 BHP 4.57 5.46 6.52 7.74

1.70 RPM 896 922 953 986 BHP 4.80 5.69 6.77 8.01

1.80 RPM 916 942 971 BHP 5.04 5.94 7.03

1.90 RPM 936 961 989 BHP 5.29 6.19 7.29

2.00 RPM 955 980 BHP 5.54 6.44

RPM BHP RPM BHP RPM 765 799 837 879 925 3.49 4.31 5.26 6.43 7.83 788 820 857 897 941 3.70 4.53 5.51 6.67 8.07 810 841 876 915 958

RPM BHP RPM 854 883 915 951 4.34 5.22 6.26 7.46 875 902 934 969

5-HP Standard Motor & Drive

5-HP Standard Motor & High Static Drive Accessory

7.5-HP Oversized Motor & Drive


For Standard Evaporator Fan Speed (RPM), reference Table 19. For High Evaporator Fan Speed (RPM), reference Table 20. For Oversized Evaporator Fan Speed (RPM), reference Table 21. Fan motor heat (MBH) = 3.15 x Fan BHP. Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table 22 to determine additional static pressure drop due to other options/accessories. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.
(i) (ii) (iii)

Field Supplied Fan Sheave B5V200 and Field Supplied Motor Sheave 1VP34 Required. Field Supplied Belt may be necessary. 5-HP Standard Motor & Field Supplied Low Static Drive - Field Supplied Fan Sheave BK190 required. Field Supplied Belt may be necessary. Field Supplied Belt may be necessary.

32

RT-PRC028-EN

Performance Data (20 Tons Standard Efficiency)


Table 16. Evaporator Fan Performance 20 Tons with Gas Heat YC*240E Standard Refrigeration System Downflow or Horizontal
External Static Pressure (Inches of Water) .10 CFM 6400 7200 8000 8800 9600 .20 .30 RPM 586 640 965 750 807 BHP 2.13 2.88 3.79 4.87 6.15 .40 RPM 611 664 718 772 827 BHP 2.28 3.06 4.01 5.13 6.45 .50 .60 .70 RPM 684 729 778 830 883 BHP 2.82 3.61 4.61 5.81 7.23 .80 RPM 709 751 798 848 900 BHP 3.02 3.82 4.82 6.03 7.46 .90 RPM 733 773 817 866 916 BHP 3.22 4.04 5.04 6.25 7.70 1.00 RPM 756 795 837 883 933 BHP 3.41 4.26 5.27 6.48 7.94 RPM BHP RPM BHP 527 585 643 702 761 1.76 2.44 3.29 4.33 5.56 558 614 670 727 784 1.96 2.67 3.54 4.59 5.85 RPM BHP RPM BHP 635 686 739 792 847 2.45 3.24 4.21 5.37 6.73 660 708 759 811 865 2.62 3.42 4.41 5.60 6.99

5-HP Standard Motor & Field Supplied Low Static Drive(i)

5-HP Standard Motor & Drive

7.5-HP Oversized Motor w/Field Supplied Sheave(ii) Continued

7.5-HP Oversized Motor & Drive

External Static Pressure (Inches of Water) 1.10 CFM 6400 7200 8000 8800 9600 1.20 1.30 RPM 852 857 896 937 BHP 4.05 4.94 6.01 7.25 1.40 RPM 846 878 915 955 BHP 4.27 5.17 6.26 7.52 1.50 1.60 1.70 RPM 909 938 970 BHP 4.96 5.90 7.01 1.80 RPM 929 958 989 BHP 5.20 6.14 7.26 1.90 RPM 949 978 BHP 5.45 6.38 2.00 RPM 968 999 BHP 5.71 6.63 RPM BHP RPM BHP 779 816 857 901 949 3.62 4.49 5.57 6.73 8.19 802 837 876 919 965 3.83 4.71 5.76 6.98 8.44 RPM BHP RPM BHP 868 898 933 973 4.49 5.41 6.51 7.80 889 919 952 991 4.72 5.65 6.76 8.07

5-HP Standard Motor & Drive

5-HP Standard Motor & High Static Drive Accessory

7.5-HP Oversized Motor & Drive


For Standard Evaporator Fan Speed (RPM), reference Table 19. For High Evaporator Fan Speed (RPM), reference Table 20. For Oversized Evaporator Fan Speed (RPM), reference Table 21. Fan motor heat (MBH) = 3.15 x Fan BHP. Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table 22 to determine additional static pressure drop due to other options/accessories. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.
(i) (ii)

Field Supplied Fan Sheave BK190 required. Field Supplied Belt may be necessary. Motor Sheave IVP50 required. Field Supplied Belt may be necessary.

RT-PRC028-EN

33

Performance Data (25 Tons Standard Efficiency)


Table 17. Evaporator Fan Performance 25 Ton TC*300E
External Static Pressure (Inches of Water) .10 CFM 7000 7500 8000 8500 9000 9500 10000 10500 11000 RPM BHP 610 644 677 714 747 785 816 3.03 3.61 4.22 4.98 5.73 6.68 7.53 .20 RPM 607 639 673 705 739 773 806 840 BHP 2.74 3.26 3.86 4.50 5.25 6.07 6.93 7.90 .30 RPM 603 635 667 699 731 764 797 829 864 BHP 2.50 2.97 3.50 4.09 4.77 5.53 6.35 7.25 8.27 .40 RPM 629 660 691 723 755 787 818 851 885 BHP 2.69 3.18 3.74 4.36 5.05 5.81 6.62 7.54 8.58 .50 .60 BHP 3.04 3.57 4.17 4.83 5.57 6.37 7.24 8.18 .70 RPM 698 726 755 785 816 846 878 908 BHP 3.22 3.76 4.37 5.04 5.81 6.63 7.52 8.48 .80 RPM 720 747 775 804 834 864 896 BHP 3.41 3.95 4.57 5.26 6.03 6.87 7.81 .90 RPM 741 767 795 823 852 882 912 BHP 3.61 4.16 4.78 5.48 6.25 7.10 8.04 1.00 RPM 763 787 814 841 870 899 929 BHP 3.82 4.36 4.99 5.69 6.48 7.34 8.30 RPM BHP RPM 653 683 714 745 776 807 839 872 2.87 3.38 3.97 4.61 5.31 6.08 6.93 7.86 675 704 735 765 796 828 859 891

7.5 HP Standard Motor & Low Static Drive Accessory

7.5 HP Standard Motor & Drive

7.5 HP Standard Motor & Drive Continued External Static Pressure (Inches of Water) 1.10 CFM 7000 7500 8000 8500 9000 9500 10000 10500 11000 RPM BHP 786 808 833 860 887 915 945 4.05 4.59 5.21 5.92 6.71 7.58 8.55 1.20 RPM 809 829 852 877 904 932 BHP 4.28 4.82 5.44 6.15 6.95 7.83 1.30 RPM 831 850 871 895 921 949 BHP 4.51 5.07 5.69 6.39 7.19 8.08 1.40 RPM 852 871 891 913 938 965 BHP 4.73 5.31 5.94 6.64 7.44 8.33 -

7.5 HP Standard Motor & High Static Drive Accessory

1.50 RPM BHP 872 892 911 932 955 981 4.94 5.56 6.21 6.91 7.70 8.60 -

7.5-HP Standard Motor & Sheaves

7.5 HP Standard Motor & High Static Drive Accessory


For Standard Evaporator Fan Speed (RPM), reference Table 19. For High Evaporator Fan Speed (RPM), reference Table 20. For Oversized Evaporator Fan Speed (RPM), reference Table 21. Fan motor heat (MBH) = 3.15 x Fan BHP. Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table 22 to determine additional static pressure drop due to other options/accessories. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.

34

RT-PRC028-EN

Performance Data (25 Tons Standard Efficiency)


Table 18. Evaporator Fan Performance 25 Ton YC*300E
External Static Pressure (Inches of Water) .10 CFM 7000 7500 8000 8500 9000 9500 10000 10500 11000 RPM BHP 607 641 678 717 752 791 828 867 2.75 3.27 3.89 4.63 5.38 6.27 7.23 8.33 .20 RPM 599 634 670 705 740 777 814 850 886 BHP 2.46 2.97 3.54 4.16 4.86 5.68 6.56 7.55 8.60 .30 RPM 625 659 693 728 763 799 834 869 BHP 2.66 3.18 3.76 4.42 5.14 5.97 6.86 7.80 .40 RPM 649 682 716 750 785 818 854 889 BHP 2.84 3.38 3.99 4.67 5.43 6.23 7.16 8.15 .50 .60 BHP 3.19 3.76 4.39 5.11 5.89 6.76 7.73 .70 RPM 716 746 777 808 841 874 908 BHP 3.38 3.94 4.59 5.30 6.12 7.00 7.99 .80 RPM 738 767 797 827 859 891 924 BHP 3.58 4.15 4.80 5.53 6.34 7.24 8.24 .90 RPM 760 787 816 846 877 908 940 BHP 3.79 4.36 5.02 5.75 6.57 7.48 8.47 1.00 RPM 783 807 835 864 894 925 BHP 4.01 4.57 5.24 5.98 6.81 7.72 RPM BHP RPM 672 704 737 770 804 838 872 907 3.01 3.57 4.19 4.89 5.66 6.50 7.43 8.45 694 725 757 790 823 856 891

7.5 HP Standard Motor & Low Static Drive Accessory

7.5 HP Standard Motor & Drive

5 HP Standard Motor & Drive Continued External Static Pressure (Inches of Water) 1.10 CFM 7000 7500 8000 8500 9000 9500 10000 10500 11000 RPM BHP 805 828 853 882 911 941 4.24 4.82 5.46 6.21 7.04 7.96 1.20 RPM 827 850 873 900 928 957 BHP 4.47 5.06 5.72 6.45 7.29 8.21 1.30 RPM 849 871 893 918 945 974 BHP 4.69 5.31 5.97 6.71 7.55 8.48 1.40 RPM 869 891 913 936 961 BHP 4.91 5.55 6.24 6.97 7.80

7.5 HP Standard Motor & High Static Drive Accessory

1.50 RPM BHP 888 911 933 955 979 5.13 5.79 6.50 7.26 8.08

7.5 HP Standard Motor & Drive

7.5 HP Standard Motor & High Static Drive Accessory


For Standard Evaporator Fan Speed (RPM), reference Table 19. For High Evaporator Fan Speed (RPM), reference Table 20. For Oversized Evaporator Fan Speed (RPM), reference Table 21. Fan motor heat (MBH) = 3.15 x Fan BHP. Notes: Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table 22 to determine additional static pressure drop due to other options/accessories. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be affected.

RT-PRC028-EN

35

Performance Data
Table 19.
Tons 12 15 17 20 25
Factory set at 3 turns open.

Standard Motor & Drive/Fan Speed (Rpm)


Unit Model Number T/YC*150E3,4,W T/YC*180E3,4,W T/YC*210E3,4,W T/YC*240E3,4,W T/YC*300E3,4,W 6 Turns Open 640 560 615 615 694 5 Turns Open 680 600 659 659 731 4 Turns Open 720 640 703 703 768 3 Turns Open 760 680 747 747 805 2 Turns Open 800 720 791 791 842 1 Turn Open 840 760 835 835 881 Closed N/A N/A N/A N/A N/A

Table 20.
Tons 12 15 17 20 25

Standard Motor & High Static Drive Accessory Sheave/Fan Speed (Rpm)
Unit Model Number T/YC*150E3,4,W T/YC*180E3,4,W T/YC*210E3,4,W T/YC*240E3,4,W T/YC*300E3,4,W 6 Turms Open 807 640 835 835 806 5 Turns Open 857 680 879 879 844 4 Turns Open 908 720 923 923 882 3 Turns Open 958 760 967 967 920 2 Turns Open 1009 800 1011 1011 958 1 Turn Open 1059 840 1055 1055 994 Closed N/A N/A N/A N/A N/A

Table 21.
Tons 12 15 17 20

Oversized Motor & Drive Fan Speed (Rpm)


Unit Model Number T/YC*150E3,4,W T/YC*180E3,4,W T/YC*210E3,4,W T/YC*240E3,4,W Fan Sheave 869 705 816 816 5 Turns Open 923 755 853 853 4 Turns Open 978 806 890 890 3 Turns Open 1032 856 928 928 2 Turns Open 1087 907 965 965 1 Turn Open 1141 957 1002 1002 Closed N/A N/A N/A N/A

36

RT-PRC028-EN

Performance Data (12-20 Tons)


Table 22. Static Pressure Drop Through Accessories (Inches Water Column)
Economizer with OA/RA Dampers(i) Unit Model Number T/Y*150E Standard Filters 2" Pleated (iii) Filter(iv) 0.05 0.07 0.10 0.04 0.06 0.09 0.03 0.05 0.07 0.06 0.09 0.12 0.05 0.07 0.10 0.07 0.11 0.16 0.06 0.09 0.13 0.09 0.14 0.21 0.07 0.11 0.17 0.08 0.11 0.15 0.07 0.10 0.13 0.06 0.09 0.11 0.08 0.11 0.14 0.08 0.11 0.14 0.11 0.15 0.20 0.10 0.13 0.17 0.13 0.18 0.25 0.11 0.15 0.22 100% OA 0.19 0.26 0.33 0.14 0.20 0.27 0.14 0.20 0.27 0.18 0.26 0.35 0.18 0.26 0.35 0.22 0.32 0.44 0.22 0.32 0.44 0.26 0.4 0.57 0.26 0.4 0.6 100% RA 0.02 0.03 0.04 0.03 0.04 0.05 0.03 0.04 0.05 0.04 0.04 0.06 0.04 0.04 0.06 0.04 0.05 0.07 0.04 0.05 0.07 0.04 0.07 0.1 0.04 0.07 0.1 Electric Heater Accessory (kW)(ii)

Tons 12

CFM 4000 5000 6000

5-12

14-27 0.03 0.04 0.06 0.04 0.06 0.09 0.04 0.06 0.09

36 0.03 0.05 0.07 0.04 0.07 0.10 0.04 0.07 0.10 0.05 0.08 0.12 0.05 0.08 0.12 0.06 0.10 0.14 0.06 0.10 0.14 0.08 0.13 0.18 0.08 0.13 0.18

54 0.04 0.06 0.09 0.05 0.08 0.12 0.05 0.08 0.12 0.06 0.09 0.13 0.06 0.09 0.13 0.08 0.12 0.17 0.08 0.12 0.17 0.10 0.15 0.22 0.10 0.15 0.22

72 0.07 0.11 0.16 0.07 0.11 0.16 0.09 0.14 0.20 0.09 0.14 0.20 0.11 0.18 0.26 0.11 0.18 0.26

15

T/YCD180E

4800 6000 7200

T/YCH180E

4800 6000 7200

17

T/YCD210E

5600 7000 8400

T/YCH210E

5600 7000 8400

20

T/YCD240E

6400 8000 9600

T/YCH240E

6400 8000 9600

25

TCD300E

7000 9000 11000

TCH300E

7000 9000 11000

(i) (ii) (iii) (iv)

OA = Outside Air and RA = Return Air. Nominal kW ratings at 240, 480, 600 volts. Tested with: 2" filters 12-25 tons. Difference in pressure drop should be considered when utilizing optional 2 pleated filters. Indicates both downflow and horizontal units.

Table 23.

Gas Fired Heating Capacities


Unit Model Heating Input MBH(i) 150/100 250/175 250/175 350/250 250/175 350/250 250/175 400/300 250/175 400/300 Heating Output MBH(ii) 122/81 203/142 203/142 284/203 203/142 284/203 203/142 324/243 203/142 324/243 Air Temp. Rise, F 10-40 25-55 15-45 35-65 15-45 35-65 15-45 25-55 15-45 25-55

Tons 12 15 17 20 25
(i) (ii)

Number YC*150E-L1 YC*150E-H1 YC*180E-L1 YC*180E-H1 YC*210E-L1 YC*210E-H1 YC*240E-L1 YC*240E-H1 YC*300E-L1 YC*300E-H1

For two stage heaters (input or output), Second stage is total heating capacity. Second Stage/First Stage. For two stage heaters (input or output), Second stage is total heating capacity. Second Stage/First Stage.

RT-PRC028-EN

37

Performance Data

Table 24.

Auxiliary Electric Heat Capacity


Total(i) Unit Model kW Input(ii) 18.00 27.00(iii) 36.00 54.00 MBH Output 61.47 92.15 122.94 184.41 122.94 184.41 245.88 No. of Stages 1 2 2 2 2 2 2 kW Input 18.00 9.00 18.00 36.00 18.00 36.00 36.00 Stage1 MBH Output 61.47 30.72 61.47 122.94 61.47 122.94 122.94 kW Input 18.00 18.00 18.00 18.00 18.00 36.00 Stage 2 MBH Output 61.43 61.47 61.47 61.47 61.47 122.94

Tons 12-15

Number. TC*150 or 180E3,E4,EW

17-25

TC*210, 240, or 300E3, E4, EW

36.00 54.00 72.00

(i) (ii) (iii)

Heaters are rated at 240v,380v,480v and 600v. For other than rated voltage, CAP= (voltage/rated voltage)2 x rated cap. For all input/output categories, does not include fan power or heat. 27 kW heater can be used with TCD180E4, TCD210E4, TCD240E4, and TCD300E4 only. Cannot be used with oversized motor. Indicates both downflow and horizontal units.

Table 25.
Nominal Voltage

Electric Heater Voltage Correction Factors (Applicable to Auxiliary Heat Capacity)


Distribution Voltage 208 Capacity Multiplier 0.75 0.92 1.00 0.84 0.94 1.00 0.81 0.92 1.00

240

230 240 440

480

460 480 540

600

575 600

Table 26.

Air Temperature Rise Across Electric Heaters (Degrees F)


12 Tons 5000 CFM Three Phase TC*150E 11.4 22.8 34.1 15 Tons 6000 CFM Three Phase TC*180E 9.5 14.2(i) 19.0 28.5 17 Tons 7000 CFM Three Phase TC*210E 12.2 16.3 24.4 32.5 20 Tons 8000 CFM Three Phase TC*240E 10.7 14.2 21.3 28.5 25 Ton 9000 CFM Three Phase TC*300E 9.5 12.6 19.0 25.3

kW 9.00 17.30 18.00 27.00 36.00 54.00 72.00

Stages 1 1 1 2 2 2 2

For minimum design airflow, see airflow performance table for each unit. To calculate temp rise at different airflow, use the following formula: Temp. rise across Electric Heater = kWx3414/1.08xCFM. *Indicates both downflow and horizontal units.
(i)

27 kW heater can be used with TCD180E4, TCD210E4, TCD240E4, and TCD300E4 only. Cannot be used with oversized motor.

38

RT-PRC028-EN

Controls
ReliaTel Controlled Units
Zone Sensors are the building occupants comfort control devices. They replace the conventional electro-mechanical thermostats. The following zone sensor options are available for Voyager units with ReliaTel control:

Dual Thermistor Remote Zone Sensor


This sensor will allow the customer to reduce the total number of remote sensors to obtain space temperature averaging. This sensor should be utilized with ReliaTel controls.

Manual/Automatic Changeover
Auto, Heat, Cool or Off System Switch. Fan Auto or Off Switch. Two temperature setpoint levers. Optional Status Indication LED lights, System On, Heat, Cool, or Service.

Economizer Controls
The standard equipment offering is a fixed dry bulb changeover control. In addition, there are two optional controls, Enthalpy and Differential Enthalpy Control.

Differential Enthalpy
Replaces the standard dry bulb control with two enthalpy sensors that compare total heat content of the indoor air and outdoor air to determine the most efficient air source. This control option offers the highest level of comfort control, plus energy efficiency, available.

Programmable Night Setback


Auto or manual changeover with seven-day programming. Keyboard selection of Heat, Cool, Fan, Auto, or On. All programmable sensors have System On, Heat, Cool, Service LED/ indicators as standard. Night Setback Sensors have one (1) Occupied, one (1) Un-occupied, and two (2) Override programs per day.

Enthalpy Control
Replaces the dry bulb control with a wet bulb changeover controller which has a fully adjustable set point. Enthalpy control offers a higher level of comfort control, along with energy savings potential, than the standard dry bulb control. This is due to the additional wet bulb sensing capability.

Differential Pressure Switches


This factory or field-installed option allows individual fan failure and dirty filter indication. The fan failure switch will disable all unit functions and flash the Service LED on the zone sensor. The dirty filter switch will light the Service LED on the zone sensor and will allow continued unit operation.

Mo

Integrated Comfort System


Sensor(s) available with optional temperature adjustment and override buttons to provide central control through a Trane Integrated Comfort system.

PM OCCUPIED
MODE AUTO FAN AUTO

MODE

Digital Display Zone Sensor


The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone sensors. This sensor includes a digital display of set point adjustment and space temperature in F (Fahrenheit) or C (Celsius). Includes FAN and SYSTEM buttons (supports the service functions of the standard sensor). E-squared memory stores last programmed set points. Requires 24 VAC (Volts AC). This sensor should be utilized with ReliaTel controls.

Remote Sensor
Sensor(s) available for all zone sensors to provide remote sensing capabilities.

Manual Changeover
Heat, Cool or Off System Switch. Fan Auto or Off Switch. One temperature setpoint lever.

Remote Potentiometer
Minimum position setting of economizer can be remotely adjusted with this accessory.

RT-PRC028-EN

39

Controls

Trane Communication Interface (TCI)


This factory or field-installed microprocessor interface allows the unit to communicate to Tranes Integrated ComfortTM system.

Touchscreen Programmable Thermostat (2H/2C)


Two Heat/Two Cool programmable thermostat with touch screen digital display. Menu-driven programming. Effortless set-up. Program each day separately with no need to copy multiple days. All programming can be done on one screen. Easy to read and use. Large, clear backlit digital display.

Digital Display Thermostat (3H/2C)


Three Heat, Two Cool digital display thermostat. Easy access battery replacement. Flip-out door for easy battery replacement without removing or disassembling the thermostat.

CO2 Sensing
The CO2 sensor shall have the ability to monitor space occupancy levels within the building by measuring the parts per million of CO2 (Carbon Dioxide) in the air. As the CO2 levels increase, the outside air damper modulates to meet the CO2 space ventilation requirements. The CO2 accessory shall be available as field installed.

MON
FAN ON AUTO CIRC

TUE

WED

THU

FRI

SAT

SUN

HEAT

SYSTEM EM HEAT HEAT OFF COOL AUTO DONE

RESET

CANCEL PERIOD

DEHUMIDIFIER

PM

COOL

EDIT

WAKE

LEAVE

RETURN

SLEEP

CANCEL

RA Remote Sensor
Return Air Remote Sensor which can be mounted in the return air duct to report return air temperature.

Digital Display Programmable Thermostat with Built-In Relative Humidity Sensing (3H/2C)
Three Heat/Two Cool digital display thermostat with built-in humidity control and display. This thermostat combines both humidity and dry bulb into one. Fully programmable with night setback.
Tue

Room Remote Sensor


Space Remote Sensor which can be mounted on the wall to report/control from a remote location in the space.

Digital Display Programmable Thermostat (2H/2C)


Two Heat/Two Cool digital display thermostat. 7-day programmable stat with night setback shall be available.

Tue Hold Until

Heat

Auto

System & Fan

Override

More

40

RT-PRC028-EN

Electrical Data
Table 27. Unit Wiring with Cooling (No Electric Heat) or Gas Heat Standard Refrigeration System
Standard Indoor Fan Motor Unit Operating Voltage Range
187-253 414-506 517-633 187-253 414-506 517-633 187-253 414-506 517-633 187-253 414-506 517-633 187-253 414-506 517-633

Oversize Indoor Fan Motor Maximum Fuse Size or Maximum Circuit Breaker
90 45 30 100 50 40 125 60 45 150 70 50

Ton s
12

Unit Model Number


T/YC*150E3 T/YC*150E4 T/YC*150EW

Minimum Circuit Ampacity(i)


63 33 26 76 39 30 88 45 33 113 49 40 115 59 45

Maximum Fuse Size or Maximum Circuit Breaker


80 40 30 90 50 40 110 60 45 150 60 50 125 70 50

Minimum Circuit Ampacity


74 35 27 82 42 32 96 49 36 121 53 42

15

T/YC*180E3 T/YC*180E4 T/YC*180EW

17

T/YC*210E3 T/YC*210E4 T/YC*210EW

20

T/YC*240E3 T/YC*240E4 T/YC*240EW

25

T/YC*300E3 T/YC*300E4 T/YC*300EW

(i)

For Standard and Oversized Indoor Fan Motor, values do not include power exhaust accessory. Indicates both downflow and horizontal units.

RT-PRC028-EN

41

Electrical Data (Standard Efficiency)


Table 28. Unit Wiring with Electric Heat (Single Point Connection) Standard Refrigeration System (Downflow and Horizontal)
Standard Indoor Motor Unit Model Number TC*150E3 Heater Model Number AYDHTRK318A/AYHHTRN318A AYDHTRK336A/AYHHTRP336A AYDHTRK354A/AYHHTRP354A 15 TC*180E3 AYDHTRK318A/AYHHTRN318A AYDHTRK336A/AYHHTRP336A AYDHTRK354A/AYHHTRP354A 17 TC*210E3 AYDHTRL336A/AYHHTRN336A AYDHTRL354A/AYHHTRN354A AYDHTRK372A/AYHHTRN372A 20 TC*240E3 AYDHTRL336A/AYHHTRN336A AYDHTRL354A/AYHHTRN354A AYDHTRK372A/AYHHTRN372A 25 TC*300E3 AYDHTRL336A / AYHHTRN336A AYDHTRL354A / AYHHTRN354A AYDHTRK372A / AYHHTRN372A 12 TC*150E4 AYDHTRL418A/AYHHTRN418A AYDHTRK436A/AYHHTRP436A AYDHTRK454A/AYHHTRP454A 15 TC*180E4 AYDHTRL418A/AYHHTRN418A AYDHTRK436A/AYHHTRP436A AYDHTRK454A/AYHHTRP454A 17 TC*210E4 AYDHTRL436A/AYHHTRN436A AYDHTRL454A/AYHHTRN454A AYDHTRK472A/AYHHTRN472A 20 TC*240E4 AYDHTRL436A/AYHHTRN436A AYDHTRL454A/AYHHTRN454A AYDHTRK472A/AYHHTRN472A 25 TC*300E4 AYDHTRL436A / AYHHTRN436A AYDHTRL454A / AYHHTRN454A AYDHTRK472A / AYHHTRN472A 12 TC*150EW AYDHTRKW18A/AYHHTRNW18A AYDHTRMW36A/AYHHTRPW36A AYDHTRKW54A/AYHHTRPW54A 15 TC*180EW AYDHTRKW18A/AYHHTRNW18A AYDHTRMW36A/AYHHTRPW36A AYDHTRKW54A/AYHHTRPW54A 17 TC*210EW AYDHTRMW36A/AYHHTRMW36A AYDHTRLW54A/AYHHTRNW54A AYDHTRKW72A/AYHHTRNW72A 20 TC*240EW AYDHTRMW36A/AYHHTRMW36A AYDHTRLW54A/AYHHTRNW54A AYDHTRKW72A/AYHHTRNW72A 25 TC*300EW AYDHTRMW36A/AYHHTRMW36A AYDHTRLW54A/AYHHTRNW54A AYDHTRKW72A/AYHHTRNW72A
(i)

Oversize Indoor Motor Max Fuse Size or Max Circuit Breaker(i) 90/90 125/150 175/200 100/100 125/150 175/200 125/150 175/200 225/250 150/150 175/200 225/250 45 70 100 50 70 100 70 100 125 70 100 125 30 60 80 40 60 80 60 80 100 60 80 100

Tons 12

Heater kW Rating 13.5/18.0 27.0/36.0 40.5/54.0 13.5/18.0 27.0/36.0 40.5/54.0 27.0/36.0 40.5/54.0 54.0/72.0 27.0/36.0 40.5/54.0 54.0/72.0 27.0/ 36.0 40.5/ 54.0 54.0/ 72.0 18.0 36.0 54.0 18.0 36.0 54.0 36.0 54.0 72.0 36.0 54.0 72.0 36.0 54.0 72.0 18.0 36.0 54.0 18.0 36.0 54.0 36.0 54.0 72.0 36.0 54.0 72.0 36.0 54.0 72.0

Control Stages 1 2 2 1 2 2 2 2 2 2 2 2 2 2 2 1 2 2 1 2 2 2 2 2 2 2 2 2 2 2 1 2 2 1 2 2 2 2 2 2 2 2 2 2 2

MCA 68/68 108/122 154/176 76/76 108/122 154/176 115/130 162/184 209/238 115/130 162/184 209/238 125/ 139 171/ 193 218/ 247 34 61 88 39 61 88 64 91 118 64 91 118 68 95 123 27 49 70 30 49 70 51 73 95 51 73 95 55 77 98

Max Fuse Size or Max Circuit Breaker 80/80 110/125 175/200 100/100 110/125 175/200 125/150 175/200 225/250 150/150 175/200 225/250 150/150 175/200 225/250 40 70 90 50 70 90 70 100 125 70 100 125 75 100 125 30 50 70 40 50 70 60 80 100 60 80 100 60 80 100

MCA 74/76 115/130 162/184 82/82 115/130 162/184 125/139 171/193 218/247 125/139 171/193 218/247 37 64 91 42 64 91 68 95 123 68 95 123 30 51 73 32 51 73 55 77 98 55 77 98

208/230 Volts Three Phase

460 Volts Three Phase

575 Volts Three Phase

Values do not include power exhaust accessory. Indicates both downflow and horizontal units.

42

RT-PRC028-EN

Electrical Data (Standard Efficiency)


Table 29. Electrical Characteristics Compressor Motor and Condenser Motor 60 Cycle
Compressor Motors Amps(i) Tons 12 Unit Model Number T/YC*150E3 T/YC*150E4 T/YC*150EW 15 T/YC*180E3 T/YC*180E4 T/YC*180EW 17 T/YC*210E3 T/YC*210E4 T/YC*210EW 20 T/YC*240E3 T/YC*240E4 T/YC*240EW 25 T/YC*300E3 T/YC*300E4 T/YC*300EW
(i) (ii)

Condenser Fan Motors Amps No. 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Phase 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 HP .50 .50 .50 .50 .50 .50 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 FLA 3.2 1.6 1.3 3.2 1.6 1.3 5.5 2.9 2.0 5.5 2.9 2.0 5.5 2.9 2 LRA 8.8 3.8 3.2 8.8 3.8 3.2 18.3 9.3 5.7 18.3 9.3 5.7 18.3 9.3 5.7

No. 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2

Volts 208-230 460 575 208-230 460 575 208-230 460 575 208-230 460 575 208-230 460 575

Phase 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

HP(ii) 5.60 5.60 5.60 8.60/4.75 8.60/4.75 8.60/4.75 10.0/4.5 10.0/4.5 10.0/4.5 11.4/6.9 11.4/6.9 11.4/6.9 10.0 10.0 10.0

RPM 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450 3450

RLA 22.4 10.6 7.7 30.1/20.5 16.7/9.6 12.2/7.7 33.5/18.2 18/9 12.8/6.8 48/25 18.6/12.2 15.2/10.1 35.4 18.5 14.2

LRA 149 75 54 225/155 114/75 80/54 239/137 125/62 80/50 245/164 125/100 100/78 239 125 80

For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps. HP for each compressor. *Indicates both downflow and horizontal units.

RT-PRC028-EN

43

Electrical Data

Table 30.

Electrical Characteristics Evaporator Fan Motor 60 Cycle Standard and Oversized


Standard Evaporator Fan Motor Amps(i) Unit Model Number T/YC*150E3 T/YC*150E4 Oversized Evaporator Fan Motor Amps No. 1 1 1 1 1 1 1 1 1 1 1 1 Volts 208-230 460 575 208-230 460 575 208-230 460 575 208-230 460 575 Phase 3 3 3 3 3 3 3 3 3 3 3 3 HP 5.00 5.00 5.00 5.00 5.00 5.00 7.50 7.50 7.50 7.50 7.50 7.50 FLA 16.7 7.6 6.1 16.7 7.6 6.1 24.2 11.0 9.0 24.2 11.0 9.0 LRA 109.8 54.9 41.6 109.8 54.9 41.6 120.4 74.0 60.0 120.4 74.0 60.0

Tons 12

No. 1 1 1 1 1 1 1 1 1 1

Volts 460 575 460 575 460 575 460 575 460 575

Phase 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

HP(ii) 3.00 3.00 3.00 3.00 3.00 3.00 5.00 5.00 5.00 5.00 5.00 5.00 7.50 7.50 7.50

FLA 10.6 4.8 3.9 10.6 4.8 3.9 16.7 7.6 6.1 16.7 7.6 6.1 24.2 11.0 9.0

LRA 81.0 40.5 31.0 81.0 40.5 31.0 109.8 54.9 41.6 109.8 54.9 41.6 120.4 74.0 60

1 208-230

T/YC*150EW 15 T/YC*180E3 T/YC*180E4 T/YC*180EW 17 T/YC*210E3 T/YC*210E4 T/YC*210EW 20 T/YC*240E3 T/YC*240E4 T/YC*240EW 25 T/YC*300E3 T/YC*300E4 T/YC*300EW
(i) (ii)

1 208-230

1 208-230

1 208-230

1 208-230

For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps. HP for each compressor. Indicates downflow and horizontal units.

Table 31.

Electrical Characteristics Combustion Blower Motor (Gas/Electric)


Amps Heating Stages 2 2

Unit Model Number YC*150E YC*180E, 210E, 240E, 300E


(i)

Heat Low Low

HP 1/20 1/10

RPM(i) 3500/2800 3500/2800

Volts 208-230 208-230

Phase 1 1

FLA 0.5 0.8

LRA 0.78 2.00

High/Low Speed. Indicates both downflow and horizontal units.

Table 32.

Electrical Characteristics Power Exhaust (Cooling and Gas/Electric)


Amps Volts 208-230 460 575 Phase 1 1 1 HP 3/4 3/4 3/4 RPM 1040 1040 1040 FLA 6.6 3.2 2.1 LRA 13.5 8.4 5.2

Tons 12-25

44

RT-PRC028-EN

Jobsite Connections
Table 33.
A

Typical Number of Wires


Manual Changeover.............................. 4 Manual/Auto Changeover...................... 5 Manual/Auto Changeover with Status Indication LEDs......................... 10 Programmable Night Setback with Status Indication LEDs................... 7

Zone Sensors

Thermostats B 3 Power Wires + 1 Ground Wire (three phase) 2 Power Wires + 1 Ground Wire (single phase)

DISCONNECT SWITCH (BY OTHERS)

B ZONE SENSOR OR THERMOSTAT A ROOFTOP UNIT

For specific wiring information, see the installation instructions. All wiring except power wire is low voltage. All customer supplied wiring to be copper and must conform to applicable electrical codes (such as NEC or CEC) and local electric codes. Wiring shown dotted is to be furnished and installed by the customer.

RT-PRC028-EN

45

Typical Wiring

Figure 2. 46

12.5-25 Tons Cooling with Optional Electric Heat.


RT-PRC028-EN

Typical Wiring (12-25 Tons Cooling with Optional Electric Heat)

Figure 2. (continued from previous page)12-25 Tons Cooling with Optional Electric Heat - for specific wiring, see service facts.
RT-PRC028-EN

47

Typical Wiring (12-25 Tons Cooling with Optional Electric Heat)

Figure 3.
48

12-25 Tons Cooling with Optional Electric Heat - for specific wiring, see service facts.
RT-PRC028-EN

Typical Wiring (12-25 Tons Cooling with Optional Electric Heat)

Figure 3. (continued from previous page)12-25 Tons Cooling with Optional Electric Heat - for specific wiring, see service facts.
RT-PRC028-EN

49

Typical Wiring (12-25 Tons Gas/Electric)

Figure 4.
50

12-25 Tons Gas/Electric- for specific wiring, see service facts.


RT-PRC028-EN

Typical Wiring (12-25 Tons Gas/Electric)

Figure 4. (continued from previous page)12-25 Tons Gas/Electric - for specific wiring, see service facts.
RT-PRC028-EN

51

Typical Wiring (12-25 Tons Gas/Electric)

Figure 5.
52

12-25 Tons Gas/Electric- for specific wiring, see service facts.


RT-PRC028-EN

Typical Wiring (12-25 Tons Gas/Electric)

Figure 5. (continued from previous page)12-25 Tons Gas/Electric- for specific wiring, see service facts.
RT-PRC028-EN

53

Dimensional Data

1819 MM

50 1/8

1229 MM

168 MM

Figure 6.

* All dimensions are in inches/millimeters. **1/2 NPT Gas Connection = (Y_C Models only); 2" Electrical Connection: Single Point Power When Heat Installed (T_C Models only.)

Cooling with Optional Electric Heat and Gas/Electric Models - 12 Tons Standard Efficiency

Figure 7. Cooling with Optional Electric Heat and Gas/Electric Models - 12 Tons Standard Efficiency Horizontal Unit Clearance
* All dimensions are in inches/millimeters.

54

RT-PRC028-EN

Dimensional Data (Standard Efficiency)

Figure 8. Cooling with Optional Electric Heat and Gas/Electric Models 12 Tons Standard Efficiency - Roof Curb
* All dimensions are in inches/millimeters.

26 5/16

Figure 9. Cooling with Optional Electric Heat and Gas/Electric Models 12 Tons Standard Efficiency - Downflow Duct Connections - Field Fabricated
* Duct flanges mount 7-7/16" down inside the curb on the 1-1 curb flanges. Roofcurb is intended for downflow use only. * All dimensions are in inches/millimeters.

Figure 10. Cooling with Optional Electric Heat and Gas/Electric Models 12 Standard Efficiency - Downflow Unit Supply/Return and Unit Clearance
* All dimensions are in inches/millimeters.

RT-PRC028-EN

55

Dimensional Data (Standard Efficiency)

2138 MM

Figure 11. Cooling with Optional Electric Heat and Gas/Electric Models - 15-25 Tons Standard Efficiency
* All dimensions are in inches/millimeters.

Figure 12. Cooling with Optional Electric Heat and Gas/Electric Models - 15-25 Tons Standard Efficiency - Unit Clearance and Horizontal Unit Supply/Return
* All dimensions are in inches/millimeters.

56

RT-PRC028-EN

Dimensional Data (Standard Efficiency)

Figure 13. Cooling with Optional Electric Heat and Gas/Electric Models 15-25 Tons Standard Efficiency - Roof Curb
* All dimensions are in inches/millimeters.

Figure 14. Cooling with Optional Electric Heat and Gas/Electric Models 15-25 Tons Standard Efficiency - Downflow Duct Connections - Field Fabricated
* Duct flanges mount 7-7/16" down inside the curb on the 1-1 curb flanges. Roofcurb is intended for downflow use only. * All dimensions are in inches/millimeters.

Figure 15. Cooling with Optional Electric Heat and Gas/Electric Models 15-25 Tons Standard Efficiency - Downflow Unit Clearance
* All dimensions are in inches/millimeters.

RT-PRC028-EN

57

Dimensional Data (12-25 Tons)

Table 34.
Tons

High Efficiency Units (Cooling and Gas/Electric)


Condensate Downflow Only A B 22 1/2 28 3/4 C 18 11/16 19 15/16 D 4 1/4 4 1/4 F 4 1/4 4 1/4 G H 1 NPT 1 NPT 26 7/16 26 7/16 62 7/16 54 11/16 76 5/16 68 11/16 Drain Size Condensate Drain Location Downflow J 25 5/8 26 3/4 Horizontal K 6 5 3/8

12 15-25

58

RT-PRC028-EN

Dimensional Data (12-25 Tons)


Table 35.
Unit Model # TCD150E TCD180, 210-300E TCH150E TCH180, 210-300E A 42 3/8 29 1/2 42 3/8 29 1/2 B 48 3/8 56 N/A N/A C 31 38 1/2 31 38 1/2 D N/A 18 1/2 N/A 18 1/2 E N/A N/A 12 14

All dimensions are in inches.

TOP VIEW SHOWING THROUGH THE BASE ELECTRICAL UTILITY LOCATIONS AND ACCESS PANEL SWING CLEARANCES.

6 7/8" SWING RADIUS (E) HORIZONTAL FILTER ACCESS PANEL

SWING RADIUS (A) ID SECTION ACCESS PANEL SWING RADIUS (D) ID FAN SECTION ACCESS PANEL THROUGH THE BASE ELECTRICAL

SWING RADIUS (C) OD SECTION ACCESS PANEL

Figure 16.
Table 36.

Cooling Unit - Swing Diameter & Through the Base Electrical

Unit Model # YCD150E YCD180, 210, 300E YCH150E YCH180, 210, 300E

A 42 3/8 29 1/2 42 3/8 29 1/2

B 66 3/8 77 7/8 N/A N/A

C 48 3/8 56 N/A N/A

D N/A 18 1/2 N/A 18 1/2

E N/A N/A 12 14

All dimensions are in inches.

TOP VIEW SHOWING THROUGH THE BASE ELECTRICAL UTILITY LOCATIONS AND ACCESS PANEL SWING CLEARANCES.

B C SWING RADIUS (E) HORIZONTAL FILTER ACCESS PANEL

6 7/8"

7 3/8"

SWING RADIUS (A ) ID SECTION ACCESS PANEL THROUGH THE BASE ELECTRICAL THROUGH THE BASE GAS SEE DETAIL A

SWING RADIUS 31" OD SECTION ACCESS PANEL

SWING RADIUS (D) ID FAN SECTION ACCESS PANEL

Figure 17. Gas/Electric Unit - Swing Diameter & Through the Base Electrical; Height of Gas Pipe (Second Drawing)
RT-PRC028-EN

59

Dimensional Data (12-25 Tons Accessories)

FRESH AIR HOOD (MANUAL) HORIZONTAL UNITS 19

Figure 18.

Fresh Air Hood (Horizontal Units)

Figure 21.

Economizer - Horizontal Units

Note: When applying economizer to horizontal units, connected ductwork must be run full size to allow proper operation of economizer damper.

495 MM

Figure 19.

Fresh Air Hood (Downflow Units) Figure 22. Economizer - Downflow Units

Figure 20. Power Exhaust - Downflow Economizers

C POWER EXHAUST with DOWNFLOW ECONOMIZERS only, SIDE VIEW

Figure 23. Power Exhaust - Downflow Economizers - Side View


Table 37. Power Exhaust Dimensions
Unit Model # T/YC*150, 180, 210, 240E, 300E
(i) (ii)

A 17 19

B(i) 53 64

C(ii) 36 39

Horizontal dimension only. Downflow economizer is width of end panel. Power exhaust is applied on downflow economizer only.

60

RT-PRC028-EN

Weights
Table 38.
Tons 12 15 17 20 25
(i) (ii) (iii)

Maximum Unit & Corner Weights (Lbs) and Center of Gravity Dimensions (in.) Cooling with Optional Electric Heat Units only
Unit Model No. TC*150E TC*180E TC*210E TC*240E TC*300E Weights (Lbs)(i),(ii) Shipping 1857 2371 2375 2447 2407 Net 1489 1912 1916 1988 1948 A 497 646 641 682 615 Corner Weights(iii) B 369 479 494 517 511 C 266 335 340 341 375 D 357 449 441 448 447 Center of Gravity (in.) Length 46 52 53 53 57.125 Width 30 35 34 33 "36.5"

Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly. Weights do not include additional factory or field installed options/accessories. For option/accessory additional weights, reference Table 40, Table 41, Table 42 to be added to unit weights. Corner weights are given for information only. 12-25 ton models must be supported continuously by a curb or equivalent frame support. Indicates both downflow and horizontal units.

Table 39.
Tons 12 15 17 20 25
(i) (ii) (iii)

Maximum Unit & Corner Weights (Lbs) and Center of Gravity Dimensions (in.) Gas/Electric Heat Units only
Unit Model No. YC*150E YC*180E YC*210E YC*240E YC*300E Weights (Lbs)(i),(ii) Shipping 1952 2474 2542 2602 2583 Net 1584 2015 2083 2143 2124 A 536 689 699 736 675 Corner Weights(iii) B 392 506 537 557 556 C 277 347 368 366 406 D 379 472 479 484 487 Center of Gravity (in.) Length 52 52 53 53 57.125 Width 35 34 34 33 "36.5"

Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly. Weights do not include additional factory or field installed options/accessories. For option/accessory additional weights, reference Table 40, Table 41, Table 42 to be added to unit weights. Corner weights are given for information only. 12-20 ton models must be supported continuously by a curb or equivalent frame support. Indicates both downflow and horizontal units.

RT-PRC028-EN

61

Weights (12-25 Tons)


Table 40. Accessory Net Weights (Lbs)(i),(ii)
Unit Model No. T/YCD150E 65 T/YCD180,210, 240E, 300E T/YCH150E 50 T/YCH180,210 240E, 300E
(i) (ii) (iii) (iv) (v) (vi)

Economizer Outside Air Damper Net Manual 32 32 32 32

Power

Roof Curb(iv) 205 235

Oversized Motor Adder 5 5 5 5

High Static Drive(v) 2 2 2 2

Low Static Drive(vi) 2 2

LPG Conversion Kit 5 5 5 5

Motorized Exhaust(iii) 60 75 60 75 95 95

80

65

Net weight should be added to unit weight when ordering factory installed accessories. TC*150-240 factory installed options for economizers, multiply net capacity x .99, EER x .97. For oversized motors, multiply net capacity x .98, EER x .93. This is provided in compliance with ARI certification program. Downflow only. Downflow only. Not available on all models (See Fan Performance tables for specific models). Not available on all models (See Fan Performance tables for specific models).

Table 41.

(continued) Accessory Net Weights (Lbs)


Electric Heaters Unit Model No. T/YCD150, 180E All Zone Sensors 1 1 1 1 6-23 kW 28/21(ix) 28/21(x) 27-36 kW 31/27 33/27 31/27 33/27 54 kW 240/480V(v),(vi) 38/32 40/32 38/32 40/32 72 kW 240/480V(vii),(viii) 43/34 43/34 240/480V(i),(ii) 240/480V(iii),(iv)

T/YCD210, 240E, 300E T/YCH150, 180E T/YCH210, 240E, 300E

(i) For 600V heaters net weights are same as 480V heaters. (ii) To estimate shipping weight add 5 lbs to net weight. (iii) For 600V heaters net weights are same as 480V heaters. (iv) To estimate shipping weight add 5 lbs to net weight. (v) For 600V heaters net weights are same as 480V heaters. (vi) To estimate shipping weight add 5 lbs to net weight. (vii) For 600V heaters net weights are same as 480V heaters. (viii) To estimate shipping weight add 5 lbs to net weight. (ix) 9 - 23 KW Heaters not available for TC*210C. (x) 9 - 23 KW Heaters not available for TC*210C.

62

RT-PRC028-EN

Weights (12-25 Tons)


Table 42. Factory Installed Options (FIOPS) Net Weights(i),(ii),(iii)
Accessory High Efficiency Motors(iv) Weight 49 36 0 Hinged Doors Powered Convenience Outlet Through the Base Electrical Unit Mounted Circuit Breaker Unit Mounted Disconnect Smoke Detectors Supply/Return Stainless Steel Heat Exchanger 5 50 (150 MBh) 50 (250 MBh) 75 (350 MBh) 75 (400 MBh) Tool-less Hail Guard Novar 2024 Novar 3051
(i) (ii) (iii) (iv)

Unit Model Number T/YC*150E, 180E standard size motor T/YC*210E, 240Estandard size motor T/YC*150E,180E oversize motor T/YC*210E-240E oversize motor T/YC*300E standard size motor All T/YC* units All T/YC* units All T/YC* units All T/YC* units except those with 54&72 kW heaters & 208/230V All T/YC* units with 54&72 kW heaters & 208/230V All T/YC* units except those with 54&72 kW heaters & 208/230V All T/YC* units with 54&72 kW heaters & 208/230V All T/YC* units YC*150E low heat YC*150E high heat YC*180E, 210E, 240E, 300E low heat YC*180E, 210E high heat YC*240E, 300E high heat T/YC*150E T/YC*180E, 210E, 240E, 300E All T/YC* units All T/YC* units

27 38 23 5 10 5 10

38 43 7 5

Weights for FIOP accessories not listed are >5 lbs. Net weight should be added to unit weight when ordering factory installed accessories. See Table 40, Table 41 for standard factory installed economizer and oversized motors. Standard factory installed motors are already included in unit net and shipping weights. Values shown for high efficiency motors are in addition to the standard motor weight. Indicates both downflow and horizontal units.

RT-PRC028-EN

63

Mechanical Specifications
General
The units shall be dedicated downflow or horizontal airflow. The operating range shall be between 115F and 0F in cooling as standard from the factory for all units. Cooling performance shall be rated in accordance with ARI testing procedures. All units shall be factory assembled, internally wired, fully charged with R-410A, and 100 percent run tested to check cooling operation, fan and blower rotation and control sequence, before leaving the factory. Wiring internal to the unit shall be colored and numbered for simplified identification. Units shall be UL listed and labeled, classified in accordance to UL 1995/ CAN/CSA No. 236-M90 for Heat Pumps. Canadian units shall be CSA Certified.

Unit Top
The top cover shall be one piece, or where seams exist, double hemmed and gasket sealed to prevent water leakage.

Sloped condensate drain pans are standard. Patent-pending 1+1+1 condenser coils, permanently gapped for easy cleaning.

Gas Heating Section


The heating section shall have a drum and tube heat exchanger design using corrosion resistant steel components. A forced combustion blower shall supply premixed fuel to a single burner ignited by a pilotless hot surface ignition system. In order to provide reliable operation, a negative pressure gas valve shall be used that requires blower operation to initiate gas flow. On an initial call for heat, the combustion blower shall purge the heat exchanger 45 seconds before ignition. After three unsuccessful ignition attempts, the entire heating system shall be locked out until manually reset at the thermostat. Units shall be suitable for use with natural gas or propane (field installed kit) and shall also comply with California requirements for low NOx emissions. The 12-25 tons shall have two stage heating (Gas/Electric Only).

Filters
Two inch standard filters shall be factory supplied on all units. Optional two inch pleated media filters shall be available.

Compressors
All units shall have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of nameplate voltage. Internal overloads shall be provided with the scroll compressors. All models shall have crankcase heaters, low and high pressure control as standard.

Casing
Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather-resistant baked enamel finish. Unit's surface shall be tested 500 hours in a salt spray test in compliance with ASTM B117. Cabinet construction shall allow for all maintenance on one side of the unit. In order to ensure a water and air tight seal, service panels shall have lifting handles and no more than three screws to remove. All exposed vertical panels and top covers in the indoor air section shall be insulated with a 1/2 inch, 1 pound density foil-faced, fire-resistant, permanent, odorless, glass fiber material. The base of the downflow unit shall be insulated with 1/2 inch, 1 pound density foil-faced, closedcell material. The downflow unit's base pan shall have no penetrations within the perimeter of the curb other than the raised 11/8 inch high supply/return openings to provide an added water integrity precaution, if the condensate drain backs up. The base of the unit shall have provisions for forklift and crane lifting.

Crankcase Heaters
These band heaters provide improved compressor reliability by warming the oil to prevent migration during off-cycles or low ambient conditions. These are standard on all Voyager models.

Outdoor Fans
The outdoor fan shall be direct-drive, statically and dynamically balanced, draw-through in the vertical discharge position. The fan motor(s) shall be permanently lubricated and shall have built-in thermal overload protection.

Refrigerant Circuits
Each refrigerant circuit shall have independent fixed orifice or thermostatic expansion devices, service pressure ports, and refrigerant line filter driers factory installed as standard. An area shall be provided for replacement suction line driers.

Indoor Fan
Units above shall have belt driven, FC centrifugal fans with adjustable motor sheaves. Units with standard motors shall have an adjustable idler-arm assembly for quickadjustment of fan belts and motor sheaves. All motors shall be thermally protected. Oversized motors shall be available for high static application. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT).

Evaporator and Condenser Coils


Internally finned, 3/8" copper tubes mechanically bonded to a configured aluminum plate fin shall be standard. Coils shall be leak tested at the factory to ensure the pressure integrity. The evaporator coil and condenser coil shall be leak tested to 200 psig and pressure tested to 450 psig. All dual compressor units shall have intermingled evaporator coils.

64

RT-PRC028-EN

Mechanical Specifications

Controls
Unit shall be completely factory wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Unit shall provide an external location for mounting a fused disconnect device. ReliaTel controls shall be provided for all 24 volt control functions. The resident control algorithms shall make all heating, cooling, and/or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures. The control algorithm maintains accurate temperature control, minimizes drift from set point, and provides better building comfort. A centralized control shall provide anti-short cycle timing and time delay between compressors to provide a higher level of machine protection.

Powered or Unpowered Convenience Outlet


This option is a GFCI, 120v/15amp, 2 plug, convenience outlet, either powered or unpowered. When the convenience outlet is powered, a service receptacle disconnect will be available. The convenience outlet is powered from the line side of the disconnect or circuit breaker, and therefore will not be affected by the position of the disconnect or circuit breaker. This option can only be ordered when the Through the Base Electrical with either the Disconnect Switch, or Circuit Breaker, option is ordered. This option is available on all downflow models (Gas/Electric Only).

Horizontal Side Access with Circuit Breaker


This option is a thermal magnetic, molded case, HACR Circuit Breaker with provisions for through the base electrical connections. The circuit breaker will be installed in a water tight enclosure in the unit with access through a swinging door. Factory wiring will be provided from the switch to the unit high voltage terminal block. The circuit breaker will provide overcurrent protection, be sized per NEC and UL guidelines, and be agency recognized by UL/ CSA.

Through the Base Electrical with Disconnect Switch


Three-pole, molded case, disconnect switch with provisions for through the base electrical connections are available. The disconnect switch will be installed in the unit in a water tight enclosure with access through a swinging door. Factory wiring will be provided from the switch to the unit high voltage terminal block. The switch will be UL/CSA agency recognized. Note: The disconnect switch will be sized per NEC and UL guidelines but will not be used in place of unit overcurrent protection.

Stainless Steel Heat Exchanger


Gas heat exchanger shall be of drum and tube design constructed from a minimum 304 Grade stainless steel. The stainless steel heat exchanger shall have a 10-year warranty as standard (Gas/Electric Only).

Defrost Controls
Adaptive demand defrost shall be provided to permit defrost wherever coil icing conditions begin to significantly reduce unit capacity.

Supply and/or Return Air Smoke Detector


With this option installed, if smoke is detected, all unit operation will be shut down. Reset will be manual at the unit. Return Air Smoke Detectors require minimum allowable airflow when used with certain models. See the Installation, Operation, and Maintenance (IOM) manual for the models affected and the minimum allowable airflow required. This option is available on all downflow models.

Factory Installed Options


Black Epoxy Coated Pre-Coated Coils
The black epoxy coils have a thermoset vinyl coating that is bonded to the aluminum fin stock prior to the fin-stamping process. The pre-coated coils are an economical option for protection in mildly corrosive environments.

Horizontal Side Access with Disconnect Switch


Three-pole, molded case, disconnect switch with provisions for through the base electrical connections are available. The disconnect switch will be installed in the unit in a water tight enclosure with access through a swinging door. Factory wiring will be provided from the switch to the unit high voltage terminal block. The switch will be UL/CSA agency recognized. Note: The disconnect switch will be sized per NEC and UL guidelines but will not be used in place of unit overcurrent protection.

High Efficiency Motors


This option is available with efficiency ratings from 86.5 up to 91.0. It is not available for all models.

Through the Base Electrical with Circuit Breaker


This option is a thermal magnetic, molded case, HACR Circuit Breaker with provisions for through the base electrical connections. The circuit breaker will be installed in a water tight enclosure in the unit with access through a swinging door. Factory wiring will be provided from the switch to the unit high voltage terminal block. The circuit breaker will provide overcurrent protection, be sized per NEC and UL guidelines, and be agency recognized by UL/ CSA.

High Pressure Cutout


This option is offered for units that do not have High Pressure cutout as standard.

Hinged Access Doors


Sheet metal hinges are available on the Filter/Evaporator Access Door and the Compressor/Control Access Door. This option is available on all downflow models.

Through the Base Utilities Access


An electrical service entrance shall be provided allowing electrical access for both control and main power

RT-PRC028-EN

65

Mechanical Specifications

connections inside the curb and through the base of the unit. Option will allow for field installation of liquid-tight conduit and an external field installed disconnect switch.

Electric Heaters
Electric heat modules shall be available for installation within the basic unit. Electric heater elements shall be constructed of heavy-duty nickel chromium elements internally delta connected for 240 volt, wye connected for 480 and 600 volt. Staging shall be achieved through ReliaTel. Each heater package shall have automatically reset high limit control operating through heating element contactors. All heaters shall be individually fused from the factory, where required, and shall meet all NEC and CEC requirements when properly installed. Power assemblies shall provide single-point connection. Electric heat modules shall be UL listed or CSA certified. If ordering the Through the Base Electrical option with an Electric Heater, the heater must be factory installed.

Tool-less Hail Guards


Tool-less, hail protection quality coil guards are available for condenser coil protection.

Two-Inch Pleated Filters


Two inch pleated media filters shall be available on all models.

Trane Communication Interface


This factory or field-installed option shall be provided to interface ReliaTel controlled units with the Trane Integrated Comfort systems.

Factory or Field Installed Options


Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch is available to achieve active fan failure indication and/or clogged filter indication. These indications will be registered with either a zone sensor with status indication lights or an Integrated Comfort System.

Field Installed Options


CO2 Sensing
The CO2 sensor has the ability to monitor space occupancy levels within the building by measuring the parts per million of CO2 (Carbon Dioxide) in the air. As the CO2 levels increase, the outside air damper modulates to meet the CO2 space ventilation requirements.

Differential Pressure Switches


These options allow for individual fan failure and dirty filter indication. The fan failure switch will disable all unit functions and "flash" the Service LED on the zone sensor. The dirty filter switch will light the Service LED on the zone sensor and will allow continued unit operation.

LonTalk Communications Interface


The LonTalk communications interface, when installed in a Voyager unit, allows the unit to communicate as a Tracer LCI-V device or directly with generic LonTalk Network Building Automation System Controls.

Digital Display Zone Sensor


The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone sensors. This sensor includes a digital display of set point adjustment and space temperature in F (Fahrenheit) or C (Celsius). Includes FAN and SYSTEM buttons (supports the service functions of the standard sensor). E-squared memory stores last programmed set points. Requires 24 VAC (Volts AC). This sensor should be utilized with ReliaTel controls.

Discharge Air Sensing Kit


This kit provides true discharge air sensing in heating models. This sensor is a status indicator readable through Tracer or Tracker. The kit is functional only with the ReliaTel Options Module.

Oversized Motors
Oversized motors shall be available for high static applications.

Reference or Comparative Enthalpy


Reference Enthalpy is used to measure and communicate outdoor humidity. The unit receives and uses this information to provide improved comfort cooling while using the economizer. Comparative Enthalpy measures and communicates humidity for both outdoor and return air conditions, and return air temperature. The unit receives and uses this information to maximize use of economizer cooling, and to provide maximum occupant comfort control. Reference or Comparative Enthalpy option shall be available when a factory or field installed Downflow Economizer is ordered. This option is available on all downflow models.

Dual Thermistor Remote Zone Sensor


This sensor will allow the customer to reduce the total number of remote sensors to obtain space temperature averaging. This sensor should be utilized with ReliaTel controls.

Economizer - Downflow
The assembly includes fully modulating 0-100 percent motor and dampers, barometric relief, minimum position setting, preset linkage, wiring harness with plug, fixed dry bulb and spring return actuator. The barometric relief damper shall be standard with the downflow economizer and shall provide a pressure operated damper that shall be gravity closing and shall prohibit entrance of outside air during the equipment "off" cycle. Solid state enthalpy and differential enthalpy control shall be field-installed.

High Static Drive


The high static drive option shall allow the standard motor on the 12 and 20 ton units to operate with improved external static capabilities.

Manual Outside Air Damper


The rain hood and screen shall provide up to 25 percent outside air.

66

RT-PRC028-EN

Mechanical Specifications

Motorized Outside Air Dampers


Manually set outdoor air dampers shall provide up to 50 percent outside air. Once set, outdoor air dampers shall open to set position when indoor fan starts. The damper shall close to the full closed position when indoor fan shuts down.

Curb shall be shipped knocked down for field assembly and shall include wood nailer strips.

Economizer - Horizontal
The horizontal economizer shall contain the same features as the downflow economizer with the exception of barometric relief.

Powered Exhaust
The powered exhaust shall provide exhaust of return air, when using an economizer, to maintain better building pressurization.

Remote Potentiometer
The minimum position setting of the economizer shall be adjusted with this accessory.

Roof Curb - Downflow


The roof curb shall be designed to mate with the downflow unit and provide support and a water tight installation when installed properly. The roof curb design shall allow field-fabricated rectangular supply/ return ductwork to be connected directly to the curb. Curb design shall comply with NRCA requirements.

Ventilation Override Accessory


With the Ventilation Override Accessory installed, the unit can be set to transition up to 3 different preprogrammed sequences for Smoke Purge, Pressurization, and Exhaust. The transition occurs when a binary input on the RTOM is closed (shorted). This would typically be a hard wired relay output from a smoke detector or fire control panel.

Zone Sensors
This option shall be provided to interface with the Micro equipped Voyagers and shall be available in either manual, automatic, programmable with night setback, with system malfunction lights or remote sensor options.

RT-PRC028-EN

67

Literature Order Number Date Trane A business of American Standard Companies www.trane.com For more information, contact your local Trane office or e-mail us at comfort@trane.com Supersedes

RT-PRC028-EN July 2007 RT-PRC028-EN (May 2006)

Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.