SITRANS P measuring instruments for pressure

Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series

Overview

SITRANS P pressure transmitters, DS III series, are digital pressure transmitters featuring extensive user-friendliness and high accuracy. Parameterization is performed using input keys or by means of HART communication. Extensive functionality enables the pressure transmitter to be precisely adapted to the plants requirements. Operation is very simple in spite of the numerous setting options. Transmitters with type of protection "Intrinsic safety" and "Explosion-proof" may be installed within potentially explosive atmospheres (zone 1) or in zone 0. The transmitters are provided with an EC type examination certificate and comply with the corresponding harmonized European standards (ATEX). The transmitters can be equipped with various designs of remote seals for special applications such as the measurement of highly viscous substances. Various versions of the DS III pressure transmitters are available for measuring: Pressure Absolute pressure For differential pressure transmitters Level Volume Volume flow Mass flow

Application
The pressure transmitters of the DS III series, can be used in industrial areas with extreme chemical and mechanical loads. Electromagnetic compatibility in the range 10 kHz to 1 GHz makes the DS III pressure transmitters suitable for locations with high electromagnetic emissions. Pressure transmitters with type of protection "Intrinsic safety" and "Explosion-proof" may be installed within potentially explosive atmospheres (zone 1) or in zone 0. The pressure transmitters are provided with an EC type examination certificate and comply with the corresponding harmonized European standards (ATEX). Pressure transmitters with the type of protection "Intrinsic safety" for use in zone 0 may be operated with power supply units of category "ia" and "ib". The transmitters can be equipped with various designs of remote seals for special applications such as the measurement of highly viscous substances. The pressure transmitters can be programmed locally using three input keys or externally through HART communication. Pressure transmitters for pressure Measured variable: Pressure of aggressive and non-aggressive gases, vapors and liquids. Nominal measuring ranges: 1 ... 400 bar (14.5 ... 5802 psi) Pressure transmitters for absolute pressure Measured variable: Absolute pressure of aggressive and nonaggressive gases, vapors and liquids. Nominal measuring ranges: 250 mbar ... 100 bar (3.63 ... 1450 psi) There are two series: Pressure series Differential pressure series Pressure transmitters for differential pressure and flow Measured variables: Differential pressure Small positive or negative pressure

Benefits
High quality and long life High reliability even under extreme chemical and mechanical loads Extensive diagnosis and simulation functions Separate replacement of measuring cell and electronics without recalibration Minimum conformity error Small long-term drift Wetted parts made of high-grade materials (e.g. stainless steel, Hastelloy, gold, Monel, tantalum) Measuring range 1 mbar ... 400 bar High measuring accuracy Parameterization using input keys and HART communication

Siemens FI 01 2005

2/23

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series

Flow q ~ p (together with a primary differential pressure device) Nominal measuring ranges: 20 mbar ... 30 bar (0.29 ... 435 psi) Pressure transmitters for level Measured variable: Level of aggressive and non-aggressive liquids in open and closed vessels. Nominal measuring ranges: 250 mbar ... 5 bar (3.63 ... 72.5 psi) Nominal diameter of the mounting flange: DN 80 or DN 100 3 inch or 4 inch In the case of level measurements in open containers, the lowpressure connection of the measuring cell remains open (measurement "compared to atmospheric"). In the case of measurements in closed containers, the lowerpressure connection has to be connected to the container in order to compensate the static pressure. The wetted parts are constructed from a variety of materials depending on the degree of corrosion resistance required.

The electrical connections for the power supply and screen are accessible by unscrewing the rear cover. The bottom part of the housing contains the measuring cell with process connection (1). The measuring cell is protected from rotating by a locking screw (8). As the result of this modular design, the measuring cell and the electronics can be replaced separately from each other. The set parameter data are retained. At the top of the housing is a plastic cover (5), under which the input keys can be found.

Function
Mode of operation of the electronics
9 M 2 3 4 mC 7 HART interface EEPROM 6 0 0 00 0 00 5 10 IA, UH

Design

Electronics 1 Sensor Pe 1 2 3 4 5 6 7 8 9 10 IA UH Pe 6 EEPROM Measuring cell

Measuring cell sensor Instrument amplifier Analog-to-digital converter Microcontroller Digital-to-analog converter One non-volatile memory each in the measuring cell and electronics HART interface Three input keys (local operation) Digital display Diode circuit and connection for external ammeter Output current Power supply Input variable

Front view

Function diagram of the electronics

The transmitter consists of various components depending on the order. The possible versions are listed in the ordering information. The components described below are the same for all transmitters. The rating plate (3, Figure "Front view") with the Order No. is located on the side of the housing. The specified number together with the ordering information provide details on the optional design details and on the possible measuring range (physical properties of built-in sensor element). The approval label is located on the opposite side. The housing is made of die-cast aluminium or stainless steel precision casting. A round cover is screwed on at the front and rear of the housing. The front cover (6) can be fitted with a viewing pane so that the measured values can be read directly on the digital display. The inlet (4) for the electrical connection is located either on the left or right side. The unused opening on the opposite side is sealed by a blanking plug. The protective earth connection is located on the rear of the housing.

The bridge output voltage created by the sensor (1, Figure "Function diagram of the electronics") is amplified by the instrument amplifier (2) and digitized in the analog-to-digital converter (3). The digital information is evaluated in a microcontroller, its linearity and temperature response corrected, and converted in a digital-to-analog converter (5) into an output current of 4 to 20 mA. The diode circuit (10) protects against incorrect polarity. The data specific to the measuring cell, the electronics data, and the parameter data are stored in the two non-volatile memories (6). The one memory is coupled to the measuring cell, the other to the electronics. As the result of this modular design, the electronics and the measuring cell can be replaced separately from each other. Using the 3 input keys (8) you can parameterize the pressure transmitter directly at the point of measurement. The input keys can also be used to control the view of the results, the error messages and the operating modes on the digital display (9).

2/24

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series
The HART modem (7) permits parameterization using a protocol according to the HART specification. The pressure transmitters with spans 63 bar measure the input pressure compared to atmosphere, transmitters with spans 160 bar compared to vacuum. Mode of operation of the measuring cells Measuring cell for pressure
1 5 pe 6
5 4 3 1

Measuring cell for absolute pressure from differential pressure series

1 2 3 4 5 6 7 8 pe

Reference vacuum Overload diaphragm Silicon pressure sensor O-ring Process flange Seal diaphragm Body of measuring cell Filling liquid Absolute pressure as input variable

8 1 2 3 4 5 pe Measuring cell Process connection Seal diaphragm Filling liquid Silicon pressure sensor Pressure as input variable

Measuring cell for absolute pressure from differential pressure series, functional diagram

2 p e

The input pressure pe is transmitted through the seal diaphragm (6, Figure "Measuring cell for absolute pressure from differential pressure series, functional diagram") and the filling liquid (8) to the silicon pressure sensor (3). The difference in pressure between the input pressure pe and the reference vacuum (1) on the low-pressure side of the measuring cell flexes the measuring diaphragm. The resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit thus changes. This change in resistance results in a bridge output voltage proportional to the absolute pressure. An overload diaphragm is installed to provide protection from overloads. If the measuring limits are exceeded, the overload diaphragm (2) is flexed until the seal diaphragm rests on the body of the measuring cell (7), thus protecting the silicon pressure sensor from overloads. Measuring cell for differential pressure and flow

Measuring cell for pressure, functional diagram

The pressure pe is applied through the process connection (2, Figure "Measuring cell for pressure, functional diagram) to the measuring cell (1). This pressure is subsequently transmitted further through the seal diaphragm (3) and the filling liquid (4) to the silicon pressure sensor (5) whose measuring diaphragm is then flexed. The resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit thus changes. This change in resistance results in a bridge output voltage proportional to the input pressure. Measuring cell for absolute pressure from pressure series

4 1 2 3 4 5 6 7 Seal diaphragm O-ring Overload diaphragm Silicon pressure sensor Process flange Body of measuring cell Filling liquid

5 4 3 1 1 2 3 4 5 pe Measuring cell Process connection Seal diaphragm Filling liquid Silicon absolute pressure sensor Absolute pressure as input variable

1 5

Measuring cell for differential pressure and flow, functional diagram

pe

The differential pressure is transmitted through the seal diaphragms (1, Figure "Measuring cell for differential pressure and flow, functional diagram") and the filling liquid (7) to the silicon pressure sensor (4). The measuring diaphragm is flexed by the applied differential pressure. The resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit thus changes. This change in resistance results in a bridge output voltage proportional to the absolute pressure. An overload diaphragm is installed to provide protection from overloads. If the measuring limits are exceeded, the overload diaphragm (2) is flexed until the seal diaphragm rests on the body of the measuring cell (7), thus protecting the silicon pressure sensor from overloads.

Measuring cell for absolute pressure from the pressure series, functional diagram

The absolute pressure pe is transmitted through the seal diaphragm (3, Figure "Measuring cell for absolute pressure from pressure series, functional diagram") and the filling liquid (4) to the silicon absolute pressure sensor (5) whose measuring diaphragm is then flexed. The resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit thus changes. This change in resistance results in a bridge output voltage proportional to the input pressure.

Siemens FI 01 2005

2/25

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series

Measuring cell for level

3 2 +

8 1 10 9 6 7 8 9 10 Silicon pressure sensor O-ring Process flange Filling liquid Capillary with filling liquid of mounting flange

The following diagnostics functions are available using HART communication: Zero correction display Event counter Limit transmitter Saturation alarm Slave pointer Simulation functions Maintenance timer Parameterization using the input keys (local operation) With the input keys you can easily set the most important parameters without any additional equipment. Parameterization using HART communication Parameterization using HART communication is performed with a HART communicator or a PC.
+

1 2 3 4 5

Flange with tube Seal diaphragm on mounting flange Seal diaphragm Body of measuring cell Overload diaphragm

Measuring cell for level, functional diagram

The input pressure (hydrostatic pressure) acts hydraulically on the measuring cell through the seal diaphragm on the mounting flange (2, Figure "Measuring cell for level, functional diagram"). This differential pressure is subsequently transmitted further through the measuring cell (3) and the filling liquid (9) to the silicon pressure sensor (6) whose measuring diaphragm is then flexed. The resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit thus changes. This change in resistance results in a bridge output voltage proportional to the differential pressure. An overload diaphragm is installed to provide protection from overloads. If the measuring limits are exceeded, the overload diaphragm (2) is flexed until the seal diaphragm rests on the body of the measuring cell (7), thus protecting the silicon pressure sensor from overloads. Parameterization Depending on the version, there are different possibilities for parameterizing the pressure transmitter and for setting or scanning the parameters. Adjustable parameters
Parameters Start of scale Full-scale value Electrical damping Input keys x x x HART communication x x x x x x x x x 1) x x 2) x x x

SITRANS P transmitter HART communicator

230 ... 1100 W

Power supply

HART communication between a HART communicator and a pressure transmitter

When parameterizing with the HART communicator, the connection is made directly to the 2-wire system.

SITRANS P transmitter HART modem

230 ... 500 W PC or laptop RS 232

Power supply

HART communication between a PC communicator and a pressure transmitter

When parameterizing with a PC, the connection is made through a HART modem. The signals needed for communication in conformity with the HART 5.x or 6.x protocols are superimposed on the output current using the Frequency Shift Keying (FSK) method. Physical dimensions available for the display
Physical variable Pressure (setting can also be made in the factory) Level (height data) Volume Volume flow Mass flow Physical dimensions Pa, MPa, kPa, hPa, bar, mbar, torr, atm, psi, g/cm2, kg/cm2, inH20, inH20 (4 C), mmH20, ftH20, inHg, mmHg m, cm, mm, ft, in m3, dm3, hl, yd3, ft3, in3, US gallon, lmp, gallon, bushel, barrel, barrel liquid m3/d, m3/h, m3/s, l/min, l/s, ft3/d, ft3/min, ft3/s, US gallon/min, US gallon/s t/d, t/h, t/min, kg/d, kg/h, kg/min, kg/s, g/d, g/h, g/min, g/s, lb/d, lb/h, lb/min, lb/s, LTon/d, LTon/h, STon/d, STon/h, STon/min t, kg, g, lb, oz, LTon, STon K, C, F, R %, mA

Start-of-scale value without application of a x pressure ("Blind setting") End-of-scale value without application of a x pressure ("Blind setting") Zero adjustment Current transmitter Fault current Disabling of keys, write protection Type of dimension and actual dimension Characteristic (linear / square-rooted) Input of characteristic Freely-programmable LCD Diagnostics functions
1) 2)

x x x x x x 2)

Cancel apart from write protection Only differential pressure

Total mass flow Temperature Miscellaneous

2/26

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for pressure

Technical specifications
SITRANS P pressure transmitters, DS III series, for pressure Input Measured variable Span (continuously adjustable) 0.01 ... 1 bar (0.145 ... 14.5 psi) 0.04 ... 4 bar (0.58 ... 58 psi) 0.16 ... 16 bar (2.32 ... 232 psi) 0.6 ... 63 bar (9.14 ... 914 psi) 1.6 ... 160 bar (23.2 ... 2320 psi) 4.0 ... 400 bar (58 ... 5802 psi) Lower measuring limit Measuring cell with silicone oil filling Upper measuring limit 30 mark (0.435 psi) absolute 100% of max. span (max. 160 bar (2320 psi) with oxygen measurement and inert liquid) 4 ... 20 mA Increasing characteristic Start-of-scale value 0 bar Stainless steel seal diaphragm Silicone oil filling Room temperature (25 C (77 C)) r: Span ratio (r = max. span / set span) Pressure Maximum working pressure 6 bar (87 psi) 10 bar (145 psi) 32 bar (464 psi) 100 bar (1450 psi) 250 bar (3626 psi) 500 bar (7252 psi)

Process connection

Connection shank GA to DIN EN 837-1, female thread -14 NPT or oval flange (PN 160 (MWP 2320)) with mounting thread M10 or 7/16-20 UNF to EN 61518 10.5 ... 45 V DC 10.5 ... 30 V DC in intrinsicallysafe mode For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) PTB 99 ATEX 2122 Ex II 1/2 G EEx ia/ib IIB/IIC T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +70 C (-40 ... +158 F) temperature class T5; -40 ... +60 C (-40 ... +140 F) temperature class T6 To certified intrinsically-safe circuits with maximum values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW; Ri = 300 Li = 0.4 mH, Ci = 6 nF PTB 99 ATEX 1160 Ex II 1/2 G EEx d IIC T4/T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +60 C (-40 ... +140 F) temperature class T6 To circuits with values: UH = 10.5 ... 45 V DC PTB 01 ATEX 2055 Ex II 1 D IP65 T 120C Ex II 1/2 D IP65 T 120 C -40 ... +85 C (-40 ... +185 F) 120 C (248 F) To certified intrinsically-safe circuits with maximum values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 Li = 0.4 mH, Ci = 6 nF PTB 01 ATEX 2055 Ex II 2 D IP65 T 120 C To circuits with values: UH = 10.5 ... 45 V DC; Pmax = 1.2 W TV 01 ATEX 1696 X Ex II 3 G EEx nA L IIC T4/T5/T6 Certificate of Compliance 3008490 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III

Power supply UH Terminal voltage on transmitter

Certificates and approvals Classification according to pressure equipment directive (DRGL 97/23/EC)

Explosion protection Intrinsic safety "i" - Identification - Permissible ambient temperature

Output Output signal Measuring accuracy Reference conditions - Connection

- Effective internal inductance/capacitance Explosion-proof "d" - Identification - Permissible ambient temperature

Error in measurement and fixedpoint setting (including hysteresis and repeatability) Linear characteristic - r 10 - 10 < r 30 - 30 < r 100 Influence of ambient temperature With -10 ... +60 C (14 ... 140 F) With -40 ... -10 C and +60 C ... +85 C (-40 ... +14 and 140 ... 185 F) Rated conditions Degree of protection (to EN 60529) Process temperature Measuring cell with silicone oil filling Measuring cell with inert filling liquid In conjunction with dust explosion protection Design Weight (without options) Wetted parts materials Connection shank Stainless steel, mat. No. 1.4404/316L or Hastelloy C4, mat. No. 2.4610 Stainless steel, mat. No. 1.4404/316L or Hastelloy C276, mat. No. 2.4819 Silicone oil or inert filling liquid (max. 160 bar (2320 psi) with oxygen measurement) 1.5 kg ( 3.3 lb) -40 ... +100 C (-40 ... +212 F) -20 ... +100 C (-4 ... +212 F) -20 ... +60 C (-4 ... +140 F) IP65 (0.08 r +0.1)% (0.1 r +0.15)% / 10 K ( (0.1 r +0.15)% / 18 F) (0.0029 r +0.071)% (0.0045 r +0.071)% (0.005 r +0.05)%

- Connection Dust explosion protection for zone 20 - Identification - Permissible ambient temperature - Max.surface temperature - Connection

- Effective internal inductance/capacitance Dust explosion protection for zone 21/22 - Identification - Connection

Type of protection "n" (zone 2) - Identification Explosion protection to FM - Identification (XP/DIP) or (IS); (NI)

Seal diaphragm

Measuring cell filling

Siemens FI 01 2005

2/27

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for pressure

Explosion protection to CSA - Identification (XP/DIP) or (IS)

Certificate of Compliance 1153651 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III

Dimensional drawings
15 (0.6) 138 (5.4)

20 (0.8)

69 (2.7)

50 (1.97)

55 (0.6)
28 (1.1)

ca. 30 (1.2)

4)

100 (3.94)

ca. 96 (3.78)
50 (1.97)

80 (3.15)

117 (4.6)

3
171 (6.7) 237 (9.3) 36,5 (1,44) 105 (4.1)

1)

1)

8
68 (2.7)

72 (2.8)

123 (4.8) min. 77 (3.0) 5)


1 Process connection: - -14 NPT, - connection shank GA or - oval flange Blanking plug Electrical connection: - screwed gland Pg 13,5 (adapter)2) 3), - screwed gland M20x1,5 3), - screwed gland -14 NPT or - Han 7D/ Han 8U plug 2) 3) Terminal side Electronics side, digital display (longer overall length for cover with window) Protective cover over keys Mounting bracket (option) Screw cover - safety bracket (only for type of protection "Explosion-proof enclosure", not shown in the drawing)

2 3

4 5 6 7 8

1) 2) 3) 4) 5)

Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing Not with type of protection "explosion-proof enclosure" Not with type of protection "FM + CSA [is + xp]" 45 mm (1.8 inch) for Pg 13,5 with adapter Minimum distance for rotation

SITRANS P pressure transmitters, DS III series for pressure, dimensional drawing, dimensions in mm (inch)

2/28

Siemens FI 01 2005

120 (4.7)

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for pressure
Selection and Ordering data Order No.
1) 2) 3) 4) For oxygen application, add Order code E10. Without cable gland, with blanking plug With enclosed cable gland EEx ia and blanking plug Not together with type of protection "Explosion-proof"

SITRANS P pressure transmitter, DS III series, } 7 M F 4 0 3 3 for pressure 77777 - 7777 2-wire system Measuring cell filling Silicone oil Inert liquid1) Measured span 0.01 ... 1 bar 0.04 ... 4 bar 0.16 ... 16 bar 0.63 ... 63 bar 1.6 ... 160 bar 4.0 ... 400 bar Measuring cell cleaning Standard Grease-free (0.15 ... 14.5 psi) (0.58 ... 58 psi) (2.32 ... 232 psi) (9.14 ... 914 psi) (23.2 ... 2320 psi) (58.0 ... 5802 psi)

} 1 3 } } } } } } B C D E F G

Wetted parts materials Seal diaphragm Process connection Stainless steel Stainless steel Hastelloy Stainless steel Hastelloy Hastelloy Version as diaphragm seal Process connection Connection shank GB to EN 837-1 Female thread -14 NPT Oval flange made of stainless steel, max. span 160 bar (2320 psi) - Mounting thread 7/16-20 UNF to EN 61518 - Mounting thread M10 to DIN 19213 Non-wetted parts materials Housing made of die-cast aluminium Housing stainless steel precision casting } A B C Y0 0 1

2 3 } 0 3 1 2

Design Standard design International version, English label inscriptions, } documentation in 5 languages on CD Explosion protection without with ATEX, Type of protection: - "Intrinsic safety (EEx ia)" - "Explosion-proof (EEx d)" 2) - "Intrinsic safety and explosion-proof enclosure } (EEx ia + EEx d)" 3) - "n (zone 2)" - "Intrinsic safety, explosion-proof enclosure and dust explosion protection (EEx ia + EEx d + zone 1D/2D)" 3) with FM + CSA, Type of protection: - "Intrinsic safety and explosion-proof (is + xp)" 2) Electrical connection / cable inlet Screwed gland Pg 13.5 (adapter) 4) Screwed gland M20x1.5 Screwed gland -14 NPT Han 7D plug (plastic housing) incl. mating connector 4) Display without (digital indicator hidden, setting: mA) with visible digital indicator, setting: mA with customer-specific digital indicator (setting as specified, Order code "Y21" or "Y22" required)

A B D P E R

NC A B C D

1 6 7

} Available ex stock
Power supply units see "SITRANS I power supply units and input isolators". Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation

Siemens FI 01 2005

2/29

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for pressure

Further designs Please add "-Z" to Order No. and specify Order code.

Order code

Additional data Please add "-Z" to Order No. and specify Order code. Measuring range to be set specify in plain text: Y01: ... to ... mbar, bar, kPa, MPa, psi Measuring point number/identification max. 16 characters, specify in plain text: Y15: ........................................... Measuring point text max. 27 characters, specify in plain text: Y16: ........................................... Entry of HART address (TAG) max. 8 characters, specify in plain text: Y17: ........................................... Setting of pressure indicator in pressure units specify in plain text (standard setting: mA): Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, mA, Torr, ATM or % *) Reference temperature 20 C Setting of pressure indicator in non-pressure units specify in plain text: Y22: ..... up to ..... l/min, m3/h, m, USgpm, ... (specification of measuring range in pressure units "Y01" is essential, unit with max. 5 characters)

Order code Y01

Pressure transmitter with mounting bracket made of: Steel A01 Stainless steel A02 Plug Han 7D (metal, gray) Han 8U (instead of Han 7D) Rating plate inscription (instead of German) English French Spanish Italian English rating plate Pressure units in inH2O or psi Manufacturer's test certificate M (calibration certificate) to DIN 55350, Part 18 and to ISO 8402 Acceptance test certificate B to EN 10204-3.1.B Factory certificate to EN 10204-2.2 Certificate "Functional Safety (SIL)" Setting of upper limit of output signal to 22.0 mA Acid gas version to NACE (only together with seal diaphragm made of Hastelloy) Type of protection IP68 (not together with Han 7D / Han 8U plug, Pg 13.5 screwed gland) Digital indicator along side the input keys (only together with the devices 7MF4033-....0-.A.6 or -.A.7-Z, Y21 or Y22 + Y01) Use in or at zone 1D/2D (only together with type of protection "Intrinsic safety (EEx ia)" Use at zone 0 (only together with type of protection "Intrinsic safety (EEx ia)" Oxygen application (max. 160 bar (2320 psi) with oxygen measurement and inert liquid) A30 A31

Y15

Y16

B11 B12 B13 B14 B21 C11

Y17

Y21

C12 C14 C20 D05 D07 D12

Y22 + Y01

Only the settings for "Y01", "Y21", "Y22" and "D05" can be made in the factory Ordering example Item line: 7MF4033-1EA00-1AA7-Z B line: A01 + Y01 + Y21 C line: Y01: 10 ... 20 bar (145 ... 290 psi) C line: Y21: bar (psi)

D27

E01

E02

E10

2/30

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for absolute pressure (from pressure series)

Technical specifications
SITRANS P pressure transmitters, DS III series for absolute pressure, from the pressure series Input Measured variable Span 8.3 ... 250 mbar (0.12 ... 3.6 psi) 43 ... 1300 mbar (0.62 ... 18.9 psi) 160 ... 5000 mbar (2.32 ... 72.5 psi) 1 ... 30 bar (14.5 ... 435 psi) Lower measuring limit Measuring cell with silicone oil filling Upper measuring limit 0 mark (0 psi) absolute 100% of max. span (max. 160 bar (2320 psi) with oxygen measurement and inert liquid) 4 ... 20 mA Increasing characteristic Start-of-scale value 0 bar Stainless steel seal diaphragm Silicone oil filling Room temperature (25 C (77 F)) r: Span ratio (r = max. span / set span) Absolute pressure Maximum working pressure 6 bar (87 psi) 10 bar (145 psi) 30 bar (435 psi) 100 bar (1450 psi)

Process connection

Connection shank GA to DIN EN 837-1, female thread -14 NPT or oval flange (PN 160 (MWP 2320)) with mounting thread M10 or 7/16-20 UNF to EN 61518 10.5 ... 45 V DC 10.5 ... 30 V DC in intrinsicallysafe mode For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) PTB 99 ATEX 2122 Ex II 1/2 G EEx ia/ib IIB/IIC T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +70 C (-40 ... +158 F) temperature class T5; -40 ... +60 C (-40 ... +140 F) temperature class T6 To certified intrinsically-safe circuits with maximum values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW; Ri = 300 Li = 0.4 mH, Ci = 6 nF PTB 99 ATEX 1160 Ex II 1/2 G EEx d IIC T4/T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +60 C (-40 ... +140 F) temperature class T6 To circuits with values: UH = 10.5 ... 45 V DC PTB 01 ATEX 2055 Ex II 1 D IP65 T 120 C Ex II 1/2 D IP65 T 120 C -40 ... +85 C (-40 ... +185 F) 120 C (248 F) To certified intrinsically-safe circuits with maximum values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 Li = 0.4 mH, Ci = 6 nF PTB 01 ATEX 2055 Ex II 2 D IP65 T 120 C To circuits with values: UH = 10.5 ... 45 V DC; Pmax = 1.2 W TV 01 ATEX 1696 X Ex II 3 G EEx nA L IIC T4/T5/T6 Certificate of Compliance 3008490 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III

Power supply UH Terminal voltage on pressure transmitter Certificates and approvals Classification according to pressure equipment directive (DRGL 97/23/EC)

Explosion protection Intrinsic safety "i" - Identification - Permissible ambient temperature

Output Output signal Measuring accuracy Reference conditions

- Connection

- Effective internal inductance/capacitance Explosion-proof "d" - Identification - Permissible ambient temperature

Error in measurement and fixedpoint setting (including hysteresis and repeatability) Linear characteristic - r 10 - 10 < r 30 Influence of ambient temperature With -10 ... +60 C (14 ... 140 F) With -40 ... -10 C and +60 C ... +85 C (-40 ... +14 and 140 ... 185 F) Rated conditions Degree of protection (to EN 60529) Process temperature Measuring cell with silicone oil filling Measuring cell with inert filling liquid In conjunction with dust explosion protection Design Weight (without options) Wetted parts materials Connection shank Stainless steel, mat. No. 1.4404/316L or Hastelloy C4, mat. No. 2.4610 Stainless steel, mat. No. 1.4404/316L or Hastelloy C276, mat. No. 2.4819 Silicone oil or inert filling liquid (max. 160 bar (2320 psi) with oxygen measurement) 1.5 kg ( 3.3 lb) -40 ... +100 C (-40 ... +212 F) -20 ... +100 C (-4 ... +212 F) -20 ... +60 C (-4 ... +140 F) IP65 (0.1 r +0.2)% (0.1 r +0.15)% / 10 K ( (0.1 r +0.15)% / 18 F) (0.0029 r +0.071)% (0.0045 r +0.071)%

- Connection Dust explosion protection for zone 20 - Identification - Permissible ambient temperature - Max.surface temperature - Connection

- Effective internal inductance/capacitance Dust explosion protection for zone 21/22 - Identification - Connection

Seal diaphragm

Type of protection "n" (zone 2) - Identification Explosion protection to FM - Identification (XP/DIP) or (IS); (NI)

Measuring cell filling

Siemens FI 01 2005

2/31

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for absolute pressure (from pressure series)

Explosion protection to CSA - Identification (XP/DIP) or (IS)

Certificate of Compliance 1153651 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III

Dimensional drawings
15 (0.6) 138 (5.4)

20 (0.8)

69 (2.7)

50 (1.97)

55 (0.6)
28 (1.1)

ca. 30 (1.2)

4)

100 (3.94)

ca. 96 (3.78)
50 (1.97)

80 (3.15)

117 (4.6)

3
171 (6.7) 237 (9.3) 36,5 (1,44) 105 (4.1)

1)

1)

8
68 (2.7)

72 (2.8)

123 (4.8) min. 77 (3.0) 5)


1 Process connection: - -14 NPT, - connection shank GA or - oval flange Blanking plug Electrical connection: - screwed gland Pg 13,5 (adapter)2) 3), - screwed gland M20x1,5 3), - screwed gland -14 NPT or - Han 7D/ Han 8U plug 2) 3) Terminal side Electronics side, digital display (longer overall length for cover with window) Protective cover over keys Mounting bracket (option) Screw cover - safety bracket (only for type of protection "Explosion-proof enclosure", not shown in the drawing)

2 3

4 5 6 7 8

1) 2) 3) 4) 5)

Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing Not with type of protection "explosion-proof enclosure" Not with type of protection "FM + CSA [is + xp]" 45 mm (1.8 inch) for Pg 13,5 with adapter Minimum distance for rotation

SITRANS P pressure transmitters, DS III series for absolute pressure, from the pressure series, dimensional drawing, dimensions in mm (inch)

2/32

Siemens FI 01 2005

120 (4.7)

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for absolute pressure (from pressure series)
Selection and Ordering data SITRANS P pressure transmitters, DS III series for absolute pressure from the pressure series 2-wire system Measuring cell filling Silicone oil Inert liquid Measured span 8.3 ... 250 mbar 43 ... 1300 mbar 0.16 ... 5 bar 1 ... 30 bar Measuring cell cleaning Standard Grease-free (0.12 ... 3.63 psi) (0.62 ... 18.9 psi) (2.32 ... 72.5 psi) (14.5 ... 435 psi) E) E) E) Order No. 7MF 4 2 3 3 77777 - 7777 4) Not together with type of protection "Explosion-proof" E) Combinations of the versions marked with E) are subject to the export regulations AL: 2B230, ECCN: N.

1 3 D F G H

Wetted parts materials Seal diaphragm Process connection Stainless steel Stainless steel Hastelloy Stainless steel Hastelloy Hastelloy Version for diaphragm seal 1) Process connection Connection shank GB to EN 837-1 Female thread -14 NPT Oval flange made of stainless steel, max. span 160 bar (2320 psi) - Mounting thread 7/16-20 UNF to EN 61518 - Mounting thread M10 to DIN 19213 Non-wetted parts materials Housing made of die-cast aluminium Housing stainless steel precision casting Design Standard design International version, English label inscriptions, documentation in 5 languages on CD Explosion protection without with ATEX, Type of protection: - "Intrinsic safety (EEx ia)" - "Explosion-proof (EEx d)" 2) - "Intrinsic safety and explosion-proof enclosure (EEx ia + EEx d)" 3) - "n (zone 2)" - "Intrinsic safety, explosion-proof enclosure and dust explosion protection (EEx ia + EEx d + zone 1D/2D)" 3) with FM + CSA, Type of protection: - "Intrinsic safety and explosion-proof (is + xp)" 2) Electrical connection / cable inlet Screwed gland Pg 13.5 4) Screwed gland M20x1.5 Screwed gland -14 NPT Han 7D plug (plastic housing) incl. mating connector 4) Display without (digital indicator hidden, setting: mA) with visible digital indicator with customer-specific digital indicator (setting as specified, Order code "Y21" required) E) E) A B C Y0 0 1

2 3 0 3 1 2

A B D P E R

NC A B C D

1 6 7

Power supply units see "SITRANS I power supply units and input isolators". The device is delivered together with brief instructions (Leporello) and a CD-ROM containing detailed documentation.
1) Version 7MF4233-1DY... only up to max. span 200 mbar (2.9 psi) 2) Without cable gland, with blanking plug 3) With enclosed cable gland EEx ia and blanking plug

Siemens FI 01 2005

2/33

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for absolute pressure (from pressure series)

Further designs Please add "-Z" to Order No. and specify Order code.

Order code

Further designs Please add "-Z" to Order No. and specify Order code. Additional data Measuring range to be set specify in plain text: Y01: ... to ... mbar, bar, kPa, MPa, psi Measuring point number/identification max. 16 characters, specify in plain text: Y15: ........................................... Measuring point text max. 27 characters, specify in plain text: Y16: ........................................... Entry of HART address (TAG) max. 8 characters, specify in plain text: Y17: ........................................... Setting of pressure indicator in pressure units specify in plain text (standard setting: mA): Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, mA, Torr, ATM or % *) Reference temperature 20 C Setting of pressure indicator in non-pressure units specify in plain text: Y22: ..... up to ..... l/min, m3/h, m, USgpm, ... (specification of measuring range in pressure units "Y01" is essential, unit with max. 5 characters)

Order code

Pressure transmitter with mounting bracket made of: Steel A01 Stainless steel A02 Plug Han 7D (metal, gray) Han 8U (instead of Han 7D) Rating plate inscription (instead of German) English French Spanish Italian English rating plate Pressure units in inH2O or psi Manufacturer's test certificate M (calibration certificate) to DIN 55350, Part 18 and to ISO 8402 Acceptance test certificate B to EN 10204-3.1.B Factory certificate to EN 10204-2.2 Certificate "Functional Safety (SIL)" Setting of upper limit of output signal to 22.0 mA Acid gas version to NACE (only together with seal diaphragm made of Hastelloy) Type of protection IP68 (not together with Han 7D / Han 8U plug, Pg 13.5 screwed gland) Digital indicator along side the input keys (only together with the devices 7MF4233-....0-.A.6 or -.A.7-Z, Y21 or Y22 + Y01). Use in or at zone 1D/2D (only together with type of protection "Intrinsic safety (EEx ia)" Use at zone 0 (only together with type of protection "Intrinsic safety (EEx ia)" Oxygen application (max. 160 bar (2320 psi) with oxygen measurement and inert liquid) A30 A31

Y01

Y15

Y16

B11 B12 B13 B14 B21 C11

Y17

Y21

C12 C14 C20 D05 D07 D12

Y22 + Y01

Only the settings for "Y01", "Y21", "Y22" and "D05" can be made in the factory

D27

E01

E02

E10

2/34

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for absolute pressure (from differential pressure series)

Technical specifications
SITRANS P pressure transmitters, DS III series for absolute pressure, from the differential pressure series Input Measured variable Span 8.3 ... 250 mbar (0.12 ... 3.6 psi) 43 ... 1300 mbar (0.62 ... 18.9 psi) 160 ... 5000 mbar (2.32 ... 72.5 psi) 1 ... 30 bar (14.5 ... 435 psi) 5.3 ... 100 bar (76.9 ... 1450 psi) Absolute pressure Maximum working pressure 32 bar (464 psi) 32 bar (464 psi) 32 bar (464 psi) 160 bar (2320 psi) 160 bar (2320 psi) With connection thread M10 and 7/ -20 UNF in the process flan16 ges 0 mark (0 psi) absolute 100% of max. span (max. 160 bar (2320 psi) with oxygen measurement and inert liquid) Continuously adjustable between the measuring limits

Measuring cell filling

Silicone oil or inert filling liquid (max. 160 bar (2320 psi) with oxygen measurement) Female thread -18 NPT and flange connection to DIN 19 213 with mounting thread M10 or 7/ -20 UNF 16 10.5 ... 45 V DC 10.5 ... 30 V DC in intrinsicallysafe mode For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) PTB 99 ATEX 2122 Ex II 1/2 G EEx ia/ib IIB/IIC T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +70 C (-40 ... +158 F) temperature class T5; -40 ... +60 C (-40 ... +140 F) temperature class T6 To certified intrinsically-safe circuits with maximum values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW; Ri = 300 Li = 0.4 mH, Ci = 6 nF PTB 99 ATEX 1160 Ex II 1/2 G EEx d IIC T4/T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +60 C (-40 ... +140 F) temperature class T6 To circuits with values: UH = 10.5 ... 45 V DC PTB 01 ATEX 2055 Ex II 1 D IP65 T 120 C Ex II 1/2 D IP65 T 120 C -40 ... +85 C (-40 ... +185 F) 120 C (248 F) To certified intrinsically-safe circuits with maximum values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 Li = 0.4 mH, Ci = 6 nF PTB 01 ATEX 2055 Ex II 2 D IP65 T 120 C To circuits with values: UH = 10.5 ... 45 V DC; Pmax = 1.2 W TV 01 ATEX 1696 X Ex II 3 G EEx nA L IIC T4/T5/T6 Certificate of Compliance 3008490 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III Siemens FI 01 2005

Process connection

Power supply UH Terminal voltage on pressure transmitter Certificates and approvals Classification according to pressure equipment directive (DRGL 97/23/EC)

Explosion protection Intrinsic safety "i" - Identification - Permissible ambient temperature

Lower measuring limit Measuring cell with silicone oil filling Upper measuring limit

Start of scale Output Output signal Measuring accuracy Reference conditions

- Connection 4 ... 20 mA Increasing characteristic Start-of-scale value 0 bar Stainless steel seal diaphragm Silicone oil filling Room temperature (25 C (77 F)) r: Span ratio (r = max. span / set span) - Effective internal inductance/capacitance Explosion-proof "d" - Identification - Permissible ambient temperature

Error in measurement and fixedpoint setting (including hysteresis and repeatability) Linear characteristic - r 10 - 10 < r 30 Influence of ambient temperature With -10 ... +60 C (14 ... 140 F) (0.1 r +0.2)% Twice the value with 20-mbar (0.29 psi) measuring cell (0.1 r +0.15)% / 10 K ( (0.1 r +0.15)% / 18 F) Twice the value with 20-mbar (0.29 psi) measuring cell IP65 -40 ... +100 C (-40 ... +212 F) -20 ... +100 C (-4 ... +212 F) -20 ... +60 C (-4 ... +140 F) (0.0029 r + 0.071)% (0.0045 r + 0.071)%

- Connection Dust explosion protection for zone 20 - Identification - Permissible ambient temperature - Max.surface temperature - Connection

With -40 ... -10 C and +60 C ... +85 C (-40 ... +14 and 140 ... 185 F) Rated conditions Degree of protection (to EN 60529) Process temperature Measuring cell with silicone oil filling Measuring cell with inert filling liquid In conjunction with dust explosion protection Design Weight (without options) Wetted parts materials Seal diaphragm

- Effective internal inductance/capacitance Dust explosion protection for zone 21/22 - Identification - Connection

Type of protection "n" (zone 2) - Identification 4.5 kg ( 9.9 lb) Stainless steel, mat. No. 1.4404/316L, Hastelloy C276, mat. No. 2.4819, Monel, mat. No. 2.4360, tantalum or gold Explosion protection to FM - Identification (XP/DIP) or (IS); (NI)

2/35

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for absolute pressure (from differential pressure series)

Explosion protection to CSA - Identification (XP/DIP) or (IS)

Certificate of Compliance 1153651 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III

Dimensional drawings
15 (0.6) 138 (5.4)

50 (1.97)
20 (0.8)

approx. 30 (1.2) 5)

100 (3.94) 6 2

80 (3.15)

117 (4.6)

50 (1.97)

3 198 (7.8) approx. 261 (10.3) 96 (3.8) 7 11

1)

69 (2.7) 77 (3) 4)

1)

9 10

Space for rotation of housing

1 134 (5.27)
+

ca. 96 (3.78)

52 (2.05)

3 72 (2.83) 105 (4.1) 1 2 3 Process connection: -18 NPT (EN 61518) Blanking plug Electrical connection: - screwed gland Pg 13,5 (adapter) 2) 3), - screwed gland M20x1,5 3), - screwed gland -14 NPT or - Han 7D/ Han 8U plug 2) 3) Terminal side Electronics side, digital display (longer overall length for cover with window) Protective cover over keys Mounting bracket (option) Sealing screw with valve (option) Screw cover - safety bracket (only for type of protection "Explosion-proof enclosure", not shown in the drawing) Lateral venting for liquid measurement Lateral venting for gas measurement (suffix H02) 68 (2.7) 120 (4.7)

4 5 6 7 8 9 10 11

1) 2) 3) 4) 5)

Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing Not with type of protection "explosion-proof enclosure" Not with type of protection "FM + CSA [is + xp]" 92 mm (3.62 inch) for minimum distance to permit rotation with indicator 45 mm (1.8 inch) for Pg 13,5 with adapter

SITRANS P pressure transmitters, DS III series for absolute pressure, from the differential pressure series, dimensional drawing, dimensions in mm (inch)

2/36

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for absolute pressure (from differential pressure series)
Selection and Ordering data SITRANS P pressure transmitters, DS III series for absolute pressure from the series Differential pressure 2-wire system Measuring cell filling Silicone oil Inert liquid1) Measured span 8.3 ... 250 mbar 43 ... 1300 mbar 0.16 ... 5 bar 1 ... 30 bar 5.3 ... 100 bar Measuring cell cleaning Standard Grease-free (0.12 ... 3.63 psi) (0.62 ... 18.9 psi) (2.32 ... 72.5 psi) (14.5 ... 435 psi) (76.9 ... 1450 psi) E) E) E) Order No. 7MF 4 3 3 3 Selection and Ordering data SITRANS P pressure transmitters, DS III series for absolute pressure from the series Differential pressure 2-wire system Display without (digital indicator hidden, setting: mA) with visible digital indicator with customer-specific digital indicator (setting as specified, Order code "Y21" required) D F G H KE Order No. 7MF 4 3 3 3 -

2
1 6 7

77777 - 7777

77777 - 7777

1 3

Power supply units see "SITRANS I power supply units and input isolators". Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation Sealing plug(s) or sealing screw(s) for the process flanges(s)
1) 2) 3) 4) 5) 6) E) For oxygen applications, add Order code E10. Version 7MF4433-1DY... only up to max. span 200 mbar (2.9 psi) Not for span "5.3 ... 100 bar (76.9 ... 1450 psi)" Without cable gland, with blanking plug With enclosed cable gland EEx ia and blanking plug Not together with type of protection "Explosion-proof" Combinations of the versions marked with E) are subject to the export regulations AL: 2B230, ECCN: N.

Wetted parts materials Seal diaphragm Parts of measuring cell Stainless steel Stainless steel Hastelloy Stainless steel Hastelloy Hastelloy Tantalum Tantalum Monel Monel Gold Gold Version for diaphragm seal 2) Process connection Female thread -18 NPT with flange connection Sealing screw opposite process connection - Mounting thread M10 to DIN 19213 - Mounting thread 7/16-20 UNF to EN 61518 Vent on side of process flange 3) - Mounting thread M10 to DIN 19213 - Mounting thread 7/16-20 UNF to EN 61518 Non-wetted parts materials Process flange screws Electronics housing Stainless steel Stainless steel Die-cast aluminium Stainless steel precision casting 2 3 E) E) E) A B C E H L Y

0 2 4 6

Design Standard design International version, English label inscriptions, documentation in 5 languages on CD Explosion protection without with ATEX, Type of protection: - "Intrinsic safety (EEx ia)" - "Explosion-proof (EEx d)" 4) - "Intrinsic safety and explosion-proof enclosure (EEx ia + EEx d)" 5) - "n (zone 2)" - "Intrinsic safety, explosion-proof enclosure and dust explosion protection (EEx ia + EEx d + zone 1D/2D)" 5) with FM + CSA, Type of protection: - "Intrinsic safety and explosion-proof (is + xp)" 4) Electrical connection / cable inlet Screwed gland Pg 13.5 6) Screwed gland M20x1.5 Screwed gland -14 NPT Han 7D plug (plastic housing) incl. mating connector 6)

1 2

A B D P E R

NC A B C D

Siemens FI 01 2005

2/37

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for absolute pressure (from differential pressure series)

Further designs Please add "-Z" to Order No. and specify Order code.

Order code

Further designs Please add "-Z" to Order No. and specify Order code. Additional data Measuring range to be set specify in plain text: Y01: ... up to ... mbar, bar, kPa, MPa, psi Measuring point number/identification max. 16 characters, specify in plain text: Y15: ........................................... Measuring point text max. 27 characters, specify in plain text: Y16: ........................................... Entry of HART address (TAG) max. 27 characters, specify in plain text: Y17: ........................................... Setting of pressure indicator in pressure units specify in plain text (standard setting: mA): Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, mA, Torr, ATM or % *) Reference temperature 20 C Setting of pressure indicator in non-pressure units specify in plain text: Y22: ..... up to ..... l/min, m3/h, m, USgpm, ... (specification of measuring range in pressure units "Y01" is essential, unit with max. 5 characters)

Order code

Pressure transmitter with mounting bracket made of: Steel A01 Stainless steel A02 O-rings for process flanges (instead of FPM (Viton)) PTFE (Teflon) FEP (with silicone core, approved for food) FFPM (Kalrez, compound 4079) NBR (Buna N) Plug Han 7D (metal, gray) Han 8U (instead of Han 7D) Sealing screws -18 NPT, with valve in material of process flanges Rating plate inscription (instead of German) English French Spanish Italian English rating plate Pressure units in inH2O or psi Manufacturer's test certificate M (calibration certificate) to DIN 55350, Part 18 and to ISO 8402 Acceptance test certificate B to EN 10204-3.1.B Factory certificate to EN 10204-2.2 Certificate "Functional Safety (SIL)" Setting of upper limit of output signal to 22.0 mA Acid gas version to NACE (only together with seal diaphragm made of Hastelloy) Type of protection IP68 (not together with Han 7D / Han 8U plug, Pg 13.5 screwed gland) Digital indicator along side the input keys (only together with the devices 7MF4333-....0-.A6 or -.A.7-Z, Y21 or Y22 + Y01) Use in or at zone 1D/2D (only together with type of protection "Intrinsic safety (EEx ia)" Use at zone 0 (only together with type of protection "Intrinsic safety (EEx ia)" Oxygen application (max. 160 bar (2320 psi) with oxygen measurement and inert liquid) Interchanging of process connection side Vent on side for gas measurements Process flange Hastelloy Monel Stainless steel with PVDF insert max. PN 10 (MWP 145 psi), Max. temperature of medium 90 C (194 F)

Y01

Y15

A20 A21 A22 A23 A30 A31 A40

Y16

Y17

Y21

B11 B12 B13 B14 B21 C11

Y22 + Y01

C12 C14 C20 D05 D07 D12

Only the settings for "Y01", "Y21", "Y22" and "D05" can be made in the factory

D27

E01

E02

E10

H01 H02 K01 K02 K04

2/38

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for differential pressure and flow

Technical specifications
SITRANS P pressure transmitters, DS III series, for differential pressure and flow Input Measured variable Span PN 32 (MWP 464 psi) - 1 ... 20 mbar (0.0145 ... 0.29 psi) 32 bar (464 psi) PN 160 (MWP 2320 psi) - 1 ... 60 mbar (0.0145 ... 0.87 psi) 160 bar (2320 psi) - 2.5 ... 250 mbar (0.036 ... 3.63 psi) - 6 ... 600 mbar (0.087 ... 8.7 psi) - 16 ... 1600 mbar (0.232 ... 23.2 psi) - 50 ... 5000 mbar (0.725 ... 72.5 psi) - 0.3 ... 30 bar (4.35 ... 435 psi) PN 420 (MWP 6092) - 2.5 ... 250 mbar (0.036 ... 3.63 psi) - 6 ... 600 mbar (0.087 ... 8.7 psi) - 16 ... 1600 mbar (0.232 ... 23.3 psi) - 50 ... 5000 mbar (0.725 ... 72.5 psi) - 0.3 ... 30 bar (4.35 ... 435 psi) Lower measuring limit Measuring cell with silicone oil filling -100% of max. span (-33% with 30 bar (435 psi) measuring cell) or 30 mbar (0.44 psi) absolute 100% of max. span (max. 160 bar (2320 psi) with oxygen measurement and inert liquid) 4 ... 20 mA Increasing characteristic Start-of-scale value 0 bar Stainless steel seal diaphragm Silicone oil filling Room temperature (25 C (77 F)) r: Span ratio (r = max. span / set span) 420 bar (6092 psi) 160 bar (2320 psi) 160 bar (2320 psi) 160 bar (2320 psi) 160 bar (2320 psi) 160 bar (2320 psi) Differential pressure and flow Maximum working pressure

Influence of ambient temperature With -10 ... +60 C (14 ... 140 F) With -40 ... -10 C and +60 C ... +85 C (-40 ... +14 and 140 ... 185 F) Rated conditions Degree of protection (to EN 60529) Process temperature Measuring cell with silicone oil filling Measuring cell with inert filling liquid In conjunction with dust explosion protection Design Weight (without options) Wetted parts materials Seal diaphragm Stainless steel, mat. No. 1.4404/316L, Hastelloy C276, mat. No. 2.4819, Monel, mat. No. 2.4360, tantalum or gold Silicone oil or inert filling liquid (max. 160 bar (2320 psi) with oxygen measurement) Female thread -18 NPT and flange connection to DIN 19 213 with mounting thread M10 or 7/ -20 UNF to EN 61518 16 10.5 ... 45 V DC 10.5 ... 30 V DC in intrinsicallysafe mode 4.5 kg ( 9.9 lb) -40 ... +100 C (-40 ... +212 F) -20 ... +100 C (-4 ... +212 F) -20 ... +60 C (-4 ... +140 F) IP65 (0.08 r +0.1)% (0.1 r +0.15)% / 10 K ( (0.1 r +0.15)% / 18 F) Twice the value with 20-mbar (0.29 psi) measuring cell.

Measuring cell filling 420 bar (6092 psi) 420 bar (6092 psi) Process connection 420 bar (6092 psi) 420 bar (6092 psi) Power supply UH Terminal voltage on pressure transmitter Certificates and approvals Classification according to pressure equipment directive (DRGL 97/23/EC) PN 32/160 (MWP 464/2320)

Upper measuring limit

Output Output signal Measuring accuracy Reference conditions

For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) For gases of fluid group 1 and liquids of fluid group 1; complies with basic safety requirements of article 3, paragraph 1 (appendix 1); assigned to category III, conformity evaluation module H by the TV Nord PTB 99 ATEX 2122 Ex II 1/2 G EEx ia/ib IIB/IIC T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +70 C (-40 ... +158 F) temperature class T5; -40 ... +60 C (-40 ... +140 F) temperature class T6 To certified intrinsically-safe circuits with maximum values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW; Ri = 300 L i = 0.4 mH, Ci = 6 nF

PN 420 (MWP 6092)

Error in measurement and fixedpoint setting (including hysteresis and repeatability) Linear characteristic - r 10 - 10 < r 30 - 30 < r 100 Square-root characteristic (flow > 50%) - r 10 - 10 < r 30 Square-root characteristic (flow 25 ... 50%) - r 10 - 10 < r 30 0.2% 0.4% 0.1% 0.2% (0.0029 r + 0.071)% (0.0045 r + 0.071)% (0.005 r +0.05)%

Explosion protection Intrinsic safety "i" - Identification - Permissible ambient temperature

- Connection

- Effective internal inductance/capacitance

Siemens FI 01 2005

2/39

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for differential pressure and flow

Explosion-proof "d" - Identification - Permissible ambient temperature

PTB 99 ATEX 1160 Ex II 1/2 G EEx d IIC T4/T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +60 C (-40 ... +140 F) temperature class T6 To circuits with values: UH = 10.5 ... 45 V DC PTB 01 ATEX 2055 Ex II 1 D IP65 T 120 C Ex II 1/2 D IP65 T 120 C -40 ... +85 C (-40 ... +185 F) 120 C (248 F) To certified intrinsically-safe circuits with maximum values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 Li = 0.4 mH, Ci = 6 nF PTB 01 ATEX 2055 Ex II 2 D IP65 T 120 C To circuits with values: UH = 10.5 ... 45 V DC; Pmax = 1.2 W TV 01 ATEX 1696 X Ex II 3 G EEx nA L IIC T4/T5/T6 Certificate of Compliance 3008490 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III Certificate of Compliance 1153651 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III

- Connection Dust explosion protection for zone 20 - Identification - Permissible ambient temperature - Max.surface temperature - Connection

- Effective internal inductance/capacitance Dust explosion protection for zone 21/22 - Identification - Connection

Type of protection "n" (zone 2) - Identification Explosion protection to FM - Identification (XP/DIP) or (IS); (NI)

Explosion protection to CSA - Identification (XP/DIP) or (IS)

2/40

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for differential pressure and flow

Dimensional drawings
15 (0.6) 138 (5.4)

2
50 (1.97)
20 (0.8)

approx. 30 (1.2) 5)

100 (3.94) 6 2

80 (3.15)

117 (4.6)

50 (1.97)

3 198 (7.8) approx. 261 (10.3) 96 (3.8) 7 11

5 1)

69 (2.7) 77 (3) 4)

1)

9 10

Space for rotation of housing

1 134 (5.27)
+

ca. 96 (3.78)

52 (2.05)

3 72 (2.83) 105 (4.1) 1 2 3 Process connection: -18 NPT (EN 61518) Blanking plug Electrical connection: - screwed gland Pg 13,5 (adapter) 2) 3), - screwed gland M20x1,5 3), - screwed gland -14 NPT or - Han 7D/ Han 8U plug 2) 3) Terminal side Electronics side, digital display (longer overall length for cover with window) Protective cover over keys Mounting bracket (option) Sealing screw with valve (option) Screw cover - safety bracket (only for type of protection "Explosion-proof enclosure", not shown in the drawing) Lateral venting for liquid measurement Lateral venting for gas measurement (suffix H02) 68 (2.7) 120 (4.7)

4 5 6 7 8 9 10 11

1) 2) 3) 4) 5)

Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing Not with type of protection "explosion-proof enclosure" Not with type of protection "FM + CSA [is + xp]" 92 mm (3.62 inch) for minimum distance to permit rotation with indicator 45 mm (1.8 inch) for Pg 13,5 with adapter

SITRANS P pressure transmitters, DS III series for differential pressure and flow, dimensional drawing, dimensions in mm (inch)

Siemens FI 01 2005

2/41

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for differential pressure and flow

2
80 (3.15)

15 (0.6) 69 (2.7)

138 (5.4)

20 (0.8)

50 (1.97)

ca. 96 (3.78)
50 (1.97)

approx. 30 (1.18)8)

100 (3.94) 6 2

4 1)

5 1)

77 (3)4)

Space for rotation of housing

ca. 85 (3.35)6)

8 1

67 (2.64)5)

ca. 84,6 (3.33)

1 2 3

4 5 6 7 8 9

Process connection: -18 NPT (EN 61518) Blanking plug Electrical connection: - screwed gland Pg 13,5 (adapter) 2) 3), - screwed gland M20x1,5 3), - screwed gland -14 NPT or - Han 7D/ Han 8U plug 2) 3) Terminal side Electronics side, digital display (longer overall length for cover with window) Protective cover over keys Mounting bracket (option) Sealing screw with valve (option) Screw cover - safety bracket (only for type of protection "Explosion-proof enclosure", not shown in the drawing)

1) 2) 3) 4) 5) 6) 7) 8)

Allow approx. 20 mm (0.79 inch) thread length to permit unscrewing Not with type of protection "explosion-proof enclosure" Not with type of protection "FM + CSA [is + xp]" 92 mm (3.6 inch) for minimum distance to permit rotation with indicator 74 mm (2.9 inch) for PN 420 (MWP 6092 psi) 91 mm (3.6 inch) for PN 420 (MWP 6092 psi) 219 mm (8.62 inch) for PN 420 (MWP 6092 psi) 45 mm (1.8 inch) for Pg 13,5 with adapter

SITRANS P pressure transmitters, DS III series for differential pressure and flow, with process covers for vertical differential pressure lines, dimensional drawing, dimensions in mm (inch)

SITRANS P pressure transmitters, DS III series for differential pressure and flow, with process covers for vertical differential pressure lines

2/42

Siemens FI 01 2005

approx. 217 (8.54)7)

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for differential pressure and flow
4 6

115 (4.5)

183 (7.2)

77 (3.0)
2

193 (7.6)

SITRANS P pressure transmitters, DS III series for differential pressure and flow, with digital indicator beside control keys, dimensional drawing, dimensions in mm (inch)

SITRANS P pressure transmitters, DS III series for differential pressure and flow, with digital indicator beside control keys

FIELD TERMINALS

1 2 3 4 5 6 7 8

Process connection, -18 NPT (EN 61 518) Terminal side, analog indicator (optional) External digital indicator (optional) Sealing plug Fixing screw Blanking plug Protective cover for keys Electrical connection

Siemens FI 01 2005

2/43

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for differential pressure and flow

Selection and Ordering data

Order No.

Selection and Ordering data

Order No.

} 7MF 4 4 3 3 SITRANS P pressure transmitters, DS III series for differential pressure and flow 77777 - 7777 PN 32/160 (MWP 464/2320 psi) 2-wire system Measuring cell filling Silicone oil Inert liquid1) Measured span PN 32 (MWP 464 psi) 1 ... 20 mbar 2) PN 160 (MWP 2320 psi) 1 ... 60 mbar 2.5 ... 250 mbar 6 ... 600 mbar 16 ... 1600 mbar 50 ... 5000 mbar 0.3 ... 30 bar Measuring cell cleaning standard grease-free

} 7MF 4 4 3 3 SITRANS P pressure transmitters, DS III series for differential pressure and flow 77777 - 7777 PN 32/160 (MWP 464/2320 psi) 2-wire system Display without (digital indicator hidden, setting: mA) } with visible digital indicator with customer-specific digital indicator (setting as specified, Order code "Y21" required) 1 6 7

} 1 3

} Available ex stock
(0.0145 ... 0.29 psi) (0.0145 ... 0.87 psi) (0.036 ... 3.63 psi) (0.087 ... 8.70 psi) (0.232 ... 23.2 psi) (0.725 ... 72.5 psi) (4.35 ... 435 psi) } } } } } } } B C D E F G H Power supply units see "SITRANS I power supply units and input isolators". Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation Sealing plug(s) or sealing screw(s) for the process flanges(s)
1) For oxygen application, add Order code E10. 2) Not suitable for connection of remote seal 3) Only together with max. spans 250, 1600, 5000 and 30000 mbar (3.63, 23.2, 72.5 and 435 psi). 4) Without cable gland, with blanking plug 5) With enclosed cable gland EEx ia and blanking plug 6) Not together with type of protection "Explosion-proof"

Wetted parts materials (stainless steel process flanges) Seal diaphragm Parts of measuring cell Stainless steel Stainless steel Hastelloy Stainless steel Hastelloy Hastelloy Tantalum 3) Tantalum Monel 3) Monel Gold 3) Gold Version for diaphragm seal } A B C E H L Y

Process connection Female thread -18 NPT with flange connection Sealing screw opposite process connection - Mounting thread M10 to DIN 19213 } - Mounting thread 7/16-20 UNF to EN 61518 Vent on side of process flange 2) - Mounting thread M10 to DIN 19213 - Mounting thread 7/16-20 UNF to EN 61518 Non-wetted parts materials Process flange screws Electronics housing Stainless steel Stainless steel Die-cast aluminium } Stainless steel precision casting

0 2 4 6

2 3

Design Standard design International version, English label inscriptions, } documentation in 5 languages on CD Explosion protection without with ATEX, Type of protection: - "Intrinsic safety (EEx ia)" - "Explosion-proof (EEx d)" 4) - "Intrinsic safety and explosion-proof enclosure } (EEx ia + EEx d)" 5) - "n (zone 2)" - "Intrinsic safety, explosion-proof enclosure and dust explosion protection (EEx ia + EEx d + zone 1D/2D)" 5) with FM + CSA, Type of protection: - "Intrinsic safety and explosion-proof (is + xp)" 4) Electrical connection / cable inlet Screwed gland Pg 13.5 6) Screwed gland M20x1.5 Screwed gland -14 NPT Han 7D plug (plastic housing) incl. mating connector 6)

1 2

A B D P E R

NC A B C D

2/44

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for differential pressure and flow
Further designs Please add "-Z" to Order No. and specify Order code. Pressure transmitter with mounting bracket made of: Steel A01 Stainless steel A02 O-rings for process flanges (instead of FPM (Viton)) PTFE (Teflon) FEP (with silicone core, approved for food) FFPM (Kalrez, compound 4079) NBR (Buna N) Plug Han 7D (metal, gray) Han 8U (instead of Han 7D) Sealing screws -18 NPT, with valve in material of process flanges Rating plate inscription (instead of German) English French Spanish Italian English rating plate (calibration certificate) Pressure units in inH2O or psi Manufacturer's test certificate M to DIN 55.350, Part 18 and to ISO 8402 Acceptance test certificate B to EN 10 204-3.1.B Factory certificate to EN 10.204-2.2 Certificate "Functional Safety (SIL)" Setting of upper limit of output signal to 22.0 mA Acid gas version to NACE (only together with seal diaphragm made of Hastelloy) Type of protection IP68 (not together with Han 7D / Han 8U plug, Pg 13.5 screwed gland) Digital indicator along side the input keys (only together with the devices 7MF4433-....0-.A.6 or -.A.7-Z, Y21 or Y22 + Y01) Use in or at zone 1D/2D (only together with type of protection "Intrinsic safety (EEx ia)" Use at zone 0 (only together with type of protection "Intrinsic safety (EEx ia)" TV approval to AD/TRD Overfilling safety device for flammable and non-flammable liquids (max. PN 32 (MVWP 464 psi), basic device with type of protection "Intrinsic safety (EEx ia)", to WHG and VbF) Order code Further designs Please add "-Z" to Order No. and specify Order code. Oxygen application (max. 160 bar (2320 psi) with oxygen measurement and inert liquid) Interchanging of process connection side Vent on side for gas measurements A20 A21 A22 A23 A30 A31 A40 Stainless steel process flanges for vertical differential pressure lines (not together with K01, K02 and K04) 1) Process flange Hastelloy Monel Stainless steel with PVDF insert Max. PN 10 (MWP 145 psi) Max. temperature of medium 90 C (194 F) Additional data B11 B12 B13 B14 B21 C11 C12 C14 C20 D05 D07 D12 Measuring range to be set specify in plain text: with linear characteristic: Y01: ... up to ... mbar, bar, kPa, MPa, psi with square-root characteristic: Y01: ... up to ... mbar, bar, kPa, MPa, psi Measuring point number/identification max. 16 characters, specify in plain text: Y15: ........................................... Measuring point text max. 27 characters, specify in plain text: Y16: ........................................... Entry of HART address (TAG) max. 27 characters, specify in plain text: Y17: ........................................... Setting of pressure indicator in pressure units specify in plain text (standard setting: mA): Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, mA, Torr, ATM or % *) Reference temperature 20 C Setting of pressure indicator in non-pressure units specify in plain text: Y22: ..... up to ..... l/min, m3/h, m, USgpm, ... (specification of measuring range in pressure units "Y01" or "Y02" is essential, unit with max. 5 characters) E10 Order code

H01 H02 H03

K01 K02 K04

Y01 Y02 Y15

Y16

Y17

Y21

D27

Y22 2)+ Y01 or Y02

E01

E02

Only the settings for "Y01", "Y21", "Y21", "Y22" and "D05"can be made in the factory
1) Not suitable for connection of remote seal 2) Not together with over-filling safety device for flammable and non-flammable liquids (Order code "E08")

E06 E08

Siemens FI 01 2005

2/45

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for differential pressure and flow

Selection and Ordering data SITRANS P pressure transmitters, DS III series for differential pressure and flow PN 420 (MWP 6092 psi) 2-wire system Measuring cell filling Silicone oil Measured span 2.5 ... 250 mbar 6 ... 600 mbar 16 ... 1600 mbar 50 ... 5000 mbar 0.3 ... 30 bar Measuring cell cleaning Standard (0.036 ... 3.63 psi) (0.087 ... 8.70 psi) (0.232 ... 23.2 psi) (0.725 ... 72.5 psi) (4.35 ... 435 psi)

Order No. 7MF 4 5 3 3 77777 - 7777

Selection and Ordering data SITRANS P pressure transmitters, DS III series for differential pressure and flow PN 420 (MWP 6092 psi) 2-wire system Display without (digital indicator hidden, setting: mA) with visible digital indicator with customer-specific digital indicator (setting as specified, Order code "Y21" required)

Order No. 7MF 4 5 3 3 77777 - 7777

1 D E F G H

1 6 7

Power supply units see "SITRANS I power supply units and input isolators". Scope of delivery: Pressure transmitter as ordered (Instruction Manual is extra ordering item)
1) 2) 3) 4) Not together with max. span 600 mbar Without cable gland, with blanking plug With enclosed cable gland EEx ia and blanking plug Not together with type of protection "Explosion-proof"

Wetted parts materials (stainless steel process flanges) Seal diaphragm Parts of measuring cell Stainless steel Hastelloy Gold 1) Stainless steel Stainless steel Gold A B L

Process connection Female thread -18 NPT with flange connection Sealing screw opposite process connection - Mounting thread M12 to DIN 19213 - Mounting thread 7/16-20 UNF to EN 61518 Vent on side of process flanges - Mounting thread M12 to DIN 19213 - Mounting thread 7/16-20 UNF to EN 61518 Non-wetted parts materials Process flange screws Electronics housing Stainless steel Stainless steel Die-cast aluminium Stainless steel precision casting

1 3

5 7

2 3

Design Standard design International version, English label inscriptions, documentation in 5 languages on CD Explosion protection without with ATEX, Type of protection: - "Intrinsic safety (EEx ia)" - "Explosion-proof (EEx d)" 2) - "Intrinsic safety and explosion-proof enclosure (EEx ia + EEx d)" 3) - "n (zone 2)" - "Intrinsic safety, explosion-proof enclosure and dust explosion protection (EEx ia + EEx d + zone 1D/2D)" 3) with FM + CSA, Type of protection: - "Intrinsic safety and explosion-proof (is + xp)" 2), max. PN 360 Electrical connection / cable inlet Screwed gland Pg 13.5 4) Screwed gland M20x1.5 Screwed gland -14 NPT Han 7D plug (plastic housing) incl. mating connector 4)

1 2

A B D P E R

NC

A B C D

2/46

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for differential pressure and flow
Further designs Please add "-Z" to Order No. and specify Order code. Pressure transmitter with mounting bracket made of: Steel A01 Stainless steel A02 O-rings for process flanges (instead of FPM (Viton)) PTFE (Teflon) FEP (with silicone core, approved for food) FFPM (Kalrez, compound 4079) NBR (Buna N) Plug Han 7D (metal, gray) Han 8U (instead of Han 7D) Sealing screws -18 NPT, with valve in material of process flanges Rating plate inscription (instead of German) English French Spanish Italian English rating plate Pressure units in inH2O or psi Manufacturer's test certificate M (calibration certificate) to DIN 55350, Part 18 and to ISO 8402 Acceptance test certificate B to EN 10204-3.1.B Factory certificate to EN 10204-2.2 Certificate "Functional Safety (SIL)" Setting of upper limit of output signal to 22.0 mA Acid gas version to NACE (only together with seal diaphragm made of Hastelloy) Type of protection IP68 (not together with Han 7D / Han 8U plug, Pg 13.5 screwed gland) Digital indicator along side the input keys (only together with the devices 7MF4533-....2-.A.6 or -.A.7-Z, Y21 or Y22 + Y01) Use in or at zone 1D/2D (only together with type of protection "Intrinsic safety (EEx ia)" Use at zone 0 (only together with type of protection "Intrinsic safety (EEx ia)" Interchanging of process connection side Stainless steel process flanges for vertical differential pressure lines Order code Further designs Please add "-Z" to Order No. and specify Order code. Additional data Measuring range to be set specify in plain text: with linear characteristic: Y01: ... up to ... mbar, bar, kPa, MPa, psi with square-root characteristic: Y01: ... up to ... mbar, bar, kPa, MPa, psi Measuring point number/identification max. 16 characters, specify in plain text: Y15: ........................................... Measuring point text max. 27 characters, specify in plain text: Y16: ........................................... Entry of HART address (TAG) max. 27 characters, specify in plain text: Y17: ........................................... Setting of pressure indicator in pressure units specify in plain text (standard setting: mA): Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, mA, Torr, ATM or % *) Reference temperature 20 C Setting of pressure indicator in non-pressure units specify in plain text: Y22: ..... up to ..... l/min, m3/h, m, USgpm, ... (specification of measuring range in pressure units "Y01" or "Y02" is essential, unit with max. 5 characters) Order code

Y01 Y02 Y15

A20 A21 A22 A23 A30 A31 A40

Y16

Y17

B11 B12 B13 B14 B21 C11

Y21

Y22 + Y01 or Y02

C12 C14 C20 D05 D07 D12

Only the settings for "Y01", "Y21", "Y22" and "D05" can be made in the factory

D27

E01

E02

H01 H03

Siemens FI 01 2005

2/47

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for level

Technical specifications
SITRANS P pressure transmitters, DS III series, for level Input Measured variable Span 25 ... 250 mbar (0.36 ... 3.63 psi) 25 ... 600 mbar (0.36 ... 8.7 psi) 53 ... 1600 mbar (0.77 ...23.2 psi) 160 ... 5000 mbar (2.32 ... 72.5 psi) Lower measuring limit (measuring cell with silicone oil filling) Upper measuring limit Output Output signal Measuring accuracy Reference conditions Increasing characteristic Start-of-scale value 0 bar Stainless steel seal diaphragm Mounting flange without tube Silicone oil filling Room temperature (25 C (77 F)) r: Span ratio (r = max. span / set span) 4 ... 20 mA -100% of max. span or 30 mbar (0.435 psi) abs., depending on mounting flange 100% of max. span Level Maximum working pressure (nominal pressure) See "Mounting flange"

Measuring cell with silicone oil filling - High-pressure side pabs 1 bar: -40 ... +175 C (-40 ... +347 F) pabs < 1 bar: -40 ... +80 C (-40 ... +176 F) -40 ... +100 C (-40 ... +212 F) -20 ... +60 C (-4 ... +140 F) in conjunction with dust explosion protection

- Low-pressure side

Design Weight (without options) To DIN (pressure transmitter with mounting flange, without tube) To ANSI (pressure transmitter with mounting flange, without tube) Wetted parts materials High-pressure side: Seal diaphragm of mounting flange Stainless steel, mat. No. 1.4404/316L, Monel 400, mat. No. 2.4360, Hastelloy B2, mat. No. 2.4617, Hastelloy C276, mat. No. 2.4819, Hastelloy C4, mat. No. 2.4610, tantalum, PTFE, ECTFE Silicone oil Flange to DIN and ANSI Female thread -18 NPT and flange connection to DIN 19213 with mounting thread M10 or 7/ -20 UNF to EN 61518 16 10.5 ... 45 V DC 10.5 ... 30 V DC in intrinsicallysafe mode For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) PTB 99 ATEX 2122 Ex II 1/2 G EEx ia/ib IIB/IIC T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +70 C (-40 ... +158 F) temperature class T5; -40 ... +60 C (-40 ... +140 F) temperature class T6 To certified intrinsically-safe circuits with maximum values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW; Ri = 300 Li = 0.4 mH, Ci = 6 nF PTB 99 ATEX 1160 Ex II 1/2 G EEx d IIC T4/T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +60 C (-40 ... +140 F) temperature class T6 To circuits with values: UH = 10.5 ... 45 V DC 11 ... 13 kg ( 24.2 ... 28.7 lb) 11 ... 18 kg ( 24.2 ... 39.7 lb)

Measuring cell filling Process connection High-pressure side Low-pressure side

Error in measurement and fixedpoint setting (including hysteresis and repeatability) Linear characteristic - r 10 - 10 < r 30 - 30 < r 100 Influence of ambient temperature With -10 ... +60 C (14 ... 140 F) - 250-mbar (3.63 psi) measuring cell - 600-mbar (8.7 psi) measuring cell - 1,600 and 5,000 mbar (23.2 and 72.5 psi) measuring cells With -40 ... -10 C and +60 C ... +85 C (-40 ... +14 and 140 ... 185 F) - 250-mbar (3.63 psi) measuring cell - 600-mbar (8.7 psi) measuring cell - 1,600 and 5,000 mbar (23.2 and 72.5 psi) measuring cells Rated conditions Degree of protection (to EN 60529) Process temperature IP65 Note: Note the assignment of the max. permissible operating temperature to the max. permissible operating pressure of the respective flange connection! (0.25 r +0.15)% / 10 K ( (0.25 r +0.15)% / 18 F) (Twice the value for 10 < r 30) (0.15 r +0.15)% / 10 K ( (0.15 r +0.15)% / 18 F) (Twice the value for 10 < r 30) (0.12 r +0.15)% / 10 K ( (0.12 r +0.15)% / 18 F) (Twice the value for 10 < r 30) - Effective internal inductance/capacitance Explosion-proof "d" - Identification - Permissible ambient temperature (0.5 r + 0.2)% (0.4 instead of 0.2 with 10 < r 30) (0.3 r + 0.2)% (0.4 instead of 0.2 with 10 < r 30) (0.25 r + 0.2)% (0.4 instead of 0.2 with 10 < r 30) 0.15% 0.3% (0.0075 r + 0.075)% Certificates and approvals Classification according to pressure equipment directive (DRGL 97/23/EC) Power supply UH Terminal voltage on pressure transmitter

Explosion protection Intrinsic safety "i" - Identification - Permissible ambient temperature

- Connection

- Connection

2/48

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for level
Dust explosion protection for zone 20 - Identification - Permissible ambient temperature - Max.surface temperature - Connection PTB 01 ATEX 2055 Ex II 1 D IP65 T 120 C Ex II 1/2 D IP65 T 120 C -40 ... +85 C (-40 ... +185 F) 120 C (248 F) To certified intrinsically-safe circuits with maximum values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 Li = 0.4 mH, Ci = 6 nF PTB 01 ATEX 2055 Ex II 2 D IP65 T 120 C To circuits with values: UH = 10.5 ... 45 V DC; Pmax = 1.2 W TV 01 ATEX 1696 X Ex II 3 G EEx nA L IIC T4/T5/T6 Certificate of Compliance 3008490 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III Certificate of Compliance 1153651 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III To ASME B16.5 - 3 inch - 4 inch class 150 class 300 class 150 class 300 Mounting flange Nom. diam. To EN 1092-1 - DN 80 - DN 100 PN 40 PN 16 PN 40 Nom. press.

- Effective internal inductance/capacitance Dust explosion protection for zone 21/22 - Identification - Connection

Type of protection "n" (zone 2) - Identification Explosion protection to FM - Identification (XP/DIP) or (IS); (NI)

Explosion protection to CSA - Identification (XP/DIP) or (IS)

Siemens FI 01 2005

2/49

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for level

Dimensional drawings
approx. 30 (1.18)5)

185 100 (3.94) 6


50 (1.97)

138 (5.4) 69 (2.72)

15 (0.6)

2 165 (6.5) 51) L

77 (3)4)

8 d5 d4 3 1 54 (2.1) 108 (4.25) Space for rotation of housing b f nxd 2 D k

approx. 96 (3.78)

1 2 3

4 5 6 8 9 1) 2) 3) 4) 5)

Process connection of low pressure side -18 NPT (EN 61 518) Blanking plug Electrical connection: screwed gland Pg 13.5 (adapter) 2) 3), screwed gland M20x1.5, screwed gland -14 NPT or Han 7D/ Han 8U plug 2) 3) Terminal side Electronics side, digital display (longer overall length for cover with window) Protective cover over keys Sealing screw with valve (option) Screw cover safety bracket (only for type of protection "Explosion-proof enclosure", not shown in the drawing) Allow approx. 20 mm (0.79 inch) thread length in addition Not with type of protection "Explosion-proof enclosure" Not with type of protection "FM + CSA [is + xp]" 92 mm (3.62 inch) for minimum distance to permit rotation without indicator Approx. 45 mm (1.77 inch) for Pg 13.5 with adapter

6 41)

51)

SITRANS P pressure transmitters, DS III series for level, including mounting flange, dimensional drawing, dimensions in mm (inch)

Connection to EN 1092-1
Nom. diam. DN 80 DN 100 Nom. press. PN 40 PN 40 PN 40 b mm 24 20 24 D mm 200 220 235 d mm 90 115 115 d2 mm 18 18 22 d4 mm 138 158 162 d5 mm 76 94 94 dM mm 72 1) 89 89 f mm 2 2 2 k mm 160 180 190 n mm 8 8 8 L mm 0, 50, 100, 150 or 200

Connection to ASME B16.5


Nom. diam. 3 inch Nom. press. b lb/sq.in. 150 300 4 inch 150 300 inch (mm) 0.94 (23.8) 1.12 (28.6) 0.94 (23.8) 1.25 (31.7) D inch (mm) 7.5 (190.5) 8.25 (209.5) 9 (228.5) 10 (254) d2 inch (mm) 0.75 (19.0) 0.87 (22.2) 0.75 (19.0) 0.87 (22.2) d4 inch (mm) 5 (127) 5 (127) 6,19 (157.2) 6,19 (157.2)
1)

d5 3 (76) 3 (76) 3.69 (94) 3.69 (94)

dM 2.81 1) (72) 2.81 1) (72) 3.5 (89) 3.5 (89)

f 0.06 (1.6) 0.06 (1.6) 0.06 (1.6) 0.06 (1.6)

k 6 (152.4) 6.69 (168.3) 7.5 (190.5) 7.88 (200)

n 4 8 8 8

L inch (mm) 0, 2, 3.94, 5.94 or 7.87 (0, 50, 100, 150 or 200)

inch (mm) inch (mm) inch (mm) inch (mm)

d: Internal diameter of gasket to DIN 2690 dM: Effective diaphragm diameter

89 mm = 3 inch with tube length L = 0.

2/50

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for level
Selection and Ordering data SITRANS P pressure transmitters, DS III series for level 2-wire system Measuring cell filling Silicone oil Measured span 25 ... 250 mbar 25 ... 600 mbar 53 ... 1600 mbar 0.16 ... 5 bar Measuring cell cleaning Standard (0.363 ... 3.63 psi) (0.363 ... 8.70 psi) (0.77 ... 23.2 psi) (2.32 ... 72.5 psi) Order No. 7MF 4 6 3 3 77 Y77 - 7777

Further designs Please add "-Z" to Order No. and specify Order code. O-rings for process flanges (instead of FPM (Viton)) PTFE (Teflon) FEP (with silicone core, approved for food) FFPM (Kalrez, compound 4079) NBR (Buna N) Plug Han 7D (metal, gray) Han 8U (instead of Han 7D) Sealing screws -18 NPT, with valve in material of process flanges

Order code

1 D E F G

A20 A21 A22 A23 A30 A31 A40

Process connection of low-pressure side Female thread -18 NPT with flange connection Mounting thread M10 to DIN 19213 Mounting thread 7/16-20 UNF to EN 61518 Non-wetted parts materials Process flange screws Electronics housing Stainless steel Stainless steel Die-cast aluminium Stainless steel precision casting

0 2

2 3

Rating plate inscription (instead of German) English French Spanish Italian English rating plate Pressure units in inH2O or psi 1 2 Manufacturer's test certificate M (calibration certificate) to DIN 55350, Part 18 and to ISO 8402 A B D P E R Acceptance test certificate B to EN 10204-3.1.B Factory certificate to EN 10204-2.2 Certificate "Functional Safety (SIL)" Setting of upper limit of output signal to 22.0 mA Type of protection IP68 (not together with Han 7D / Han 8U plug, Pg 13.5 screwed gland) Use in or at zone 1D/2D (only together with type of protection "Intrinsic safety (EEx ia)" Use at zone 0 (only together with type of protection "Intrinsic safety (EEx ia)" Overfilling safety device for flammable and non-flammable liquids (max. PN 32, only together with type of protection "Intrinsic safety (EEx ia)"), to WHG and VbF 1 6 7 Interchanging of process connection side

B11 B12 B13 B14 B21 C11

Design Standard design International version, English label inscriptions, documentation in 5 languages on CD Explosion protection without with ATEX, Type of protection: - "Intrinsic safety (EEx ia)" - "Explosion-proof (EEx d)" 1) - "Intrinsic safety and explosion-proof enclosure (EEx ia + EEx d)" 2) - "n (zone 2)" - "Intrinsic safety, explosion-proof enclosure and dust explosion protection (EEx ia + EEx d + zone 1D/2D)" 2) with FM + CSA, Type of protection: - "Intrinsic safety and explosion-proof (is + xp)" 1) Electrical connection / cable inlet Screwed gland Pg 13.5 3) Screwed gland M20x1.5 Screwed gland -14 NPT Han 7D plug (plastic housing) incl. mating connector 3) Display without (digital indicator hidden, setting: mA) with visible digital indicator with customer-specific digital indicator (setting as specified, Order code "Y21" required) Ordering information: 1st order item: Pressure transmitter 7MF4633-... 2nd order item: Mounting flange 7MF4912-3... Example of ordering: Item line 1: 7MF4633-1EY20-1AA1-Z B line: Y01 C line: Y01: 80 to 143 mbar (1.16 to 2.1 psi) Item line 2: 7MF4912-3GE01

C12 C14 C20 D05 D12

E01

NC A B C D

E02

E08

H01

Power supply units see "SITRANS I power supply units and input isolators". Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation Sealing plug(s) or sealing screw(s) for the process flanges(s)
1) Without cable gland, with blanking plug 2) With enclosed cable gland EEx ia and blanking plug 3) Not together with type of protection "Explosion-proof"

Siemens FI 01 2005

2/51

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III series for level

Further designs Please add "-Z" to Order No. and specify Order code. Additional data Measuring range to be set specify in plain text: Y01: ... up to ... mbar, bar, kPa, MPa, psi Measuring point number/identification max. 16 characters, specify in plain text: Y15: ........................................... Measuring point text max. 27 characters, specify in plain text: Y16: ........................................... Entry of HART address (TAG) max. 8 characters, specify in plain text: Y17: ........................................... Setting of pressure indicator in pressure units specify in plain text (standard setting: mA): Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, mA, Torr, ATM or % *) Reference temperature 20 C Setting of pressure indicator in non-pressure units specify in plain text: Y22: ..... up to ..... l/min, m3/h, m, USgpm, ... (specification of measuring range in pressure units "Y01" is essential, unit with max. 5 characters)

Order code

Selection and Ordering data Mounting flange directly fitted to pressure transmitter SITRANS P (converter part) for level, for DS III series Wetted parts materials Stainless steel 316L - Coated with PFA 1) - Coated with PTFE 1) - Coated with ECTFE 1) Monel 400, mat. No. 2.4360 Hastelloy B2, mat. No. 2.4617 Hastelloy C276, mat. No. 2.4819 Hastelloy C4, mat. No. 2.4610 Tantalum Other version Add Order code and plain text: Wetted parts materials: ... Sealing face, see "Technical data" Tube length without 50 mm (1.97 inch) 100 mm (3.94 inch) 150 mm (5.90 inch) 200 mm (7.87 inch) Other version: Add Order code and plain text: Tube length: ... Filling liquid Silicone oil M5 Silicone oil M50 High-temperature oil Halocarbon oil (for O2 measurements) Vegetable Glycerin / water2) Other version Add Order code and plain text: Filling liquid: ... Ordering example see previous page

Order No. Ord. code 7MF 4 9 1 2 3 7777


777

Y01

Y15

Y16

A D E0 F G H J U K Z K1Y

Y17

Y21

Y22 1)+ Y01

0 1 2 3 4 9

L1Y

Only the settings for "Y01", "Y21", "Y22" and "D05" can be made in the factory
1) Not together with over-filling safety device for flammable and non-flammable liquids (Order code "E08")

Selection and Ordering data Mounting flange directly fitted to pressure transmitter SITRANS P (converter part) for level, for DS III series Connection to EN 1092-1 Nom. diam. Nom. press. DN 80 PN 40 DN 100 PN 16 PN 40 Connection to ASME B16.5 Nom. diam. Nom. press. 3 inch Class 150 Class 300 4 inch Class 150 Class 300 Other version Add Order code and plain text: Nominal diameter: ...; Nominal pressure: ...

Order No. Ord. code 7MF 4 9 1 2 3 7777


777

1 2 3 4 5 6 9 M1 Y

D G H

1) For vacuum on request 2) Not suitable for use in low-pressure range

Further designs Please add "-Z" to Order No. and specify Order code. Spark arrestor for mounting on zone 0 (including documentation) Manufacturer's test certificate M to DIN 55.350, Part 18 and to ISO 8402 J1Y Acceptance test certificate B to EN 10 204-3.1B Vacuum-proof design (for use in low-pressure range) Calculation of span of associated pressure transmitter (enclose filled-in questionnaire with order) Note: Suffix "Y01" required with pressure transmitter

Order code A01 C11 C12 V04 Y05

Q R T U Z

2/52

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA series (PROFIBUS)

Overview

SITRANS P pressure transmitters of the DS III PA series are digital pressure transmitters featuring extensive user-friendliness and high accuracy. Parameterization is performed using input keys or through the PROFIBUS interface. Extensive functionality enables the pressure transmitter to be precisely adapted to the plants requirements. Operation is very simple in spite of the numerous setting options. Transmitters with type of protection "Intrinsic safety" and "Explosion-proof" may be installed within potentially explosive atmospheres (zone 1) or in zone 0. The transmitters are provided with an EC type examination certificate and comply with the corresponding harmonized European standards (ATEX). The transmitters can be equipped with various designs of remote seals for special applications such as the measurement of highly viscous substances. Various versions of the DS III PA pressure transmitters are available for measuring: Pressure Absolute pressure Differential pressure Level Volume Volume flow Mass flow

High measuring accuracy Parameterization using input keys and PROFIBUS PA, profile 3.0

Application
SITRANS P pressure transmitters, DS III PA series, can be used in industrial areas with extreme chemical and mechanical loads. Electromagnetic compatibility in the range 10 kHz to 1 GHz makes the DS III PA pressure transmitters suitable for locations with high electromagnetic emissions. Pressure transmitters with type of protection "Intrinsic safety" and "Explosion-proof" may be installed within potentially explosive atmospheres (zone 1) or in zone 0. The pressure transmitters are provided with an EC type examination certificate and comply with the corresponding harmonized European standards of the CENELEC. Pressure transmitters with the type of protection "Intrinsic safety" for use in zone 0 may be operated with power supply units of category "ia" and "ib". The transmitters can be equipped with various designs of remote seals for special applications such as the measurement of highly viscous substances. Pressure transmitters for pressure Measured variable: Pressure of aggressive and non-aggressive gases, vapors and liquids. Measured spans: 0.01 ... 400 bar (0.145 ... 5802 psi) Pressure transmitters for absolute pressure Measured variable: Absolute pressure of aggressive and nonaggressive gases, vapors and liquids. Measured spans: 8.3 mbar ... 100 bar (0.12 ... 1450 psi) There are two series: Pressure series Differential pressure series

Benefits
High quality and long life High reliability even under extreme chemical and mechanical loads For aggressive and non-aggressive gases, vapors and liquids Extensive diagnosis and simulation functions Separate replacement of measuring cell and electronics without recalibration Minimum conformity error Small long-term drift Wetted parts made of high-grade materials (stainless steel, Hastelloy, gold, Monel, tantalum) Choice of several nominal measuring ranges

Siemens FI 01 2005

2/53

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA series (PROFIBUS)

Pressure transmitters for differential pressure and flow Measured variables: Differential pressure Small positive or negative pressure Flow q ~ p (together with a primary differential pressure device) Nominal measuring ranges: 1 mbar ... 30 bar (0.0145 ... 435 psi) Pressure transmitters for level Measured variable: Level of aggressive and non-aggressive liquids in open and closed vessels. Nominal measuring ranges: 25 mbar ... 5 bar (0.363 ... 72.5 psi) Nominal diameter of the mounting flange: DN 80 or DN 100 3 inch or 4 inch In the case of level measurements in open containers, the lowpressure connection of the measuring cell remains open (measurement "compared to atmospheric"). In the case of measurements in closed containers, the lowerpressure connection has to be connected to the container in order to compensate the static pressure. The wetted parts are constructed from a variety of materials depending on the degree of corrosion resistance required.

pane so that the measured values can be read directly on the digital display. The inlet (4) for the electrical connection is located either on the left or right side. The unused opening on the opposite side is sealed by a blanking plug. The protective earth connection is located on the rear of the housing. The electrical connections for the power supply and screen are accessible by unscrewing the rear cover. The bottom part of the housing contains the measuring cell with process connection (1). The measuring cell is protected from rotating by a locking screw (8). As the result of this modular design, the measuring cell and the electronics can be replaced separately from each other. The set parameter data are retained. At the top of the housing is a plastic cover (5), under which the input keys can be found.

Function
Mode of operation of the electronics
9 M 2 3 4 mC 0 0 00 0 00 5 PA interface PROFIBUS-PA 7 Power supply 10 PROFIBUS-DP BusMaster Power supply unit

Design

EEPROM

Coupler

Electronics 1 Sensor pe 6 EEPROM

11 12

Measuring cell 8 9 10 11 12 pe Three input keys (local operation) Digital display Power supply DP/PA coupler or link Bus master Input variable

1 2 3 4 5 6 7

Measuring cell sensor Instrument amplifier Analog-to-digital converter Microcontroller Electrical isolation One non-volatile memory each in the measuring cell and electronics PROFIBUS-PA interface

Function diagram of the electronics

Front view

The transmitter consists of various components depending on the order. The possible versions are listed in the ordering information. The components described below are the same for all transmitters. The rating plate (3, Figure "Front view") with the Order No. is located on the side of the housing. The specified number together with the ordering information provide details on the optional design details and on the possible measuring range (physical properties of built-in sensor element). The approval label is located on the opposite side. The housing is made of die-cast aluminium or stainless steel precision casting. A round cover is screwed on at the front and rear of the housing. The front cover (6) can be fitted with a viewing

The bridge output voltage created by the sensor (1, Figure "Function diagram of the electronics") is amplified by the instrument amplifier (2) and digitized in the analog-to-digital converter (3). The digital information is evaluated in the microcontroller, its linearity and temperature response corrected, and provided on the PROFIBUS PA through an electrically isolated PA interface (7). The data specific to the measuring cell, the electronics data, and the parameter data are stored in the two non-volatile memories (6). The one memory is coupled to the measuring cell, the other to the electronics. As the result of this modular design, the electronics and the measuring cell can be replaced separately from each other. Using the three input keys (8) you can parameterize the pressure transmitter directly at the point of measurement. The input keys can also be used to control the view of the results, the error messages and the operating modes on the digital display (9).

2/54

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA series (PROFIBUS)
The results with status values and diagnostic values are transferred by cyclic data transmission on the PROFIBUS PA. Parameterization data and error messages are transferred by acyclic data transmission. Special software such as SIMATIC PDM is required for this. Mode of operation of the measuring cells Measuring cell for pressure
5 pe 6
5 4 3 1

Measuring cell for absolute pressure from differential pressure series

1 2 3 4 5 6 7 8 pe

Reference vacuum Overload diaphragm Silicon pressure sensor O-ring Process flange Seal diaphragm Body of measuring cell Filling liquid Absolute pressure as input variable

8 1 2 3 4 5 pe Measuring cell Process connection Seal diaphragm Filling liquid Silicon pressure sensor Pressure as input variable

Measuring cell for absolute pressure from differential pressure series, functional diagram

2 p e

The input pressure pe is transmitted through the seal diaphragm (6, Figure "Measuring cell for absolute pressure from differential pressure series, functional diagram") and the filling liquid (8) to the silicon pressure sensor (3). The difference in pressure between the input pressure pe and the reference vacuum (1) on the low-pressure side of the measuring cell flexes the measuring diaphragm. The resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit thus changes. This change in resistance results in a bridge output voltage proportional to the absolute pressure. An overload diaphragm is installed to provide protection from overloads. If the measuring limits are exceeded, the overload diaphragm (2) is flexed until the seal diaphragm rests on the body of the measuring cell (7), thus protecting the silicon pressure sensor from overloads. Measuring cell for differential pressure and flow

Measuring cell for pressure, functional diagram

Measuring cell for absolute pressure from pressure series The pressure pe is applied through the process connection (2, Figure "Measuring cell for pressure, functional diagram) to the measuring cell (1). This pressure is subsequently transmitted further through the seal diaphragm (3) and the filling liquid (4) to the silicon pressure sensor (5) whose measuring diaphragm is then flexed. The resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit thus changes. This change in resistance results in a bridge output voltage proportional to the absolute pressure.

4 1 2 3 4 5 6 7 Seal diaphragm O-ring Overload diaphragm Silicon pressure sensor Process flange Body of measuring cell Filling liquid

5 4 3 1 1 2 3 4 5 pe Measuring cell Process connection Seal diaphragm Filling liquid Silicon absolute pressure sensor Absolute pressure as input variable 1 + 1 5

Measuring cell for differential pressure and flow, functional diagram

pe

The differential pressure is transmitted through the seal diaphragms (1, Figure "Measuring cell for differential pressure and flow, functional diagram") and the filling liquid (7) to the silicon pressure sensor (4). The measuring diaphragm is flexed by the applied differential pressure. The resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit thus changes. This change in resistance results in a bridge output voltage proportional to the absolute pressure. An overload diaphragm is installed to provide protection from overloads. If the measuring limits are exceeded, the overload diaphragm (2) is flexed until the seal diaphragm rests on the body of the measuring cell (7), thus protecting the silicon pressure sensor from overloads.

Measuring cell for absolute pressure from the pressure series, functional diagram

The absolute pressure pe is transmitted through the seal diaphragm (3, Figure "Measuring cell for absolute pressure from pressure series, functional diagram") and the filling liquid (4) to the silicon absolute pressure sensor (5) whose measuring diaphragm is then flexed. The resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit thus changes. This change in resistance results in a bridge output voltage proportional to the input pressure.

Siemens FI 01 2005

2/55

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA series (PROFIBUS)

Measuring cell for level

Adjustable parameters
Parameters
3 4 5 6 7

Input keys x x x x x x x

PROFIBUS interface x x x x x x x x x x x

Electrical damping Zero adjustment (correction of position)


8

2 + 1 10 9 6 7 8 9 10

Keys and/or function disabling Physical dimension of display Position of decimal point Bus address Adjustment of characteristic Input of characteristic Freely-programmable LCD Diagnostics functions

Source of measured-value display x

1 2 3 4 5

Flange with tube Seal diaphragm on mounting flange Seal diaphragm Body of measuring cell Overload diaphragm

Silicon pressure sensor O-ring Process flange Filling liquid Capillary with filling liquid of mounting flange

Measuring cell for level, functional diagram

The input pressure (hydrostatic pressure) acts hydraulically on the measuring cell through the seal diaphragm on the mounting flange (2, Figure "Measuring cell for level, functional diagram"). This differential pressure is subsequently transmitted further through the measuring cell (3) and the filling liquid (9) to the silicon pressure sensor (6) whose measuring diaphragm is then flexed. The resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit thus changes. This change in resistance results in a bridge output voltage proportional to the differential pressure. An overload diaphragm is installed to provide protection from overloads. If the measuring limits are exceeded, the overload diaphragm (2) is flexed until the seal diaphragm rests on the body of the measuring cell (7), thus protecting the silicon pressure sensor from overloads. Parameterization Depending on the version, there are different possibilities for parameterizing the pressure transmitter and for setting or scanning the parameters. Parameterization using the input keys (local operation) With the input keys you can easily set the most important parameters without any additional equipment. Parameterization through PROFIBUS PA interface Fully digital communication through PROFIBUS PA, profile 3.0, is particularly user-friendly. The PROFIBUS puts the DS III PA is in connection with a process control system, e.g. SIMATIC PSC 7. Communication is possible even in a potentially explosive environment. For parameterization through PROFIBUS you need suitable software, e.g. SIMATIC PDM (Process Device Manager).

Diagnostic functions Event counter Slave pointer Maintenance timer Simulation functions Display of zero correction Limit transmitter Saturation alarm Physical dimensions available for the display
Physical variable Pressure (setting can also be made in the factory) Physical dimensions MPa, hPa, kPa, Pa, bar, mbar, torr, atm, psi, g/cm2, kg/cm2, mmH20, mmH20 (4 C), inH20, inH20 (4 C), ftH20, mmHg, inHg m, cm, mm, ft, in, yd m3, dm3, hl, yd3, ft3, in3, US gallon, lmp, gallon, bushel, barrel, barrel liquid m3/s, m3/min, m3/h, m3/d, l/s, l/min, l/h, l/ d, Ml/d, ft3/s, ft3/min, ft3/h, ft3/d, US gallon/s, US gallon/min, US gallon/h, US gallon/d, bbl/s, bbl/min, bbl/h, bbl/d g/s, g/min, g/h, g/d, kg/s, kg/min, kg/h, kg/d, t/s, t/min, t/h, /t/d, lb/s, lb/min, lb/h, lb/d, STon/s, STon/min, STon/h, STon/d, LTon/s, LTon/min, LTon/h, LTon/d t, kg, g, lb, oz, LTon, STon K, C, F, R %

Level (height data) Volume

Volume flow

Mass flow

Total mass flow Temperature Miscellaneous

2/56

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA series for pressure

Technical specifications
SITRANS P pressure transmitters, DS III PA series for pressure Input Measured variable Nominal measuring range 1 bar (14.5 psi) 4 bar (58 psi) 16 bar (232 psi) 63 bar (913 psi) 160 bar (2320 psi) 400 bar (5802 psi) Lower measuring limit Measuring cell with silicone oil filling Upper measuring limit 30 mark (0.435 psi) absolute Pressure Max. working pressure 6 bar (87 psi) 10 bar (145 psi) 32 bar (464 psi) 100 bar (1450 psi) 250 bar (3626 psi) 500 bar (7252 psi)

Power supply UH

Supplied through bus

Separate 24 V power supply neces- No sary Bus voltage Not Ex With intrinsically-safe operation Current consumption Basic current (max.) Max. current in event of fault Certificate and approvals Classification according to pressure equipment directive (DRGL 97/23/EC) For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) PTB 99 ATEX 2122 Ex II 1/2 G EEx ia/ib IIB/IIC T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +70 C (-40 ... +158 F) temperature class T5; -40 ... +60 C (-40 ... +140 F) temperature class T6 To a certified intrinsically-safe circuit with maximum values: FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W Li = 7 H, Ci = 1.1 nF PTB 99 ATEX 1160 Ex II 1/2 G EEx d IIC T4/T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +60 C (-40 ... +140 F) temperature class T6 To circuits with values: UH = 9 ... 32 V DC PTB 01 ATEX 2055 Ex II 1 D IP65 T 120 C Ex II 1/2 D IP65 T 120 C -40 ... +85 C (-40 ... +185 F) 120 C (248 F) To a certified intrinsically-safe circuit with maximum values: FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W Li = 7 H, Ci = 1.1 nF PTB 01 ATEX 2055 Ex II 2 D IP65 T 120 C To circuits with values: UH = 9 ... 32 V DC; Pmax = 1.2 W Planned 12.5 mA 15.5 mA 9 ... 32 V 9 ... 24 V

Explosion protection 100% of nominal measuring range (max. 160 bar (2320 psi) with oxygen measurement and inert filling liquid) Digital PROFIBUS PA signal IEC 61158-2 Increasing characteristic, start-ofscale value 0 bar, stainless steel seal diaphragm, silicone oil filling, room temperature (25 C (77 F)) Intrinsic safety "i" - Identification - Permissible ambient temperature

Output Physical bus Measuring accuracy Reference conditions

- Connection

Error in measurement (including hysteresis and repeatability) - Linear characteristic Rated conditions Degree of protection (to EN 60529) Process temperature Measuring cell with silicone oil filling Measuring cell with inert filling liquid In conjunction with dust explosion protection Influence of ambient temperature With -10 ... +60 C (14 ... 140 F) With -40 ... -10 C and +60 C ... +85 C (-40 ... +14 and 140 ... 185 F) Design Weight (without options) Wetted parts materials Connection shank Stainless steel, mat. No. 1.4404/316L or Hastelloy C4, mat. No. 2.4610 Stainless steel, mat. No. 1.4404/316L or Hastelloy C276, mat. No. 2.4819 Silicone oil or inert filling liquid (max. 160 bar (2320 psi) with oxygen measurement) Connection shank GA to DIN EN 837, female thread -14 NPT or oval flange (PN 160 (MWP 2320)) to DIN 19213 with mounting thread M10 or 7/ -20 UNF to EN 61518 16 1.5 kg ( 3.3 lb) 0.3% 0.25% / 10 K ( 0.25% / 18 F) Dust explosion protection for zone 20 - Identification - Permissible ambient temperature - Max.surface temperature - Connection -40 ... +100 C (-40 ... +212 F) -20 ... +100 C (-4 ... +212 F) -20 ... +60 C (-4 ... +140 F) - Connection IP65 - Effective internal inductance/capacitance Explosion-proof "d" - Identification - Permissible ambient temperature 0.075%

Seal diaphragm

Measuring cell filling

- Effective internal inductance/capacitance Dust explosion protection for zone 21/22 - Identification - Connection Type of protection "n" (zone 2)

Process connection

Siemens FI 01 2005

2/57

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA series for pressure

Explosion protection to FM - Identification (XP/DIP) or (IS); (NI)

Certificate of Compliance 3008490 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III Certificate of Compliance 1153651 CL I, GP ABCD; CL II, GP EFG; CL III; Enclosure Type 4X, CL I, DIV 2, GP ABCD; CL II, DIV 2, GP FG; CL III; Enclosure Type 4X

Explosion protection to CSA - Identification

Dimensional drawings
15 (0.6) 138 (5.4)

20 (0.8)

69 (2.7)

50 (1.97)

55 (0.6)
28 (1.1)

ca. 30 (1.2)

100 (3.94)

6
50 (1.97)

80 (3.15)

117 (4.6)

3
171 (6.7) 237 (9.3) 36,5 (1,44) 105 (4.1)

1)

1)

8
68 (2.7)

72 (2.8)

123 (4.8) min. 77 (3.0) 2)


1 Process connection: - -14 NPT, - connection shank GA or - oval flange Blanking plug Electrical connection: - screwed gland M20x1,5 4), - screwed gland -14 NPT or - PROFIBUS plug M12 3) 4) Terminal side Electronics side, digital display (longer overall length for cover with window) Protective cover over keys Mounting bracket (option) Screw cover safety bracket (only for explosion-proof enclosure, not shown in the drawing)

2 3

4 5 6 7 8

1) 2) 3) 4)

Allow approx. 20 mm (0.79 inch) thread length in addition Minimum distance for rotating Not with type of protection "Explosion-proof enclosure". Not with type of protection "FM + CSA".

SITRANS P pressure transmitters, DS III PA series for pressure, dimensional drawing, dimensions in mm (inch)

2/58

Siemens FI 01 2005

120 (4.7)

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA series for pressure
Selection and Ordering data SITRANS P pressure transmitter for pressure DS III PA series Measuring cell filling Silicone oil Inert liquid Measuring cell cleaning Standard Grease-free Order No. 7MF 4 0 3 4 77777 - 7777

Further designs Please add "-Z" to Order No. and specify Order code.

Order code

1 3 B C D E F G

Pressure transmitter with mounting bracket made of: Steel A01 Stainless steel A02 Rating plate inscription (instead of German) English French Spanish Italian English rating plate Pressure units in inH2O or psi Manufacturer's test certificate M to DIN 55.350, Part 18 and to ISO 8402

Rated measuring range 1 bar (14.5 psi) 4 bar (58 psi) 16 bar (232 psi) 63 bar (914 psi) 160 bar (2320 psi) 400 bar (5802 psi) Wetted parts materials Seal diaphragm Process connection Stainless steel Stainless steel Hastelloy Stainless steel Hastelloy Hastelloy Version as diaphragm seal Process connection Connection shank GB to EN 837-1 Female thread -14 NPT Oval flange made of stainless steel, max. span 160 bar (2320 psi) - Mounting thread 7/16-20 UNF to EN 61518 - Mounting thread M10 to DIN 19213 Non-wetted parts materials Housing made of die-cast aluminium Housing stainless steel precision casting Design Standard design International version, English label inscriptions, documentation in 5 languages on CD Explosion protection without with CENELEC, Type of protection: - "Intrinsic safety (EEx ia)" - "Explosion-proof (EEx d)" 1) - "Intrinsic safety and explosion-proof enclosure (EEx ia + EEx d)" 2) - "n (zone 2)" (planned) - "Intrinsic safety, explosion-proof enclosure and dust explosion protection (EEx ia + EEx d + zone 1D/2D)" 2) with FM + CSA, Type of protection: - "Intrinsic safety and explosion-proof (is + xp)" 1) Electrical connection / cable inlet Screwed gland M20x1.5 Screwed gland -14 NPT PROFIBUS plug M12 incl. mating connector 3) Display without (digital display hidden) with visible digital indicator with customer-specific digital indicator (setting as specified, Order code "Y21" required)

B11 B12 B13 B14 B21 C11 C12 C14 D07 D12

A B C Y0 0 1

Acceptance test certificate B to EN 10 204-3.1B Factory certificate to EN 10.204-2.2 Acid gas version to NACE (only together with seal diaphragm made of Hastelloy) Type of protection IP68 (not together with PROFIBUS plug M12 and nominal measuring range 63 bar ( 914 psi)) Digital indicator along side the input keys (only together with the devices 7MF4034-....0-.A-6 or -.A.7-Z, Y21) Use on zone 1D / 2D (only together with type of protection "Intrinsic safety (EEx ia)" 1 2 Use at zone 0 (only together with type of protection "Intrinsic safety (EEx ia)" A B D P E R Oxygen application (max. 160 bar (2320 psi) with oxygen measurement and inert liquid) Additional data Measuring point number/identification max. 16 characters, specify in plain text: Y15: ........................................... Measuring point text max. 27 characters, specify in plain text: Y16: ........................................... Setting of pressure indicator in pressure units specify in plain text (standard setting: mA): Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, mA, Torr, ATM or % *) Reference temperature 20 C Preset bus address specify in plain text (standard setting: 126) Y25: ...........................................

2 3 0 3

D27

E01

E02

E10

Y15

Y16

NC B C F 1 6 7

Y21

Y25

The device is delivered together with brief instructions (Leporello) and a CD-ROM containing detailed documentation.
1) Without cable gland, with blanking plug 2) With enclosed cable gland EEx ia and blanking plug 3) Not together with types of protection "Explosion-proof" or "Intrinsic safety und explosion-proof"

Only the settings for "Y21" and "Y25" can be made in the factory Ordering example Item line: 7MF4034-1EA00-1AA7-Z B line: A01 + Y21 C line: Y21: ... m

Siemens FI 01 2005

2/59

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA series for pressure

Technical specifications
SITRANS P pressure transmitters, DS III PA series for absolute pressure, from the pressure series Input Measured variable Nominal measuring range 250 mbar (3.6 psi) 1300 mbar (18.9 psi) 5 bar (72.5 psi) 30 bar (435 psi) Lower measuring limit Measuring cell with silicone oil filling Upper measuring limit 0 mbar absolute 100% of nominal measuring range (max. 160 bar (2320 psi) with oxygen measurement and inert filling liquid) Digital PROFIBUS PA signal IEC 61158-2 Increasing characteristic Start-of-scale value 0 bar Stainless steel seal diaphragm Silicone oil filling Room temperature (25 C (77 F)) Absolute pressure Max. working pressure 6 bar (87 psi) 10 bar (145 psi) 30 bar (435 psi) 100 bar (1450 psi)

Not Ex With intrinsically-safe operation Current consumption Basic current (max.) Max. current in event of fault Certificates and approvals Classification according to pressure equipment directive (DRGL 97/23/EC)

9 ... 32 V 9 ... 24 V 12.5 mA 15.5 mA For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) PTB 99 ATEX 2122 Ex II 1/2 G EEx ia/ib IIB/IIC T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +70 C (-40 ... +158 F) temperature class T5; -40 ... +60 C (-40 ... +140 F) temperature class T6 To a certified intrinsically-safe circuit with maximum values: FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W Li = 7 H, Ci = 1.1 nF PTB 99 ATEX 1160 Ex II 1/2 G EEx d IIC T4/T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +60 C (-40 ... +140 F) temperature class T6 To circuits with values: UH = 9 ... 32 V DC PTB 01 ATEX 2055 Ex II 1 D IP65 T 120 C Ex II 1/2 D IP65 T 120 C -40 ... +85 C (-40 ... +185 F) 120 C (248 F) To a certified intrinsically-safe circuit with maximum values: FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W Li = 7 H, Ci = 1.1 nF PTB 01 ATEX 2055 Ex II 2 D IP65 T 120 C To circuits with values: UH = 9 ... 32 V DC; Pmax = 1.2 W Planned

Explosion protection Intrinsic safety "i" - Identification - Permissible ambient temperature

Output Physical bus Measuring accuracy Reference conditions

- Connection

Error in measurement (including hysteresis and repeatability) - Linear characteristic Influence of ambient temperature With -10 ... +60 C (14 ... 140 F) With -40 ... -10 C and +60 ... +85 C (-40 ... +14 and 140 ... 185 F) Rated conditions Degree of protection (to EN 60529) Process temperature Measuring cell with silicone oil filling In conjunction with dust explosion protection Design Weight (without options) Wetted parts materials Connection shank Stainless steel, mat. No. 1.4404/316L or Hastelloy C4, mat. No. 2.4610 Stainless steel, mat. No. 1.4404/316L or Hastelloy C276, mat. No. 2.4819 Silicone oil or inert filling liquid (max. 160 bar (2320 psi) with oxygen measurement) Connection shank GA to DIN EN 837, female thread -14 NPT or oval flange (PN 160 (MWP 2320)) to DIN 19 213 with mounting thread M10 or 7/ -20 UNF to EN 61518 16 Supplied through bus 1.5 kg ( 3.3 lb) -40 ... +100 C (-40 ... +212 F) -20 ... +60 C (-4 ... +140 F) IP65 0.3% 0.25% / 10 K ( 0.25% / 18 F) 0.075%

- Effective internal inductance/ capacitance Explosion-proof "d" - Identification - Permissible ambient temperature

- Connection Dust explosion protection for zone 20 - Identification - Permissible ambient temperature - Max.surface temperature - Connection

Seal diaphragm

Measuring cell filling

- Effective internal inductance/ capacitance Dust explosion protection for zone 21/22 - Identification - Connection Type of protection "n" (zone 2)

Process connection

Power supply UH

Separate 24 V power supply neces- No sary Bus voltage

2/60

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA series for absolute pressure (from pressure series)
Explosion protection to FM - Identification (XP/DIP) or (IS); (NI) Certificate of Compliance 3008490 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III Certificate of Complianc1153651 CL I, GP ABCD; CL II, GP EFG; CL III; Enclosure Type 4X, CL I, DIV 2, GP ABCD; CL II, DIV 2, GP FG; CL III; Enclosure Type 4X

Explosion protection to CSA - Identification

Dimensional drawings
15 (0.6) 138 (5.4)

20 (0.8)

69 (2.7)

50 (1.97)

55 (0.6)
28 (1.1)

ca. 30 (1.2)

100 (3.94)

6
50 (1.97)

80 (3.15)

117 (4.6)

3
171 (6.7) 237 (9.3) 36,5 (1,44) 105 (4.1)

1)

1)

8
68 (2.7)

72 (2.8)

123 (4.8) min. 77 (3.0) 2)


1 Process connection: - -14 NPT, - connection shank GA or - oval flange Blanking plug Electrical connection: - screwed gland M20x1,5 4), - screwed gland -14 NPT or - PROFIBUS plug M12 3) 4) Terminal side Electronics side, digital display (longer overall length for cover with window) Protective cover over keys Mounting bracket (option) Screw cover safety bracket (only for explosion-proof enclosure, not shown in the drawing)

2 3

4 5 6 7 8

1) 2) 3) 4)

Allow approx. 20 mm (0.79 inch) thread length in addition Minimum distance for rotating Not with type of protection "Explosion-proof enclosure". Not with type of protection "FM + CSA".

SITRANS P pressure transmitters, DS III PA series for absolute pressure from the pressure series, dimensional drawing, dimensions in mm (inch)

120 (4.7)

Siemens FI 01 2005

2/61

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA series for absolute pressure (from pressure series)

Selection and Ordering data SITRANS P pressure transmitters for absolute pressure from the pressure series DS III PA series Measuring cell filling Silicone oil Inert liquid Measuring cell cleaning Standard Grease-free

Order No. 7MF 4 2 3 4 77777 - 7777

Further designs Please add "-Z" to Order No. and specify Order code.

Order code

Pressure transmitter with mounting bracket made of: Steel A01 Stainless steel A02 Rating plate inscription (instead of German) English French Spanish Italian English rating plate Pressure units in inH2O or psi Manufacturer's test certificate M to DIN 55.350, Part 18 and to ISO 8402

1 3 D F G H

Rated measuring range 250 mbar (3.63 psi) 1300 mbar (18.9 psi) 5 bar (72.5 psi) 30 bar (435 psi) Wetted parts materials Seal diaphragm Process connection Stainless steel Stainless steel Hastelloy Stainless steel Hastelloy Hastelloy Version as diaphragm seal 1) Process connection Connection shank GB to EN 837-1 Female thread -14 NPT Oval flange made of stainless steel, max. span 160 bar (2320 psi) - Mounting thread 7/16-20 UNF to EN 61518 - Mounting thread M10 to DIN 19213 Non-wetted parts materials Housing made of die-cast aluminium Housing stainless steel precision casting Design Standard design International version, English label inscriptions, documentation in 5 languages on CD Explosion protection without with CENELEC, Type of protection: - "Intrinsic safety (EEx ia)" - "Explosion-proof (EEx d)" 2) - "Intrinsic safety and explosion-proof enclosure (EEx ia + EEx d)" 3) - "n (zone 2)" (planned) - "Intrinsic safety, explosion-proof enclosure and dust explosion protection (EEx ia + EEx d + zone 1D/2D)" 3) with FM + CSA, Type of protection: - "Intrinsic safety and explosion-proof (is + xp)" 2) Electrical connection / cable inlet Screwed gland M20x1.5 Screwed gland -14 NPT PROFIBUS plug M12 incl. mating connector 4) Display without (digital display hidden) with visible digital indicator with customer-specific digital indicator (setting as specified, Order code "Y21" required) E) E)

B11 B12 B13 B14 B21 C11 C12 C14 D07 D12 D27

A B C Y0 0 1

Acceptance test certificate B to EN 10 204-3.1B Factory certificate to EN 10.204-2.2 Acid gas version to NACE (only together with seal diaphragm made of Hastelloy) Type of protection IP68 (not together with PROFIBUS plug M12)

2 3 0 3 1 2

Digital indicator along side the input keys (only together with the devices 7MF4234-....0-.A.6 or -.A.7-Z, Y21) Use on zone 1D / 2D (only together with type of protection "Intrinsic safety (EEx ia)" Use at zone 0 (only together with type of protection "Intrinsic safety (EEx ia)" Oxygen application A B D P E R Additional data Measuring point number/identification max. 16 characters, specify in plain text: Y15: ........................................... Measuring point text max. 27 characters, specify in plain text: Y16: ........................................... Setting of pressure indicator in pressure units specify in plain text (standard setting: mA): Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, mA, Torr, ATM or % *) Reference temperature 20 C Preset bus address 1 6 7 specify in plain text (standard setting: 126) Y25: ...........................................

E01

E02

E10

Y15

Y16

Y21

NC B C F

Y25

Only the settings for "Y21" and "Y25" can be made in the factory

The device is delivered together with brief instructions (Leporello) and a CD-ROM containing detailed documentation.
1) 2) 3) 4) Version 7MF4233-1DY... only up to max. span 200 mbar (2.9 psi) Without cable gland, with blanking plug With enclosed cable gland EEx ia and blanking plug Not together with types of protection "Explosion-proof" and "Intrinsic safety und explosion-proof" E) Combinations of the versions marked with E) are subject to the export regulations AL: 2B230, ECCN: N.

2/62

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA series for absolute pressure (from differential pressure series)

Technical specifications
SITRANS P transmitters, DS III PA series for absolute pressure, from the differential pressure series Mode of operation and system design Measuring principle Input Measured variable Nominal measuring range 250 mbar (3.6 psi) 1300 mbar (18.9 psi) 5 bar (72.5 psi) 30 bar (435 psi) 100 bar (1450 psi) Absolute pressure Max. working pressure 32 bar (464 psi) 32 bar (464 psi) 32 bar (464 psi) 160 bar (2320 psi) 160 bar (2320 psi) with pressure cover screws M10 and 7/ -20 UNF 16 0 mbar absolute 100% of nominal measuring range (max. 160 bar (2320 psi) with oxygen measurement and inert filling liquid) Digital PROFIBUS PA signal IEC 61158-2 Increasing characteristic Start-of-scale value 0 bar Stainless steel seal diaphragm Silicone oil filling Room temperature (25 C (77 F)) Piezo-resistive

Power supply

Supplied through bus

Separate 24 V power supply neces- No sary Bus voltage Not Ex With intrinsically-safe operation Current consumption Basic current (max.) Max. current in event of fault Certificate and approvals Classification according to pressure equipment directive (DRGL 97/23/EC) For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) PTB 99 ATEX 2122 Ex II 1/2 G EEx ia/ib IIB/IIC T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +70 C (-40 ... +158 F) temperature class T5; -40 ... +60 C (-40 ... +140 F) temperature class T6 To a certified intrinsically-safe circuit with maximum values: FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W Li = 7 H, Ci = 1.1 nF PTB 99 ATEX 1160 Ex II 1/2 G EEx d IIC T4/T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +60 C (-40 ... +140 F) temperature class T6 To circuits with values: UH = 9 ... 32 V DC PTB 01 ATEX 2055 Ex II 1 D IP65 T 120 C Ex II 1/2 D IP65 T 120 C -40 ... +85 C (-40 ... +185 F) 120 C (248 F) To a certified intrinsically-safe circuit with maximum values: FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W Li = 7 H, Ci = 1.1 nF PTB 01 ATEX 2055 Ex II 2 D IP65 T 120 C To circuits with values: UH = 9 ... 32 V DC; Pmax = 1.2 W Planned 12.5 mA 15.5 mA 9 ... 32 V 9 ... 24 V

Explosion protection Intrinsic safety "i" - Identification - Permissible ambient temperature

Lower measuring limit Measuring cell with silicone oil filling Upper measuring limit

Output Physical bus Measuring accuracy Reference conditions

- Connection

Error in measurement (including hysteresis and repeatability) - Linear characteristic Influence of ambient temperature With -10 ... +60 C (14 ... 140 F) With -40 ... -10 C and +60 C ... +85 C (-40 ... +14 and 140 ... 185 F) Rated conditions Degree of protection (to EN 60529) Process temperature - Measuring cell with silicone oil fil- -40 ... +100 C (-40 ... +212 F) ling -20 ... +60 C (-4 ... +140 F) in conjunction with dust explosion protection Design Weight (without options) Wetted parts materials - Seal diaphragm Stainless steel, mat. No. 1.4404/316L, Hastelloy C276, mat. No. 2.4819, Monel, mat. No. 2.4360, tantalum or gold Silicone oil or inert filling liquid (max. 160 bar (2320 psi) with oxygen measurement) Female thread 1/4-18 NPT and flange connection to DIN 19213 with mounting thread M10 or 7/ -20 UNF to EN 61518 16 4.5 kg ( 9.9 lb) IP65 0.3% 0.25% / 10 K ( 0.25% / 18 F) 0.075%

- Effective internal inductance/ capacitance Explosion-proof "d" - Identification - Permissible ambient temperature

- Connection Dust explosion protection for zone 20 - Identification - Permissible ambient temperature - Max.surface temperature - Connection

Measuring cell filling

- Effective internal inductance/ capacitance Dust explosion protection for zone 21/22 - Identification - Connection Type of protection "n" (zone 2)

Process connection

Siemens FI 01 2005

2/63

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA series for absolute pressure (from differential pressure series)

Explosion protection to FM - Identification (XP/DIP) or (IS); (NI)

Certificate of Compliance 3008490 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III Certificate of Compliance 1153651 CL I, GP ABCD; CL II, GP EFG; CL III; Enclosure Type 4X, CL I, DIV 2, GP ABCD; CL II, DIV 2, GP FG; CL III; Enclosure Type 4X

Explosion protection to CSA - Identification

Dimensional drawings
15 (0.6) 138 (5.4)

50 (1.97)
20 (0.8)

approx. 30 (1.2)

100 (3.94) 6 2

80 (3.15)

117 (4.6)

50 (1.97)

3 198 (7.8) approx. 261 (10.3) 96 (3.8) 7 11 52 (2.05)

5 1)

69 (2.7) 77 (3) 2)

1)

9 10

Space for rotation of housing

1 134 (5.27)
+

72 (2.83) 105 (4.1) 1 2 3 Process connection: -18 NPT (EN 61518) Blanking plug Electrical connection: - screwed gland M20x1,5 4), - screwed gland -14 NPT or - PROFIBUS plug M12 3) 4) Terminal side Electronic side, digital display (longer overall length for cover with window) Protective cover over keys Mounting bracket (option) Sealing screw with valve (option) Screw cover safety bracket (only for explosion-proof enclosure, not shown in the drawing) Lateral venting for liquid measurement Lateral venting for gas measurement (suffix H02)

68 (2.7) 120 (4.7)

4 5 6 7 8 9 10 11

1) 2) 3) 4)

Allow approx. 20 mm (0.79 inch) thread length in addition 92 mm (3.62 inch) for minimum distance to permit rotation with indicator Not with type of protection "explosion-proof enclosure" Not with type of protection "FM + CSA"

SITRANS P pressure transmitters, DS III PA series for absolute pressure from the differential pressure series, dimensional drawing, dimensions in mm (inch)

2/64

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA series for absolute pressure (from differential pressure series)
Selection and Ordering data SITRANS P pressure transmitters for absolute pressure from the series Differential pressure DS III PA series Measuring cell filling Silicone oil Inert liquid Measuring cell cleaning Standard Grease-free Order No. 7MF 4 3 3 4 Selection and Ordering data SITRANS P pressure transmitters for absolute pressure from the series Differential pressure DS III PA series Display without (digital display hidden) with visible digital indicator with customer-specific digital indicator (setting as specified, Order code "Y21" required) Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation Sealing plug(s) or sealing screw(s) for the process flanges(s)
1) 2) 3) 4) 5) Version 7MF4334-1DY... only up to max. span 200 mbar (2.9 psi) Not for nominal measuring range 100 bar (1450 psi). Without cable gland, with blanking plug With enclosed cable gland EEx ia and blanking plug Not together with types of protection "Explosion-proof" and "Intrinsic safety und explosion-proof" E) Combinations of the versions marked with E) are subject to the export regulations AL: 2B230, ECCN: N.

Order No. 7MF 4 3 3 4 -

2
1 6 7

77777 - 7777

77777 - 7777

1 3 D F G H KE

Rated measuring range 250 mbar (3.63 psi) 1300 mbar (18.9 psi) 5 bar (72.5 psi) 30 bar (435 psi) 100 bar (1450 psi) Wetted parts materials Seal diaphragm Parts of measuring cell Stainless steel Stainless steel Hastelloy Stainless steel Hastelloy Hastelloy Tantalum Tantalum Monel Monel Gold Gold Version as diaphragm seal 1) Process connection Female thread -18 NPT with flange connection Sealing screw opposite process connection - Mounting thread M10 to DIN 19 213 - Mounting thread 7/16-20 UNF to EN 61518 Vent on side of process flange 2) - Mounting thread M10 to DIN 19 213 - Mounting thread 7/16-20 UNF to EN 61518 Non-wetted parts materials Process flange screws Electronics housing Stainless steel Stainless steel Die-cast aluminium Stainless steel precision casting E) E) E)

A B C E H L Y

0 2 4 6

2 3

Design Standard design International version, English label inscriptions, documentation in 5 languages on CD Explosion protection without with CENELEC, Type of protection: - "Intrinsic safety (EEx ia)" - "Explosion-proof (EEx d)" 3) - "Intrinsic safety and explosion-proof enclosure (EEx ia + EEx d)" 4) - "n (zone 2)" (planned) - "Intrinsic safety, explosion-proof enclosure and dust explosion protection (EEx ia + EEx d + zone 1D/2D)" 4) with FM + CSA, Type of protection: - "Intrinsic safety and explosion-proof (is + xp)" 3) Electrical connection / cable inlet Screwed gland M20x1.5 Screwed gland -14 NPT PROFIBUS plug M12 incl. mating connector 5)

1 2

A B D P E R

NC B C F

Siemens FI 01 2005

2/65

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA series for absolute pressure (from differential pressure series)

Further designs Please add "-Z" to Order No. and specify Order code.

Order code

Further designs Please add "-Z" to Order No. and specify Order code. Additional data Measuring point number/identification max. 16 characters, specify in plain text: Y15: ........................................... Measuring point text max. 27 characters, specify in plain text: Y16: ........................................... Setting of pressure indicator in pressure units specify in plain text Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, mA, Torr, ATM or % *) Reference temperature 20 C Preset bus address specify in plain text (standard setting: 126) Y25: ...........................................

Order code

Pressure transmitter with mounting bracket made of: Steel A01 Stainless steel A02 O-rings for process flanges (instead of FPM (Viton)) PTFE (Teflon) FEP (with silicone core, approved for food) FFPM (Kalrez, compound 4079) NBR (Buna N) Sealing screws -18 NPT, with valve in material of process flanges Rating plate inscription (instead of German) English French Spanish Italian English rating plate Pressure units in inH2O or psi Manufacturer's test certificate M to DIN 55.350, Part 18 and to ISO 8402 Acceptance test certificate B to EN 10 204-3.1B Factory certificate to EN 10.204-2.2 Acid gas version to NACE (only together with seal diaphragm made of Hastelloy and process flange screws made of stainless steel) Type of protection IP68 (not together with PROFIBUS plug M12) Digital indicator along side the input keys (only together with the devices 7MF4334-...0.2-.A.6 or -.A.7-Z, Y21) Use on zone 1D / 2D (only together with type of protection "Intrinsic safety (EEx ia)" Use at zone 0 (only together with type of protection "Intrinsic safety (EEx ia)" Oxygen application (max. 160 bar (2320 psi) with oxygen measurement and inert liquid) Interchanging of process connection side Vent on side for gas measurements Process flange Hastelloy Monel Stainless steel with PVDF insert Max. PN 10 (MWP 145 psi) Max. temperature of medium 90 C (194 F)

Y15

Y16

A20 A21 A22 A23 A40

Y21

B11 B12 B13 B14 B21 C11 C12 C14 D07

Y25

Only the settings for "Y21" and "Y25" can be made in the factory

D12 D27

E01

E02

E10

H01 H02 K01 K02 K04

2/66

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA series for differential pressure and flow

Technical specifications
SITRANS P pressure transmitters, DS III PA series for differential pressure and flow Input Measured variable Nominal measuring range PN 32 (MWP 464 psi) - 20 mbar (0.29 psi) PN 160 (MWP 2320 psi) - 60 mbar (0.87 psi) - 250 mbar (3.63 psi) - 600 mbar (8.7 psi) - 1600 mbar (23.3 psi) - 5 bar (72.5 psi) - 30 bar (435 psi) PN 400 (MWP 6092 psi) - 250 mbar (3.63 psi) - 600 mbar (8.7 psi) - 1600 mbar (23.3 psi) - 5 bar (72.5 psi) - 30 bar (435 psi) Lower measuring limit Measuring cell with silicone oil filling -100% of nominal measuring range (-33% with nominal measuring range 30 bar (435 psi)) or 30 mbar (0.435 psi) absolute 100% of nominal measuring range (max. 160 bar (2320 psi) with oxygen measurement and inert filling liquid) Digital PROFIBUS PA signal IEC 61158-2 Increasing characteristic Start-of-scale value 0 bar Stainless steel seal diaphragm Silicone oil filling Room temperature (25 C (77 F)) 420 bar (6092 psi) 420 bar (6092 psi) 420 bar (6092 psi) 420 bar (6092 psi) 420 bar (6092 psi) 160 bar (2320 psi) 160 bar (2320 psi) 160 bar (2320 psi) 160 bar (2320 psi) 160 bar (2320 psi) 160 bar (2320 psi) 32 bar (464 psi) Differential pressure and flow Max. working pressure

Design Weight (without options) Wetted parts materials Seal diaphragm Stainless steel, mat. No. 1.4404/316L, Hastelloy C276, mat. No. 2.4819, Monel, mat. No. 2.4360, tantalum or gold Silicone oil or inert filling liquid (max. 160 bar (2320 psi) with oxygen measurement) Female thread 1/4-18 NPT and flange connection to DIN 19213 with mounting thread M10 or 7/ -20 UNF to EN 61518 16 Supplied through bus 4.5 kg ( 9.9 lb)

Measuring cell filling

Process connection

Power supply UH

Separate 24 V power supply neces- No sary Bus voltage Not Ex With intrinsically-safe operation Current consumption Basic current (max.) Max. current in event of fault Certificates and approvals Classification according to pressure equipment directive (DRGL 97/23/EC) - PN 32/160 (MWP 464/2320) For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) For gases of fluid group 1 and liquids of fluid group 1; complies with basic safety requirements of article 3, paragraph 1 (appendix 1); assigned to category III, conformity evaluation module H by the TV Nord PTB 99 ATEX 2122 Ex II 1/2 G EEx ia/ib IIB/IIC T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +70 C (-40 ... +158 F) temperature class T5; -40 ... +60 C (-40 ... +140 F) temperature class T6 To a certified intrinsically-safe circuit with maximum values: FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W Li = 7 H, Ci = 1.1 nF PTB 99 ATEX 1160 Ex II 1/2 G EEx d IIC T4/T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +60 C (-40 ... +140 F) temperature class T6 To circuits with values: UH = 9 ... 32 V DC 12.5 mA 15.5 mA 9 ... 32 V 9 ... 24 V

Upper measuring limit

- PN 420 (MWP 6092)

Output Physical bus Measuring accuracy Reference conditions

Explosion protection Intrinsic safety "i" - Identification - Permissible ambient temperature

Error in measurement (including hysteresis and repeatability) - Linear characteristic - Square-root characteristic, flow > 50 % - Square-root characteristic, flow 25 ... 50% Influence of ambient temperature With -10 ... +60 C (14 ... 140 F) 0.3% (Twice the value with 20mbar (0.29 psi) nominal measuring range) 0.25% / 10 K ( 0.25% / 18 F) (Twice the value with 20 mbar (0.29 psi) nominal measuring range) IP65 -40 ... +100 C (-40 ... +212 F) -20 ... +60 C (-4 ... +140 F) in conjunction with dust explosion protection 0.075% 0.1% 0.2%

- Connection

With -40 ... -10 C and +60 C ... +85 C (-40 ... +14 and 140 ... 185 F) Rated conditions Degree of protection (to EN 60529) Process temperature Measuring cell with silicone oil filling

- Effective internal inductance/ capacitance Explosion-proof "d" - Identification - Permissible ambient temperature

- Connection

Siemens FI 01 2005

2/67

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA series for differential pressure and flow

Dust explosion protection for zone 20 - Identification - Permissible ambient temperature - Max.surface temperature - Connection

PTB 01 ATEX 2055 Ex II 1 D IP65 T 120 C Ex II 1/2 D IP65 T 120 C -40 ... +85 C (-40 ... +185 F)

Dust explosion protection for zone 21/22 - Identification - Connection Type of protection "n" (zone 2)

PTB 01 ATEX 2055 Ex II 2 D IP65 T 120 C To circuits with values: UH = 9 ... 32 V DC; Pmax = 1.2 W Planned Certificate of Compliance 3008490 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III Certificate of Compliance 1153651 CL I, GP ABCD; CL II, GP EFG; CL III; Enclosure Type 4X, CL I, DIV 2, GP ABCD; CL II, DIV 2, GP FG; CL III; Enclosure Type 4X

120 C (248 F) To a certified intrinsically-safe circuit with maximum values: FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W Li = 7 H, Ci = 1.1 nF

Explosion protection to FM - Identification (XP/DIP) or (IS); (NI)

Explosion protection to CSA - Identification

- Effective internal inductance/capacitance

Dimensional drawings
15 (0.6) 138 (5.4)

50 (1.97)
20 (0.8)

approx. 30 (1.2)

100 (3.94) 6 2

80 (3.15)

117 (4.6)

50 (1.97)

3 198 (7.8) approx. 261 (10.3) 96 (3.8) 7 11 52 (2.05)

5 1)

69 (2.7) 77 (3) 2)

1)

9 10

Space for rotation of housing

1 134 (5.27)
+

72 (2.83) 105 (4.1) 1 2 3 Process connection: -18 NPT (EN 61518) Blanking plug Electrical connection: - screwed gland M20x1,5 4), - screwed gland -14 NPT or - PROFIBUS plug M12 3) 4) Terminal side Electronic side, digital display (longer overall length for cover with window) Protective cover over keys Mounting bracket (option) Sealing screw with valve (option) Screw cover safety bracket (only for explosion-proof enclosure, not shown in the drawing) Lateral venting for liquid measurement Lateral venting for gas measurement (suffix H02)

68 (2.7) 120 (4.7)

4 5 6 7 8 9 10 11

1) 2) 3) 4)

Allow approx. 20 mm (0.79 inch) thread length in addition 92 mm (3.62 inch) for minimum distance to permit rotation with indicator Not with type of protection "explosion-proof enclosure" Not with type of protection "FM + CSA"

SITRANS P pressure transmitters, DS III PA series for differential pressure and flow, dimensional drawing, dimensions in mm (inch)

2/68

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA series for differential pressure and flow
15 (0.6) 69 (2.7)

138 (5.4)

20 (0.8)

50 (1.97)

approx 30 (1.18)6)

100 (3.94) 6 2

diam. 80 (3.15)

50 (1.97)

4 1)

3 approx. 217 (8.54)5)

5 1)

77 (3)2)

Space for rotation of housing

approx. 85 (3.35)4)

8 1

67 (2.64)3)

approx. 84,6 (3.33)

1 2 3

4 5 6 7 8 9

Process connection -18 NPT (EN 61 518) Blanking plug Electrical connection: screwed gland M20x1.5, screwed gland -14 NPT or PROFIBUS plug M12 Terminal side Electronics side, digital display (longer overall length for cover with window) Protective cover over keys Mounting bracket (option) Sealing screw with valve (option) Screw cover safety bracket (only for explosion-proof enclosure, not shown in the drawing)

1) 2) 3) 4) 5) 6)

Allow approx. 20 mm (0.79 inch) thread length in addition 92 mm (3.6 inch) for minimum distance to permit rotation without indicator 74 mm (2.9 inch) for PN 420 (MWP 6092 psi) 91 mm (3.6 inch) for PN 420 (MWP 6092 psi) 219 mm (8.62 inch) for PN 420 (MWP 6092 psi) Approx. 45 mm (1.77 inch) for Pg 13.5 with adapter

SITRANS P pressure transmitters, DS III PA series for differential pressure and flow, with process covers for vertical differential pressure lines, dimensional drawing, dimensions in mm (inch)

SITRANS P pressure transmitters, DS III PA series for differential pressure and flow, with process covers for vertical differential pressure lines

Siemens FI 01 2005

2/69

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA series for differential pressure and flow

115 (4.5)

183 (7.2)

77 (3.0)
2

193 (7.6)

SITRANS P pressure transmitters, DS III PA series for differential pressure and flow, with digital indicator beside control keys, dimensional drawing, dimensions in mm (inch)

SITRANS P pressure transmitters, DS III PA series for differential pressure and flow, with digital indicator beside control keys

2/70

Siemens FI 01 2005

FIELD TERMINALS

1 2 3 4 5 6 7 8

Process connection, -18 NPT (EN 61 518) Terminal side, analog indicator (optional) External digital indicator (optional) Sealing plug Fixing screw Blanking plug Protective cover for keys Electrical connection

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA series for differential pressure and flow
Selection and Ordering data SITRANS P pressure transmitters for differential pressure and flow Measuring cell filling Silicone oil Inert liquid Measuring cell cleaning Standard Grease-free Order No. 7MF 4 4 3 4 Selection and Ordering data SITRANS P pressure transmitters for differential pressure and flow Display without (digital display hidden) with visible digital indicator with customer-specific digital indicator (setting as specified, Order code "Y21" required) B C D E F G H Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation Sealing plug(s) or sealing screw(s) for the process flanges(s)
1) Not suitable for connection of remote seal 2) Only together with max. spans 250, 1600, 5000 and 30000 mbar (3.63, 23.2, 72.5 and 435 psi). 3) Without cable gland, with blanking plug 4) With enclosed cable gland EEx ia and blanking plug 5) Not together with types of protection "Explosion-proof" and "Intrinsic safety und explosion-proof"

Order No. 7MF 4 4 3 4 -

2
1 6 7

DS III PA series, PN 32 / 160 (MWP 464 / 2320 psi) 7 7 7 7 7 - 7 7 7 7 1 3

DS III PA series, PN 32 / 160 (MWP 464 / 2320 psi) 7 7 7 7 7 - 7 7 7 7

Rated measuring range PN 32 (MWP 464 psi) 20 mbar 1) (0.29 psi) PN 160 (MWP 2320 psi) 60 mbar 250 mbar 600 mbar 1600 mbar 5000 mbar 30 bar (0.87 psi) (3.63 psi) (8.70 psi) (23.2 psi) (72.5 psi) (435 psi)

Wetted parts materials (stainless steel process flanges) Seal diaphragm Parts of measuring cell Stainless steel Stainless steel Hastelloy Stainless steel Hastelloy Hastelloy Tantalum 2) Tantalum Monel 2) Monel Gold 2) Gold Version as diaphragm seal Process connection Female thread -18 NPT with flange connection Sealing screw opposite process connection - Mounting thread M10 to DIN 19 213 - Mounting thread 7/16-20 UNF to EN 61518 Venting on side of process flanges 2) - Mounting thread M10 to DIN 19 213 - Mounting thread 7/16-20 UNF to EN 61518 Non-wetted parts materials Process flange screws Electronics housing Stainless steel Stainless steel Die-cast aluminium Stainless steel precision casting 2 3 A B C E H L Y

0 2 4 6

Design Standard design International version, English label inscriptions, documentation in 5 languages on CD Explosion protection without with CENELEC, Type of protection: - "Intrinsic safety (EEx ia)" - "Explosion-proof (EEx d)" 3) - "Intrinsic safety and explosion-proof enclosure (EEx ia + EEx d)" 4) - "n (zone 2)" (planned) - "Intrinsic safety, explosion-proof enclosure and dust explosion protection (EEx ia + EEx d + zone 1D/2D)" 4) with FM + CSA, Type of protection: - "Intrinsic safety and explosion-proof (is + xp)" 3) Electrical connection / cable inlet Screwed gland M20x1.5 Screwed gland -14 NPT PROFIBUS plug M12 incl. mating connector 5)

1 2

A B D P E R

NC B C F

Siemens FI 01 2005

2/71

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA series for differential pressure and flow

Further designs Please add "-Z" to Order No. and specify Order code.

Order code

Further designs Please add "-Z" to Order No. and specify Order code. Additional data Measuring point number/identification max. 16 characters, specify in plain text: Y15: ........................................... Measuring point text max. 27 characters, specify in plain text: Y16: ........................................... Setting of pressure indicator in pressure units specify in plain text Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, mA, Torr, ATM or % *) Reference temperature 20 C Preset bus address specify in plain text (standard setting: 126) Y25: ...........................................

Order code

Pressure transmitter with mounting bracket made of: Steel A01 Stainless steel A02 O-rings for process flanges (instead of FPM (Viton)) PTFE (Teflon) FEP (with silicone core, approved for food) FFPM (Kalrez, compound 4079) NBR (Buna N) Sealing screws -18 NPT, with valve in material of process flanges Rating plate inscription (instead of German) English French Spanish Italian English rating plate Pressure units in inH2O or psi Manufacturer's test certificate M to DIN 55.350, Part 18 and to ISO 8402 Acceptance test certificate B to EN 10 204-3.1B Factory certificate to EN 10.204-2.2 Acid gas version to NACE (only together with seal diaphragm made of Hastelloy and process flange screws made of stainless steel) Type of protection IP68 (not together with PROFIBUS plug M12) Digital indicator along side the input keys (only together with the devices 7MF4434-....0-.A.6 or -.A.7-Z, Y21) Use on zone 1D / 2D (only together with type of protection "Intrinsic safety (EEx ia)" Use at zone 0 (only together with type of protection "Intrinsic safety (EEx ia)" Overfilling safety device for flammable and non-flammable liquids (max. PN 32 (MVWP 464 psi), basic device with type of protection "Intrinsic safety (EEx ia)") Oxygen application (max. 160 bar (2320 psi) with oxygen measurement and inert liquid) Interchanging of process connection side Vent on side for gas measurements Stainless steel process flanges for vertical differential pressure lines (not together with K01, K02 and K04) 1) Process flange Hastelloy Monel Stainless steel with PVDF insert Max. PN 10 (MWP 145 psi) Max. temperature of medium 90 C (194 F)

Y15

Y16

A20 A21 A22 A23 A40

Y21

B11 B12 B13 B14 B21 C11 C12 C14 D07

Y25

Only the settings for "Y21" and "Y25" can be made in the factory
1) Not suitable for connection of remote seal

D12 D27

E01

E02

E08

E10

H01 H02 H03

K01 K02 K04

2/72

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA series for differential pressure and flow
Selection and Ordering data SITRANS P pressure transmitters for differential pressure and flow DS III PA series, PN 420 (MWP 6092 psi) Rated measuring range 250 mbar (3.63 psi) 600 mbar (8.70 psi) 1600 mbar (23.2 psi) 5 bar (72.5 psi) 30 bar (435 psi) Wetted parts materials (stainless steel process flanges) Seal diaphragm Parts of measuring cell Stainless steel Hastelloy Gold 1) Stainless steel Stainless steel Gold A B L Order No. 7MF 4 5 3 4 1 7777 - 7777 D E F G H Further designs Please add "-Z" to Order No. and specify Order code. Pressure transmitter with mounting bracket made of: Steel A01 Stainless steel A02 O-rings for process flanges (instead of FPM (Viton)) PTFE (Teflon) FEP (with silicone core, approved for food) FFPM (Kalrez, compound 4079) NBR (Buna N) Sealing screws -18 NPT, with valve in material of process flanges Rating plate inscription (instead of German) English French Spanish Italian 1 3 5 7 English rating plate Pressure units in inH2O or psi Manufacturer's test certificate M to DIN 55.350, Part 18 and to ISO 8402 Acceptance test certificate B to EN 10 204-3.1B 2 3 Factory certificate to EN 10.204-2.2 Acid gas version to NACE (only together with seal diaphragm made of Hastelloy and process flange screws made of stainless steel) 1 2 Type of protection IP68 (not together with PROFIBUS plug M12) Digital indicator along side the input keys (only together with the devices 7MF4534-...0.2-.A.6 or -.A.7-Z, Y21) Use on zone 1D / 2D (only together with type of protection "Intrinsic safety (EEx ia)" Use at zone 0 (only together with type of protection "Intrinsic safety (EEx ia)" Interchanging of process connection side Stainless steel process flanges for vertical differential pressure lines NC Order code

A20 A21 A22 A23 A40

Process connection Female thread -18 NPT with flange connection Sealing screw opposite process connection - Mounting thread M12 to DIN 19 213 - Mounting thread 7/16-20 UNF to EN 61518 Venting on side of process flanges - Mounting thread M12 to DIN 19 213 - Mounting thread 7/16-20 UNF to EN 61518 Non-wetted parts materials Process flange screws Electronics housing Stainless steel Stainless steel Die-cast aluminium Stainless steel precision casting

B11 B12 B13 B14 B21 C11 C12 C14 D07

Design Standard design International version, English label inscriptions, documentation in 5 languages on CD Explosion protection without with CENELEC, Type of protection: - "Intrinsic safety (EEx ia)" - "Explosion-proof (EEx d)" 2) - "Intrinsic safety and explosion-proof enclosure (EEx ia + EEx d)" 3) - "n (zone 2)" (planned) - "Intrinsic safety, explosion-proof enclosure and dust explosion protection (EEx ia + EEx d + zone 1D/2D)" 3) with FM + CSA, Type of protection: - "Intrinsic safety and explosion-proof (is + xp)" 2) max. PN 360 Electrical connection / cable inlet Screwed gland M20x1.5 Screwed gland -14 NPT PROFIBUS plug M12 incl. mating connector 4) Display without (digital display hidden) with visible digital indicator with customer-specific digital indicator (setting as specified, Order code "Y21" required) Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation Sealing plug(s) or sealing screw(s) for the process flanges(s)
1) 2) 3) 4)

D12 D27

A B D P E R

E01

E02

H01 H03

B C F 1 6 7

Not together with max. span 600 mbar Without cable gland, with blanking plug With enclosed cable gland EEx ia and blanking plug Not together with types of protection "Explosion-proof" and "Intrinsic safety und explosion-proof"

Siemens FI 01 2005

2/73

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA series for differential pressure and flow

Further designs Please add "-Z" to Order No. and specify Order code. Additional data Measuring point number/identification max. 16 characters, specify in plain text: Y15: ........................................... Measuring point text max. 27 characters, specify in plain text: Y16: ........................................... Setting of pressure indicator in pressure units specify in plain text (standard setting: mA): Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, mA, Torr, ATM or % *) Reference temperature 20 C Preset bus address specify in plain text (standard setting: 126) Y25: ...........................................

Order code

Y15

Y16

Y21

Y25

Only the settings for "Y21" and "Y25" can be made in the factory

2/74

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA (PROFIBUS) for level

Technical specifications
SITRANS P pressure transmitters, DS III PA series for level Input Measured variable Rated measuring range 250 mbar (3.63 psi) 600 mbar (8.7 psi) 1600 mbar (23.2 psi) 5000 mbar (72.5 psi) Lower measuring limit Measuring cell with silicone oil filling Upper measuring limit Output Physical bus Measuring accuracy Reference conditions Increasing characteristic Start-of-scale value 0 bar Stainless steel seal diaphragm Mounting flange without tube Silicone oil filling Room temperature (25 C (77 F)) -100% of max. span or 30 mbar (0.435 psi) absolute, depending on mounting flange 100% of max. span Digital PROFIBUS PA signal IEC 61158-2 Level Max. working pressure See "Mounting flange"

Design Weight To DIN (pressure transmitter with mounting flange, without tube) To ASME (pressure transmitter with mounting flange, without tube) Wetted parts materials High-pressure side: Seal diaphragm of mounting flange Stainless steel 316L, Monel 400, mat. No. 2.4360, Hastelloy B2, mat. No. 2.4617, Hastelloy C276, mat. No. 2.4819, Hastelloy C4, mat. No. 2.4610, tantalum, PTFE, ECTFE Silicone oil Flange to DIN and ANSI Female thread -18 NPT and flange connection to DIN 19213 with mounting thread M10 or 7/ -20 UNF to EN 61518 16 Supplied through bus 11 ... 13 kg (24.2 ... 28.7 lb) 11 ... 18 kg (24.2 ... 39.2 lb)

Measuring cell filling Process connection High-pressure side Low-pressure side

Power supply UH

Separate 24 V power supply neces- No sary Bus voltage Not Ex 9 ... 32 V 9 ... 24 V 12.5 mA 15.5 mA For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) PTB 99 ATEX 2122 Ex II 1/2 G EEx ia/ib IIB/IIC T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +70 C (-40 ... +158 F) temperature class T5; -40 ... +60 C (-40 ... +140 F) temperature class T6 To a certified intrinsically-safe circuit with maximum values: FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W Li = 7 H, Ci = 1.1 nF PTB 99 ATEX 1160 Ex II 1/2 G EEx d IIC T4/T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +60 C (-40 ... +140 F) temperature class T6 To circuits with values: UH = 9 ... 32 V DC With intrinsically-safe operation Current consumption Basic current (max.) Max. current in event of fault Certificates and approvals Classification according to pressure equipment directive (DRGL 97/23/EC)

Error in measurement (including hysteresis and repeatability) - Linear characteristic Influence of ambient temperature With -10 ... +60 C (14 ... 140 F) - 250-mbar (3.63 psi) measuring cell - 600-mbar (8.7 psi) measuring cell - 1,600 and 5,000 mbar (23.2 and 72.5 psi) measuring cells With -40 ... -10 C and +60 C ... +85 C (-40 ... +14 and 140 ... 185 F) - 250-mbar (3.63 psi) measuring cell - 600-mbar (8.7 psi) measuring cell - 1,600 and 5,000 mbar (23.2 and 72.5 psi) measuring cells Rated conditions 0.4% / 10 K ( 0.4% / 18 F) 0.3% / 10 K ( 0.4% / 18 F) 0.27% / 10 K ( 0.4% / 18 F) Note Note the assignment of the max. permissible operating temperature to the max. permissible operating pressure of the respective flange connection! IP65 0.7% 0.5% 0.45% 0.15%

Explosion protection Intrinsic safety "i" - Identification - Permissible ambient temperature

- Connection

Degree of protection (to EN 60529) Temperature of medium Measuring cell with silicone oil filling - High-pressure side

- Effective internal inductance/capacitance pabs 1bar: -40 ... +175 C (-40 ... +347 F) pabs < 1bar:-40 ... +80 C (-40 ... +176 F) -40 ... +100 C (-40 ... +212 F) -20 ... +60 C (-4 ... +140 F) in conjunction with dust explosion protection Explosion-proof "d" - Identification - Permissible ambient temperature

- Low-pressure side

- Connection

Siemens FI 01 2005

2/75

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA (PROFIBUS) for level

Dust explosion protection for zone 20 - Identification - Permissible ambient temperature - Max.surface temperature - Connection

PTB 01 ATEX 2055 Ex II 1 D IP65 T 120 C Ex II 1/2 D IP65 T 120 C -40 ... +85 C (-40 ... +185 F) 120 C (248 F) To a certified intrinsically-safe circuit with maximum values: FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W L i = 7 H, Ci = 1.1 nF PTB 01 ATEX 2055 Ex II 2 D IP65 T 120 C To circuits with values: UH = 9 ... 32 V DC; Pmax = 1.2 W Planned Certificate of Compliance 3008490 CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III Certificate of Compliance 1153651 CL I, GP ABCD; CL II, GP EFG; CL III; Enclosure Type 4X, CL I, DIV 2, GP ABCD; CL II, DIV 2, GP FG; CL III; Enclosure Type 4X

Mounting flange Nom. diam. To EN 1092-1 - DN 80 - DN 100 To ASME B16.5 - 3 inch - 4 inch class 150 class 300 class 150 class 300 PN 40 PN 16 PN 40 Nom. press.

- Effective internal inductance/capacitance Dust explosion protection for zone 21/22 - Identification - Connection Type of protection "n" (zone 2) Explosion protection to FM - Identification (XP/DIP) or (IS); (NI)

Explosion protection to CSA - Identification

2/76

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA (PROFIBUS) for level

Dimensional drawings
ca. 30 (1.18)

2
185 100 (3.94) 6
50 (1.97)

138 (5.4) 69 (2.72)

15 (0.6)

2 165 (6.5) 51) L

77 (3)4)

8 d5 d4 1 54 (2.1) 108 (4.25) Space for rotation of housing b f 1 2 3 Process connection of low pressure side -18 NPT (EN 61518) Blanking plug Electrical connection: - screwed connection M20x1,5 3), - screwed connection -14 NPT or - PROFIBUS plug M12 2) 3) Terminal side Electronics side, digital display (longer overall length for cover with window) Protective cover over keys Sealing screw with valve (option) Screw cover safety bracket (only for "explosion-proof enclosure", not shown in the drawing) Allow approx. 20 mm (0.79 inch) thread length in addition Not with type of protection "Explosion-proof enclosure" Not with type of protection "FM + CSA [is + xp]" 92 mm (3.62 inch) for minimum distance to permit rotation with indicator nxd 2 D k

6 41)

51)

4 5 6 8 9 1) 2) 3) 4)

SITRANS P pressure transmitters, DS III PA series for level, including mounting flange, dimensions in mm (inch)

Connection to EN 1092-1
Nom. diam. DN 80 DN 100 Nom. press. PN 40 PN 40 PN 40 b mm 24 20 24 D mm 200 220 235 d mm 90 115 115 d2 mm 18 18 22 d4 mm 138 158 162 d5 mm 76 94 94 dM mm 72 1) 89 89 f mm 2 2 2 k mm 160 180 190 n mm 8 8 8 L mm 0, 50, 100, 150 or 200

Connection to ASME B16.5


Nom. diam. 3 inch Nom. press. lb/sq.in. 150 300 4 inch 150 300 b 0.94 (23.8) 1.12 (28.6) 0.94 (23.8) 1.25 (31.7) D 7.5 (190.5) 8.25 (209.5) 9 (228.5) 10 (254) d2 0.75 (19.0) 0.87 (22.2) 0.75 (19.0) 0.87 (22.2) d4 5 (127) 5 (127) 6,19 (157.2) 6,19 (157.2)
1)

d5 3 (76) 3 (76) 3.69 (94) 3.69 (94)

dM 2.81 1) (72) 2.81 1) (72) 3.5 (89) 3.5 (89)

f 0.06 (1.6) 0.06 (1.6) 0.06 (1.6) 0.06 (1.6)

k 6 (152.4) 6.69 (168.3) 7.5 (190.5) 7.88 (200)

n 4 8 8 8

L inch (mm) 0, 2, 3.94, 5.94 or 7.87 (0, 50, 100, 150 or 200)

inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm)

d: Internal diameter of gasket to DIN 2690 dM: Effective diaphragm diameter

89 mm = 3 inch with tube length L = 0.

Siemens FI 01 2005

2/77

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA (PROFIBUS) for level

Selection and Ordering data SITRANS P pressure transmitters for level DS III PA series Rated measuring range 250 mbar (3.63 psi) 600 mbar (8.70 psi) 1600 mbar (23.2 psi) 5 bar (72.5 psi) Process connection of low-pressure side Female thread -18 NPT with flange connection Mounting thread M10 to DIN 19 213 Mounting thread 7/16-20 UNF to EN 61518 Non-wetted parts materials Process flange screws Electronics housing Stainless steel Stainless steel Die-cast aluminium Stainless steel precision casting

Order No. 7MF 4 6 3 4 1 7 Y77 - 7777 D E F G

Further designs Please add "-Z" to Order No. and specify Order code. O-rings for process flanges on low-pressure side (instead of FPM (Viton)) PTFE (Teflon) FEP (with silicone core, approved for food) FFPM (Kalrez, compound 4079) NBR (Buna N) Sealing screws -18 NPT, with valve in material of process flanges

Order code

A20 A21 A22 A23 A40

0 2

2 3

Rating plate inscription (instead of German) English French Spanish Italian English rating plate Pressure units in inH2O or psi 1 2 Manufacturer's test certificate M to DIN 55.350, Part 18 and to ISO 8402 Acceptance test certificate B to EN 10 204-3.1B A B D P E R Factory certificate to EN 10.204-2.2 Type of protection IP68 (not together with PROFIBUS plug M12) Use on zone 1D / 2D (only together with type of protection "Intrinsic safety (EEx ia)" Use at zone 0 (only together with type of protection "Intrinsic safety (EEx ia)" Overfilling safety device for flammable and non-flammable liquids (max. PN 32 (MWP 464 psi), basic device with type of protection "Intrinsic safety (EEx ia)") Interchanging of process connection side Additional data Measuring point number/identification max. 16 characters, specify in plain text: Y15: ........................................... Measuring point text max. 27 characters, specify in plain text: Y16: ........................................... Setting of pressure indicator in pressure units specify in plain text (standard setting: mA): Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, mA, Torr, ATM or % *) Reference temperature 20 C Preset bus address specify in plain text (standard setting: 126) Y25: ...........................................

B11 B12 B13 B14 B21 C11 C12 C14 D12 E01

Design Standard design International version, English label inscriptions, documentation in 5 languages on CD Explosion protection without with CENELEC, Type of protection: - "Intrinsic safety (EEx ia)" - "Explosion-proof (EEx d)" 1) - "Intrinsic safety and explosion-proof enclosure (EEx ia + EEx d)" 2) - "n (zone 2)" - "Intrinsic safety, explosion-proof enclosure and dust explosion protection (EEx ia + EEx d + zone 1D/2D)" 2) with FM + CSA, Type of protection: - "Intrinsic safety and explosion-proof (is + xp)" 1) Electrical connection / cable inlet Screwed gland M20x1.5 Screwed gland -14 NPT PROFIBUS plug M12 incl. mating connector 3) Display without (digital display hidden) with visible digital indicator with customer-specific digital indicator (setting as specified, Order code "Y21" required) Ordering information: 1st order item: Pressure transmitter 7MF4634-... 2nd order item: Mounting flange 7MF4912-... Example of ordering: Item line 1: 7MF4634-1EY20-1AA1 Item line 2: 7MF4912-3GE01 Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation Sealing plug(s) or sealing screw(s) for the process flanges(s)

E02

NC B C F 1 6 7

E08

H01

Y15

Y16

Y21

1) Without cable gland, with blanking plug 2) With enclosed cable gland EEx ia and blanking plug 3) Not together with types of protection "Explosion-proof" and "Intrinsic safety und explosion-proof"

Y25

Only the settings for "Y21" and "Y25" can be made in the factory

2/78

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III PA (PROFIBUS) for level
Selection and Ordering data Mounting flange directly fitted to pressure transmitter SITRANS P (converter part) for level, for DS III series Connection to EN 1092-1 Nom. diam. Nom. press. DN 80 PN 40 DN 100 PN 16 PN 40 Connection to ASME B16.5 Nom. diam. Nom. press. 3 inch Class 150 Class 300 4 inch Class 150 Class 300 Other version Add Order code and plain text: Nominal diameter: ...; Nominal pressure: ... Wetted parts materials Stainless steel 316L 1) - Coated with PFA - Coated with PTFE - Coated with ECTFE Monel 400, mat. No. 2.4360 Hastelloy B2, mat. No. 2.4617 Hastelloy C276, mat. No. 2.4819 Hastelloy C4, mat. No. 2.4610 Tantalum Other version Add Order code and plain text: Wetted parts materials: ... Sealing face, see "Technical data" Tube length Without 50 mm (1.97 inch) 100 mm (3.94 inch) 150 mm (5.90 inch) 200 mm (7.87 inch) Other version: Add Order code and plain text: Tube length: ... Filling liquid Silicone oil M5 Silicone oil M50 High-temperature oil Halocarbon oil (for O2 measurements) Vegetable oil Glycerin / water2) Other version Add Order code and plain text: Filling liquid: ...
1) For vacuum on request 2) Not suitable for use in low-pressure range

Order No. 7MF 4 9 1 2 3 7777


777

Further designs Please add "-Z" to Order No. and specify Order code. Spark arrestor for mounting on zone 0 (including documentation) Manufacturer's test certificate M to DIN 55.350, Part 18 and to ISO 8402

Order code A01 C11 C12 V04 Y05

D G H

Acceptance test certificate B to EN 10 204-3.1B Vacuum-proof design (for use in low-pressure range) Calculation of span of associated pressure transmitter (enclose filled-in questionnaire with order) Note: Suffix "Y01" required with pressure transmitter J1Y

Q R T U Z

A D E0 F G H J U K Z K1Y

0 1 2 3 4 9

L1Y

1 2 3 4 5 6 9 M1 Y

Siemens FI 01 2005

2/79

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series (Foundation Fieldbus)

Overview

SITRANS P pressure transmitters of the DS III FF series are digital pressure transmitters featuring extensive user-friendliness and high accuracy. Parameterization is performed using input keys or through the Foundation Fieldbus Interface. Extensive functionality enables the pressure transmitter to be precisely adapted to the plants requirements. Operation is very simple in spite of the numerous setting options. Transmitters with type of protection "Intrinsic safety" and "Explosion-proof" (planned) may be installed within potentially explosive atmospheres (zone 1) or in zone 0. The transmitters are provided with an EC type examination certificate and comply with the corresponding harmonized European standards (ATEX). The transmitters can be equipped with various designs of remote seals for special applications such as the measurement of highly viscous substances. Various versions of the DS III FF pressure transmitters are available for measuring: Pressure Absolute pressure For differential pressure transmitters Level Volume Volume flow Mass flow

Application
SITRANS P pressure transmitters, DS III FF series, can be used in industrial areas with extreme chemical and mechanical loads. Electromagnetic compatibility in the range 10 kHz to 1 GHz makes the DS III FF pressure transmitters suitable for locations with high electromagnetic emissions. Transmitters with type of protection "Intrinsic safety" and "Explosion-proof" (planned) may be installed within potentially explosive atmospheres (zone 1) or in zone 0. The pressure transmitters are provided with an EC type examination certificate and comply with the corresponding harmonized European standards of the CENELEC. Pressure transmitters with the type of protection "Intrinsic safety" for use in zone 0 may be operated with power supply units of category "ia" and "ib". The transmitters can be equipped with various designs of remote seals for special applications such as the measurement of highly viscous substances. Pressure transmitters for pressure Measured variable: Pressure of aggressive and non-aggressive gases, vapors and liquids. Measured spans: 0.01 ... 400 bar (0.145 ... 5802 psi) Pressure transmitters for absolute pressure Measured variable: Absolute pressure of aggressive and nonaggressive gases, vapors and liquids. Measured spans: 8.3 mbar ... 100 bar (0.12 ... 1450 psi) There are two series: Pressure series Differential pressure series Pressure transmitters for differential pressure and flow Measured variables: Differential pressure Small positive or negative pressure Flow q ~ p (together with a primary differential pressure device) Nominal measuring ranges: 1 mbar ... 30 bar (0.0145 ... 435 psi)

Benefits
High quality and long life High reliability even under extreme chemical and mechanical loads For aggressive and non-aggressive gases, vapors and liquids Extensive diagnosis and simulation functions Separate replacement of measuring cell and electronics without recalibration Minimum conformity error Small long-term drift Wetted parts made of high-grade materials (stainless steel, Hastelloy, gold, Monel, tantalum) Choice of several nominal measuring ranges High measuring accuracy Parameterization using input keys and Foundation Fieldbus

2/80

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series (Foundation Fieldbus)
Pressure transmitters for level Measured variable: Level of aggressive and non-aggressive liquids in open and closed vessels. Nominal measuring ranges: 25 mbar ... 5 bar (0.363 ... 72.5 psi) Nominal diameter of the mounting flange: DN 80 or DN 100 3 inch or 4 inch In the case of level measurements in open containers, the lowpressure connection of the measuring cell remains open (measurement "compared to atmospheric"). In the case of measurements in closed containers, the lowerpressure connection has to be connected to the container in order to compensate the static pressure. The wetted parts are constructed from a variety of materials depending on the degree of corrosion resistance required. cell and the electronics can be replaced separately from each other. The set parameter data are retained. At the top of the housing is a plastic cover (5), under which the input keys can be found.

Function
Mode of operation of the electronics
9 M 2 3 4 mC 0 0 00 0 00 5 FF interface 7 Power supply 10 Power supply unit

Design

EEPROM

Coupler

Electronics 1 Sensor pe 6 EEPROM Measuring cell 8 9 10 pe Three input keys (local operation) Digital display Power supply Input variable

1 2 3 4 5 6 7

Measuring cell sensor Instrument amplifier Analog-to-digital converter Microcontroller Electrical isolation One non-volatile memory each in the measuring cell and electronics FF interface

Function diagram of the electronics

Front view

The transmitter consists of various components depending on the order. The possible versions are listed in the ordering information. The components described below are the same for all transmitters. The rating plate (3, Figure "Front view") with the Order No. is located on the side of the housing. The specified number together with the ordering information provide details on the optional design details and on the possible measuring range (physical properties of built-in sensor element). The approval label is located on the opposite side. The housing is made of die-cast aluminium or stainless steel precision casting. A round cover is screwed on at the front and rear of the housing. The front cover (6) can be fitted with a viewing pane so that the measured values can be read directly on the digital display. The inlet (4) for the electrical connection is located either on the left or right side. The unused opening on the opposite side is sealed by a blanking plug. The protective earth connection is located on the rear of the housing. The electrical connections for the power supply and screen are accessible by unscrewing the rear cover. The bottom part of the housing contains the measuring cell with process connection (1). The measuring cell is protected from rotating by a locking screw (8). As the result of this modular design, the measuring

The bridge output voltage created by the sensor (1, Figure "Function diagram of the electronics") is amplified by the instrument amplifier (2) and digitized in the analog-to-digital converter (3). The digital information is evaluated in the microcontroller, its linearity and temperature response corrected, and provided on the Foundation Fieldbus through an electrically isolated Foundation Fieldbus Interface (7). The data specific to the measuring cell, the electronics data, and the parameter data are stored in the two non-volatile memories (6). The one memory is coupled to the measuring cell, the other to the electronics. As the result of this modular design, the electronics and the measuring cell can be replaced separately from each other. Using the three input keys (8) you can parameterize the pressure transmitter directly at the point of measurement. The input keys can also be used to control the view of the results, the error messages and the operating modes on the digital display (9). The results with status values and diagnostic values are transferred by cyclic data transmission on the Foundation Fieldbus. Parameterization data and error messages are transferred by acyclic data transmission. Special software such as National Instruments Configurator is required for this.

Siemens FI 01 2005

2/81

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series (Foundation Fieldbus)

Mode of operation of the measuring cells Measuring cell for pressure

Measuring cell for absolute pressure from differential pressure series

2
5 4 3 1

1 2 3 4 5 pe

Measuring cell Process connection Seal diaphragm Filling liquid Silicon pressure sensor Pressure as input variable

5 pe 6

1 2 3 4 5 6 7 8 pe

Reference vacuum Overload diaphragm Silicon pressure sensor O-ring Process flange Seal diaphragm Body of measuring cell Filling liquid Absolute pressure as input variable

2 p e

Measuring cell for absolute pressure from differential pressure series, functional diagram

Measuring cell for pressure, functional diagram

Measuring cell for absolute pressure from pressure series The pressure pe is applied through the process connection (2, Figure "Measuring cell for pressure, functional diagram) to the measuring cell (1). This pressure is subsequently transmitted further through the seal diaphragm (3) and the filling liquid (4) to the silicon pressure sensor (5) whose measuring diaphragm is then flexed. The resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit thus changes. This change in resistance results in a bridge output voltage proportional to the input pressure.

The input pressure pe is transmitted through the seal diaphragm (6, Figure "Measuring cell for absolute pressure from differential pressure series, functional diagram") and the filling liquid (8) to the silicon pressure sensor (3). The difference in pressure between the input pressure pe and the reference vacuum (1) on the low-pressure side of the measuring cell flexes the measuring diaphragm. The resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit thus changes. This change in resistance results in a bridge output voltage proportional to the absolute pressure. An overload diaphragm is installed to provide protection from overloads. If the measuring limits are exceeded, the overload diaphragm (2) is flexed until the seal diaphragm rests on the body of the measuring cell (7), thus protecting the silicon pressure sensor from overloads. Measuring cell for differential pressure and flow

5 4 3 1 1 2 3 4 5 pe Measuring cell Process connection Seal diaphragm Filling liquid Silicon absolute pressure sensor Absolute pressure as input variable 2 3 4 1 2 3 4 5 6 7 Seal diaphragm O-ring Overload diaphragm Silicon pressure sensor Process flange Body of measuring cell Filling liquid

1 5

pe

Measuring cell for differential pressure and flow, functional diagram Measuring cell for absolute pressure from the pressure series, functional diagram

The absolute pressure pe is transmitted through the seal diaphragm (3, Figure "Measuring cell for absolute pressure from pressure series, functional diagram") and the filling liquid (4) to the silicon absolute pressure sensor (5) whose measuring diaphragm is then flexed. The resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit thus changes. This change in resistance results in a bridge output voltage proportional to the input pressure.

The differential pressure is transmitted through the seal diaphragms (1, Figure "Measuring cell for differential pressure and flow, functional diagram") and the filling liquid (7) to the silicon pressure sensor (4). The measuring diaphragm is flexed by the applied differential pressure. The resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit thus changes. This change in resistance results in a bridge output voltage proportional to the absolute pressure. An overload diaphragm is installed to provide protection from overloads. If the measuring limits are exceeded, the overload diaphragm (2) is flexed until the seal diaphragm rests on the body of the measuring cell (7), thus protecting the silicon pressure sensor from overloads.

2/82

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series (Foundation Fieldbus)
Measuring cell for level Adjustable parameters
Parameters
3 2 + 1 10 9 6 7 8 9 10 Silicon pressure sensor O-ring Process flange Filling liquid Capillary with filling liquid of mounting flange 4 5 6 7

Input keys

Foundation Fieldbus Interface x x x x x x x x x x x

Electrical damping
8

x x x x x x x x

Zero adjustment (correction of position) Keys and/or function disabling Source of measured-value display Physical dimension of display Position of decimal point Bus address Adjustment of characteristic Input of characteristic Freely-programmable LCD Diagnostics functions

1 2 3 4 5

Flange with tube Seal diaphragm on mounting flange Seal diaphragm Body of measuring cell Overload diaphragm

Measuring cell for level, functional diagram

The input pressure (hydrostatic pressure) acts hydraulically on the measuring cell through the seal diaphragm on the mounting flange (2, Figure "Measuring cell for level, functional diagram"). This differential pressure is subsequently transmitted further through the measuring cell (3) and the filling liquid (9) to the silicon pressure sensor (6) whose measuring diaphragm is then flexed. The resistance of the four piezo-resistors fitted in the diaphragm in a bridge circuit thus changes. This change in resistance results in a bridge output voltage proportional to the differential pressure. An overload diaphragm is installed to provide protection from overloads. If the measuring limits are exceeded, the overload diaphragm (2) is flexed until the seal diaphragm rests on the body of the measuring cell (7), thus protecting the silicon pressure sensor from overloads. Parameterization Depending on the version, there are different possibilities for parameterizing the pressure transmitter and for setting or scanning the parameters. Parameterization using the input keys (local operation) With the input keys you can easily set the most important parameters without any additional equipment. Parameterization through Foundation Fieldbus Interface Fully digital communication through Foundation Fieldbus is particularly user-friendly. Through the Foundation Fieldbus the DS III FF is connected to a process control system. Communication is possible even in a potentially explosive environment. For parameterization through the Foundation Fieldbus you need suitable software, e.g. National Instruments Configurator.

Diagnostic functions Event counter Slave pointer Maintenance timer Simulation functions Display of zero correction Limit transmitter Saturation alarm Physical dimensions available for the display
Physical variable Pressure (setting can also be made in the factory) Physical dimensions MPa, hPa, kPa, Pa, bar, mbar, torr, atm, psi, g/cm2, kg/cm2, mmH20, mmH20 (4 C), inH20, inH20 (4 C), ftH20, mmHg, inHg m, cm, mm, ft, in, yd m3, dm3, hl, yd3, ft3, in3, US gallon, lmp, gallon, bushel, barrel, barrel liquid m3/s, m3/min, m3/h, m3/d, l/s, l/min, l/h, l/ d, Ml/d, ft3/s, ft3/min, ft3/h, ft3/d, US gallon/s, US gallon/min, US gallon/h, US gallon/d, bbl/s, bbl/min, bbl/h, bbl/d g/s, g/min, g/h, g/d, kg/s, kg/min, kg/h, kg/d, t/s, t/min, t/h, /t/d, lb/s, lb/min, lb/h, lb/d, STon/s, STon/min, STon/h, STon/d, LTon/s, LTon/min, LTon/h, LTon/d t, kg, g, lb, oz, LTon, STon K, C, F, R %

Level (height data) Volume

Volume flow

Mass flow

Total mass flow Temperature Miscellaneous

Siemens FI 01 2005

2/83

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series for pressure

Technical specifications
SITRANS P pressure transmitters, DS III FF series, for pressure Input Measured variable Nominal measuring range 1 bar (14.5 psi) 4 bar (58 psi) 16 bar (232 psi) 63 bar (913 psi) 160 bar (2320 psi) 400 bar (5802 psi) Lower measuring limit Measuring cell with silicone oil filling Upper measuring limit 30 mark (0.435 psi) absolute 100% of nominal measuring range (max. 160 bar (2320 psi) with oxygen measurement and inert filling liquid) Digital Foundation Fieldbus signal IEC 61158-2 Pressure Max. working pressure 6 bar (87 psi) 10 bar (145 psi) 32 bar (464 psi) 100 bar (1450 psi) 250 bar (3626 psi) 500 bar (7252 psi)

Power supply UH

Supplied through bus

Separate 24 V power supply neces- No sary Bus voltage Not Ex With intrinsically-safe operation Current consumption Basic current (max.) Certificates and approvals Classification according to pressure equipment directive (DRGL 97/23/EC) For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) PTB 99 ATEX 2122 Ex II 1/2 G EEx ia/ib IIB/IIC T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +70 C (-40 ... +158 F) temperature class T5; -40 ... +60 C (-40 ... +140 F) temperature class T6 To a certified intrinsically-safe circuit with maximum values: FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W Li = 7 H, Ci = 1.1 nF Planned Planned Planned Planned 12.5 mA 9 ... 32 V 9 ... 24 V

Explosion protection Intrinsic safety "i" - Identification - Permissible ambient temperature

Output Physical bus Measuring accuracy Reference conditions

- Connection Increasing characteristic, start-ofscale value 0 bar, stainless steel seal diaphragm, silicone oil filling, room temperature (25 C (77 F))

Error in measurement (including hysteresis and repeatability) - Linear characteristic Influence of ambient temperature With -10 ... +60 C (14 ... 140 F) With -40 ... -10 C and +60 C ... +85 C (-40 ... +14 and 140 ... 185 F) Rated conditions Degree of protection (to EN 60529) Process temperature Measuring cell with silicone oil filling Measuring cell with inert filling liquid Design Weight (without options) Wetted parts materials Connection shank Stainless steel, mat. No. 1.4404/316L or Hastelloy C4, mat. No. 2.4610 Stainless steel, mat. No. 1.4404/316L or Hastelloy C276, mat. No. 2.4819 Silicone oil or inert filling liquid (max. 160 bar (2320 psi) with oxygen measurement) Connection shank GA to DIN EN 837, female thread -14 NPT or oval flange (PN 160 (MWP 2320)) to DIN 19213 with mounting thread M10 or 7/ -20 UNF to EN 61518 16 1.5 kg ( 3.3 lb) -40 ... +100 C (-40 ... +212 F) -20 ... +100 C (-4 ... +212 F) IP65 0.3% 0.25% / 10 K ( 0.25% / 18 F) 0.075% - Effective internal inductance/capacitance Explosion-proof "d" Type of protection "n" (zone 2) Explosion protection to FM Explosion protection to CSA

Seal diaphragm

Measuring cell filling

Process connection

2/84

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series for pressure

Dimensional drawings
15 (0.6) 138 (5.4)

2
50 (1.97) 55 (0.6)
28 (1.1) 20 (0.8)

approx. 30 (1.2)

100 (3.94)

69 (2.7)

6
50 (1.97)

80 (3.15)

117 (4.6)

3
171 (6.7) 237 (9.3) 36,5 (1,44) 105 (4.1)

1)

1)

8
68 (2.7)

72 (2.8)

123 (4.8) min. 77 (3.0) 2)


1 Process connection: - -14 NPT, - connection shank GA or - oval flange Blanking plug Electrical connection: - screwed gland M20x1,5 3) or - screwed gland -14 NPT Terminal side Electronics side (long er overall length for cover with window) Safety cover over keys Mounting bracket (option) Screw cover safety bracket (only for explosion-proof cover, not shown in the drawing)

2 3 4 5 6 7 8

1) 2) 3)

Allow approx. 20 mm (0.79 inch) thread length in addition Minimum distance to permit rotation Not for type of protection "FM + CSA".

SITRANS P pressure transmitters, DS III FF series for pressure, dimensional drawing, dimensions in mm (inch)

120 (4.7)

Siemens FI 01 2005

2/85

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series for pressure

Selection and Ordering data SITRANS P pressure transmitter for pressure DS III FF series Measuring cell filling Silicone oil Inert liquid1) Measuring cell cleaning Standard Grease-free

Order No. 7MF 4 0 3 5 77777 - 7777

Further designs Please add "-Z" to Order No. and specify Order code.

Order code

1 3 B C D E F G

Pressure transmitter with mounting bracket made of: Steel A01 Stainless steel A02 Rating plate inscription (instead of German) English French Spanish Italian English rating plate Pressure units in inH2O or psi Manufacturer's test certificate M to DIN 55.350, Part 18 and to ISO 8402

Rated measuring range 1 bar (14.5 psi) 4 bar (58 psi) 16 bar (232 psi) 63 bar (914 psi) 160 bar (2320 psi) 400 bar (5802 psi) Wetted parts materials Seal diaphragm Process connection Stainless steel Stainless steel Hastelloy Stainless steel Hastelloy Hastelloy Version as diaphragm seal Process connection Connection shank GB to EN 837-1 Female thread -14 NPT Oval flange made of stainless steel, max. span 160 bar (2320 psi) - Mounting thread 7/16-20 UNF to EN 61518 - Mounting thread M10 to DIN 19213 Non-wetted parts materials Housing made of die-cast aluminium Housing stainless steel precision casting Design Standard design International version, English label inscriptions, documentation in 5 languages on CD Explosion protection without with CENELEC, Type of protection: - "Intrinsic safety (EEx ia)" - "Explosion-proof (EEx d)" 2) (planned) - "Intrinsic safety and explosion-proof enclosure (EEx ia + EEx d)" 3) (planned) - "n (zone 2)" (planned) with FM + CSA, Type of protection: - "Intrinsic safety and explosion-proof (is + xp)" 1) (planned) Electrical connection / cable inlet Screwed gland M20x1.5 Screwed gland -14 NPT Display without (digital display hidden) with visible digital indicator with customer-specific digital indicator (setting as specified, Order code "Y21" required)

B11 B12 B13 B14 B21 C11 C12 C14 D07 D12

A B C Y0 0 1

Acceptance test certificate B to EN 10 204-3.1B Factory certificate to EN 10.204-2.2 Acid gas version to NACE (only together with seal diaphragm made of Hastelloy) Type of protection IP68 (not together with nominal measuring range 63 bar ( 914 psi)) Digital indicator along side the input keys (only together with the devices 7MF4035-....0-.A.6 or -.A.7-Z, Y21) Use on zone 1D / 2D (only together with type of protection "Intrinsic safety (EEx ia)" 1 2 Use at zone 0 (only together with type of protection "Intrinsic safety (EEx ia)" A B D P E NC Oxygen application (max. 160 bar (2320 psi) with oxygen measurement and inert liquid) Additional data Measuring point number/identification Max. 16 characters, specify in plain text: Y15: ........................................... Measuring point text max. 27 characters, specify in plain text: Y16: ........................................... Setting of pressure indicator in pressure units specify in plain text (standard setting: mA): Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, mA, Torr, ATM or % *) Reference temperature 20 C Only the settings for "Y21" can be made in the factory. Ordering example Item line: 7MF4034-1EA00-1AA7-Z B line: A01 + Y21 C line: Y21: ... mbar

2 3 0 3

D27

E01

E02

E10

Y15

Y16

B C 1 6 7

Y21

The device is delivered together with brief instructions (Leporello) and a CD-ROM containing detailed documentation.
1) For oxygen application, add Order code E10. 2) Without cable gland, with blanking plug 3) With enclosed cable gland EEx ia and blanking plug

2/86

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series for absolute pressure (from pressure series)

Technical specifications
SITRANS P pressure transmitters, DS III FF series for absolute pressure, from the pressure series Input Measured variable Nominal measuring range 250 mbar (3.6 psi) 1300 mbar (18.9 psi) 5 bar (72.5 psi) 30 bar (435 psi) Lower measuring limit Measuring cell with silicone oil filling Upper measuring limit 0 mbar absolute 100% of nominal measuring range (max. 160 bar (2320 psi) with oxygen measurement and inert filling liquid) Digital Foundation Fieldbus signal IEC 61158-2 Increasing characteristic Start-of-scale value 0 bar Stainless steel seal diaphragm Silicone oil filling Room temperature (25 C (77 F)) Absolute pressure Max. working pressure 6 bar (87 psi) 10 bar (145 psi) 30 bar (435 psi) 100 bar (1450 psi)

Power supply UH

Supplied through bus

Separate 24 V power supply neces- No sary Bus voltage Not Ex With intrinsically-safe operation Current consumption Basic current (max.) Certificates and approvals Classification according to pressure equipment directive (DRGL 97/23/EC) For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) PTB 99 ATEX 2122 Ex II 1/2 G EEx ia/ib IIB/IIC T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +70 C (-40 ... +158 F) temperature class T5; -40 ... +60 C (-40 ... +140 F) temperature class T6 To a certified intrinsically-safe circuit with maximum values: FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W L i = 7 H, Ci = 1.1 nF Planned Planned Planned Planned 12.5 mA 9 ... 32 V 9 ... 24 V

Explosion protection Intrinsic safety "i" - Identification - Permissible ambient temperature

Output Physical bus Measuring accuracy Reference conditions

- Connection

Error in measurement (including hysteresis and repeatability) - Linear characteristic Influence of ambient temperature With -10 ... +60 C (14 ... 140 F) With -40 ... -10 C and +60 C ... +85 C (-40 ... +14 and 140 ... 185 F) Rated conditions Degree of protection (to EN 60529) Process temperature Measuring cell with silicone oil filling Design Weight (without options) Wetted parts materials Connection shank Stainless steel, mat. No. 1.4404/316L or Hastelloy C4, mat. No. 2.4610 Stainless steel, mat. No. 1.4404/316L or Hastelloy C276, mat. No. 2.4819 Silicone oil or inert filling liquid (max. 160 bar (2320 psi) with oxygen measurement) Connection shank GA to DIN EN 837, female thread -14 NPT or oval flange (PN 160 (MWP 2320)) to DIN 19,213 with mounting thread M10 or 7/ -20 UNF to EN 61518 16 1.5 kg ( 3.3 lb) -40 ... +100 C (-40 ... +212 F) IP65 0.3% 0.25% / 10 K ( 0.25% / 18 F) 0.075% - Effective internal inductance/capacitance Explosion-proof "d" Type of protection "n" (zone 2) Explosion protection to FM Explosion protection to CSA

Seal diaphragm

Measuring cell filling

Process connection

Siemens FI 01 2005

2/87

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series for absolute pressure (from pressure series)

Dimensional drawings
15 (0.6) 138 (5.4)

20 (0.8)

69 (2.7)

50 (1.97)

55 (0.6)
28 (1.1)

approx. 30 (1.2)

100 (3.94)

6
50 (1.97)

80 (3.15)

117 (4.6)

3
171 (6.7) 237 (9.3) 36,5 (1,44) 105 (4.1)

1)

1)

8
68 (2.7)

72 (2.8)

123 (4.8) min. 77 (3.0) 2)


1 Process connection: - -14 NPT, - connection shank GA or - oval flange Blanking plug Electrical connection: - screwed gland M20x1,5 3) or - screwed gland -14 NPT Terminal side Electronics side (long er overall length for cover with window) Safety cover over keys Mounting bracket (option) Screw cover safety bracket (only for explosion-proof cover, not shown in the drawing)

2 3 4 5 6 7 8

1) 2) 3)

Allow approx. 20 mm (0.79 inch) thread length in addition Minimum distance to permit rotation Not for type of protection "FM + CSA".

SITRANS P pressure transmitters, DS III FF series for absolute pressure, from the pressure series, dimensional drawing, dimensions in mm (inch)

2/88

Siemens FI 01 2005

120 (4.7)

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series for absolute pressure (from pressure series)
Selection and Ordering data SITRANS P pressure transmitters for absolute pressure from the pressure series DS III FF series Measuring cell filling Silicone oil Inert liquid1) Measuring cell cleaning Standard Grease-free E) E) E) Order No. 7MF 4 2 3 5 77777 - 7777

Further designs Please add "-Z" to Order No. and specify Order code.

Order code

Pressure transmitter with mounting bracket made of: Steel A01 Stainless steel A02 Rating plate inscription (instead of German) English French Spanish Italian English rating plate Pressure units in inH2O or psi

1 3 D F G H

Rated measuring range 250 mbar (3.63 psi) 1300 mbar (18.9 psi) 5 bar (72.5 psi) 30 bar (435 psi) Wetted parts materials Seal diaphragm Process connection Stainless steel Stainless steel Hastelloy Stainless steel Hastelloy Hastelloy Version as diaphragm seal 2) Process connection Connection shank GB to EN 837-1 Female thread -14 NPT Oval flange made of stainless steel, max. span 160 bar (2320 psi) - Mounting thread 7/16-20 UNF to EN 61518 - Mounting thread M10 to DIN 19213 Non-wetted parts materials Housing made of die-cast aluminium Housing stainless steel precision casting Design Standard design International version, English label inscriptions, documentation in 5 languages on CD Explosion protection without with CENELEC, Type of protection: - "Intrinsic safety (EEx ia)" - "Explosion-proof (EEx d)" 3) (planned) - "Intrinsic safety and explosion-proof enclosure (EEx ia + EEx d)" 4) (planned) - "n (zone 2)" (planned) with FM + CSA, Type of protection: - "Intrinsic safety and explosion-proof (is + xp)" 3) (planned) Electrical connection / cable inlet Screwed gland M20x1.5 Screwed gland -14 NPT Display without (digital display hidden) with visible digital indicator with customer-specific digital indicator (setting as specified, Order code "Y21" required)

B11 B12 B13 B14 B21 C11 C12 C14 D07 D12 D27

E) E)

A B C Y0 0 1

Manufacturer's test certificate M to DIN 55350, Part 18 and to ISO 8402 Acceptance test certificate B to EN 10204-3.1B Factory certificate to EN 10204-2.2 Acid gas version to NACE (only together with seal diaphragm made of Hastelloy) Type of protection IP68 Digital indicator along side the input keys (only together with the devices 7MF4235-...0-.A.6 or .A.7-Z, Y21) 0 3 1 2 Use on zone 1D / 2D (only together with type of protection "Intrinsic safety (EEx ia)" Use at zone 0 (only together with type of protection "Intrinsic safety (EEx ia)" A B D P E NC Oxygen application (max. 160 bar (2320 psi) with oxygen measurement and inert liquid) Additional data Measuring point number/identification max. 16 characters, specify in plain text: Y15: ........................................... Measuring point text max. 27 characters, specify in plain text: Y16: ........................................... Setting of pressure indicator in pressure units specify in plain text (standard setting: mA): Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, mA, Torr, ATM or % *) Reference temperature 20 C Only the settings for "Y21" can be made in the factory

2 3

E01

E02

E10

Y15

Y16

B C 1 6 7

Y21

The device is delivered together with brief instructions (Leporello) and a CD-ROM containing detailed documentation.
1) 2) 3) 4) E) For oxygen application, add Order code E10. Version 7MF4235-1DY... only up to max. span 200 mbar (2.9 psi) Without cable gland, with blanking plug With enclosed cable gland EEx ia and blanking plug Combinations of the versions marked with E) are subject to the export regulations AL: 2B230, ECCN: N

Siemens FI 01 2005

2/89

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series for absolute pressure (from differential pressure series)

Technical specifications
SITRANS P pressure transmitters, DS III FF series for absolute pressure, from the differential pressure series Mode of operation and system design Measuring principle Input Measured variable Nominal measuring range 250 mbar (3.6 psi) 1300 mbar (18.9 psi) 5 bar (72.5 psi) 30 bar (435 psi) 100 bar (1450 psi) Absolute pressure Max. working pressure 32 bar (464 psi) 32 bar (464 psi) 32 bar (464 psi) 160 bar (2320 psi) 160 bar (2320 psi) with pressure cover screws M10 and 7/ -20 UNF 16 0 mbar absolute 100% of nominal measuring range (max. 160 bar (2320 psi) with oxygen measurement and inert filling liquid) Digital Foundation Fieldbus signal IEC 61158-2 Increasing characteristic Start-of-scale value 0 bar Stainless steel seal diaphragm Silicone oil filling Room temperature (25 C (77 F)) Piezo-resistive

Power supply

Supplied through bus

Separate 24 V power supply neces- No sary Bus voltage Not Ex With intrinsically-safe operation Current consumption Basic current (max.) Certificates and approvals Classification according to pressure equipment directive (DRGL 97/23/EC) For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) PTB 99 ATEX 2122 Ex II 1/2 G EEx ia/ib IIB/IIC T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +70 C (-40 ... +158 F) temperature class T5; -40 ... +60 C (-40 ... +140 F) temperature class T6 To a certified intrinsically-safe circuit with maximum values: FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W Li = 7 H, Ci = 1.1 nF Planned Planned Planned Planned 12.5 mA 9 ... 32 V 9 ... 24 V

Explosion protection Intrinsic safety "i" - Identification - Permissible ambient temperature

Lower measuring limit Measuring cell with silicone oil filling Upper measuring limit

- Connection

Output Physical bus Measuring accuracy Reference conditions

- Effective internal inductance/capacitance Explosion-proof "d" Type of protection "n" (zone 2)

Error in measurement (including hysteresis and repeatability) - Linear characteristic Influence of ambient temperature With -10 ... +60 C (14 ... 140 F) With -40 ... -10 C and +60 C ... +85 C (-40 ... +14 and 140 ... 185 F) Rated conditions Degree of protection (to EN 60529) Process temperature - Measuring cell with silicone oil fil- -40 ... +100 C (-40 ... +212 F) ling Design Weight (without options) Wetted parts materials - Seal diaphragm Stainless steel, mat. No. 1.4404/316L, Hastelloy C276, mat. No. 2.4819, Monel, mat. No. 2.4360, tantalum or gold Silicone oil or inert filling liquid (max. 160 bar (2320 psi) with oxygen measurement) Female thread 1/4-18 NPT and flange connection to DIN 19213 with mounting thread M10 or 7/ -20 UNF to EN 61518 16 4.5 kg ( 9.9 lb) IP65 0.3% 0.25% / 10 K ( 0.25% / 18 F) 0.075%

Explosion protection to FM Explosion protection to CSA

Measuring cell filling

Process connection

2/90

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series for absolute pressure (from differential pressure series)

Dimensional drawings
15 (0.6) 138 (5.4)

2
50 (1.97)
20 (0.8)

approx. 30 (1.2)

100 (3.94) 6 2

80 (3.15)

117 (4.6)

50 (1.97)

3 198 (7.8) approx. 261 (10.3) 96 (3.8) 7 11 52 (2.05)

5 1)

69 (2.7) 77 (3) 2)

1)

9 10

Space for rotation of housing

1 134 (5.27)
+

72 (2.83) 105 (4.1) 1 2 3 4 5 6 7 8 9 10 11 Process connection -18 NPT (EN 61518) Blanking plug Electrical connection - screwed gland M20x1,5 3) or - screwed gland -14 NPT Terminal side Electronics side, digital display (longer overall length for cover with window) Protective cover over keyes Mounting bracket (option) Sealing screw with valve (option) Screw cover safety bracket (only for explosion-proof enclosure, not shown in the drawing) Lateral venting for liquid measurement Lateral venting for gas measurement (suffix H02)

68 (2.7) 120 (4.7)

1) 2) 3)

Allow approx. 20 mm (0.79 inch) thread length in addition 92 mm (3.62 inch) for minimum distance to permit rotation with indicator Not with type of protection "FM + CSA"

SITRANS P pressure transmitters, DS III FF series for absolute pressure, from the differential pressure series, dimensional drawing, dimensions in mm (inch)

Siemens FI 01 2005

2/91

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series for absolute pressure (from differential pressure series)

Selection and Ordering data SITRANS P pressure transmitters for absolute pressure from the series Differential pressure DS III FF series Measuring cell filling Silicone oil Inert liquid1) Measuring cell cleaning Standard Grease-free E) E) E)

Order No. 7MF 4 3 3 5 -

77777 - 7777

1) 2) 3) 4) 5)

For oxygen application, add Order code E10. Version 7MF4335-1DY... only up to max. span 200 mbar (2.9 psi) Not for nominal measuring range 100 bar (1450 psi). Without cable gland, with blanking plug With enclosed cable gland EEx ia and blanking plug

1 3 D F G H KE

E) Combinations of the versions marked with E) are subject to the export regulations AL: 2B230, ECCN: N.

Rated measuring range 250 mbar (3.63 psi) 1300 mbar (18.9 psi) 5 bar (72.5 psi) 30 bar (435 psi) 100 bar (1450 psi) Wetted parts materials Seal diaphragm Parts of measuring cell Stainless steel Stainless steel Hastelloy Stainless steel Hastelloy Hastelloy Tantalum Tantalum Monel Monel Gold Gold Version as diaphragm seal 2) Process connection Female thread -18 NPT with flange connection Sealing screw opposite process connection - Mounting thread M10 to DIN 19 213 - Mounting thread 7/16-20 UNF to EN 61518 Vent on side of process flange 3) - Mounting thread M10 to DIN 19 213 - Mounting thread 7/16-20 UNF to EN 61518 Non-wetted parts materials Process flange screws Electronics housing Stainless steel Stainless steel Die-cast aluminium Stainless steel precision casting

E) E) E)

A B C E H L Y

0 2

4 6

2 3

Design Standard design International version, English label inscriptions, documentation in 5 languages on CD Explosion protection without with CENELEC, Type of protection: - "Intrinsic safety (EEx ia)" - "Explosion-proof (EEx d)" 4) (planned) - "Intrinsic safety and explosion-proof enclosure (EEx ia + EEx d)" 5) (planned) - "n (zone 2)" (planned) with FM + CSA, Type of protection: - "Intrinsic safety and explosion-proof (is + xp)" 4) (planned) Electrical connection / cable inlet Screwed gland M20x1.5 Screwed gland -14 NPT Display without (digital display hidden) with visible digital indicator with customer-specific digital indicator (setting as specified, Order code "Y21" required) Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation Sealing plug(s) or sealing screw(s) for the process flanges(s)

1 2

A B D P E NC

B C 1 6 7

2/92

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series for absolute pressure (from differential pressure series)
Further designs Please add "-Z" to Order No. and specify Order code. Pressure transmitter with mounting bracket made of: Steel A01 Stainless steel A02 O-rings for process flanges (instead of FPM (Viton)) PTFE (Teflon) FEP (with silicone core, approved for food) FFPM (Kalrez, compound 4079) NBR (Buna N) Sealing screws -18 NPT, with valve in material of process flanges Rating plate inscription (instead of German) English French Spanish Italian English rating plate Pressure units in inH2O or psi Manufacturer's test certificate M to DIN 55350, Part 18 and to ISO 8402 Acceptance test certificate B to EN 10204-3.1B Factory certificate to EN 10204-2.2 Acid gas version to NACE (only together with seal diaphragm made of Hastelloy and process flange screws made of stainless steel) Type of protection IP68 Digital indicator along side the input keys (only together with the devices 7MF4335-...0.2-.A.6 or -.A.7-Z, Y21) Use on zone 1D / 2D (only together with type of protection "Intrinsic safety (EEx ia)" Use at zone 0 (only together with type of protection "Intrinsic safety (EEx ia)" Oxygen application (max. 160 bar (2320 psi) with oxygen measurement and inert liquid) Interchanging of process connection side Vent on side for gas measurements Process flange Hastelloy Monel Stainless steel with PVDF insert max. PN 10 (MWP 145 psi) max. temperature of medium 90 C (194 F) Order code Further designs Please add "-Z" to Order No. and specify Order code. Additional data Measuring point number/identification max. 16 characters, specify in plain text: Y15: ........................................... Measuring point text max. 27 characters, specify in plain text: Y16: ........................................... Setting of pressure indicator in pressure units specify in plain text Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, mA, Torr, ATM or % *) Reference temperature 20 C Only the settings for "Y21" can be made in the factory. Y15 Order code

Y16

A20 A21 A22 A23 A40

Y21

B11 B12 B13 B14 B21 C11 C12 C14 D07

D12 D27

E01

E02

E10

H01 H02 K01 K02 K04

Siemens FI 01 2005

2/93

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series for differential pressure and flow

Technical specifications
SITRANS P pressure transmitters, DS III FF series, for differential pressure and flow Input Measured variable Nominal measuring range PN 32 (MWP 464 psi) - 20 mbar (0.29 psi) PN 160 (MWP 2320 psi) - 60 mbar (0.87 psi) - 250 mbar (3.63 psi) - 600 mbar (8.7 psi) - 1600 mbar (23.3 psi) - 5 bar (72.5 psi) - 30 bar (435 psi) PN 400 (MWP 6092 psi) - 250 mbar (3.63 psi) - 600 mbar (8.7 psi) - 1600 mbar (23.3 psi) - 5 bar (72.5 psi) - 30 bar (435 psi) Lower measuring limit Measuring cell with silicone oil filling -100% of nominal measuring range (-33% with nominal measuring range 30 bar (435 psi)) or 30 mbar (0.435 psi) absolute 100% of nominal measuring range (max. 160 bar (2320 psi) with oxygen measurement and inert filling liquid) Digital Foundation Fieldbus signal IEC 61158-2 Increasing characteristic Start-of-scale value 0 bar Stainless steel seal diaphragm Silicone oil filling Room temperature (25 C (77 F)) 420 bar (6092 psi) 420 bar (6092 psi) 420 bar (6092 psi) 420 bar (6092 psi) 420 bar (6092 psi) 160 bar (2320 psi) 160 bar (2320 psi) 160 bar (2320 psi) 160 bar (2320 psi) 160 bar (2320 psi) 160 bar (2320 psi) 32 bar (464 psi) Differential pressure and flow Max. working pressure

Design Weight (without options) Wetted parts materials Seal diaphragm Stainless steel, mat. No. 1.4404/316L, Hastelloy C276, mat. No. 2.4819, Monel, mat. No. 2.4360, tantalum or gold Silicone oil or inert filling liquid (max. 160 bar (2320 psi) with oxygen measurement) Female thread 1/4-18 NPT and flange connection to DIN 19213 with mounting thread M10 or 7/ -20 UNF to EN 61518 16 Supplied through bus 4.5 kg ( 9.9 lb)

Measuring cell filling

Process connection

Power supply UH

Separate 24 V power supply neces- No sary Bus voltage Not Ex With intrinsically-safe operation Current consumption Basic current (max.) Certificates and approvals Classification according to pressure equipment directive (DRGL 97/23/EC) - PN 32/160 (MWP 464/2320) For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) For gases of fluid group 1 and liquids of fluid group 1; complies with basic safety requirements of article 3, paragraph 1 (appendix 1); assigned to category III, conformity evaluation module H by the TV Nord PTB 99 ATEX 2122 Ex II 1/2 G EEx ia/ib IIB/IIC T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +70 C (-40 ... +158 F) temperature class T5; -40 ... +60 C (-40 ... +140 F) temperature class T6 To a certified intrinsically-safe circuit with maximum values: FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W Li = 7 H, Ci = 1.1 nF Planned Planned Planned Planned 12.5 mA 9 ... 32 V 9 ... 24 V

Upper measuring limit

- PN 420 (MWP 6092)

Output Physical bus Measuring accuracy Reference conditions

Explosion protection Intrinsic safety "i" - Identification - Permissible ambient temperature

Error in measurement (including hysteresis and repeatability) - Linear characteristic - Square-root characteristic, flow > 50 % - Square-root characteristic, flow 25 ... 50 % Influence of ambient temperature With -10 ... +60 C (14 ... 140 F) 0.3% (Twice the value with 20-mbar (0.29 psi) nominal measuring range) 0.25% / 10 K ( 0.25% / 18 F) (Twice the value with 20 mbar (0.29 psi) nominal measuring range) IP65 -40 ... +100 C (-40 ... +212 F) 0.075% 0.1% 0.2%

- Connection

With -40 ... -10 C and +60 C ... +85 C (-40 ... +14 and 140 ... 185 F) Rated conditions Degree of protection (to EN 60529) Process temperature Measuring cell with silicone oil filling

- Effective internal inductance/capacitance Explosion-proof "d" Type of protection "n" (zone 2) Explosion protection to FM Explosion protection to CSA

2/94

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series for differential pressure and flow

Dimensional drawings
15 (0.6) 138 (5.4)

2
50 (1.97)
20 (0.8)

approx. 30 (1.2)

100 (3.94) 6 2

80 (3.15)

117 (4.6)

50 (1.97)

3 198 (7.8) approx. 261 (10.3) 96 (3.8) 7 11 52 (2.05)

5 1)

69 (2.7) 77 (3) 2)

1)

9 10

Space for rotation of housing

1 134 (5.27)
+

72 (2.83) 105 (4.1) 1 2 3 4 5 6 7 8 9 10 11 Process connection -18 NPT (EN 61518) Blanking plug Electrical connection - screwed gland M20x1,5 3) or - screwed gland -14 NPT Terminal side Electronics side, digital display (longer overall length for cover with window) Protective cover over keyes Mounting bracket (option) Sealing screw with valve (option) Screw cover safety bracket (only for explosion-proof enclosure, not shown in the drawing) Lateral venting for liquid measurement Lateral venting for gas measurement (suffix H02)

68 (2.7) 120 (4.7)

1) 2) 3)

Allow approx. 20 mm (0.79 inch) thread length in addition 92 mm (3.62 inch) for minimum distance to permit rotation with indicator Not with type of protection "FM + CSA"

SITRANS P pressure transmitters, DS III FF series for differential pressure and flow, dimensional drawing, dimensions in mm (inch)

Siemens FI 01 2005

2/95

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series for differential pressure and flow

2
80 (3.15)

15 (0.6) 69 (2.7)

138 (5.4)

20 (0.8)

50 (1.97)

approx. 30 (1.18) approx.

100 (3.94) 6 2

50 (1.97)

4 1)

3 approx. 217 (8.54)6)

5 1)

77 (3)3)

Space for rotation of housing

ca. 85 (3.35)5)

8 1

67 (2.64)4)

ca. 84,6 (3.33)

1 2 3 4 5 6 7 8 9

Process connection: -18 NPT (EN 61518) Blanking plug Electrical connection: - screwed gland M20x1,5 3) or - screwed gland -14 NPT Terminal side Electronics side, digital display (longer overall length for cover with window) Safety cover over keys Mounting bracket (option) Sealing screw with valve (option) Screw cover safety bracket (only for explosion-proof enclosure, not shown in the drawing)

1) 2) 3) 4) 5) 6)

Allow approx. 20 mm (0.79 inch) thread length in addition Not for type of protection "FM + CSA [is + xp]" 92 mm (3.6 inch) minimum distance to permit rotation with indicator 74 mm (2.9 inch) for PN 420 (MWP 6092 psi) 91 mm (3.6 inch) for PN 420 (MWP 6092 psi) 219 mm (8.62 inch) for PN 420 (MWP 6092 psi)

SITRANS P pressure transmitters, DS III FF series for differential pressure and flow, with process covers for vertical differential pressure lines, dimensional drawing, dimensions in mm (inch)

SITRANS P pressure transmitters, DS III FF series for differential pressure and flow, with process covers for vertical differential pressure lines

2/96

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series for differential pressure and flow
4 6

115 (4.5)

183 (7.2)

77 (3.0)
2

193 (7.6)

SITRANS P pressure transmitters, DS III FF series for differential pressure and flow, with digital indicator beside control keys, dimensional drawing, dimensions in mm (inch)

SITRANS P pressure transmitters, DS III FF series for differential pressure and flow, with digital indicator beside control keys

FIELD TERMINALS

1 2 3 4 5 6 7 8

Process connection, -18 NPT (EN 61 518) Terminal side, analog indicator (optional) External digital indicator (optional) Sealing plug Fixing screw Blanking plug Protective cover for keys Electrical connection

Siemens FI 01 2005

2/97

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series for differential pressure and flow

Selection and Ordering data SITRANS P pressure transmitters for differential pressure and flow DS III FF series, PN 32 / 160 (MWP 464 / 2320 psi) Measuring cell filling Silicone oil Inert liquid1) Measuring cell cleaning Standard Grease-free

Order No. 7MF 4 4 3 5 77777 - 7777

Selection and Ordering data SITRANS P pressure transmitters for differential pressure and flow DS III FF series, PN 32 / 160 (MWP 464 / 2320 psi) Display without (digital display hidden) with visible digital indicator with customer-specific digital indicator (setting as specified, Order code "Y21" required)

Order No. 7MF 4 4 3 5 77777 - 7777

1 3

Rated measuring range PN 32 (MWP 464 psi) 20 mbar 2) (0.29 psi) PN 160 (MWP 2320 psi) 60 mbar 250 mbar 600 mbar 1600 mbar 5000 mbar 30 bar (0.87 psi) (3.63 psi) (8.70 psi) (23.2 psi) (72.5 psi) (435 psi)

1 6 7

B C D E F G H

Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation Sealing plug(s) or sealing screw(s) for the process flanges(s)
1) For oxygen application, add Order code E10 2) Not suitable for connection of remote seal 3) Only together with max. spans 250, 1600, 5000 and 30000 mbar (3.63, 23.2, 72.5 and 435 psi). 4) Without cable gland, with blanking plug 5) With enclosed cable gland EEx ia and blanking plug

Wetted parts materials (stainless steel process flanges) Seal diaphragm Parts of measuring cell Stainless steel Stainless steel Hastelloy Stainless steel Hastelloy Hastelloy Tantalum 3) Tantalum Monel 3) Monel Gold 3) Gold Version as diaphragm seal Process connection Female thread -18 NPT with flange connection Sealing screw opposite process connection - Mounting thread M10 to DIN 19 213 - Mounting thread 7/16-20 UNF to EN 61518 Venting on side of process flanges - Mounting thread M10 to DIN 19 213 - Mounting thread 7/16-20 UNF to EN 61518 Non-wetted parts materials Process flange screws Electronics housing Stainless steel Stainless steel Die-cast aluminium Stainless steel precision casting 2 3 A B C E H L Y

0 2 4 6

Design Standard design International version, English label inscriptions, documentation in 5 languages on CD Explosion protection without with CENELEC, Type of protection: - "Intrinsic safety (EEx ia)" - "Explosion-proof (EEx d)" 4) (planned) - "Intrinsic safety and explosion-proof enclosure (EEx ia + EEx d)" 5) (planned) - "n (zone 2)" (planned) with FM + CSA, Type of protection: - "Intrinsic safety and explosion-proof (is + xp)" 4) (planned) Electrical connection / cable inlet Screwed gland M20x1.5 Screwed gland -14 NPT

1 2

A B D P E NC

B C

2/98

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series for differential pressure and flow
Further designs Please add "-Z" to Order No. and specify Order code. Pressure transmitter with mounting bracket made of: Steel A01 Stainless steel A02 O-rings for process flanges (instead of FPM (Viton)) PTFE (Teflon) FEP (with silicone core, approved for food) FFPM (Kalrez, compound 4079) NBR (Buna N) Sealing screws -18 NPT, with valve in material of process flanges Rating plate inscription (instead of German) English French Spanish Italian English rating plate Pressure units in inH2O or psi Manufacturer's test certificate M to DIN 55350, Part 18 and to ISO 8402 Acceptance test certificate B to EN 10204-3.1B Factory certificate to EN 10204-2.2 Acid gas version to NACE (only together with seal diaphragm made of Hastelloy and process flange screws made of stainless steel) Type of protection IP68 Digital indicator along side the input keys (only together with the devices 7MF4435-....0-.A.6 or -.A.7-Z, Y21) Use on zone 1D / 2D (only together with type of protection "Intrinsic safety (EEx ia)" Use at zone 0 (only together with type of protection "Intrinsic safety (EEx ia)" Oxygen application (max. 160 bar (2320 psi) with oxygen measurement and inert liquid) Interchanging of process connection side Vent on side for gas measurements Stainless steel process flanges for vertical differential pressure lines (not together with K01, K02 and K04) 1) Process flange Hastelloy Monel Stainless steel with PVDF insert max. PN 10 (MWP 145 psi) max. temperature of medium 90 C (194 F) Order code Further designs Please add "-Z" to Order No. and specify Order code. Additional data Measuring point number/identification max. 16 characters, specify in plain text: Y15: ........................................... Measuring point text max. 27 characters, specify in plain text: Y16: ........................................... Setting of pressure indicator in pressure units specify in plain text Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, mA, Torr, ATM or % *) Reference temperature 20 C Only the settings for "Y21" can be made in the factory
1) Not suitable for connection of remote seal

Order code

Y15

Y16

A20 A21 A22 A23 A40

Y21

B11 B12 B13 B14 B21 C11 C12 C14 D07

D12 D27

E01

E02

E10

H01 H02 H03

K01 K02 K04

Siemens FI 01 2005

2/99

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series for differential pressure and flow

Selection and Ordering data SITRANS P pressure transmitters for differential pressure and flow DS III FF series, PN 420 (MWP 6092 psi) Rated measuring range 250 mbar (3.63 psi) 600 mbar (8.70 psi) 1600 mbar (23.2 psi) 5 bar (72.5 psi) 30 bar (435 psi) Wetted parts materials (stainless steel process flanges) Seal diaphragm Parts of measuring cell Stainless steel Hastelloy Gold 1) Stainless steel Stainless steel Gold

Order No. 7MF 4 5 3 5 1 7777 - 7777 D E F G H

Further designs Please add "-Z" to Order No. and specify Order code.

Order code

Pressure transmitter with mounting bracket made of: Steel A01 Stainless steel A02 O-rings for process flanges (instead of FPM (Viton)) PTFE (Teflon) FEP (with silicone core, approved for food) FFPM (Kalrez, compound 4079) NBR (Buna N) Sealing screws -18 NPT, with valve in material of process flanges

A20 A21 A22 A23 A40

A B L

Process connection Female thread -18 NPT with flange connection to DIN 19 213 Sealing screw opposite process connection - Mounting thread M12 to DIN 19 213 - Mounting thread 7/16-20 UNF to EN 61518 Venting on side of process flanges - Mounting thread M12 to DIN 19 213 - Mounting thread 7/16-20 UNF to EN 61518 Non-wetted parts materials Process flange screws Electronics housing Stainless steel Stainless steel Die-cast aluminium Stainless steel precision casting

Rating plate inscription (instead of German) English French Spanish Italian 1 3 5 7 English rating plate Pressure units in inH2O or psi Manufacturer's test certificate M to DIN 55.350, Part 18 and to ISO 8402 Acceptance test certificate B to EN 10 204-3.1B Factory certificate to EN 10.204-2.2 2 3 Acid gas version to NACE (only together with seal diaphragm made of Hastelloy and process flange screws made of stainless steel) 1 2 Type of protection IP68 Digital indicator along side the input keys (only together with the devices 7MF4535-...0.2-.A.6 or -.A.7-Z, Y21) A B D P E NC Use on zone 1D / 2D (only together with type of protection "Intrinsic safety (EEx ia)" Use at zone 0 (only together with type of protection "Intrinsic safety (EEx ia)" Interchanging of process connection side Stainless steel process flanges for vertical differential pressure lines Additional data Measuring point number/identification max. 16 characters, specify in plain text: Y15: ........................................... 1 6 7 Measuring point text max. 27 characters, specify in plain text: Y16: ........................................... Setting of pressure indicator in pressure units specify in plain text (standard setting: mA): Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, mA, Torr, ATM or % *) Reference temperature 20 C Only the settings for "Y21" can be made in the factory.

B11 B12 B13 B14 B21 C11 C12 C14 D07

Design Standard design International version, English label inscriptions, documentation in 5 languages on CD Explosion protection without with CENELEC, Type of protection: - "Intrinsic safety (EEx ia)" - "Explosion-proof (EEx d)" 2) (planned) - "Intrinsic safety and explosion-proof enclosure (EEx ia + EEx d)" 3) (planned) - "n (zone 2)" (planned) with FM + CSA, Type of protection: - "Intrinsic safety and explosion-proof (is + xp)" 2) (planned), max. PN 360 Electrical connection / cable inlet Screwed gland M20x1.5 Screwed gland -14 NPT Display without (digital display hidden) with visible digital indicator with customer-specific digital indicator (setting as specified, Order code "Y21" required) Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation Sealing plug(s) or sealing screw(s) for the process flanges(s)
1) Not together with max. span 600 mbar 2) Without cable gland, with blanking plug 3) With enclosed cable gland EEx ia and blanking plug

D12 D27

E01

E02

H01 H03

B C

Y15

Y16

Y21

2/100

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series for level

Technical specifications
SITRANS P pressure transmitters, DS III FF series for level Input Measured variable Nominal measuring range 250 mbar (3.63 psi) 600 mbar (8.7 psi) 1600 mbar (23.2 psi) 5000 mbar (72.5 psi) Lower measuring limit Measuring cell with silicone oil filling Upper measuring limit Output Physical bus Measuring accuracy Reference conditions Increasing characteristic Start-of-scale value 0 bar Stainless steel seal diaphragm Mounting flange without tube Silicone oil filling Room temperature (25 C (77 F)) -100% of max. span or 30 mbar (0.435 psi) absolute, depending on mounting flange 100% of max. span Digital Foundation Fieldbus signal IEC 61158-2 Level Max. working pressure See "Mounting flange"

Wetted parts materials High-pressure side: Seal diaphragm of mounting flange Stainless steel 316L, Monel 400, mat. No. 2.4360, Hastelloy B2, mat. No. 2.4617, Hastelloy C276, mat. No. 2.4819, Hastelloy C4, mat. No. 2.4610, tantalum, PTFE, ECTFE Silicone oil Flange to DIN and ANSI Female thread -18 NPT and flange connection to DIN 19213 with mounting thread M10 or 7/ -20 UNF to EN 61518 16 Supplied through bus

Measuring cell filling Process connection High-pressure side Low-pressure side

Power supply UH

Separate 24 V power supply neces- No sary Bus voltage Not Ex With intrinsically-safe operation Current consumption Basic current (max.) Certificates and approvals Classification according to pressure equipment directive (DRGL 97/23/EC) For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice) PTB 99 ATEX 2122 Ex II 1/2 G EEx ia/ib IIB/IIC T6 -40 ... +85 C (-40 ... +185 F) temperature class T4; -40 ... +70 C (-40 ... +158 F) temperature class T5; -40 ... +60 C (-40 ... +140 F) temperature class T6 To a certified intrinsically-safe circuit with maximum values: FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W Li = 7 H, Ci = 1.1 nF Planned Planned Planned Planned 12.5 mA 9 ... 32 V 9 ... 24 V

Error in measurement (including hysteresis and repeatability) - Linear characteristic Influence of ambient temperature With -10 ... +60 C (14 ... 140 F) - 250-mbar (3.63 psi) measuring cell - 600-mbar (8.7 psi) measuring cell - 1,600 and 5,000 mbar (23.2 and 72.5 psi) measuring cells With -40 ... -10 C and +60 C ... +85 C (-40 ... +14 and 140 ... 185 F) - 250-mbar (3.63 psi) measuring cell - 600-mbar (8.7 psi) measuring cell - 1,600 and 5,000 mbar (23.2 and 72.5 psi) measuring cells Rated conditions Degree of protection (to EN 60529) Temperature of medium Measuring cell with silicone oil filling - High-pressure side pabs 1bar: -40 ... +175 C (-40 ... +347 F) pabs < 1bar:-40 ... +80 C (-40 ... +176 F) -40 ... +100 C (-40 ... +212 F) IP65 0.4% / 10 K ( 0.4% / 18 F) 0.3% / 10 K ( 0.4% / 18 F) 0.27% / 10 K ( 0.4% / 18 F) 0.7% 0.5% 0.45% 0.15%

Explosion protection Intrinsic safety "i" - Identification - Permissible ambient temperature

- Connection

- Effective internal inductance/capacitance Explosion-proof "d" Type of protection "n" (zone 2) Explosion protection to FM Explosion protection to CSA

Mounting flange Nom. diam. To EN 1092-1 - DN 80 - DN 100 To ASME B16.5 - 3 inch - 4 inch Nom. press. PN 40 PN 16 PN 40 Class 150 Class 300 Class 150 Class 300

- Low-pressure side Design Weight To DIN (pressure transmitter with mounting flange, without tube) To ASME (pressure transmitter with mounting flange, without tube)

11 ... 13 kg (24.2 ... 28.7 lb) 11 ... 18 kg (24.2 ... 39.2 lb)

Siemens FI 01 2005

2/101

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series for level

Dimensional drawings
approx. 30 (1.18) 100 (3.94) 185 6
50 (1.97)

138 (5.4) 69 (2.72)

15 (0.6)

2 165 (6.5) 51) L

77 (3)3)

8 d5 d4 1 54 (2.1) 108 (4.25) Space for rotation of housing b f 1 2 3 4 5 6 8 9 1) 2) 3) Process connection: Low-pressure side -18 NPT (EN 61518) Blanking plug Electrical connection: - screwed gland M20x1,5 2 ) or - screwed gland -14 NPT Terminal side Electronics side, digital display (longer overall length for cover with window) Protective cover over keys Sealing screw with valve (option) Screw cover safety bracket (only for explosion-proof enclosure, not shown in the drawing) Allow approx. 20 mm (0.79 inch) thread length in addition Not with type of protection "FM + CSA [is + xp]" 92 mm (3.62 inch) for minimum distance to permit rotation without indicator nxd 2 D k

6 41)

51)

SITRANS P pressure transmitters, DS III FF series for level, including mounting flange, dimensional drawing, dimensions in mm (inch)

Connection to EN 1092-1
Nom. diam. DN 80 DN 100 Nom. press. PN 40 PN 40 PN 40 b mm 24 20 24 D mm 200 220 235 d mm 90 115 115 d2 mm 18 18 22 d4 mm 138 158 162 d5 mm 76 94 94 dM mm 72 1) 89 89 f mm 2 2 2 k mm 160 180 190 n mm 8 8 8 L mm 0, 50, 100, 150 or 200

Connection to ASME B16.5


Nom. diam. 3 inch Nom. press. lb/sq.in. 150 300 4 inch 150 300 b 0.94 (23.8) 1.12 (28.6) 0.94 (23.8) 1.25 (31.7) D 7.5 (190.5) 8.25 (209.5) 9 (228.5) 10 (254) d2 0.75 (19.0) 0.87 (22.2) 0.75 (19.0) 0.87 (22.2) d4 5 (127) 5 (127) 6,19 (157.2) 6,19 (157.2)
1)

d5 3 (76) 3 (76) 3.69 (94) 3.69 (94)

dM 2.81 1) (72) 2.81 1) (72) 3.5 (89) 3.5 (89)

f 0.06 (1.6) 0.06 (1.6) 0.06 (1.6) 0.06 (1.6)

k 6 (152.4) 6.69 (168.3) 7.5 (190.5) 7.88 (200)

n 4 8 8 8

L inch (mm) 0, 2, 3.94, 5.94 or 7.87 (0, 50, 100, 150 or 200)

inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm) inch (mm)

d: Internal diameter of gasket to DIN 2690 dM: Effective diaphragm diameter

89 mm = 3 inch with tube length L = 0.

2/102

Siemens FI 01 2005

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series for level
Selection and Ordering data SITRANS P pressure transmitters for level DS III FF series Rated measuring range 250 mbar (3.63 psi) 600 mbar (8.70 psi) 1600 mbar (23.2 psi) 5 bar (72.5 psi) Process connection of low-pressure side Female thread -18 NPT with flange connection Mounting thread M10 to DIN 19 213 Mounting thread 7/16-20 UNF to EN 61518 Non-wetted parts materials Process flange screws Electronics housing Stainless steel Stainless steel Die-cast aluminium Stainless steel precision casting 2 3 Order No. 7MF 4 6 3 5 1 7 Y77 - 7777 D E F G Further designs Please add "-Z" to Order No. and specify Order code. O-rings for process flanges on low-pressure side (instead of FPM (Viton)) PTFE (Teflon) FEP (with silicone core, approved for food) FFPM (Kalrez, compound 4079) NBR (Buna N) Sealing screws -18 NPT, with valve in material of process flanges 0 2 Rating plate inscription (instead of German) English French Spanish Italian English rating plate Pressure units in inH2O or psi 1 2 Manufacturer's test certificate M to DIN 55350, Part 18 and to ISO 8402 Acceptance test certificate B to EN 10204-3.1B A B D P E NC Factory certificate to EN 10204-2.2 Type of protection IP68 Use on zone 1D / 2D (only together with type of protection "Intrinsic safety (EEx ia)" Use at zone 0 (only together with type of protection "Intrinsic safety (EEx ia)" Interchanging of process connection side B C 1 6 7 Additional data Measuring point number/identification max. 16 characters, specify in plain text: Y15: ........................................... Measuring point text max. 27 characters, specify in plain text: Y16: ........................................... Setting of pressure indicator in pressure units specify in plain text (standard setting: mA): Y21: mbar, bar, kPa, MPa, psi, ... Note: The following pressure units can be selected: bar, mbar, mm H2O*), inH2O*), ftH2O*), mmHG, inHG, psi, Pa, kPa, MPa, g/cm2, kg/cm2, mA, Torr, ATM or % *) Reference temperature 20 C Only the settings for "Y21" can be made in the factory. Y15 Order code

A20 A21 A22 A23 A40

B11 B12 B13 B14 B21 C11 C12 C14 D12 E01

Design Standard design International version, English label inscriptions, documentation in 5 languages on CD Explosion protection without with CENELEC, Type of protection: - "Intrinsic safety (EEx ia)" - "Explosion-proof (EEx d)" 1) (planned) - "Intrinsic safety and explosion-proof enclosure (EEx ia + EEx d)" 2) (planned) - "n (zone 2)" (planned) with FM + CSA, Type of protection: - "Intrinsic safety and explosion-proof (is + xp)" 1) (planned) Electrical connection / cable inlet Screwed gland M20x1.5 Screwed gland -14 NPT Display without (digital display hidden) with visible digital indicator with customer-specific digital indicator (setting as specified, Order code "Y21" required) Ordering information: 1st order item: Pressure transmitter 7MF4635-... 2nd order item: Mounting flange 7MF4912-... Example of ordering: Item line 1: 7MF4635-1EY22-1AB1 Item line 2: 7MF4912-3GE01 Included in delivery of the device: Brief instructions (Leporello) CD-ROM with detailed documentation Sealing plug(s) or sealing screw(s) for the process flanges(s)
1) Without cable gland, with blanking plug 2) With enclosed cable gland EEx ia and blanking plug

E02

H01

Y16

Y21

Siemens FI 01 2005

2/103

SITRANS P measuring instruments for pressure


Transmitters for pressure, absolute pressure, differential pressure, flow and level
DS III FF series for level

Selection and Ordering data Mounting flange Directly fitted to pressure transmitter SITRANS P (converter part) for level, for DS III FF series Connection to EN 1092-1 Nom. diam. Nom. press. DN 80 PN 40 DN 100 PN 16 PN 40 Connection to ASME B16.5 Nom. diam. Nom. press. 7.62 cm Class 150 Class 300 4 inch Class 150 Class 300 Other version Add Order code and plain text: Nominal diameter: ...; Nominal pressure: ... Wetted parts materials Stainless steel 316L 1) - Coated with PFA - Coated with PTFE - Coated with ECTFE Monel 400, mat. No. 2.4360 Hastelloy B2, mat. No. 2.4617 Hastelloy C276, mat. No. 2.4819 Hastelloy C4, mat. No. 2.4610 Tantalum Other version Add Order code and plain text: Wetted parts materials: ... Sealing face, see "Technical data" Tube length without 50 mm (1.97 inch) 100 mm (3.94 inch) 150 mm (5.90 inch) 200 mm (7.87 inch) Other version: Add Order code and plain text: Tube length: ... Filling liquid Silicone oil M5 Silicone oil M50 High-temperature oil Halocarbon oil (for O2 measurements) Vegetable oil Glycerin / water2) Other version Add Order code and plain text: Filling liquid: ...
1) For vacuum on request 2) Not suitable for use in low-pressure range

Order No. 7MF 4 9 1 2 3 7777 777

Further designs Please add "-Z" to Order No. and specify Order code. Spark arrestor for mounting on zone 0 (including documentation) Manufacturer's test certificate M to DIN 55350, Part 18 and to ISO 8402

Order code A01 C11 C12 V04 Y05

D G H

Acceptance test certificate B to EN 10204-3.1B Vacuum-proof design (for use in low-pressure range) Calculation of span of associated pressure transmitter (enclose filled-in questionnaire with order) Note: Suffix "Y01" required with pressure transmitter J1Y

Q R T U Z

A D E0 F G H J U K Z K1Y

0 1 2 3 4 9

L1Y

1 2 3 4 5 6 9 M1 Y

2/104

Siemens FI 01 2005