High Efficient Conversion of DC Input 48 V to Pure Sine Wave AC Output 100 V

inch 19Rack Mountable


EIA

UL:E203489

Input DC48V

Output AC100V

Stand-alone operation 1kVA 1kW

Parallel operation 2kVA 6kVA 2kW 6kW

Parallel redundant operation 1kVA 5kVA 1kW 5kW

Stand-alone operationType S

Parallel/parallel redundant operationType R

Features
1High Efciency
86.6% (maximum) high efciency. It helps to conserve energy and reduce power charges.

2Increasing the Reliability of Power Supply


The output is a pure sine wave. D11A can perform parallel redundant operation. A redundant conguration of N+1 units with a backup unit increases the reliability of inverter power supply. Totally independent control with high reliability has been realised.

3Bypass Function for security.


Even if a power failure occurs, switching to the AC input bypass circuit keeps power supply stable.

4Simple to Add Units


Up to 6 units (6 kVA) can be added. In redundant operation, a unit can be replaced without the need to shut down its power supply. A unit can be installed easily in the parallel operation cabinet from the front.

The unit can be installed and removed from the front.

Ease of connection.

Example of Output Capacity when Adding Units

Parallel operationN units 2kVA 3kVA 4kVA 5kVA 6kVA

Parallel redundant operationN+1units 1kVA 2kVA 3kVA 4kVA 5kVA

System Block Diagrams

Stand-Alone Operation Conguration (with Bypass Circuit)


Stand-alone Operation Cabinet

Inverter Unit AC bypass input Filter

Transfer signal

External transfer signal

DC input

Filter

DC/DC converter with isolation

DC/DC inverter

Filter

AC output Service receptacles NEMA 5-15R

Stand-Alone Operation Conguration (with No Bypass Circuit)


Stand-alone Operation Cabinet

Inverter Unit Transfer signal External transfer signal

DC input

Filter

DC/DC converter with isolation

DC/DC inverter

Filter

AC output Service receptacles NEMA 5-15R

Parallel Operation Conguration (with Bypass Circuit)


Parallel Operation Cabinet LCD display Monitoring circuit

Inverter Unit AC bypass input Filter

Unit information Transfer signal Transfer signal External transfer signal

DC input

Filter

DC/DC converter with isolation

DC/DC inverter

Filter

AC output

Up to 6 inverter units

Parallel Operation Conguration (with No Bypass Circuit)


Parallel Operation Cabinet LCD display Monitoring circuit

Inverter Unit

Unit information Transfer signal Transfer signal External transfer signal

DC input

Filter

DC/DC converter with isolation

DC/DC inverter

Filter

AC output

Up to 6 inverter units

Inverter Unit Front


Bypass circuit protector LED display

Bypass-inverter selector switch

ON/OFF switch

The rear view of stand alone operation.


Model No. D11A102B011 Serial port for factory used only. (D-Sub 9-pin, male) Transfer signal terminal block AC output terminal block Output LED DC input terminal block

Remote off signal terminal Setting dip switch

AC input connector
IEC-60320-C14

AC output receptacle Ground connection terminal Cable xing base


NEMA 5-15R

Model No. D11A102B011US AC input AC output terminal block terminal block

DC input terminal block

Ground connection terminal

Parallel Operation Cabinet

Front
Simulated fault signal dip switch (for testing) Bypass/power receiving conrmation LED Overload alarm LED Status display LCD Display selection button

Rear

Model No. PD-D11AB16 Serial port for factory used only. (D-Sub 9-pin, male) AC output terminal block AC input terminal block DC input terminal block

Setting dip switch Model No. PD-D11AB16US AC output terminal block

Transfer signal terminal block Ground connection terminal DC input AC input terminal block terminal block

The photos show a unit with bypass circuit. An AC input connector and AC input terminal block are not present for inverters with no bypass circuit.
The inverter units are products for parallel operation.

Specication
Inverter Unit
Item Model No. Rating capacity Bypass circuit Rating Cooling system Life of device Acoustic noise Environment AC Input Standard or Performance D11A102B011 D11A102B011US D11A102B001 1kVA(1kW)

Notes D11A102B001US Parallel operationDC/AC inverter Apparent power and active power

DC Output

Continuous Forced Air 15years 55dBMax. 5 to 40 5 to 85 Rated Voltage 48 Variation Range 40.5V to 57V Max. Input Currency 29A Input Feedback Noise 2mV Number of phase / wire Single-phase / 2 wire Voltage 100V/120V 2% Voltage regulation Frequency 50 60Hz 0.5%(1% at parallel operation) Frequency Regulation Distortion factor of voltage waveform 8 Max. Transit Voltage Variation Rated voltage 10% Response time 100Max. Load Power Factor 1 105 100V/120V 100V15% 120V15% 12.5A 10.4A 20A E203489 E203489 UL /CE UL /CE VCCI Class-AIEC62040-2: 2005 CISPR22: 2005 Class-A FCC Part 15 sub B Class A CISPR24: 1997/A1: 2001/A2: 2002 IEC62040-2: 2005

1 meter (39.4 inch) in height at the front of the unit, A characteristic A short time0 to 50 (72 hours continuation/Annual less than 15 days) A short time5 to 90 (72 hours continuation/Annual less than 15 days)

During rated output Evaluated value (at rated input and output with a resistance load) Sine waveDependent on the DIP switch setting1 Dependent on the DIP switch setting 2 During rated output 0100% load variation Variation range 0.7 (lag) to 1.0Load power factor should not exceed 1 kVA at 0.7 (lag). Sine waveDependent on the DIP switch setting

AC Input

Overcurrent Protection Rated Voltage Variation Range Max. Input Currency

During rated output During rated output UL 60950-1 , IEC 60950-1: 2005 2nd Edition

Capacity of circuit protector Safety Standard S a f e t y E M C emission Standard Immunity

1: When you change the DIP switch settings, be sure to do so before the DC power is received. Even if you change the settings after the DC power is received, the changes will not become effective. 2: When the AC input power is received, the inverter output performs synchronization operation in the frequency variation range of 5% of the AC input so the frequency regulation is 5% of the rated frequency

Model numbers of inverter units with stand-alone operation cabinet D11A102B011S (For stand-alone unit with bypass circuit)D11A102B011SUS (For stand-alone unit with bypass circuit/UL certied unit) D11A102B001S (For stand-alone unit with no bypass circuit)D11A102B001SUS (For stand-alone unit with no bypass circuit/UL certied unit) Two service receptacles (NEMA5-15R)* equip as a standard (on the rear of the unit), and AC cable (with NEMA5-15P plug) equip as a standard (for standalone unit with bypass circuit only) Other specications are the same as those of the above inverter unit, except that the input circuit protector for bypass input is 15 A.

Electrical Characteristics of the Cabinet


With Bypass Circuit
Cabinet model No.
PD-D11AB13 PD-D11AB13US PD-D11AB15 PD-D11AB15US

UL certied units are not equipped with service receptacles.

PD-D11AB16 PD-D11AB16US

Number of inverter units Device configuration N-unit configuration N+1-unit configuration N-unit configuration N+1-unit configuration N-unit configuration N+1-unit configuration N-unit configuration N+1-unit configuration N-unit configuration N+1-unit configuration DC Input Nominal voltage Voltage range to Rated input current Maximum input current Nominal voltage AC Input 100V or 120V Voltage range 85V to 115V or 102V to138V Maximum input current AC Output It dependent on the device setting Nominal voltage It dependent on the inverter unit Voltage range or to to Rated output current Rated output

With No Bypass Circuit


Cabinet model No.
PD-D11AB03 PD-D11AB03US PD-D11AB05 PD-D11AB05US PD-D11AB06 PD-D11AB06US

Number of inverter units Device configuration N-unit configuration N+1-unit configuration N-unit configuration N+1-unit configuration N-unit configuration N+1-unit configuration N-unit configuration N+1-unit configuration N-unit configuration N+1-unit configuration Nominal voltage DC Input Voltage range to Rated input current Maximum input current It dependent on the device setting Nominal voltage AC Input It dependent on the inverter unit Voltage range or to to Rated output current Rated output NoteThe cabinet can be used without connecting to a commercial power source or AC power supply. In such a case, the unit operates at a frequency preset in the inverter. When connecting the cabinet to an AC power supply, a 3.5mA per unit of leakage current will occur. In parallel operation, total leakage current must be multiplied by the number of connected units, so please pay attention to the breaking current for the breaker in the distribution board.

Dimensions
Inverter with Stand-Alone Operation Cabinet
Model No. D11A102B011S

sizemm

Inverter with Stand-Alone Operation Cabinet


Model No. D11A102B011SUS

sizemm

Fixing brackets for the rear of the rack


8.5 13

Fixing brackets for the rear of the rack


AWG 84

M4

M5
600 430

600

AWG126

AWG146

SANUPS
D11A

SANUPS
D11A

31.75

31.75

43.5

465 480

465 480

When these brackets are used to x the inverter unit in the rack, special rack support rails are not required.

Parallel Operation Cabinet (for 3 Inverter Units) sizemm


Model No. PD-D11AB13US AWG124 M8

Parallel Operation Cabinet (for 5 Inverter Units) sizemm


Model No. PD-D11AB15US AWG124 M8

23

23

38

43.5

430

450

450

Model No. PD-D11AB13

Model No. PD-D11AB15

18

M6

M8

23

18

M6

M8

23

410

440

440

88.9 75.9

88.9 75.9
465 480

177

410

465 480

EIA standard size 6.1

Parallel Operation Cabinet (for 6 Inverter Units) sizemm


Model No. PD-D11AB16US

Inverter Unit
10

sizemm

AWG124

M8

23

18

M6

M8

23

410

340.6

Model No. PD-D11AB16

38

480 465

440

Support Rails for Parallel Operation Cabinet (Option)sizemm


To use these support rails, 1U space is required under the unit to be mounted.

43.5

88.9 75.9

RMD11AA00 depth adjustable range(345500) RMD11AA01 depth adjustable range(500850)

12.6 310.5

31 50 44

319

120.4

465 480

EIA standard size 6.1

EIA universal pitch 31.8


18

The dimensions show a unit with bypass circuit. An AC input connector and AC input terminal block are not present for inverters with no bypass circuit.

EIA standard size 6.1

76.1

12.6 264.8

38

Eco Products
Sanyo Denki's ECO PRODUCTS are designed with the concept of lessening impact on the environment in the process from product development to waste.The product units and packaging materials are designed for reduced environmental impact.We have established our own assessment criteria on the environmental impacts applicable to all processes,ranging from design to manufacture.Those products that satisfy the criteria are accredited as ECO PRODUCTS.

Notes when investigating use of this product in your applications


Before starting installation, assembling and use, read the Operation Manual carefully and use the product correctly in your applications. When you are going to use this product in the following application, the special considerations are required for operation, running, maintenance and control. Be sure to consult with our company as a part of your investigations. (a) Medical equipment and other equipment that are related directly to human life. (b) Train or elevator that can give injury to human body. (c) Socially and publicly important computer systems. (d) And other equipment that are related to safety of human life and that can affect severe effects on maintenance of public functions. For the applications that undergo vibration such as vehicles, ships and transportation facilities, please consult with our company. Never modify this product or give additional processing to this product. For the installation andmaintenance work, please consult with our company or with specialized company. For any inquiry or consultation, please contact our sales representative.

http://www.sanyodenki.com
1-15-1, Kita-Otsuka, Toshima-ku, Tokyo 170-8451, Japan 468 Amapola Avenue Torrance, CA 90501 U.S.A. P .A. Paris Nord II, 48 Alle des Erables-VILLEPINTE, BP .57286, F-95958 ROISSY CDG Cedex, France Frankfurter Strasse 63-69, 65760 Eschborn, Germany Phone: +81 3 3917 5157

Phone: +1 310 783 5400 Phone: +33 1 48 63 26 61

Phone: +49 6196 76113 0

9F 5-2, Sunwha-dong Jung-gu Seoul, 100-130, Korea

Phone: +82 2 773 5623

Rm2108-2109, Bldg A, Far East International Plaza, No.319, Xianxia Rd., Shanghai, 200051, China

Phone: +86 21 6235 1107

Room 1208, 12F , No.96 Chung Shan N, Rd., Sec.2, Taipei 104, Taiwan, R.O.C.

Phone: +886 2 2511 3938

Room 2305, 23/F , South Tower, Concordia Plaza, 1 Science Museum Rd., TST East, Kowloon, Hong Kong

Phone: +852 2312 6250

10, Hoe Chiang Road, #14-03A/04, Keppel Towers, Singapore 089315

Phone: +65 6223 1071

The names of companies and/or their products specied in this catalog are the trade names, and/or trademarks and/or registered trademarks of such respective companies. *Remarks : Specications Are SubjectTo Change Without Notice. CATALOG No.953-1 10.9