Sharjah International Airport New Runway at 250m Separation Civil Works & Airside Systems Package
Client :
Sharjah Airport Authority PO Box 8 Sharjah, UAE
MSS : SN-003
Date 04.04.2013
Attached Documents : Including method statement + Site test reports + Risk Assessment + Catalougue
Other Remarks :
Engineer's Reply : Approved Approved as Noted Rejected Submission Not Required Resubmission Required (Tick as appropriate)
Remarks :
Date :
INDEX
METHOD STATEMENT FOR PRE-COMMISSIONING OF POWER CABLES TEST REPORTS RISK ASSESSMENT ELSEWEDY ELECTRIC POWER CABLE CATALOGUE
Client
Consultant
Main Contractor
Electrical Subcontractor
SIA
Halcrow
LANE-NCTC JV
SCAN Electromechanical
SHARJAH INTERNATIONAL AIRPORT NEW RUNWAY at 250m SEPARATION Method Statement for 11kV Cables Pre-Commissioning tests
0 Rev
01.04.2013 Date
Previous status
Halcrow Approved by
INDEX 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. Scope Purpose References Responsibilities HSE Requirements Test Equipment & Tools Requirement Test Procedure Supervisory Requirements Program Waste Management And Housekeeping Environmental Issues In Case Of Emergency Records Attachments
Page 1
Rev-0
MSS-001-00
Client
Consultant
Main Contractor
Electrical Subcontractor
SIA
Halcrow
LANE-NCTC JV
SCAN Electromechanical
SHARJAH INTERNATIONAL AIRPORT NEW RUNWAY at 250m SEPARATION Method Statement for 11kV Cables Pre-Commissioning tests
1. Scope
The purpose of this method statement is to identify The responsibility of each project and site personnel The safety requirements, The safe working procedures and
In order to perform Pre-Commissioning tests on 11kV Cables and associated works while fulfilling the safety and quality requirements.
2. Purpose
The purpose of this procedure is to define the inspection, testing method, and criteria for Pre-Commissioning tests on 11kV Cables to confirm as per requirements of project specification & SEWA Regulations to achieve completion of specified scope of work.
3. References
Manufacturer Instructions/ Manual. Approved Material Submittal. Approved Shop drawings Schematic Drawings/Diagrams
4. Responsibilities
Project Manager has the overall responsibility to ensure timely completion of the project and all construction activities executed safely and to the prescribed quality requirement thought out planning, coordination, and supervision of work.
MSS-001-00
Rev-0
Page 2
Client
Consultant
Main Contractor
Electrical Subcontractor
SIA
Halcrow
LANE-NCTC JV
SCAN Electromechanical
SHARJAH INTERNATIONAL AIRPORT NEW RUNWAY at 250m SEPARATION Method Statement for 11kV Cables Pre-Commissioning tests
Project Coordinator shall assist Project Manager in any site duties in terms of coordination, execution and supervision of work. Shall ensure all approved drawing, specifications and instructions are available for the working party. Site Engineer is responsible for closely monitoring the site activities designated to him. Ensure all instructions are followed and all necessary work permits and safety documents are in place prior to the commencement of work. Shall keep daily record of the work, collect required activity information from the site supervisor and prepare respective report/ record for Engineer /client review and approval. HSE Officer is responsible for ensuring all construction activities comply with the project safety plan and client safety requirements. Shall formulate safety policy, identify and resolve safety issues, prepare safety inspection report, prepare risk assessment; conduct safety briefing and safety induction training. Shall coordination with the site engineer and subcontractors concerning the safe working procedures at site. Site Supervisor is responsible for the execution of work activities in a safely manner and strict compliance to the prescribed drawings and instructions. Skilled/Non Skilled manpower has a general responsibility to the safety at work and to keep the site tidy.
5. HSE REQUIREMENTS
All applicable work permits supported with necessary document shall be secured prior to the commencement of work. Site meeting shall be held prior to the commencement of work to establish the intentions of all parties involved. Tool box talk shall be carried out and necessary safety information shall be circulated and implemented. Ensure that the expiry date on the material is well within the date of use. There is an
inherent safety problem in testing the Cables that requires care and planning by the user of the test. Operator should wear Rubber Protective Gloves while handling connections. Recommended to use a Rubber Safety Mat while operating the test set.
MSS-001-00
Rev-0
Page 3
Client
Consultant
Main Contractor
Electrical Subcontractor
SIA
Halcrow
LANE-NCTC JV
SCAN Electromechanical
SHARJAH INTERNATIONAL AIRPORT NEW RUNWAY at 250m SEPARATION Method Statement for 11kV Cables Pre-Commissioning tests
The Test Instruments and Test Leads should be maintained in a safe Condition. Adopt safest Test methods not to create Danger either for Operator or for the other Persons. Be Ensure that the Working area is Fully Protected during the HV test.
Key work members shall be given a method statement briefing, detailing the scope of works, emergency procedure, dangers, local hospitals etc. The HSE officer shall ensure that all work is carried out safely & that all plant / materials are sited and stored in a safe manner to avoid damage to persons or property. A risk assessment shall be conducted and safe manual handling techniques will be employed. No individual shall handle weights greater than 25kg. Mechanical assistance will be provided where appropriate if the materials or equipment cannot be safely moved. PPE shall he used by all operatives on site. These include the following PPE; Hard hat Safety Boots Hi-Visibility clothing Safety glasses or visor (where required) Cloves (where required) Ear protection (where required) Face mask (where required) High voltage Hand Gloves Care shall be taken to prevent dust at site. Care shall be taken to protect all existing structure and facilities.
MSS-001-00
Rev-0
Page 4
Client
Consultant
Main Contractor
Electrical Subcontractor
SIA
Halcrow
LANE-NCTC JV
SCAN Electromechanical
SHARJAH INTERNATIONAL AIRPORT NEW RUNWAY at 250m SEPARATION Method Statement for 11kV Cables Pre-Commissioning tests
7. Test Procedure
PHYSICAL INSPECTION Checking of leveling and alignment of installed equipment. Checking of tightness of connections and fastenings, and use of proper tools. Checking proper grounding. Checking of continuity and agreement with wiring drawings of all current carrying connections, including bus connections and wiring Checking of physical integrity of major equipment and all instruments and components. Checking of proper equipment and cable identification. Checking of correct circuit fusing. Checking against the equipment specification for compliance of ratings of all major components, i.e. bus, circuit breaker, fuses, relays, etc. Checking of primary and secondary circuit electrical connections for tightness.
MSS-001-00
Rev-0
Page 5
Client
Consultant
Main Contractor
Electrical Subcontractor
SIA
Halcrow
LANE-NCTC JV
SCAN Electromechanical
SHARJAH INTERNATIONAL AIRPORT NEW RUNWAY at 250m SEPARATION Method Statement for 11kV Cables Pre-Commissioning tests
PHASE IDENTIFICATION TEST Phase identification check with 500 V Megger, The Positive terminal of Megger is connected to one end of cable and the Negative terminal of Megger is connected to Ground. Another end of Cable is also connected to Ground. Now Megger is Switched ON, and it does not read the value. Then remove the Ground from another end of Cable, now the Megger reads some value. Again make the Ground, the Megger does not read the value. Similarly other Phases are also checked in this manner.
INSULATION RESISTANCE MEASUREMENT The Positive pole of the Megger is connected to the RED Phase of the Cable and the Negative pole to the YELLOW and BLUE Phase together with the Earth. The reading is taken after 1 Minute or when the readings are stabilized.
MSS-001-00
Rev-0
Page 6
Client
Consultant
Main Contractor
Electrical Subcontractor
SIA
Halcrow
LANE-NCTC JV
SCAN Electromechanical
SHARJAH INTERNATIONAL AIRPORT NEW RUNWAY at 250m SEPARATION Method Statement for 11kV Cables Pre-Commissioning tests
Connect the control Cable between Test Leads and Earthing Cable, connect the Earthing Cable between earthing grid to control unit and HV unit.
Connect the HV test lead into the DC HV Kit output connector. Now connect the HV cable shield to Earth. Connect the other end of HV test lead to the Verify all the Connections and then Turn ON main switch. Now select the Range/Scale as per requirement, gradually increase the steps in such a way that charging current stabilize in each step till you reach the value Record the steps as shown in the test report. Carry out the Insulation Resistance test after HV test & record the value
MSS-001-00
Rev-0
Page 7
Client
Consultant
Main Contractor
Electrical Subcontractor
SIA
Halcrow
LANE-NCTC JV
SCAN Electromechanical
SHARJAH INTERNATIONAL AIRPORT NEW RUNWAY at 250m SEPARATION Method Statement for 11kV Cables Pre-Commissioning tests
8. SUPERVISORY REQUIREMENTS
Work shall be supervised by SCAN competent person, who will be the document holder and will be on site during tile work period.
9. PROGRAM
Site activities are coordinated via regular consultation with LANE/Halcrow/SEWA and other suppliers representative as applicable.
MSS-001-00
Rev-0
Page 8
Client
Consultant
Main Contractor
Electrical Subcontractor
SIA
Halcrow
LANE-NCTC JV
SCAN Electromechanical
SHARJAH INTERNATIONAL AIRPORT NEW RUNWAY at 250m SEPARATION Method Statement for 11kV Cables Pre-Commissioning tests
All accident, incident and near miss events must be reported to the Project Manager/ Coordinator who will conduct investigation. Preventive measure shall be identified to avoid recurrence. The following telephone number may find useful in case of emergency; Ambulance department: 998 Police : 999 Civil Defense (FIRE): 997 Electricity: 991 Water: 992 Sharjah Municipality: 993
Nearest Hospital (Kuwaiti Hospital) (06-5242111) Safety Officer (Mr. Khalid) 055- 4109060
It is required by law to report any fatal accident, accident involving injury, worker injure from work for more than 3 days, and certain work related diseases to the Labor Department of UAE.
13. Records
Inspection request duly signed by the Consultant/Main and Subcontractor. Signed-off Start up Commissioning reports certified by Specialist Supplier.
14. ATTACHMENTS
Test format for the activity. Risk Assessment and Check list sheet
MSS-001-00
Rev-0
Page 9
TEST REPORTS
Client
Main Contractor
Consultant
SS1
SS2
Page 1 of 2 Date :
Electrical Subcontractor
Bay No :
HUMIDITY
CIRCUIT
Length
RED-1
YELLOW-1
BLUE-1
Remote end earthed Red: earthed Yellow: open Blue: open Red: open Yellow: earthed Blue: open Red: open Yellow: open Blue: earthed
Meter reading
Status
Test equipment Used Instrument Name / model Instrument Serial No. Calibration Due Date
Tested Carried-out By SCAN/LNJV Test Witnessed & Approved by HALCROW Test Witnessed & Approved by SEWA
Client
Main Contractor
Consultant
SS1
SS2
Page 2 of 2 Date :
Electrical Subcontractor
Bay No :
CALCULATION:- 11kv Cable- 11 (3) = 6.35 =6.35 4 (Uo) =25.40 KV RMS Voltage
PHASE
REMARKS
R Y B
Remarks:
Test equipment Used Instrument Name / model Instrument Serial No. Calibration Due Date
Tested Carried-out By SCAN/LNJV Test Witnessed & Approved by HALCROW Test Witnessed & Approved by SEWA
RISK ASSESSMENT
Client : SAA
Consultant : Halcrow
Electrical Subcontractor
Department/ Section : MV Section Assessment Date: 08/12/2012 01/04/2012 Activity : Medium Voltage 11kV 11kV Switchgear tests. Cable Pre-commissioning HiPOT Tests Assessor HAZARD Zaheer Ahamed HAZARD EFFECT Severity Liklihood Risk Rtg Electric Shocks, Burns
Ref. No.
Residual Rsik after the control measures are in place Severity Liklihood Risk rtg
Injury to Person
Fatal Injury
All Electrical Equipments / Circuit are Tags / Display boards shall be to be treated alive and no work is to placed whereever necessasary be carried out on any part of Barricade the area & electrical equipment except for work equipment under test. permit availed circuit. Check for secure grounding Usage of High voltage hand gloves. connection Discharge rod connected Properly to Check high voltage handgloves Secure Grounding System for any damage before use & Barricade the area
Severity of Harm Fatal or Majar Injury Injury or illness Other injuries Signature
Severity Index Likelihood 3 Harm is certain or near certain 2 Harm is likely to occur 1 Harm is unlikely
Probability Index 3 2 1
Severity Index 1 2 3
1 L L M
2 L M H
3 M H H
2010
Power Cables
Group History
Rapid Growth in Manufacturing Plant.. 2010 Due to the diversification in the company portfolio the company name has changed from Elsewedy Cables to Elsewedy Electric. Elsewedy Cables KSA, Doha Cables, Elsewedy Cables Ethiopia, Elsewedy Cables Yemen. Elsewedy cables Algeria, ECMEI, Iskraemeco, Elsewedy Electric Zambia, SWEG. Elsewedy Electric Syria, United Wires, Elsewedy Cables Egypt. Elsewedy Electric Ghana. Elsewedy Cables Syria. Itlasimea Elsewedy ( Currently Elsewedy SEDCO for Petroleum Services). Sudanese Egyptian Electrical Industries. Giad Elsewedy Cables. United Metals Sedco. United Industries Elastimold. Egytech Sedplast. Arab cables.
2009 2008 2007 2006 2005 2004 2003 2002 1998 1997 1996 1984
Telecommunication, Transformers, Wind energy generation, Energy measurement & management, and Engineering & Contracting. The business has started as a trader in electrical equipments, moving on to a distributor for the only cables manufacturer, and has grown to be the leading in the field. Owing to a successful growth rate year after year and aligning with the expansion Strategy of the company our name has been changed from ELSEWEDY CABLES to ELSEWEDY ELECTRIC
New companies every year with proven management track record of managing growth.
Group Structure
United Metals
Sedplast
Electrical Products
United Wires
Egytech
United Industries
Elsewedy Transformers Egypt Sudanese Egyptian Electrical Industries Elsewedy Electrical Syria Elsewedy Electrical Zambia Elsewedy Electrical Nigeria
Giad Elsewedy Cables Elsewedy Cables Syria Elsewedy Cables KSA Elsewedy Cables Algeria Elsewedy Cables Ethiopia
Transformers
Index
1 General Information & Technical Data
page
07
Elsewedy Electric
Doha Cables
Libya Cables
Elsewedy Power Projects PVT Ltd. India
4
Slovenia
75
Iskraemeco
Energy Measurement & Management
Iskramerilne naprave
Elsewedy for Wind Energy Generation (SWEG)
Malaysia
India
7 8 9
10
Type Test Approvals Certifications Elsewedy Cables Catalogues Elsewedy Cables Contacts
Egypt
Telecom
D d
2S d
r
18In
D d
Operating Voltage
(from 6/10 kV up to 18/30 kV)
Cable Construction
1. Conductor
Stranded, round and compacted Copper or Aluminium conductors, according to IEC 60228 - class 2.
2. Conductor Screen
An extruded layer of semi conducting material applied over the conductor as voltage stress control layer.
3. Insulation
An extruded layer of cross linked polyethylene (XLPE) is applied over the inner semi conductor with thickness as specified in IEC 60502.
4. Insulation Screen
An extruded layer of strippable or firmly bonded to the insulation. Conductor screen, XLPE insulation and insulation screen are applied at the same time using triple head extruder.
5. Metallic Screen
a. Copper Tape: an annealed Copper tape is applied helically with a suitable overlap. b. Copper Wire: helically applied and binded with a Copper tape to achieve electrical contact
6. Assembly
In case of three core cables, cores are assembled together with suitable lay length, non-hygroscopic filler is applied during assembly to fill spaces between cores then wrapped with suitable binder tape.
7. Bedding
in case of armoured cables an extruded layer of PVC or MDPE or LLDPE is applied as bedding.
8. Armouring
a. Steel Tape: double layers of steel tapes are applied helically. b. Steel Wire: galvanized steel wires are applied helically.
9. Sheath
An extruded layer of PVC is applied with thickness as specified in IEC 60502.
Option
Lead Sheath: Upon request a layer of lead is extruded over the bedding layer.
Copper Tape Binder Conductor Inner Semiconductor Insulation Outer Semiconductor Copper Wire Screen Bedding Sheath
Cu / PVC Insulated
Insulation Outer Semiconductor Copper Wire Screen Bedding AL Wire Armouring Sheath
6/10 (12) kV
Single & Three Cores Copper Conductors XLPE Insulated and PVC Sheathed Description
o o o
o o
o o
o o o
Conductor
C Copper A Aluminium D Copper+Swelling Powder B Tinned Copper
Code
12 13 14 15 16 17
mm2
25 35 50 70 95 120 150 185
Code mm2
20 30 40 50 60 70 80 81 240 300 400 500 630 800 1000 1200
Stranded circular compacted Copper conductor, semiconducting layer as conductor screen, XLPE insulated, semiconducting layer as non metallic insulation screen, Copper tape or wire as metallic insulation screen, three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape and PVC sheathed. Cables are produced according to IEC 60502 or BS 6622.
Application
These cables are generally suitable for direct burial or for installation on trays or in ducts.
Insulation
X XLPE
18 19
Nominal Max. Conductor Resistance Cross Operating Product - Code Sectional DC at AC at Capacitance Area 20 C 90 C
Current Rating Laid in Ground Flat A Laid in Free Air Trefoil A Flat A Approx. Approx. Overall Weight Diameter mm kg/km
mm2
/km
/km
f/km
mh/km mh/km
Voltage
A 1.8/3 kV B 3.6/6 kV 2 6/10 kV 3 8.7/15 kV 4 12/20 kV 5 18/30 kV (3.6) kV (7.2) kV (12) (24) (36) kV kV kV (17.5) kV
CX2-T101-U12 CX2-T101-U13 CX2-T101-U14 CX2-T101-U15 CX2-T101-U16 CX2-T101-U17 CX2-T101-U18 CX2-T101-U19 CX2-T101-U20 CX2-T101-U30 CX2-T101-U40 CX2-T101-U50 CX2-T101-U60 CX2-T101-U70 CX2-T101-U80 25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000 0.7270 0.5240 0.3870 0.2680 0.1930 0.1530 0.1240 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221 0.0176 0.9271 0.6683 0.4937 0.3420 0.2465 0.1956 0.1588 0.1272 0.0973 0.0781 0.0618 0.0490 0.0391 0.0319 0.0234 0.200 0.224 0.251 0.291 0.316 0.345 0.374 0.409 0.456 0.512 0.565 0.635 0.704 0.795 0.983
Armouring
U Unarmoured L Lead N Lead Alloy A Steel Tape B Aluminium Tape W Steel Wire X Aluminium Wire C Lead+Steel Tape D Lead+Steel Wire G Galvanized Steel Tape O Steel Wire+Copper Wire H Steel Wire+Copper Wire+Lead T Lead+Aluminium Wire P Lead+Aluminium Tape
Conductor Type
T Stranded
Sheathing
1 Single Sheath A PVC+Flame Retardant X HDPE Z PVC+Anti Termite L LSHF M PVC+2.5 % Carbon Black S PVC+Flame Retardant +Low Smoke B PVC+Flame Retardant +Anti Termite
No. of Cores
01 03 Single Core Three Cores
CX2-T103-U20 CX2-T103-U30
This data is applicable for 6.35 / 11 kV cables. The ampacity for single core sizes 800 & 1000mm2 was based on a single end bonding. The above data is approximate and subjected to manufacturing tolerance.
76
77
6/10 (12) kV
6/10 (12) kV
Single & Three Cores Aluminium Conductors, XLPE Insulated and PVC Sheathed Description
Stranded circular compacted Aluminium conductor, semiconducting layer as conductor screen, XLPE insulated, semiconducting layer as non metallic insulation screen, Copper tape or wire as metallic insulation screen, three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape and PVC sheathed. Cables are produced according to IEC 60502 or BS 6622.
Three Cores Copper or Aluminium Conductors, XLPE Insulated, Steel Tape Armoured and PVC Sheathed Description
Stranded circular compacted Copper or Aluminium conductor, semiconducting layer as conductor screen, XLPE insulated, semiconducting layer as non metallic insulation screen, Copper tape or wire as metallic insulation screen, three cores assembled together with non hygroscopic polypropylene fillers, wrapped with binder tape, covered with a layer of PVC compound as a bedding, steel tape armoured and PVC sheathed. Cables are produced according to IEC 60502.
Application
These cables are generally suitable for direct burial or for installation on trays or in ducts.
Application
These cables are generally suitable for direct burial or for installation on trays or in ducts.
Nominal Max. Conductor Resistance Cross Operating Sectional Product - Code DC at AC at Capacitance Area 20 C 90 C
Current Rating Trefoil Flat Trefoil Flat Laid in Ground Laid in Free Air
mm2
/km
/km
f/km
mh/km mh/km
mm2
mh/km
This data is applicable for 6.35 / 11 kV cables The above data is approximate and subjected to manufacturing tolerance.
This data is applicable for 6.35 / 11 kV cables The ampacity for single core sizes 800 & 1000mm2 was based on a single end bonding. The above data is approximate and subjected to manufacturing tolerance.
78
79
6/10 (12) kV
8.7/15 (17.5) kV
Three Cores Copper or Aluminium Conductors, XLPE Insulated, Steel Wire Armoured and PVC Sheathed Description
Stranded circular compacted Copper or Aluminium conductor, semiconducting layer as conductor screen, XLPE insulated, semiconducting layer as non metallic insulation screen,Copper tape or wire as metallic insulation screen, three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape, covered with a layer of PVC compound as a bedding, steel wire armoured and PVC sheathed. Cables are produced according to IEC 60502 or BS 6622.
Single & Three Cores Copper Conductors, XLPE Insulated and PVC Sheathed Description
Stranded circular compacted Copper conductor, semiconducting layer as conductor screen, XLPE insulated, semiconducting layer as non metallic insulation screen, Copper tape or wire as metallic insulation screen, three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape and PVC sheathed. Cables are produced according to IEC 60502 or BS 6622.
Application
These cables are generally suitable for direct burial or for installation on trays or in ducts.
Application
These cables are generally suitable for direct burial or for installation on trays or in ducts.
Product - Code
Nominal Max. Conductor Resistance Cross Operating Product - Code Sectional DC at AC at Capacitance Area 20 C 90 C
Current Rating Trefoil Flat Laid in Ground Trefoil Flat Laid in Free Air Approx. Approx. Overall Weight Diameter mm kg/km
mm2
mh/km
mm2
/km
/km
f/km
mh/km mh/km
25 35 50 70 95 120 150 185 240 300 400 500 630 800 1000
0.7270 0.5240 0.3870 0.2680 0.1930 0.1530 0.1240 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283 0.0221 0.0176
0.9271 0.6683 0.4937 0.3420 0.2465 0.1956 0.1588 0.1272 0.0973 0.0781 0.0618 0.0490 0.0391 0.0319 0.0234
0.165 0.183 0.204 0.234 0.253 0.275 0.297 0.324 0.360 0.402 0.442 0.495 0.548 0.616 0.759
0.469 0.446 0.412 0.387 0.373 0.361 0.351 0.338 0.324 0.313 0.304 0.293 0.285 0.277 0.274
0.654 0.631 0.597 0.572 0.558 0.546 0.536 0.522 0.509 0.498 0.489 0.478 0.470 0.462 0.459
139 166 197 242 287 326 364 411 475 535 599 674 752 869 1084
145 174 206 252 299 339 375 422 484 542 591 659 728 979 1188
143 174 209 262 317 366 416 478 565 650 745 859 981 1160 1515
173 211 255 319 384 443 498 570 669 765 853 975 1103 1480 1864
22.0 23.3 24.7 26.5 27.7 29.3 30.9 32.8 35.4 38.0 41.0 44.6 48.3 53.2 63.6
729 846 999 1230 1479 1761 2111 2512 3083 3718 4661 5808 7127 9010 11341
The ampacity for single core sizes 800 & 1000mm2 was based on a single end bonding. The above data is approximate and subjected to manufacturing tolerance.
80
81
8.7/15 (17.5) kV
8.7/15 (17.5) kV
Single & Three Cores Aluminium Conductors, XLPE Insulated and PVC Sheathed Description
Stranded circular compacted Aluminium conductor, semiconducting layer as conductor screen, XLPE insulated, semiconducting layer as non metallic insulation screen, Copper tape or wire as metallic insulation screen, three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape and PVC sheathed. Cables are produced according to IEC 60502 or BS 6622.
Three Cores Copper or Aluminium Conductors, XLPE Insulated, Steel Tape Armoured and PVC Sheathed Description
Stranded circular compacted Copper or Aluminium conductor, semiconducting layer as conductor screen, XLPE insulated, semiconducting layer as non metallic insulation screen, Copper tape or wire as metallic insulation screen, three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape, covered with a layer of PVC compound as a bedding, steel tape armoured and PVC sheathed. Cables are produced according to IEC 60502.
Application
These cables are generally suitable for direct burial or for installation on trays or in ducts.
Application
These cables are generally suitable for direct burial or for installation on trays or in ducts.
Nominal Max. Conductor Resistance Cross Operating Sectional Product - Code DC at AC at Capacitance Area 20 C 90 C
Current Rating Laid in Ground Trefoil Flat Laid in Free Air Trefoil Flat Approx. Approx. Overall Weight Diameter Product - Code mm kg/km Nominal Cross Sectional Area Max. Conductor Resistance DC at 20 C /km AC at 90 C /km Currentm Rating Inductance Laid in ground A Laid in free air A Approx. Overall Diameter mm
mm2
/km
/km
f/km
mh/km mh/km
mm2
mh/km
The ampacity for single core sizes 800 & 1000mm2 was based on a single end bonding. The above data is approximate and subjected to manufacturing tolerance.
82
83
8.7/15 (17.5) kV
12/20 (24) kV
Three Cores Copper or Aluminium XLPE Insulated, Steel Wire Armoured and PVC Sheathed Description
Stranded circular compacted Copper or Aluminium conductor, semiconducting layer as conductor screen, XLPE insulated, semiconducting layer as non metallic insulation screen, Copper tape or wire as metallic insulation screen, three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape, covered with a layer of PVC compound as a bedding, steel wire armoured and PVC sheathed. Cables are produced according to IEC 60502 or BS 6622.
Single & Three Cores Copper Conductors, XLPE Insulated and PVC Sheathed Description
Stranded circular compacted Copper conductor, semiconducting layer as conductor screen, XLPE insulated, semiconducting layer as non metallic insulation screen, Copper tape or wire as metallic insulation screen, three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape and PVC sheathed. Cables are produced according to IEC 60502 or BS 6622.
Application
These cables are generally suitable for direct burial or for installation on trays or in ducts.
Application
These cables are generally suitable for direct burial or for installation on trays or in ducts.
Product - Code
Nominal Max. Conductor Resistance Cross Operating Product - Code Sectional DC at AC at Capacitance Area 20 C 90 C
Current Rating Laid in Ground Trefoil Flat Laid in Free Air Trefoil Flat Approx. Approx. Overall Weight Diameter mm kg/km
mm2
/km
/km
f/km
mh/km mh/km
mm2
mh/km
CX4-T101-U80
This data is applicable for 12.7/22kV cables. The ampacity for single core sizes 800 & 1000mm2 was based on a single end bonding. The above data is approximate and subjected to manufacturing tolerance.
84
85
12/20 (24) kV
12/20 (24) kV
Single & Three Cores Aluminium Conductors, XLPE Insulated and PVC Sheathed Description
Stranded circular compacted Aluminium conductor, semiconducting layer as conductor screen, XLPE insulated, semiconducting layer as non metallic insulation screen, Copper tape or wire as metallic insulation screen, three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape and PVC sheathed. Cables are produced according to IEC 60502 or BS 6622.
Three Cores Copper or Aluminium Conductors, XLPE Insulated, Steel Tape Armoured and PVC Sheathed Description
Stranded circular compacted Copper or Aluminium conductor, semiconducting layer as conductor screen, XLPE insulated, semiconducting layer as non metallic insulation screen, Copper tape or wire as metallic insulation screen, three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape, covered with a layer of PVC compound as a bedding, steel tape armoured and PVC sheathed. Cables are produced according to IEC 60502.
Application
These cables are generally suitable for direct burial or for installation on trays or in ducts.
Application
These cables are generally suitable for direct burial or for installation on trays or in ducts.
Nominal Max. Conductor Resistance Cross Operating Sectional Product - Code DC at AC at Capacitance Area 20 C 90 C
Current Rating Laid in Ground Trefoil Flat Laid in Free Air Trefoil Flat Approx. Approx. Overall Weight Diameter Product - Code mm kg/km Nominal Cross Sectional Area Max. Conductor Resistance DC at 20 C /km AC at 90 C /km Currentm Rating Inductance Laid in ground A Laid in free air A Approx. Overall Diameter mm
mm2
/km
/km
f/km
mh/km mh/km
mm2
mh/km
This data is applicable for 12.7/22kV cables. The above data is approximate and subjected to manufacturing tolerance.
This data is applicable for 12.7/22kV cables. The ampacity for single core sizes 800 & 1000mm2 was based on a single end bonding. The above data is approximate and subjected to manufacturing tolerance.
86
12/20 (24) kV
18/30 (36) kV
Three Cores Copper or Aluminium Conductors, XLPE Insulated, Steel Wire Armoured and PVC Sheathed Description
Stranded circular compacted Copper or Aluminium conductor, semiconducting layer as conductor screen, XLPE insulated, semiconducting layer as non metallic insulation screen, Copper tape or wire as metallic insulation screen, three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape, covered with a layer of PVC compound as a bedding, steel wire armoured and PVC sheathed. Cables are produced according to IEC 60502 or BS 6622.
Single & Three Cores Copper Conductors, XLPE Insulated and PVC Sheathed Description
Stranded circular compacted Copper conductor, semiconducting layer as conductor screen, XLPE insulated, semiconducting layer as non metallic insulation screen, Copper tape or wire as metallic insulation screen, three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape and PVC sheathed. Cables are produced according to IEC 60502 or BS 6622.
Application
These cables are generally suitable for direct burial or for installation on trays or in ducts.
Application
These cables are generally suitable for direct burial or for installation on trays or in ducts.
Product - Code
Nominal Max. Conductor Resistance Cross Operating Product - Code Sectional DC at AC at Capacitance Area 20 C 90 C
Current Rating Laid in Ground Trefoil Flat Laid in Free Air Trefoil Flat Approx. Approx. Overall Weight Diameter mm kg/km
mm2
mh/km
mm2
/km
/km
f/km
mh/km mh/km
This data is applicable for 12.7/22kV cables. The above data is approximate and subjected to manufacturing tolerance.
This data is applicable for 19/33 kV cables The ampacity for single core sizes 800 & 1000mm2 was based on a single end bonding. The above data is approximate and subjected to manufacturing tolerance.
88
89
18/30 (36) kV
18/30 (36) kV
Single & Three Cores Aluminium Conductors, XLPE Insulated and PVC Sheathed Description
Stranded circular compacted Aluminium conductor, semiconducting layer as conductor screen, XLPE insulated, semiconducting layer as non metallic insulation screen, Copper tape or wire as metallic insulation screen, three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape and PVC sheathed. Cables are produced according to IEC 60502 or BS 6622.
Three Cores Copper or Aluminium Conductors, XLPE Insulated, Steel Tape Armoured and PVC Sheathed Description
Stranded circular compacted Copper or Aluminium conductor, semiconducting layer as conductor screen, XLPE insulated, semiconducting layer as non metallic insulation screen, Copper tape or wire as metallic insulation screen, three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape, covered with a layer of PVC compound as a bedding, steel Tape armoured and PVC sheathed. Cables are produced according to IEC 60502.
Application
These cables are generally suitable for direct burial or for installation on trays or in ducts.
Application
These cables are generally suitable for direct burial or for installation on trays or in ducts.
Nominal Max. Conductor Resistance Cross Operating Sectional Product - Code DC at AC at Capacitance Area 20 C 90 C
Current Rating Laid in Ground Trefoil Flat Laid in Free Air Trefoil Flat Approx. Approx. Overall Weight Diameter mm kg/km Product - Code
mm2
/km
/km
f/km
mh/km mh/km
mm2
mh/km
This data is applicable for 19/33 kV cables The above data is approximate and subjected to manufacturing tolerance.
This data is applicable for 19/33 kV cables The ampacity for single core sizes 800 & 1000mm2 was based on a single end bonding. The above data is approximate and subjected to manufacturing tolerance.
90
91
18/30 (36) kV
Three Cores Copper or Aluminium Conductors, XLPE Insulated, Steel Wire Armoured and PVC Sheathed Description
Stranded circular compacted Copper or Aluminium conductor, semiconducting layer as conductor screen, XLPE insulated, semiconducting layer as non metallic insulation screen, Copper tape or wire as metallic insulation screen, three cores assembled together with non hygroscopic Polypropylene fillers, wrapped with binder tape, covered with a layer of PVC compound as a bedding, steel wire armoured and PVC sheathed. Cables are produced according to IEC 60502 or BS 6622.
Application
These cables are generally suitable for direct burial or for installation on trays or in ducts.
Product - Code
mm2
mh/km
This data is applicable for 19/33 kV cables The above data is approximate and subjected to manufacturing tolerance.
92
108
109
Conductor
Insulation
PVC PVC - F.R XLPE
Copper Screen
kA
Metallic Sheath
Lead Lead Alloy Aluminum
Armour
Steel Aluminum Tape Tape Galvanized Tape Wire Galvanized Wire
110
111
Systems Certificates
Products Certificates
112
113
Products Certificates
114
115
Electrical Products
ELSEWEDY SEDCO (Cables Accessories) 13 El Obour Buildings, Salah Salem st. Nasr City, Cairo Egypt Tel: + (202) 24023683 22626763 Fax: + (202) 22639155 Email: sedco@elsewedy.com SEDCO for petroleum services (Explosion Proof Equipment) 10th of Ramadan City Zone B2 # 10 El Sharkia - Egypt Tel: + (2015)411141 Fax: + (2015) 411142 Email: sedco-petroleum@elsewedy.com Egyptian Company fo Manufacturing Electrical Insulaturs (ECMEI) Insulators Industrial Zone A3, 10th of Ramadan City, Egypt Tel: + (2015) 412560 Fax: + (2015) 411255 Email: ecmei@elsewedy.com ELSEWEDY Electric Ghana (Fiber Glass Poles) 9, Light Industrial Area No. A/36/2B Tema Ghana. P.O. Box PMB 187 TEMA - Ghana Tel: + 022311101 311102 Fax: + 022311103 Email: Ghana-fiberglass@elsewedy.com
International Operations
ELSEWEDY CABLES Jordan & Iraq 38, Abd Allah Ghosha st., Al Husseiny complex, Amman, Jordan 3rd Floor, office #311 Tel: +962 776418166 Fax: +962 65350066 Email: info-jordan@elsewedy.com ELSEWEDY CABLES Southern Africa Ltd. E263 POST DOT NET BLANTYRE, MALAWI KRISTWICK, ALONG CHIPEMBERE HIGHWAY, BLANTYRE, MALAWI TEL: +265 1 878 878 Fax: +2651 878 788 Email: info-malawi@elsewedy.com ELSEWEDY CABLES Kuwait Beneid Al Qar, Block 6, St. 65, Derwaza Tower, Office 22. P.O. Box 403 Safat 13005 Kuwait Tel: +965 22 418 524/6 Fax: +965 22 418 525 Email: info-kuwait@elsewedy.com ELSEWEDY CABLES UAE Business Avenue Building Sheikh Rashid Road P.O. BOX 90395 Dubai, UAE 5th Floor Office no. 511 Tel: +971 42955905 Fax: +971 42955135 Email: info-uae@elsewedy.com ELSEWEDY Electric Equatorial Guinea Park of Africa, Caracolas, Beside Military Camp, Malabo, Equatorial Guinea. Tel: +240 096569 Cell: +240 532 550 Fax: +240 096569 Email: info-guinea@elsewedy.com ELSEWEDY CABLES Libya Gergarsh Hay El Andalous, Tripoli Libya Tel: +218 91 325 96 25 Tel: +218 91 365 53 11 Email: info-libya@elsewedy.com ELSEWEDY CABLES Bahrain Cell:(+973) 39741298 Email: info-bahrain@elsewedy.com ELSEWEDY CABLES Oman Al Hamd House, Sultan Qabos Service road, Alkhuwair, Mascat - P.O Box 573, PC. 115 Tel: +96824486615 Fax: + 96824475765 Email: info.oman@elsewedy.com ELSEWEDY CABLES India Office no. 412, A Wing, Sagartech Plaza, Andheri-kuria Road, Andheri (East) Mumbai 400072, India Tel: +91 22 65283183 / 66790130 Fax: +91 22 66790131 Email: info-india@elsewedy.com
Telecommunication
United Industries (Fiber Optics & Copper Telecom Cables & Accessories FTTX) 68 El Tayran st. Nasr City, Cairo Egypt Tel: + (202) 22603196 24148370 24013606 Fax: + (202) 22620473 Email: uic-comcore@elsewedy.com
Transformers
ELSEWEDY Transformers 3, Kafr El Dawar St.,El Korba, Heliopolis, Cairo, Egypt. Tel: +202 2417 6710 - 2417 6711 Fax: +202 2417 5782 E-mail: sales.transformers@elsewedy.com ELSEWEDY ELECTRIC Syria (Transformers) Damascus - Adra Industrial zone - P.O. Box 12874 Tel: +963 11 585 0291 Fax: +963115850290 Email: Syria-transformers@elsewedy.com, Elsewedy-sales@elsewedy.com ELSEWEDY ELECTRIC Zambia (Transformers) Chilanga road off Kabwe road,Plot F/416A/D2 - P.O. Box 70058 Ndola, Zambia. Tel: +260 (212) 650120/1 Email: Zambia-transformers@elsewedy.com ELSEWEDY ELECTRIC Nigeria (Transformers) 10 Bauchi Close Agbara Estate, Ogun State, Lagos Nigeria Tel: + (234) 70 62939595 / + (234) 80 57922904 Email: Nigeria-transformers@elsewedy.com Sudanese Egypt Electrical Industries SUDATRAF Piece # 55/8 Square 7 Ind. Zone Khartoum Bahary - Sudan Tel: +249 185 313418 Fax: +249 185 313394 Email: info@sudatraf.com
116