Power factor
What? Why? What does it Cost?
The Power factor is a complicated concept to grasp and is often over complicated by people trying to explain a subject they don't fully understand.
If you use electricity in your factory, dairy, mill, shop, then you have a POWER FACTOR and it effects the cost of the electricity you use. The lower the power factor the higher the cost. Power factor range from 0.0 to 1.0 (normally). You should do something about a power factor less than 0.94.......................Its costing your business money !
What we call "Electricity" is actually made up of three parts. Real Power (Kw, Mw), Apparent Power (Kva), Reactive Power (Kvar).
1 of 7
01/04/2013 07:06
http://www.cip.ukcentre.com/Power Factor.htm
knowledge)
These 3 parts form the "Power Triangle" Real Power (Kw) is the part of the triangle which results in real work done, in the form of heat energy. This is the power that drives the world. Apparent Power is that portion of the power triangle that we actually measure. And then....there is Reactive Power....which serves no real function at all. The phase angle between Real Power and Apparent Power in the power triangle is identified as the angle "q" which is the Greek letter "THETA". The size, in degrees, of that angle determines the size of the Reactive Power leg of the triangle. The cosine of that angle is called Power factor or pf and the value of the pf is inversely proportional to the amount of reactive power you are generating. What this means is that the smaller the angle q, the less Reactive Power you are making and the greater your Power Factor is.
For the Engineering manager and electricians and those interested in this sort of thing
This section is reproduced with the permission of the author David Gibson of SPLat Controls, makers of embeddable programmable logic controllers (PLCs) for OEMs Power factor is one of those subjects about which there seems to be a great deal of confusion and many misconceptions. The culprit is the the assertion that power factor = cos(Phi), Phi being the phase shift between voltage and current. While this is true under certain ideal conditions, there are many real-world instances where it is quite incorrect. This article will give you a basic introduction into power factor, and explain why cos(Phi) is not the whole answer.
2 of 7
01/04/2013 07:06
http://www.cip.ukcentre.com/Power Factor.htm
The Basics
If you connect a sinusoidal voltage source to a resistor, current will flow, power will be dissipated in the resistor and the resistor will heat up. The current is given by I=V/R and the power is given by P=I*V or P=V/R. The voltage and current are the rms values.
Figure 1 shows the waveforms for this experiment. The top blue waveform is sinusoidal voltage. The voltage is 1V rms giving a peak voltage of 1.414V, The red waveform is the current. It is 1A rms, 1.414A peak. (If you are awake you will deduce that the resistor is 1Ohm). The green waveform is the instantaneous power, i.e. the product of voltage and current from moment to moment. For example, at the left hand vertical line the voltage and current are both at their peaks, so the power is 1.414V * 1.414A = 2W Fig. 1 At the right hand vertical line we are at the negative peaks of voltage and current. Here the instantaneous power is -1.414V * -1.414A = 2W i.e. the product of two negatives giving a positive. It should not take too much imagination to see that the average of the power waveform is 1W.
3 of 7
01/04/2013 07:06
http://www.cip.ukcentre.com/Power Factor.htm
Suppose we now replace the resistor with an inductor. The current in an inductor lags exactly 90 behind the applied voltage (at least for a perfect inductor, which we assume we have). This is illustrated by the red current waveform in figure 2. Now look at the instantaneous power waveform. Between the vertical lines we have a negative voltage being multiplied by a positive current, giving a negative power. Negative Power!? What does that mean? What the negative power means is that during that part of the cycle, energy is actually transferred from the inductor (load) back into the voltage source. An inductor is an energy storage device. The energy stored in an inductor is IL. Fig. 2
If the load is a perfect inductor the negative power will exactly cancel the positive power, and we get a net power dissipation of zero. However, the voltage is still 1V and the current is still 1A, giving a product which is definitely not zero. Our supposed 1W of input is not producing 1W of heat. This is commonly called "wattless watts". The correct term is Volt-Amps or VA. We say the circuit is drawing 1VA but consuming no power.
4 of 7
01/04/2013 07:06
http://www.cip.ukcentre.com/Power Factor.htm
The same voltage as before has been applied to both inductor and resistor. Hence, each one must be drawing the same current as before, with the resistor drawing 1A in phase with the supply voltage and the inductor drawing 1A at a phase lagging the voltage by 90. The overall current (Fig 3) is the moment to moment summation of these two currents. It can be shown graphically or mathematically that the total current has a phase exactly half way between the two individual currents (i.e. lagging the voltage by 45) and a magnitude of 1.414A (for unequal component currents the composite is the hypotenuse of a right angle triangle drawn with the lengths of the two other sides equal to the two components). Fig. 3 So, where does this leave us with our power factor calculation? The input voltage is 1V and the current 1.414A, so the input VA is 1.414VA. The power consumed is 1W, the same as in the resistor-only case. Hence, the power factor is 1W/1.414VA = 0.707. It just so happens that the cosine of the phase angle (Phi) between voltage and current is also 0.707 (cos45=0.707). This is informal proof of the generally accepted assertion that PF=Cos(Phi). We will now show that that is not always the case.
Imagine now that we make a load which always draws exactly 1A, with the same polarity as the voltage but with a magnitude independent of the voltage. (How make such a load is merely an engineering problem.) With this load the voltage is 1V RMS, and the current is 1A RMS, giving an input of 1VA. The average power in the green waveform is 0.9W (1.414*2/pi). And yet, there is no negative power (the load cannot store power and return it to the supply like an inductor can) and the load current is seemingly in phase with the voltage. The power factor of this circuit is 0.9, yet there is no phase shift. What gives?!
5 of 7
01/04/2013 07:06
http://www.cip.ukcentre.com/Power Factor.htm
Fig. 4 The answer lies in the shape of the current waveform, which in this instance is a square wave. A square wave can be shown to be the summation of a whole number of waveforms at different frequencies, each frequency being a multiple of the fundamental. (If this is unfamiliar to you, you can download a spreadsheet which illustrates the generation of a squarewave as the summation of many sinewaves. This ZIP file unzips to a Lotus WK1 file, which can be imported into virtually every known DOS and Windows spreadsheet. HARMONIC.ZIP, 14K.) It can be shown that in a squarewave with amplitude 1V (2Vpp) the amplitude of the fundamental frequency is 0.9V. Hence where harmonics are present in the load current (but not in the voltage) the harmonic currents contribute nothing to the power in the load but do reduce the power factor. Is such a situation likely to occur in the real world? Yes it is. In fact, the only loads on the mains which are not likely to introduce harmonic currents are purely resistive loads such as heaters and incandescent lamps.
6 of 7
01/04/2013 07:06
http://www.cip.ukcentre.com/Power Factor.htm
inputs and then measures the phase angle between them. In the Model 40, PF is the true ratio between VA and power with all harmonics factored in. We are aware that other instruments exist which are equally correct in their operation, and will list them if brought to our attention. One such instrument is a setup we made ourselves with a PC plug-in A to D card and some custom designed input circuitry. Our results correlate very well to the Fluke Model 40, giving a good feeling of confidence in both.