Introduction

Table of Contents
Introduction ..................................................................................... 2
Legend ............................................................................................ 2
Nomenclature .................................................................................. 2
Design Features .............................................................................. 3
General Features ............................................................................ 3
Main Component Features .............................................................. 4-5
Optional Features ............................................................................ 6
Compressor Starting & Capacity Control Steps .............................. 7
Installation & Application Data ......................................................... 8-11
Selection Procedure ........................................................................ 11
Specifications .................................................................................. 12-13
Capacity Ratings ............................................................................. 14-17
Electrical Data ................................................................................. 18-20
Typical Wiring Diagram ................................................................... 20
Dimensional Data ............................................................................ 21-23

SKM ACUX Series Air Cooled


Condensing Units are the specifiers
choice for commercial and industrial
applications where highly efficient
outdoor Condensing Units need to be
matched to an indoor central station
air handling unit or coil to get
maximum performance advantages of
a split system with a low initial cost.
SKM ACUX Series provides efficient
operation; a wide range of design
flexibility coupled with a packaged
concept requiring the least amount of
on-site work.

Legend
The following legends are used
throughout this manual:
cfm ....... Cubic feet per minute
EER ...... Energy Efficiency Ratio
Hz ......... Hertz
KW ....... Kilowatts
kg ......... Kilogram
lbs ......... Pounds
L/S ........ Liters per second

MBH ..... BTUH x 1000


Ph ......... Phase
PI .......... Power Input of Compressor
SST ...... Saturated Suction Temp.
TR ........ Tons of Refrigeration
V ........... Volts

Nomenclature
ACU X-5036YM
Factory
Modification Code

Air Cooled
Condensing Unit
X Series
(Semi-Hermetic Discus Compressor)
Power Supply
Frequency

SKM ACUX Series Air Cooled


Condensing Unit have been designed
for use on systems with indoor units
connected to remote outdoor located
Condensing Units. The performance
of SKM Air Cooled Condensing Units
has been proved in various
installations like residential buildings,
hotels, motels, schools, etc.

5 : 50 Hz
6 : 60 Hz

Nominal Capacity (TR)

Power Supply Code


Y:
P:
R:
E:
T:

380-415V/3Ph/50Hz
440V/3Ph/50Hz
380V/3Ph/60Hz
460V/3Ph/60Hz
220V/3Ph/60Hz

ACUX Series Condensing Units


Page 2

SKM ACUX Series Condensing Units


are available in 50 Hz and 60 Hz
versions ranging in capacity from 7.0
TR to 63.7 TR (24.6 to 224.2 kW) at 50 Hz
and 8.2 TR to 74.3 TR (28.8 to 261.5 kW)
at
60 Hz using R-134a refirgerant.
SKM offers ACUX Series Condensing
Units that are built in the UAE and are
specifically designed to meet the
requirements of the Gulf's severe
climatic conditions.
The ACUX Series features, as standard,
operating range of ambient
temperatures from 50F (10C) to
125F (52C), a low design ITD
(temperature difference between
refrigerant condensing temperatures
and ambient air temperature), high
efficiency Discus compressors - all
of which translate into lower operating
cost and longer life of the unit.
SKM ACUX Series Air Cooled
Condensing Units are constructed and
rated in accordance with and
conforming to ARI standard 365/94.

Design Features
SKM ACUX Series Air Cooled
Condensing Units have been designed
to provide:
Low Operating Cost : One of the
lowest KW/Ton in the industry.
Low Installation Cost : On site
installation and hook-up is inexpensive.
More Value for Money : Our standard
unit includes what many competitos
offer as options. Low voltage control
circuit transformer for a 24 volt
thermostat, fan starter interlocks, etc
are all standards.
Low Maintenance Costs : Selection
of components is for Gulf
environments. Maximim 12 fpi on
condenser coil. Low design ITD. High
efficiency compressors. Powder
coated cabinet panels. TEAO
condenser fan motors, class 'F'
insulated. All ensure minimal
maintenance and very low incidence
of spare parts requirement, thereby
reducung long term maintenance
costs.

General Features
High Energy Efficiency Ratio
(EER)

most competitors use, on average, higher


fin density condenser surfaces, SKM
keeping Gulf dust storms in mind and
the general level of available
maintenance, restricts itself to only 12
FPI or 144 fins per foot (max 2.1 mm fin
spacing). This ensures long life of the
condenser and the least possibility of
blockages on condenser.

SKM ACUX Series Air Cooled


Condensing Units use exclusively high
efficiency semi-hermetic Copeland
discus compressors having the unique
Discus valve design.

Compare:

The EER of ACUX Series Condensing


Unit is substantially higher compared to
units using equivalent conventional
compressors. EER rating for F-Series
Condensing Units at ARI conditions are
listed in Tables 6 & 7 for specifications.

SKM exclusively uses only 12 FPI.

Compare the average EER's of SKM units


versus industry leaders.
The high operating efficiencies of the
ACUX Series Condensing Units is
achieved by the use of the Copeland
Discus compressors and the efficient
use of condenser coil surface area and
air flow across condenser coil. While

Greater Design Flexibility : With 26


models to choose from in 50Hz and an
equal number in 60Hz, there will always
be a selection that closely matches
the designed and required capacity.
Guaranted Performance : Each
condensing unit undergoesrigorous
QA/QC procedure during manufacture
and each unit is factory tested at
various stages of manufacture before
despatch, thereby guaranteeing
trouble free performance after
installation and commissioning.
Safety of Operation : Each unit comes
protected with all safety requirements
including fuses, overloads, pressure
switches etc., necessary for safe
operation of the unit.
All of the above design features, as
further detailed ahead make the SKM
ACUX Series Air Cooled Condensing
Units
Buitl in the Gulf...for the world.

ACUX Series Condensing Units


Page 3

Competitor M uses 12, 14 & 15 FPI


Competitor T uses 12, 13 & 14 FPI
Competitor C uses 11.7, 12.4, 14.6, 15,
15.8 and 16.5 FPI

Wide Operating Range


SKM ACUX Series Condensing Units
are designed to operate at a wide range
of ambient temperatures from 50oF
(10oC), or lower if optional low ambient
operation kit is included, to 125oF
(52oC), or as high as 131oF (55oC) if
optional high ambient operation kit is
included. All ACUX Series units will
start and operate within these ranges.

Main
Features

Component

Compressors

Condensers
Condenser coils are manufactured from
seamless copper tubes mechanically
bonded to aluminium fins to ensure
optimum heat transfer. All coils are tested
against leakage by air pressure of 450
psig (3100 KPa) under water. All standard
coils are 3 or 4 rows/12 FPI, 3/8" (9.5mm)
O.D. tubes. An integral subcooling circuit
is provided to increase the Condensing
Unit cooling capacity, without additional
operating costs.
The condenser fans are individually
statically and dynamically balanced at
the factory. Complete fan assembly is
provided with suitable acrylic coated fan
guard made from heavy gauge
galvanised wire.
All AUCX Series Condensing Units utilize
these specially selected and
manufactured components to ensure
these units are :
Built in the Gulf...for the world.

Compressors used in ACUX Series Air


Cooled Condensing Units are fully
accessible, semi-hermetic, reciprocating
type. They are equipped with an oil sight
glass, suction and discharge service
valves and crankcase heater.
All compressors are refrigerant gas
cooled and equipped with an oil pressure
lubrication system. The oil pump working
in either direction is protected by an oil
screen and a valve provided for the fitting
of an oil pressure gauge. For protection,
all compressors are equipped with preset
internal relief valve between suction and
discharge sides for safety protection.
The compressors are provided with
vibration isolator mounting springs under
the compressors skid and therefore,
external to Condensing Units, AVMs
may be necessary only for critical
applications.
The compressor motors have inherent
thermal protection. This is in addition to
other standard safety and protection
controls. Compressors conform to DIN
standards.
SKM uses the Copeland Discus series
hi-efficiency compressors exclusively for
its ACUX Series.

The sub-cooling effectively eliminates


the possibility of liquid flashing,
increases unit efficiency and minimizes
operating costs.
For different application requirements,
other optional condenser fin materials
are available:

Copper fins
Copper fins electro-tinned after
manufacturing
PreCoated Aluminum fins

Condensers Fans & Motors


The condenser fans are propeller type,
aluminium alloy blades, directly driven
by electric motors. Motors are Totally
Enclosed Air Over (TEAO) six pole with
class F insulation and minimum IP55
protection. The TEAO and class F
insulation features ensure long life and
are unique to SKM. The motors are
factory wired, using special silicon wires
specially selected for high ambients
operation, to Condensing Unit control
panel where the motor contactors are
located to control the operation of these
motors.

ACUX Series Condensing Units


Page 4

Casing/Structure
Designed for ease of handling and low
costs to install. The SKM ACUX Series Air
Cooled Condensing Units are factory
assembled and mounted on a rugged
steel channel base.
The unit casing used in ACUX Series
condensing units is made of zinc coated
galvanized steel sheets conforming to
JIS-G 3302 and ASTM A653 which is
phosphatized and baked after an
electrostatic powder coat of approx. 60
microns.
This finish and coating can pass a 1000
hour in 5 % salt spray testing at 95F
(35C) and 95% relative humidity as per
ASTM B117-95.
The entire assembly comes complete
with lifting holes to ease rigging for
installation. Access panels are provided
for easy service and maintenance.
Options available include hot dipped
galvanized base frame and structural
members. Aluminium or stainless steel
panels available, on request, as options.

Refrigerant Charge

Electrical Control Panel

The ACUX
Series Air Cooled
Condensing Units come with a holding
charge of
R - 134a from the factory.

The unit mounted IP-54 control panel


enclosure comprises all starting, operating and safety controls. A dead front panel
cover screwed onto the enclosure prevents unauthorized personnel from tampering
with controls. Safety and operating controls are arranged for easy accessibility.

Piping Connections

All wiring is sized as per NEC regulations; Articles 430 & 440. Wiring is fully ferruled
enabling ease of proper identification.

The ACUX
Series Air Cooled
Condensing Units piping connections
come, as standard, terminated with
sealed and soldered copper pipe ends.

The control panel is factory wired for 220-240V 1 PH 50/60Hz control power supply.
An additional built-in 24 volts fused low voltage transformer, at no extra cost, allows
the user to easily hook up his 24 volts room thermostat without taking any burden of
arranging and installing a low voltage transformer while commissioning the unit.

Normal installation would require the


cutting off (using roller-type tube cutters)
of the ends prior to connections being
resoldered and connected to the field
supplied refrigerant pipework.

The following are the standard components used in all F-Series Air Cooled Condensing
Units.

Refrigerant Pipework
The ACUX Series Condensing Units
come complete with all internal piping,
using ACR grade copper tubing, between
compressor and condenser.
Refrigeration specialities are available
as an option (specify option CRSP)for
field connections. Each circuit of an
ACUX Series Condensing Unit, when
ordered with this option, would be
supplied with a correctly sized
thermostatic expansion valve, liquid line
solenoid valve with a suitable coil, liquid
line sight glass and moisture indicator,
and a filter drier having flared or soldered
ends isolatable with one shut-off valve
or, if specified with option CXFV, with a
shut-off valve on each side of the filter
drier.

Individual compressor and condenser fan motor contactors.


Fuses for condenser fans per NEC Article 430.
Individual condenser fan over current protection
Anti-recycle timer to prevent rapid cycling and short cycling of compressors
Low pressure safety switch, high pressure safety switch, oil failure switch one per
compressor
Head pressure control by fan cycling for low ambient operation down to 50oF
(10oC).
Control disconnect toggle switch
Control circuit fuses
24 volts low voltage fused transformer for user supplied and installed room
thermostat
Volt free contact or terminals for indoor fan motor starter interlock
Power and control circuit terminal blocks.

Legend
C
CF
CR

CS
CT
F
OL

Contactor
Control Fuse
Control Relay

Control Switch
Control Terminal Block
Power Circuit Fuse
Overload Relay

ACUX Series Condensing Units


Page 5

PTB
TDR
TFR

Power Terminal Block


Time Delay Relay
Transformer

Optional Features
Factory Installed
Microprocessor Based Control (MCP)
The controller consists of a display unit
and relay boards. The display is mounted
in a space / room and the relay card / s are
mounted in the unit control panel. Both
are connected by a 6 - core cable
(supplied by others) through a set of
connectors. Power contactors, pressure
switches and control circuit MCBs and
terminals are wired to the control board
in the unit control panel. The sensor is
directly connected to the relay board and
is placed in the return air path. Main
features of the controls are :

Built in anti recycle timer to prevent


compressor short cycling.
Auto lead-lag of the compressor.
General alarm volt free contact is
available for any remote indication
use.
Remote START/STOP of the unit is
available through a volt free contact.
Maintenance alarm available at user
specified intervals.
Cooling & heating, both functions
can be provided by the controller.

Following main indications are available on


the controller display :

Digital indication of return air / room


temperature.
High & low pressure alarm
indications.
Evaporator fan motor trip indication.

Low Ambient Operation Kit


(LAO)
For operation down to 25 o F (-4 oC)
ambient. For operation down to 40F
(4C) ambient only, additional fan cycling
only is provided. For operation at lower
than normal Gulf conditions (special
applications). Specify desired operating
temperatures for this option at enquiry/
order.
High Ambient Operation Kit (HAO)
For operation at reduced load, at ambient
temperature between 125oF (52oC) and
131oF (55oC) maximum.
Alternative Condenser Material
Made of copper tubes and alternative fin
material and/or protective coating.

For Copper Fins specify FC


For Copper Fins electrotinned
specify FCT
For Pre Coated Aluminum Fins
specify FAP

Galvanised Frame
(GFB)
Hot dip galvanised after manufacture,
steel frame and base.
Condenser Coil Guard (CGP/CGG)
Coil wire mesh guard, in painted or
galvanised finish for condensers.
Recommended on ground level
installations where coil needs to be
protected against vandalism.
Part Winding Start
(PWS)
Where specifically required by local
codes compressors may be with Part
Winding Start. Refer Table1 (page 7)
for details of models with PWS
compressors as standard and where
available as an option.
Unload Start Kit
(USK)
To minimise the compressor starting
current at initial startup or anticipated
high load at start-up. Useful for
applications where unit will be used
infrequently during peak summer
months. PWS option must be ordered
together with this option.
Hot Gas Muffler
(HGM)
To minimize compressor noise and
dampen discharge gas pulsations.

for ACUX Series models rated for 440V/


3PH/50Hz or 460V/3PH/60Hz only. When
ordering for these voltages this option
must be ordered.
Pressure Gauges
(SDG)
Suction, discharge and oil pressure
indication of each refrigerant circuit.
IP55 Control Panel
(ICP)
The standard control panel replaced by
an IP55 enclosure for extra protection
against the extreme weather conditions.
Volt Free Contact
(VFC)
An additional volt free contact for field
installed Liquid Line Solenoid Valve, if
required for pump-down control. Please
specify at enquiry/order option VFC along
with option CRSP, if required. Note: Volt
free contact for fan interlock is standard
with ACUX Series.
Modifications for DEWA Code (DVM)

To meet DEWA regulations. This option


is available for Dubai, U.A.E. only.

Options for Field Installations


Anti-vibration mounts
(CAVM)
Recommended for roof mounted units or
other locations in the vicinity of occupied
spaces, where noise may be
objectionable.

Capacity Control Steps


(CRS)
To provide additional capacity control
steps on the units. See Table 2 (page 7)
for optional steps available.

Liquid Line Controls


(CRSP)
Comprises of correctly sized thermostatic
expansion valve, suitable solenoid valve,
filter drier, sight glass and one number
shut-off valve per circuit.

Hot Gas Bypass System


(GBP)
To enable operation of a large sized unit
at part loads, below last step of capacity
control due to application requirements.

Extra Shut Off Valve


(CXFV)
To isolate filter drier on field pipe-work.
Must be ordered, if required, with CRSP
option.

Run Hour Meter(s)


(RHM)
To monitor operating hours of each
compressor.

Hi-Lo and Oil Pressure Gauges


(CSDG)
Without piping.

Voltage Monitoring Module


(VMM)
To prevent Condensing Unit operation in
the event of :
Phase burn-out
Phase reversal
Under voltage on the incoming line
voltage.

Special custom built units incorporating


specially required features like anticondensation resistance heaters
embedded in condenser motors,
explosion proof units incorporating open
compressors driven by explosion proof
motors etc. can be manufactured on
request.Consult SKM with detailed
requirements.

Control Transformer
(CXT)
This option is necessary and available

ACUX Series Condensing Units


Page 6

Compressor Starting
The ACUX Condensing Unit are provided,
as standard mode of compressor starting
as per Table 1.
All Air Cooled Condensing Units ACUX
Series with standard DOL start
compressors as shown, do not,
generally, require part winding start.
Maximum Instantaneous Current Flow
as shown in Tables 10-14 (pages 1820), must be used in determining the
need for such part winding start.
If part winding start is required, please
specify option PWS at enquiry/order,
available only for the models shown with
PWS as option in Table 1.

Capacity Control Steps

Model
ACUX

380-415/3/50
Standard
Option

Power Supply (V/Ph/Hz)


380/3/60
220/3/60
Standard
Option
Standard
Option

5011
6014
5015
6018
5021
6025
PWS
5023
6027
5026
6031
5030
6035
5032
6037
5033
6038
5036
6042
5038
6044
5042
6050
5043
6051
5045
6053
DOL
5051
6061
5052
6062
5053
6063
PWS
5060
6070
5064
6075
5070
6080
5074
6085
5075
6090
5080
6095
5085
6100
5090
6105
5095
6110
5105
6120
For legend, please see page 20

ACUX

S ta n d a r d

PWS

PWS

DOL

DOL

PWS
PWS

PWS

DOL

DOL

PWS

PWS

DOL

PWS

PWS

DOL

PWS

PWS

PWS

DOL
PWS

Table 1
N u m b er
o f S te p s

O p ti o n a l

N u m b er
o f S te p s

5007

6008

1 0 0 -0

1 0 0 -6 6 -0

The number of capacity control steps


required is determined by application
and load. For loads with a wide variation
and desired operation over a longer
operational season extending beyond
summer months it is recommended that
option CRS be considered.

5009

6010

1 0 0 -0

1 0 0 -6 6 -0

5013

6014

1 0 0 -0

1 0 0 -5 0 -0

5014

6015

1 0 0 -5 0 -0

1 0 0 -8 4 -5 0 -3 4 -0

5017

6019

1 0 0 -5 7 -0

1 0 0 -5 7 -3 8 -0

5018

6020

1 0 0 -5 0 -0

1 0 0 -8 4 -5 0 -3 4 -0

5019

6021

1 0 0 -0

1 0 0 -6 6 -0

Optional steps (specify option CRS) as


shaded, require a factory certified wiring
diagram. Please furnish the details of
user supplied and installed thermostat in
order for factory to provide the certified
wiring diagram compatible with the
thermostat. Failure to furnish the details
required at the time of order will result in
units being supplied as per the standard
Wiring Schematic of SKM.

5020

6022

1 0 0 -6 6 -0

1 0 0 -6 6 -3 3 -0

5023

6025

1 0 0 -0

1 0 0 -6 6 -0

5024

6026

1 0 0 -6 0 -0

1 0 0 -6 0 -3 0 -0

5026

6029

1 0 0 -0

1 0 0 -7 5 -5 0 -0

5027

6030

1 0 0 -5 0 -0

1 0 0 -7 5 -5 0 -2 5 -0

5028

6031

1 0 0 -6 9 -0

1 0 0 -6 9 -4 6 -0

5032

6035

1 0 0 -0

1 0 0 -7 5 -5 0 -0

5033

6036

1 0 0 -7 2 -0

1 0 0 -7 2 -4 8 -0

5034

6038

1 0 0 -6 0 -0

1 0 0 -6 0 -4 0 -0

5038

6042

1 0 0 -6 4 -0

1 0 0 -6 4 -4 3 -0

5042

6046

1 0 0 -5 0 -0

1 0 0 -8 4 -5 0 -3 4 -0

5044

6048

1 0 0 -5 3 -0

1 0 0 -8 4 -5 3 -3 5 -0

5045

6050

1 0 0 -5 0 -0

1 0 0 -8 4 -5 0 -3 4 -0

5049

6057

1 0 0 -6 0 -0

1 0 0 -8 6 -6 0 -4 5 -0

5052

6060

1 0 0 -5 4 -0

1 0 0 -8 4 -5 4 -3 6 -0

5056

6066

1 0 0 -5 0 -0

1 0 0 -8 8 -5 0 -3 8 -0

5060

6070

1 0 0 -5 4 -0

1 0 0 -8 9 -5 4 -4 1 -0

5064

6074

1 0 0 -5 0 -0

1 0 0 -8 8 -5 0 -3 8 -0

ACUX Series Condensing Units


Page 7

Installation & Application


Data
Space / Location Requirements
SKM ACUX Series Condensing Units
should be located on a flat base, either
on the ground or on a roof top, which is
strong enough to hold the operating
weight of the unit.
The most important consideration when
deciding upon the location of Air Cooled
equipment is the provision for supply of
ambient air to the condenser and removal
of heated air from the condenser.
For recommended clearances refer to
Figure A and Table 3 below. Where this
essential requirement is not adhered to,
it will result in a higher condensing
temperature which causes poor
operation, and eventual failure of the
equipment. Units should not be located

in the vicinity of steam, hot air or fume


exhausts.
ACUX Series Condensing Units should
be sited away from noise sensitive places.
Units may be mounted on anti vibration
mounts suitable for operating weight, to
prevent vibration and noise from being
transmitted into the building structure.
Orientation of the ACUX Series
Condensing Units, if possible, to be so
that prevailing winds blow against the
control panel or access end of the unit
rather than against the condenser coil(s).
For parallel location of multiple ACUX
Series a minimum 50% more than the
recommended clearances as shown
below should be maintained.
There should be no obstruction above
the fans and no ductwork should be
connected to any fan outlet.
The ACUX Series Air Cooled Condensing
Units are meant for outdoor installation

Recommended Clearances
Do not duct fan exhaust and do not place
any obstruction on any fan outlet

Figure A

ACUX Series Condensing Units


Page 8

and may not be protected any further from


the elements. However, on ground level
installations option CGP/CGG may be
desirable for protection of the condenser
coil against vandalism.

Refrigerant Piping
Correct design and size of refrigerant
piping is necessary for proper operation.
The refrigerant piping generally should
be designed to accomplish the following:
a.

To ensure proper refrigerant feed to


the evaporator.

b.

To provide practical refrigerant line


sizes without excessive pressure
drop.

c.

To maintain uniform return of


lubricating oil to the compressor.

d.

To prevent refrigerant from entering


the compressor and causing
compressor damage due to
"slugging".

ACUX
5007
6008
5009
6010
5013
6014
5014
6015
5017
6019
5018
6020
5019
6021
5020
6022
5023
6025
5024
6026
5026
6029
5027
6030
5028
6031
5032
6035
5033
6036
5034
6038
5038
6042
5042
6046
5044
6048
5045
6050
5049
6057
5052

6060

5056

6066

5060

6070

5064

6074

B
30

40

(7 6 2 )

(1 0 1 6 )

48
(1 2 1 9 )

64

36

(1 6 2 5 )

(9 1 4 )

72
(1 8 2 9 )

SKM ACUX Series Condensing Unit must


be located as close to the DX coil as
possible. On dual compressor models
the DX coil circuits must be selected to
balance and match Condensing Unit
circuits.
Recommended practice is to size liquid
lines for 1F (2.9 Psi) change in saturation
temperature (pressure drop). The normal
liquid lift without refrigeration flashing
before the expansion valve at full load

conditions is about 50 feet (15m).


A replaceable element filter-drier should
be furnished and installed in the field
before the expansion valve to aid in
maintaining the system.
Suction lines should preferably be sized
for 2F (2.9 Psi) change in saturation
temperature (pressure drop). Maximum
allowable saturated suction gas
temperature for Condensing Units is 50F

(10C) at any condensing temperature.


Suction lines should be insulated
preferably jointly with the liquid lines.
Certain applications (cond. unit above
the DX coil) and where optional capacity
reduction CRS has been ordered, may
require the use of double suction risers
for oil return. Refer to ASHRAE
Handbook for proper sizing procedures.
Typical piping layouts are as shown in
Figure B on Page 10.

SKM ACUX Series Condensing Units are designed for satisfactory operation with single suction line. In some cases of low load
operation, it is recommended connecting a double suction riser for applications having option CRS.

ACUX Series Condensing Units


Page 9

Typical Refrigeration Piping

Legend
1.
2.
3.
4.
5.
6.
7.

Expansion Valve
Sight Glass
Solenoid Valve
Filter Drier
Shut off Valve
Liquid Line
Suction Line

Single Circuit Unit shown. For dual


circuit units, piping of second circuit
is similar
Figure B

Electrical Hook- Up
Every SKM ACUX Series Condensing
Unit requires, at most, field installed fused
disconnect switches or circuit breakers,
fan interlocks and a 24 volt temperature
control thermostat.
Refer to typical wiring diagram below for
a schematic representation of required
field electrical hook-ups for a standard
ACUX Series Condensing Unit hooked
up with an air handling unit.
When option CRS is required, consult
SKM for certified Wiring Diagram and
Electrical Hook-up (see Page 7 for
Capacity Control Steps - option CRS).
All field wiring must be done in
accordance with applicable local and
national codes.
For maximum recommended fuse sizes
and minimum circuit amperes for cable
sizing, see Tables 10 - 14 (pages 18 - 20)
of this bulletin.

Field Expansion
Selection

Valve

The following recommendations should


be taken into consideration when
selecting expansion valves in field.
1.

2.

Expansion valves should be installed


as close to the evaporator as
possible, mounted directly to the
distributor.
The following possible sources of
pressure drop to be considered:
a.

Friction losses
refrigerant lines.

through

b.

Pressure drop across valves


and controls.

c.

Pressure drop due to vertical lift


of liquid line for R-134a; 1F
(0.55C) sub cooling must be
allowed for each 5.5 ft (1.7m)
vertical rise in order to avoid
flash gas forming due to the
weight of the column of liquid
refrigerant.

ACUX Series Condensing Units


Page 10

SKM ACUX Series units are designed


with a sub cooling circuit enough to
sub cool the liquid 12F (6.6 C), which
gives the liquid maximum 66 ft. (20m)
lift without additional sub cooling.
Liquid suction heat exchanger can be
used for additional sub cooling in
order to avoid flash gas forming.

Matching DX Coil Selection


For single circuit ACUX Series, the DX
coil selection in a MAH, DMAH or other air
handler from SKM should be based on
total capacity. For dual circuit F-Series,
extra care should be exercised and
correspondingly split, by face area or
number of rows to correspond and match
the capacity split available in the dual
circuited ACUX Series selected. For
optimum matching the DX coil should be
ordered from SKMas well.
SKM provides correct no. of feeds and
circuits and properly sized distribution to
ensure the correct split on the DX coil is
made available to match the particular
selected ACUX Series model.

Altitude Correction Factors


The unit ratings are based on sea level.
Above sea level apply the following
correction factors:
Altitude

Capacity

Power
Multiplier

feet

m eter

Multiplier

2000

610

0.99

1.01

4000

1219

0.98

1.02

6000

1829

0.97

1.03

8000

2438

0.96

1.04

10000

3048

0.95

1.05
Ta bl e 5

Field Wiring Requirement Schematic

Figure C

ACUX Series Condensing Units


Page 11

Specifications - 50 Hz

ACUX
T R
kW
T R
C o o l i n g C apaci t y 2
kW
T ype
C o de
C o m pr e s s
Q u an t i t y
or
U S G al
O i l C h ar ge
L it er
T ype
C o n de n s e r
ft
C o il
F ac e A r e a
m
T ype
C o n de n s e r
C o de /
F an
cf m
A ir F lo w
l /s
R at e
T ype
C o n de n s e r
S ize /
kW
M otor
P o we r In pu t /
kW
R ef r i ge r an t ( R - 13 4 a)
l bs
O pe r at i n g C h ar ge
kg
N u m be r o f R e f r i ge r an t
l bs
U n i t O pe r at i n g W e i gh t
kg
M o de l

C o o l i n g C apaci t y 1

M o de l

ACUX
T R
C o o l i n g C apaci t y 1
kW
T R
C o o l i n g C apaci t y 2
kW
T ype
C o de
C o m pr e s s
Q u an t i t y
or
U S G al
O i l C h ar ge
L it er
T ype
C o n de n s e r
ft
F ac e A r e a
C o il
m
T ype
C o n de n s e r
C o de / Q t y.
F an
cf m
A ir F lo w
l /s
R at e
T ype
C o n de n s e r
S i z e / Q t y.
kW
M otor
P o we r In pu t /
kW
R ef r i ge r an t ( R - 13 4 a)
l bs
O pe r at i n g C h ar ge
kg
N u m be r o f R e f r i ge r an t
l bs
U n i t O pe r at i n g W e i gh t
kg

1).
2).
3).

5007
7 .0
2 4 .6
6 .1
2 1.5
D 10X
1
0.9
3.4

9.7
0.9
628/1
4530
2138

0.37/1
0.55/1
4.8
2.2
1
748
340

5 0 17
5 0 13
5 0 14
5009
17 .0
13 .6
14 .0
9 .5
5 9 .8
4 7 .9
4 9 .3
3 3 .4
14 .8
11.8
12 .1
8 .3
4 2 .6
5 2 .1
2 9 .2
4 1.5
S emi-H ermetic R eciprocating D is cus
D 15X
D 25X
D 10X
D 10X
D 10X
D 15X
1
1
1
1
1
1
0.9
1.1
0.9
0.9
0.9
0.9
3.4
4.0
3.4
3.4
3.4
3.4
A ir cooled 3 or 4 rows 12 F P I (2.1 mm) fin s pacing Cu tubes A l fins
12.2
19.4
24.4
1.8
1.1
2.3
P ropeller direct drive
723/1
628/2
723/2
6720
9060
13440
3171
4275
6342
T otally enclos ed, air over Clas s F ins ulation, 6-pole, IP -55
0.75/1
0.37/2
0.75/2
1.0/1
0.55/2
1.0/2
9.9
12.1
5.9
9.9
2.7
4.5
4.5
5.5
2
2
1
1
1496
1628
755
1188
740
343
540
680

5 0 18
19 .0
6 6 .9
16 .5
5 8 .1

5 0 19
5020
5023
5024
2 0 .5
2 2 .8
2 0 .3
2 2 .9
7 1.5
7 2 .2
8 0 .3
8 0 .6
17 .6
17 .8
19 .7
19 .8
6 2 .0
6 2 .7
6 9 .3
6 9 .7
S emi-H ermetic R eciprocating D is cus
D 15X
D 15X
D 35X
D 10X
D 25X
D 40X
D 15X
D 25X
1
1
1
1
1
1
1
1
0.9
0.9
1.1
0.9
1.1
1.9
0.9
1.1
3.4
3.4
4.3
3.4
4.0
7.4
3.4
4.0
A ir cooled 3 or 4 rows 12 F P I (2.1 mm) fin s pacing Cu tubes A l fins
29.3
24.4
2.7
2.3
P ropeller direct drive
729/2
723/2
14900
15200
13440
7031
7173
6342
T otally enclos ed, air over Clas s F ins ulation, 6-pole, IP -55
1.1/2
0.75/2
1.1/2
1.0/2
1.5/2
1.5/2
12.1
12.1
12.1
14.3
14.3
5.5
5.5
5.5
6.5
6.5
2
1
2
1
2
1452
1782
1540
1826
1637
744
660
810
700
830

Cooling capacity and EER are at 95F (35C) condenser entering air temp. & 45F (7.2C) SST. (According to ARI-365/94 standard).
Cooling capacity at Gulf conditions : 115F (46.1C) condenser entering air temperature & 45F (7.2C) SST.
The approximate operating charge required for the unit when connected to a DX cooling coil. Units are shipped with holding charge only.

ACUX Series Condensing Units


Page 12

Specifications - 50 Hz
ACUX
T R
kW
T R
C o o l i n g C apaci t y 2
kW
T yp e
C o de
C o m pr es s o r
Q u an t i t y
U S G al
O i l C h ar ge
L it er
T yp e
C o n den s er C o i l
ft
F ace A r ea
m
T yp e
C o de /
C o n den s er F an
cf m
A ir F lo w
l /s
R at e
T yp e
C o n den s er M o t o r
S ize /
kW
P o we r I n p u t /
kW
l bs
R e f r i ge r a n t ( R - 13 4 a ) O p e r a t i n g
kg
C h ar ge
N u m ber o f R ef r i ger an t C i r cu i t s
l bs
U n i t O per at i n g W ei gh t
kg
M o del

C o o l i n g C apaci t y 1

M o del

ACUX
T R
kW
T R
C o o l i n g C apaci t y 2
kW
T yp e
C o de
C o m pr es s o r
Q u an t i t y
U S G al
O i l C h ar ge
L it er
T yp e
C o n den s er C o i l
ft
F ace A r ea
m
T yp e
C o d e / Q t y.
C o n den s er F an
cf m
A ir F lo w
l /s
R at e
T yp e
C o n den s er M o t o r
S i z e / Q t y.
kW
P o we r I n p u t /
kW
l bs
R e f r i ge r a n t ( R - 13 4 a ) O p e r a t i n g
kg
C h ar ge
N u m ber o f R ef r i ger an t C i r cu i t s
l bs
U n i t O per at i n g W ei gh t
kg
C o o l i n g C apaci t y 1

ACUX
T R
kW
T R
C o o l i n g C apaci t y 2
kW
T yp e
C o de
C o m pr es s o r
Q u an t i t y
U S G al
O i l C h ar ge
L it er
T yp e
C o n den s er C o i l
ft
F ace A r ea
m
T yp e
C o de /
C o n den s er F an
cf m
A ir F lo w
l /s
R at e
T yp e
C o n den s er M o t o r
S ize /
kW
P o we r I n p u t /
kW
R e f r i ge r a n t ( R - 13 4 a ) O p e r a t i n g
l bs
C h ar ge
kg
N u m ber o f R ef r i ger an t C i r cu i t s
l bs
U n i t O per at i n g W ei gh t
kg
M o del

C o o l i n g C apaci t y 1

5026
2 7 .3
9 6 .1
2 3 .7
8 3 .4
D 50X
1
2.0
7.7

18.9
8.6
1
1760
800

5027
5028
5032
5033
2 7 .4
2 9 .6
3 2 .9
3 3 .9
9 6 .4
10 4 . 2
115 . 8
119 . 3
2 3 .8
2 5 .6
2 8 .5
2 9 .5
8 3 .8
10 0 . 3
10 3 . 8
9 0 .1
S emi-H ermetic R ecipro cating D is cus
D 25X
D 25X
D 15X
D 35X
D 60X
D 15X
D 40X
1
1
1
1
1
1
1
1.1
1.1
0.9
1.1
2.0
0.9
1.9
4.0
4.0
3.4
4.3
7.7
3.4
7.4
A ir co o led 3 o r 4 ro ws 12 F P I (2.1 mm) fin s pacing Cu tubes A l fins
53.3
29.3
2.7
5.0
P ro peller direct drive
823/2
823/3
17580
28350
8296
13378
T o tally enclo s ed, air over Clas s F ins ulatio n, 6-po le, IP -55
1.5/2
1.5/3
2.1/2
2.1/3
25.3
18.9
25.3
18.9
8.6
11.5
11.5
8.6
1
2
2
2
2112
2398
2024
2002
960
1090
920
910

5034
3 5 .2
12 3 . 9
3 0 .6
10 7 . 7

5038
5042
5045
5044
4 7 .6
3 8 .9
4 3 .1
4 5 .3
13 6 . 9
15 1. 7
15 9 . 5
16 7 . 6
3 3 .9
3 7 .5
3 9 .4
4 1. 3
119 . 3
13 2 . 0
13 8 . 7
14 5 . 4
S emi-H ermetic R ecipro cating D is cus
D 25X
D 35X
D 25X
D 40X
D 35X
D 35X
D 35X
D 40X
D 40X
D 40X
1
1
1
1
1
1
1
1
1
1
1.1
1.1
1.1
1.9
1.1
1.1
1.1
1.9
1.9
1.9
4.0
4.3
4.0
7.4
4.3
4.3
4.3
7.4
7.4
7.4
A ir co o led 3 o r 4 ro ws 12 F P I (2.1 mm) fin s pacing Cu tubes A l fins
53.3
64.0
72.0
5.0
5.9
6.7
P ro peller direct drive
823/4
823/3
28350
37160
37880
13378
17536
17876
T o tally enclo s ed, air over Clas s F ins ulatio n, 6-po le, IP -55
1.5/3
1.1/4
2.1/3
1.4/4
25.3
30.36
34.1
34.1
34.1
11.5
13.8
15.5
15.5
15.5
2
2
2
2
2
2508
2574
2781
2838
2860
1140
1170
1264
1290
1300
5049
4 8 .7
17 1. 4
4 2 .3
14 8 . 9

5052
5056
5060
5064
5 1. 6
5 6 .5
6 0 .2
6 3 .7
18 1. 6
19 8 . 9
2 11. 9
2 2 4 .2
4 4 .8
4 9 .1
5 2 .2
5 5 .2
18 3 . 7
19 4 . 3
15 7 . 7
17 2 . 8
S emi-H ermetic R ecipro cating D is cus
D 50X
D 35X
D 50X
D 40X
D 50X
D 50X
D 60X
D 50X
D 60X
D 60X
1
1
1
1
1
1
1
1
1
1
2.0
1.1
2.0
1.9
2.0
2.0
2.0
2.0
2.0
2.0
3.4
3.4
4.0
3.4
3.4
3.4
3.4
A ir co o led 3 o r 4 ro ws 12 F P I (2.1 mm) fin s pacing Cu tubes A l fins
72.0
6.7
P ro peller direct drive
823/4
829/4
42160
37880
43840
17875
20688
19895
T o tally enclo s ed, air over Clas s F ins ulatio n, 6-po le, IP -55
1.1/4
1.5/4
1.5/4
2.02/4
45.3
45.3
34.1
34.1
45.3
15.5
15.5
20.6
20.6
20.6
2
2
2
2
2
3036
3014
3388
3388
3388
1380
1370
1540
1540
1540

ACUX Series Condensing Units


Page 13

Specifications - 60 Hz

ACUX
T R
kW
T R
C o o l i n g C apac i t y 2
kW
T ype
C o de
C o m pr e s s
Q u an t i t y
or
U S G al
O i l C h ar ge
L i t er
T ype
C o n de n s er
ft
C o il
F ace A r e a
m
T ype
C o n de n s er
C o de /
F an
cf m
A ir F lo w
l /s
R at e
T ype
C o n de n s er
S ize /
kW
M otor
P o we r In pu t /
kW
R e f r i ge r an t ( R - 13 4 a)
l bs
O pe r at i n g C h ar ge
kg
N u m be r o f R e f r i ger an t
l bs
U n i t O pe r at i n g W ei gh t
kg
M o de l

C o o l i n g C apac i t y 1

M o de l

ACUX
T R
C o o l i n g C apac i t y 1
kW
T R
C o o l i n g C apac i t y 2
kW
T ype
C o de
C o m pr e s s
Q u an t i t y
or
U S G al
O i l C h ar ge
L i t er
T ype
C o n de n s er
ft
F ace A r e a
C o il
m
T ype
C o n de n s er
C o de / Q t y.
F an
cf m
A ir F lo w
l /s
R at e
T ype
C o n de n s er
S i z e / Q t y.
kW
M otor
P o we r In pu t /
kW
R e f r i ge r an t ( R - 13 4 a)
l bs
O pe r at i n g C h ar ge
kg
N u m be r o f R e f r i ger an t
l bs
U n i t O pe r at i n g W ei gh t
kg

1).
2).
3).

6008
8 .2
2 8 .8
7 .1
2 4 .9
D 10X
1
0.9
3.4

9.7
0.9

628/1
4530
2138
0.55/1
0.85/1
4.8
2.2
1
748
340

6 0 19
6 0 14
6 0 15
6 0 10
19 .8
15 .9
16 .3
11.0
6 9 .6
5 6 .0
5 7 .5
3 8 .8
17 .2
13 .8
14 .1
9 .6
4 9 .7
6 0 .4
3 3 .6
4 8 .5
S emi-H ermetic R eciprocating D is cus
D 15X
D 25X
D 10X
D 10X
D 10X
D 15X
1
1
1
1
1
1
0.9
1.1
0.9
0.9
0.9
0.9
3.4
4.0
3.4
3.4
3.4
3.4
A ir cooled 3 or 4 rows 12 F P I (2.1 mm) fin s pacing Cu tubes A l fins
12.2
19.4
24.4
1.8
1.1
2.3
P ropeller direct drive A luminum B lade
723/1
628/2
723/2
6720
9060
13440
3171
4275
6342
T otally enclos ed, air over Clas s F ins ulation, 6-pole, IP -55
1.1/1
0.55/2
1.1/2
1.6/1
0.85/1
1.6/2
9.9
12.1
5.9
9.9
2.7
4.5
4.5
5.5
2
2
1
1
1496
1628
755
1188
740
343
540
680

6020
2 2 .0
7 7 .6
19 .1
6 7 .3

6021
6022
6025
6026
2 3 .7
2 6 .4
2 3 .5
2 6 .5
8 2 .8
8 3 .5
9 2 .9
9 3 .4
2 0 .4
2 0 .5
2 2 .9
2 3 .0
7 1.6
7 2 .3
8 0 .4
8 0 .9
S emi-H ermetic R eciprocating D is cus
D 15X
D 15X
D 35X
D 10X
D 25X
D 40X
D 15X
D 25X
1
1
1
1
1
1
1
1
0.9
0.9
1.1
0.9
1.1
1.9
0.9
1.1
3.4
3.4
4.3
3.4
4.0
7.4
3.4
4.0
A ir cooled 3 or 4 rows 12 F P I (2.1 mm) fin s pacing Cu tubes A l fins
29.3
24.4
2.7
2.3
P ropeller direct drive A luminum B lade
729/2
723/2
14900
15200
13440
7031
7173
6342
T otally enclos ed, air over Clas s F ins ulation, 6-pole, IP -55
1.5/2
1.1/2
1.5/2
1.6/2
2.2/2
2.2/2
12.1
12.1
12.1
14.3
14.3
5.5
5.5
5.5
6.5
6.5
2
1
2
1
2
1452
1782
1540
1826
1637
744
660
810
700
830

Cooling capacity and EER are at 95F (35C) condenser entering air temp. & 45F (7.2C) SST. (According to ARI-365/94 standard).
Cooling capacity at Gulf conditions : 115F (46.1C) condenser entering air temperature & 45F (7.2C) SST.
The approximate operating charge required for the unit when connected to a DX cooling coil. Units are shipped with holding charge only.

ACUX Series Condensing Units


Page 14

Specifications - 60 Hz
M o del
C o o lin g C apacit y 1
C o o lin g C apacit y 2

C o m pr es s
or

T yp e
C o de
Q u an t it y
O il C h ar ge

C o n den s er
C o il

T yp e
F ace A r ea

T yp e
C o n den s er
C o de /
F an
A ir F lo w
R at e
T yp e
C o n den s er
S iz e /
M otor
P o we r In pu t /
R e f r i g e r a n t ( R - 13 4 a )
O per at in g C h ar ge
N u m ber o f R ef r iger an t
U n it O per at in g W eigh t

M o del
C o o lin g C apacit y 1
C o o lin g C apacit y 2

C o m pr es s
or

T yp e
C o de
Q u an t it y
O il C h ar ge

C o n den s er
C o il

T yp e
F ace A r ea

T yp e
C o d e / Q t y.
A ir F lo w
R at e
T yp e
C o n den s er
S i z e / Q t y.
M otor
P o we r In pu t /
R e f r i g e r a n t ( R - 13 4 a )
O per at in g C h ar ge
N u m ber o f R ef r iger an t
C o n den s er
F an

U n it O per at in g W eigh t

M o del
C o o lin g C apacit y 1
C o o lin g C apacit y 2

C o m pr es s
or

T yp e
C o de
Q u an t it y
O il C h ar ge

C o n den s er
C o il

T yp e
F ace A r ea

T yp e
C o de /
A ir F lo w
R at e
T yp e
C o n den s er
S iz e /
M otor
P o we r In pu t /
R e f r i g e r a n t ( R - 13 4 a )
O per at in g C h ar ge
N u m ber o f R ef r iger an t

C o n den s er
F an

U n it O per at in g W eigh t

ACUX
T R
kW
T R
kW
U S G al
L it er
ft
m
cf m
l /s
kW
kW
lbs
kg
lbs
kg
ACUX
T R
kW
T R
kW
U S G al
L it er
ft
m
cf m
l /s
kW
kW
lbs
kg
lbs
kg
ACUX
T R
kW
T R
kW
U S G al
L it er
ft
m
cf m
l /s
kW
kW
lbs
kg
lbs
kg

6029
3 1. 8
111. 9
2 7 .6
9 7 .1
D 50X
1
2 .0
7 .7

18 .9
8 .6
1
17 6 0
800

6030
6031
6035
6036
3 2 .0
3 4 .4
3 8 .4
3 9 .6
112 . 7
13 9 . 4
12 1. 2
13 5 . 1
2 7 .8
2 9 .8
3 3 .3
3 4 .4
9 7 .7
10 5 . 0
117 . 1
12 1. 1
S em i-H er m etic R ecipr o cating D is cus
D 25X
D 25X
D 15 X
D 35X
D 60X
D 15 X
D 40X
1
1
1
1
1
1
1
1.1
1.1
0 .9
1.1
2 .0
0 .9
1.9
4 .0
4 .0
3 .4
4 .3
7 .7
3 .4
7 .4
A ir co o led 3 o r 4 r o ws 12 F P I (2 .1 m m ) fin s pacing C u tubes A l fins
2 9 .3
5 3 .3
2 .7
5 .0
P r o peller dir ect dr iv e A lum inum B lades
8 2 3 /2
8 2 3 /3
17 5 8 0
28350
8296
13 3 7 8
T o tally enclo s ed, air o v er C las s F ins ulatio n, 6 -po le, IP -5 5
1.5 /2
1.5 /3
2 .1/2
2 .1/3
18 .9
18 .9
2 5 .3
2 5 .3
8 .6
8 .6
11.5
11.5
2
2
1
2
2024
2002
2 112
2398
920
9 10
960
10 9 0

6038
4 1. 1
14 4 . 6
3 5 .7
12 5 . 6

6042
6046
6048
6050
5 5 .5
4 5 .4
5 0 .3
5 3 .0
15 9 . 9
17 7 . 2
19 5 . 3
18 6 . 4
3 9 .5
4 3 .8
4 6 .0
4 8 .1
13 9 . 0
15 4 . 0
16 1. 8
16 9 . 5
S em i-H er m etic R ecipr o cating D is cus
D 25X
D 35X
D 25X
D 40X
D 35X
D 35X
D 35X
D 40X
D 40X
D 40X
1
1
1
1
1
1
1
1
1
1
1.1
1.1
1.1
1.9
1.1
1.1
1.1
1.9
1.9
1.9
4 .0
4 .3
4 .0
7 .4
4 .3
4 .3
4 .3
7 .4
7 .4
7 .4
A ir co o led 3 o r 4 r o ws 12 F P I (2 .1 m m ) fin s pacing C u tubes A l fins
5 3 .3
6 4 .0
7 2 .0
5 .0
5 .9
6 .7
P r o peller dir ect dr iv e A lum inum B lades
8 2 3 /4
8 2 3 /3
28350
3 7 16 0
37880
17 8 7 6
13 3 7 8
17 5 3 6
T o tally enclo s ed, air o v er C las s F ins ulatio n, 6 -po le, IP -5 5
1.5 /3
1.1/4
2 .1/3
1.4 /4
2 5 .3
3 0 .3 6
3 4 .1
3 4 .1
3 4 .1
15 .5
11.5
13 .8
15 .5
15 .5
2
2
2
2
2
2508
2574
2781
2838
2860
114 0
117 0
12 6 4
12 9 0
13 0 0
6057
5 6 .8
2 0 0 .0
4 9 .3
17 3 . 6

6060
6066
6070
6074
6 0 .1
6 6 .1
7 0 .3
7 4 .3
2 4 7 .3
2 6 1. 5
2 11. 4
2 3 2 .6
5 2 .1
5 7 .4
6 0 .9
6 4 .3
2 14 . 5
2 2 6 .4
18 3 . 5
2 0 2 .0
S em i-H er m etic R ecipr o cating D is cus
D 50X
D 35X
D 50X
D 40X
D 50X
D 50X
D 60X
D 50X
D 60X
D 60X
1
1
1
1
1
1
1
1
1
1
2 .0
1.1
2 .0
1.9
2 .0
2 .0
2 .0
2 .0
2 .0
2 .0
3 .4
3 .4
4 .0
3 .4
3 .4
3 .4
3 .4
A ir co o led 3 o r 4 r o ws 12 F P I (2 .1 m m ) fin s pacing C u tubes A l fins
7 2 .0
6 .7
P r o peller dir ect dr iv e A lum inum B lades
8 2 9 /4
8 2 3 /4
4 2 16 0
37880
43840
20688
19 8 9 5
17 8 7 5
T o tally enclo s ed, air o v er C las s F ins ulatio n, 6 -po le, IP -5 5
1.1/4
1.5 /4
1.5 /4
2 .0 2 /4
4 5 .3
4 5 .3
3 4 .1
3 4 .1
4 5 .3
15 .5
15 .5
2 0 .6
2 0 .6
2 0 .6
2
2
2
2
2
3036
3 0 14
3388
3388
3388
13 8 0
13 7 0
15 4 0
15 4 0
15 4 0

ACUX Series Condensing Units


Page 15

Capacity Ratings - 50 Hz
Model

SST

ACUX

5007

5009

5013

5014

5017

5018

5019

5020

5023

5024

5026

5027

5028

F
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50

C
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0

95 F (35 C)
Total Capacity
MBH
KW
68.9
20.2
76.3
22.4
84.1
24.7
92.4
27.1
94.1
27.6
103.8
30.4
114.0
33.4
124.8
36.6
135.5
39.7
149.2
43.7
163.6
48.0
178.8
52.4
137.8
40.4
152.6
44.7
168.3
49.3
184.7
54.1
167.3
49.0
185.2
54.3
204.2
59.8
224.3
65.7
188.1
55.1
207.5
60.8
228.0
66.8
249.6
73.2
202.0
59.2
222.2
65.1
243.6
71.4
266.0
78.0
203.1
59.5
224.0
65.6
246.0
72.1
269.1
78.9
227.6
66.7
249.7
73.2
273.1
80.0
297.6
87.2
227.3
66.6
250.2
73.3
274.4
80.4
299.9
87.9
268.9
78.8
297.2
87.1
327.1
95.9
358.6
105.1
272.6
79.9
300.2
88.0
329.3
96.5
360.1
105.6
294.0
86.2
323.5
94.8
354.7
104.0
387.4
113.6

PI
KW
5.8
6.1
6.5
6.8
8.1
8.5
9.0
9.5
11.6
12.3
13.0
13.7
11.6
12.2
12.9
13.6
13.6
14.3
15.0
15.7
16.2
17.1
18.0
19.0
17.7
18.7
19.8
21.0
17.5
18.5
19.6
20.7
21.2
22.6
24.0
25.5
19.8
21.0
22.2
23.5
23.8
25.1
26.5
28.0
23.0
24.4
25.8
27.3
25.9
27.4
29.1
30.7

Condenser
105F (40C)
Total Capacity
MBH
KW
64.0
18.7
71.0
20.8
78.4
23.0
86.2
25.3
87.7
25.7
96.8
28.4
106.5
31.2
116.6
34.2
126.3
37.0
139.2
40.8
152.8
44.8
167.1
49.0
127.9
37.5
141.9
41.6
156.8
45.9
172.4
50.5
155.7
45.6
172.7
50.6
190.6
55.9
209.6
61.4
175.4
51.4
193.6
56.8
212.9
62.4
233.3
68.4
188.3
55.2
207.3
60.8
66.6
227.4
248.5
72.8
189.1
55.4
208.7
61.2
229.4
67.2
251.3
73.6
212.1
62.2
232.9
68.2
254.8
74.7
277.9
81.4
211.8
62.1
233.4
68.4
256.2
75.1
280.1
82.1
250.5
73.4
277.1
81.2
305.4
89.5
335.2
98.2
254.1
74.5
280.1
82.1
307.6
90.1
336.6
98.7
274.0
80.3
301.7
88.4
331.0
97.0
361.9
106.1

Entering Air Tem perature


115F (46C)
Total Capacity
PI
KW
MBH
KW
6.1
59.1
17.3
6.5
65.7
19.3
6.9
72.7
21.3
7.2
80.1
23.5
8.6
81.3
23.8
9.1
89.9
26.4
9.6
98.9
29.0
10.1
108.5
31.8
12.3
117.1
34.3
13.0
129.2
37.9
13.8
141.9
41.6
14.6
155.3
45.5
12.2
118.1
34.6
13.0
131.4
38.5
13.7
145.4
42.6
14.5
160.1
46.9
14.4
144.3
42.3
15.2
160.2
47.0
16.0
177.1
51.9
16.9
195.0
57.2
17.1
162.7
47.7
18.2
179.8
52.7
19.2
197.9
58.0
20.3
216.9
63.6
18.7
174.5
51.2
19.9
192.3
56.4
21.1
211.2
61.9
22.3
231.0
67.7
18.5
175.0
51.3
19.6
193.5
56.7
20.8
213.0
62.4
22.0
233.5
68.4
22.4
196.7
57.7
23.9
216.1
63.3
25.4
236.6
69.3
27.0
258.1
75.7
21.0
196.4
57.6
22.3
216.6
63.5
23.6
237.9
69.7
25.0
260.3
76.3
25.1
232.2
68.1
26.6
257.3
75.4
28.1
283.9
83.2
29.8
311.8
91.4
24.5
235.7
69.1
26.0
260.0
76.2
27.5
285.8
83.8
29.1
313.0
91.7
27.4
254.0
74.4
29.1
280.0
82.1
30.9
307.4
90.1
32.7
336.3
98.6

PI
KW
6.4
6.8
7.2
7.6
9.0
9.6
10.1
10.7
12.9
13.7
14.6
15.4
12.8
13.6
14.4
15.2
15.2
16.1
17.0
17.9
18.1
19.1
20.3
21.4
19.7
20.9
22.2
23.5
19.4
20.6
21.9
23.1
23.5
25.0
26.6
28.3
22.1
23.5
24.9
26.3
26.3
27.9
29.6
31.3
25.8
27.4
29.0
30.7
28.8
30.6
32.5
34.4

Shaded Values are at 120F (49C) condenser entering air temperature.

ACUX Series Condensing Units


Page 16

125F (52C)
Total Capacity
PI
MBH
KW
KW
54.3
15.9
6.6
60.5
17.7
7.1
67.1
19.7
7.5
74.0
21.7
7.9
75.0
22.0
9.4
83.0
24.3
10.0
91.4
26.8
10.6
100.2
29.4
11.2
108.0
31.6
13.5
119.2
34.9
14.3
131.1
38.4
15.2
143.5
42.1
16.0
108.6
31.8
13.3
121.0
35.5
14.1
134.2
39.3
15.0
148.1
43.4
15.8
133.0
39.0
15.9
147.9
43.3
16.8
163.7
48.0
17.8
180.4
52.9
18.8
150.1
44.0
18.8
166.1
48.7
20.0
182.9
53.6
21.2
200.5
58.8
22.4
160.8
47.1
20.5
177.4
52.0
21.8
194.9
57.1
23.1
213.4
62.5
24.4
161.1
47.2
20.2
178.4
52.3
21.4
196.6
57.6
22.7
215.7
63.2
24.0
181.4
53.2
24.4
199.5
58.5
26.0
218.5
64.0
27.6
238.5
69.9
29.3
181.0
53.1
23.0
199.9
58.6
24.4
219.7
64.4
25.9
240.5
70.5
27.4
214.4
62.8
27.3
237.8
69.7
29.0
262.6
77.0
30.7
288.6
84.6
32.5
63.7
26.9
217.3
240.0
70.3
28.5
264.0
77.4
30.2
289.3
84.8
32.0
234.0
68.6
30.0
258.3
75.7
31.9
283.8
83.2
33.8
310.6
91.0
35.7
Table 8 Continued

Capacity Ratings - 50 Hz
Model

SST

ACUX

5032

5033

5053

5034

5038

5042

5045

5049

5052

5056

5060

5064

F
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50

C
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0

95 F (35 C)
Total Capacity
MBH
KW
322.3
94.5
357.3
104.7
394.4
115.6
433.8
127.1
335.9
98.5
370.5
108.6
407.2
119.3
446.0
130.7
348.5
102.1
384.4
112.7
422.5
123.8
462.9
135.7
384.6
112.7
424.4
124.4
466.9
136.9
512.0
150.1
425.2
124.6
469.6
137.6
516.8
151.5
567.0
166.2
449.1
131.6
495.2
145.1
544.1
159.5
596.0
174.7
472.6
138.5
520.2
152.5
570.7
167.3
624.1
182.9
481.0
141.0
531.3
155.7
584.7
171.4
641.2
187.9
510.1
149.5
563.0
165.0
619.2
181.5
678.6
198.9
555.0
162.7
614.7
180.2
678.2
198.8
745.5
218.5
591.7
173.4
654.9
192.0
722.0
211.6
793.0
232.4
627.1
183.8
693.7
203.3
764.2
224.0
838.7
245.8

PI
KW
28.9
30.5
32.1
33.7
28.2
29.8
31.4
33.1
28.4
30.0
31.6
33.3
31.1
32.8
34.6
36.4
33.6
35.4
37.2
39.1
37.3
39.4
41.6
43.9
41.0
43.5
46.1
48.8
40.6
42.9
45.2
47.7
43.9
46.4
49.1
51.8
46.3
48.7
51.2
53.8
52.6
55.5
58.5
61.6
59.0
62.4
65.9
69.5

Condenser
105F (40C)
Total Capacity
MBH
KW
300.1
87.9
333.1
97.6
368.2
107.9
405.5
118.9
313.5
91.9
346.0
101.4
380.5
111.5
417.2
122.3
325.1
95.3
358.9
105.2
394.9
115.7
433.0
126.9
359.0
105.2
396.6
116.2
436.6
128.0
479.1
140.4
396.8
116.3
438.7
128.6
483.3
141.6
530.7
155.5
419.1
122.8
462.4
135.5
508.6
149.1
557.4
163.4
440.9
129.2
485.6
142.3
156.3
533.1
583.4
171.0
448.4
131.4
495.8
145.3
546.3
160.1
599.6
175.7
475.6
139.4
525.4
154.0
578.4
169.5
634.5
186.0
517.3
151.6
573.8
168.2
633.8
185.8
697.6
204.5
550.9
161.5
610.7
179.0
674.2
197.6
741.4
217.3
583.4
171.0
646.3
189.4
713.0
209.0
783.5
229.6

Entering Air Temperature


115F (46C)
Total Capacity
PI
KW
MBH
KW
30.5
278.0
81.5
32.2
309.1
90.6
33.9
342.3
100.3
35.7
377.4
110.6
29.9
291.1
85.3
31.7
321.5
94.2
33.5
353.9
103.7
35.4
388.3
113.8
30.2
301.7
88.4
32.0
333.5
97.7
33.8
367.2
107.6
35.6
403.0
118.1
33.1
333.5
97.8
35.0
368.7
108.1
37.0
406.3
119.1
39.1
446.2
130.8
35.9
368.5
108.0
37.9
407.8
119.5
40.0
449.7
131.8
42.1
494.2
144.9
39.7
389.1
114.1
42.0
429.8
126.0
44.5
473.0
138.6
47.0
518.9
152.1
43.5
409.4
120.0
46.2
451.2
132.2
49.1
495.7
145.3
52.0
542.8
159.1
43.1
415.9
121.9
45.6
460.5
135.0
48.2
507.9
148.9
50.9
558.0
163.6
46.5
441.3
129.3
49.3
488.1
143.1
52.2
537.8
157.6
55.2
590.5
173.1
49.0
479.9
140.7
51.8
533.1
156.2
54.6
589.6
172.8
57.5
649.7
190.4
55.5
510.6
149.7
58.7
566.9
166.2
62.0
626.7
183.7
65.4
690.0
202.2
62.1
540.3
158.4
65.7
599.5
175.7
69.4
662.3
194.1
73.2
728.7
213.6

PI
KW
31.9
33.8
35.6
37.5
31.6
33.5
35.5
37.6
31.9
33.8
35.8
37.8
35.0
37.2
39.3
41.5
38.0
40.2
42.5
44.8
41.9
44.5
47.1
49.8
45.9
48.8
51.8
54.9
45.3
48.1
50.9
53.8
48.9
52.0
55.1
58.3
51.6
54.6
57.7
60.9
58.2
61.6
65.1
68.7
64.8
68.7
72.6
76.5

Shaded Values are at 120F (49C) condenser entering air temperature.

ACUX Series Condensing Units


Page 17

125F (52C)
Total Capacity
PI
MBH
KW
KW
256.4
75.2
33.2
285.6
83.7
35.1
316.7
92.8
37.1
349.6
102.5
39.0
268.8
78.8
33.1
297.2
87.1
35.2
327.4
96.0
37.3
359.4
105.4
39.4
278.3
81.6
33.4
308.0
90.3
35.5
339.5
99.5
37.5
372.8
109.3
39.6
308.1
90.3
36.8
340.9
99.9
39.1
376.0
110.2
41.4
413.3
121.1
43.7
340.1
99.7
39.9
376.9
110.5
42.3
416.0
121.9
44.7
457.6
134.1
47.2
359.3
105.3
43.9
397.2
116.4
46.6
437.5
128.2
49.4
480.2
140.8
52.2
378.0
110.8
48.0
417.0
122.2
51.0
458.3
134.3
54.2
502.2
147.2
57.3
383.8
112.5
47.3
425.5
124.7
50.2
469.8
137.7
53.2
516.5
151.4
56.2
407.4
119.4
51.1
451.2
132.2
54.3
497.6
145.8
57.5
546.6
160.2
60.9
443.2
129.9
53.8
492.9
144.5
57.1
545.8
160.0
60.4
601.9
176.4
63.8
471.2
138.1
60.5
523.9
153.5
64.1
579.8
169.9
67.8
638.9
187.3
71.4
146.1
67.2
498.4
553.8
162.3
71.1
612.6
179.5
75.1
674.5
197.7
78.9
Table 8

Capacity Ratings - 60 Hz
Model

SST

ACUX

6008

6010

6014

6015

6019

6020

6021

6022

6025

6026

6029

6030

6031

F
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50

C
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0

95 F (35 C)
Total Capacity
MBH
KW
80.4
23.6
89.0
26.1
98.0
28.7
107.5
31.5
109.4
32.1
120.5
35.3
132.3
38.8
144.6
42.4
158.4
46.4
174.2
51.0
190.8
55.9
208.4
61.1
160.9
47.2
178.0
52.2
196.1
57.5
215.1
63.0
194.9
57.1
63.2
215.6
237.4
69.6
260.5
76.3
218.8
64.1
241.1
70.7
264.5
77.5
289.2
84.8
234.6
68.8
257.7
75.5
282.1
82.7
307.6
90.2
235.9
69.1
259.7
76.1
284.7
83.5
311.1
91.2
264.7
77.6
290.1
85.0
316.8
92.9
344.8
101.1
264.5
77.5
290.8
85.2
318.5
93.4
347.6
101.9
314.3
92.1
347.0
101.7
381.5
111.8
417.9
122.5
318.6
93.4
350.5
102.7
384.2
112.6
419.7
123.0
343.3
100.6
377.3
110.6
413.2
121.1
450.9
132.2

PI
KW
7.0
7.4
7.9
8.3
9.8
10.4
11.0
11.6
14.0
14.9
15.8
16.7
14.0
14.9
15.7
16.6
16.5
17.4
18.3
19.3
19.7
20.8
22.0
23.3
21.5
22.9
24.3
25.7
21.3
22.6
24.0
25.4
25.8
27.5
29.3
31.2
24.2
25.6
27.2
28.8
28.8
30.5
32.3
34.1
28.0
29.6
31.4
33.2
31.4
33.4
35.4
37.5

Condenser
105F (40C)
Total Capacity
MBH
KW
74.6
21.9
82.7
24.3
91.3
26.8
100.3
29.4
101.9
29.9
112.4
32.9
123.4
36.2
135.0
39.6
147.6
43.3
162.4
47.6
178.1
52.2
194.6
57.0
149.3
43.8
165.5
48.5
182.6
53.5
200.6
58.8
181.4
53.2
200.9
58.9
221.5
64.9
243.3
71.3
203.9
59.8
224.8
65.9
246.9
72.4
270.1
79.2
218.5
64.1
240.2
70.4
263.1
77.1
287.2
84.2
219.4
64.3
241.8
70.9
265.5
77.8
290.3
85.1
246.6
72.3
270.4
79.2
295.4
86.6
321.7
94.3
246.4
72.2
271.1
79.5
297.1
87.1
324.5
95.1
292.6
85.8
323.5
94.8
356.1
104.4
390.5
114.4
296.9
87.0
326.9
95.8
358.7
105.1
392.1
114.9
319.7
93.7
351.7
103.1
385.5
113.0
420.9
123.4

Entering Air Temperature


115F (46C)
PI
Total Capacity
KW
MBH
KW
7.4
68.9
20.2
7.9
76.6
22.4
8.3
84.7
24.8
8.8
93.2
27.3
10.4
94.5
27.7
11.1
104.3
30.6
11.7
114.6
33.6
12.4
125.5
36.8
14.9
136.8
40.1
15.8
150.7
44.2
16.8
165.4
48.5
17.8
180.8
53.0
14.8
137.8
40.4
15.7
153.1
44.9
16.6
169.3
49.6
17.6
186.3
54.6
17.5
168.0
49.2
18.5
186.3
54.6
19.5
205.8
60.3
20.6
226.2
66.3
20.8
189.0
55.4
22.1
208.7
61.2
23.4
229.3
67.2
24.8
250.9
73.5
22.8
202.4
59.3
24.2
222.8
65.3
25.7
244.2
71.6
27.3
266.7
78.2
22.5
203.0
59.5
23.9
224.1
65.7
25.4
246.3
72.2
26.9
269.5
79.0
27.2
228.6
67.0
29.0
250.8
73.5
30.9
274.2
80.4
87.5
32.9
298.7
25.5
228.3
66.9
27.1
251.5
73.7
28.8
275.8
80.8
30.5
301.3
88.3
30.3
271.3
79.5
32.2
300.3
88.0
34.1
330.9
97.0
36.1
363.1
106.4
29.6
275.2
80.7
31.5
303.4
88.9
33.4
333.1
97.6
35.3
364.4
106.8
33.2
296.2
86.8
35.3
326.2
95.6
37.5
357.8
104.9
39.7
390.9
114.6

PI
KW
7.7
8.2
8.7
9.2
10.9
11.6
12.3
13.0
15.6
16.6
17.6
18.7
15.5
16.5
17.5
18.5
18.4
19.5
20.6
21.8
21.9
23.2
24.6
26.1
23.9
25.4
26.9
28.5
23.5
25.0
26.6
28.1
28.5
30.4
32.3
34.3
26.8
28.5
30.2
32.0
31.7
33.7
35.8
37.9
31.2
33.1
35.1
37.2
34.9
37.1
39.3
41.6

Shaded Values are at 120F (49C) condenser entering air temperature.

ACUX Series Condensing Units


Page 18

125F (52C)
PI
Total Capacity
MBH
KW
KW
63.3
18.6
8.0
70.5
20.7
8.5
78.1
22.9
9.0
86.1
25.2
9.6
87.2
25.5
11.4
96.3
28.2
12.1
105.9
31.0
12.8
115.9
34.0
13.6
126.0
36.9
16.3
139.0
40.7
17.3
152.6
44.7
18.3
166.9
48.9
19.4
126.6
37.1
16.0
141.1
41.4
17.1
156.3
45.8
18.1
172.2
50.5
19.1
154.8
45.4
19.2
171.9
50.4
20.4
190.1
55.7
21.6
209.2
61.3
22.8
174.3
51.1
22.8
192.6
56.4
24.2
211.7
62.1
25.6
231.7
67.9
27.1
186.4
54.6
24.8
205.3
60.2
26.3
225.3
66.0
27.9
246.1
72.1
29.5
186.8
54.7
24.4
206.5
60.5
25.9
227.2
66.6
27.5
248.9
72.9
29.1
210.8
61.8
29.5
231.4
67.8
31.4
253.1
74.2
33.4
275.7
80.8
35.4
210.3
61.6
27.8
231.9
68.0
29.5
254.5
74.6
31.3
278.1
81.5
33.1
250.4
73.4
32.9
277.4
81.3
35.0
306.0
89.7
37.1
335.9
98.5
39.3
253.6
74.3
32.4
279.8
82.0
34.5
307.5
90.1
36.5
336.5
98.6
38.6
272.9
80.0
36.2
300.8
88.2
38.5
330.2
96.8
40.8
360.8
105.8
43.1
Table 9 Continued

Capacity Ratings - 60 Hz

Model

SST

ACUX

6035

6036

6038

6042

6046

6048

6050

6057

6060

6066

6070

6074

F
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50
35
40
45
50

C
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0
1.7
4.4
7.2
10.0

95 F (35 C)
Total Capacity
MBH
KW
376.9
110.5
417.5
122.4
460.5
135.0
506.0
148.3
392.9
115.2
432.9
126.9
475.3
139.3
520.2
152.5
407.4
119.4
449.0
131.6
493.1
144.5
539.7
158.2
449.9
131.9
496.2
145.4
545.3
159.8
597.4
175.1
497.7
145.9
549.3
161.0
604.1
177.0
662.1
194.1
525.4
154.0
578.8
169.6
635.4
186.2
695.3
203.8
552.4
161.9
607.5
178.1
665.8
195.1
727.4
213.2
562.1
164.7
620.3
181.8
682.0
199.9
747.1
219.0
595.0
174.4
656.0
192.3
720.7
211.2
788.9
231.2
649.8
190.5
719.2
210.8
792.9
232.4
870.8
255.2
692.0
202.8
765.4
224.3
843.1
247.1
925.2
271.2
732.8
214.8
809.8
237.4
891.3
261.2
977.3
286.4

PI
KW
35.0
36.9
38.9
41.0
34.2
36.2
38.2
40.4
34.4
36.4
38.5
40.6
37.7
39.9
42.1
44.4
40.8
43.0
45.3
47.7
45.3
47.9
50.7
53.5
49.8
52.9
56.1
59.4
49.3
52.1
55.1
58.1
53.4
56.5
59.8
63.3
56.0
59.0
62.2
65.5
63.7
67.3
71.1
74.9
71.5
75.7
80.0
84.4

Condenser
105F (40C)
Total Capacity
MBH
KW
350.8
102.8
389.1
114.0
429.8
126.0
472.9
138.6
366.5
107.4
404.1
118.4
444.1
130.2
486.3
142.5
379.9
111.4
419.1
122.8
460.6
135.0
504.5
147.9
419.9
123.1
463.4
135.8
509.7
149.4
558.8
163.8
464.4
136.1
512.9
150.3
564.6
165.5
619.4
181.5
490.1
143.6
540.3
158.4
593.6
174.0
650.0
190.5
515.2
151.0
566.9
166.2
182.2
621.7
679.6
199.2
523.8
153.5
578.7
169.6
636.9
186.7
698.3
204.7
554.5
162.5
612.0
179.4
672.9
197.2
737.3
216.1
605.5
177.5
671.1
196.7
740.7
217.1
814.5
238.7
644.2
188.8
713.4
209.1
786.9
230.6
864.6
253.4
681.5
199.7
754.2
221.1
831.3
243.7
912.6
267.5

Entering Air Temperature


115F (46C)
Total Capacity
PI
KW
MBH
KW
36.8
324.9
95.2
39.0
361.0
105.8
41.1
399.3
117.0
43.3
440.0
129.0
36.3
340.2
99.7
38.5
375.4
110.0
40.7
412.8
121.0
43.1
452.5
132.6
36.6
352.4
103.3
38.8
389.2
114.1
41.0
428.1
125.5
43.4
469.3
137.6
40.1
389.9
114.3
42.5
430.6
126.2
45.0
474.0
138.9
47.5
520.1
152.5
43.4
431.0
126.3
45.9
476.6
139.7
48.5
525.1
153.9
51.2
576.6
169.0
48.1
454.9
133.3
51.0
501.9
147.1
54.0
551.8
161.7
57.1
604.7
177.2
52.7
478.2
140.1
56.1
526.5
154.3
59.6
577.7
169.3
63.2
631.9
185.2
52.2
485.7
142.4
55.3
537.2
157.5
58.6
591.9
173.5
61.9
649.6
190.4
56.4
514.3
150.7
59.9
568.2
166.5
63.5
625.4
183.3
67.2
685.7
201.0
59.2
561.6
164.6
62.7
623.3
182.7
66.2
688.8
201.9
69.8
758.2
222.2
67.1
596.9
175.0
71.1
662.1
194.1
75.2
731.3
214.3
79.3
804.3
235.7
75.1
631.0
184.9
79.6
699.5
205.0
84.1
772.0
226.3
88.8
848.5
248.7

PI
KW
38.6
40.8
43.1
45.4
38.2
40.6
43.1
45.6
38.6
41.0
43.4
45.9
42.4
45.0
47.7
50.4
46.0
48.7
51.5
54.3
50.7
53.9
57.1
60.4
55.5
59.1
62.8
66.5
54.8
58.2
61.7
65.2
59.2
63.0
66.8
70.8
62.3
66.0
69.9
73.8
70.3
74.5
78.8
83.1
78.3
83.0
87.7
92.5

Shaded Values are at 120F (49C) condenser entering air temperature.

ACUX Series Condensing Units


Page 19

125F (52C)
Total Capacity
PI
MBH
KW
KW
299.7
87.8
40.1
333.5
97.7
42.4
369.4
108.3
44.7
407.4
119.4
47.0
314.1
92.1
40.0
346.9
101.7
42.5
381.7
111.9
45.1
418.6
122.7
47.7
325.0
95.3
40.4
359.3
105.3
42.8
395.6
115.9
45.4
433.9
127.2
47.9
360.0
105.5
44.4
398.0
116.7
47.2
438.5
128.5
50.0
481.4
141.1
52.9
397.7
116.6
48.2
440.3
129.0
51.1
485.6
142.3
54.1
533.6
156.4
57.1
419.8
123.0
53.0
463.6
135.9
56.4
510.1
149.5
59.7
559.4
163.9
63.2
441.3
129.4
57.9
486.3
142.5
61.6
534.0
156.5
65.5
584.3
171.3
69.3
448.1
131.3
57.1
496.2
145.4
60.7
547.2
160.4
64.3
600.9
176.1
67.9
474.7
139.1
61.7
525.0
153.9
65.6
578.3
169.5
69.6
634.4
185.9
73.7
518.5
152.0
64.9
576.2
168.9
68.9
637.5
186.8
73.0
702.2
205.8
77.1
550.8
161.4
73.0
611.8
179.3
77.3
676.4
198.2
81.8
744.5
218.2
86.2
170.6
81.0
582.0
646.1
189.4
85.8
713.9
209.2
90.5
785.2
230.1
95.2
Table 9

Electrical Data - 50 Hz

380-415V/3Ph/50Hz (Tolerance : 342V - 440V)

Unit Characteristic

Model
ACUX

MFA

MCA

5011
5015
5021
5023
5026
5030
5032
5033
5036
5038
5042
5043
5045
5051
5052
5053
5060
5064
5070
5074
5075
5080
5085
5090
5095
5105

63
80
100
100
125
125
160
125
160
160
160
160
200
250
250
200
250
250
250
315
315
315
315
315
400
400

31
40
57
55
68
75
87
82
89
107
101
108
120
147
138
129
149
149
172
193
190
206
213
216
241
267

Compressor

ICF
DOL
143
141
199
167
179
186
318
227
234
355
243
336
472
578
386
360
397
380
417
442
545
561
645
571
669
698

PWS
159
246
168
175
274
209
253
372
457
291
274
302
323
325
375
419
435
494
474
522
577

Condenser Fan Motor

Qty.

MOC

RLA

LRA

Qty.

FLA

LRA

1
1
1
2
+
2
1
+
+
1
2
+
1
1
+
+
+
2
+
2
+
+
+
2
+
2

22
29
42
22
+
29
64
+
+
81
42
+
91
113
+
+
+
64
+
81
+
+
+
91
+
113

20
27
38
20
+
27
58
+
+
74
38
+
84
103
+
+
+
58
+
74
+
+
+
84
+
103

121
129
177
121
+
129
288
+
+
325
177
+
444
544
+
+
+
288
+
325
+
+
+
444
+
544

1
2
2
2
3
3
3
3
3
3
4
4
4
4
4
4
4
4
6
6
6
6
6
6
8
8

4.2
2.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
3.4
3.4
3.4
4.2
4.2
4.2
4.2
4.2
3.4
4.2
4.2
4.2
4.2
4.2
3.4
4.2

18.7
8.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
14.4
14.4
14.4
18.7
18.7
18.7
18.7
18.7
14.4
18.7
18.7
18.7
18.7
18.7
14.4
18.7

1
1
1
1
1
1
1
1
1
1
1
1

1 22
1 22
1 29
1 22
1 29
1 42
1 42
1 64
1 64
1 81
1 64
1 91

29

20

42
42

20
27

64

20

81
64
81

27
38
38

81

58

91 58
91 74
113 58
113 84

27 121
38 121
38 129
58 121
74 129
58 177
74 177
74 288
84 288
84 325
103 288
103 444

129
177
177
288
325
288
325
325
444
444
544
544

Table 10

440V/3Ph/50Hz (Tolerance : 400V - 462V)

Unit Characteristic

Model
ACUX

MFA

MCA

5011
5015
5021
5023
5026
5030
5032
5033
5036
5038
5042
5043
5045
5051
5052
5053
5060
5064
5070
5074
5075
5080
5085
5090
5095
5105

63
80
100
100
125
125
160
125
160
200
160
200
200
250
200
250
250
250
250
315
315
315
315
315
315
400

30
39
56
54
66
73
85
80
87
105
98
105
117
145
135
126
146
146
168
190
186
202
210
212
236
262

Compressor
ICF

DOL
140
140
196
164
175
182
314
223
230
351
239
332
468
574
382
356
393
376
413
436
539
555
639
565
663
691

PWS
155
242
167
174
270
205
250
368
450
288
271
299
316
321
367
416
432
491
466
517
568

Condenser Fan Motor

Qty.

MOC

RLA

LRA

Qty.

FLA

LRA

1
1
1
2
+
2
1
+
+
1
2
+
1
1
+
+
+
2
+
2
+
+
+
2
+
2

22
29
42
22
+
29
64
+
+
81
42
+
91
113
+
+
+
64
+
81
+
+
+
91
+
113

20
27
38
20
+
27
58
+
+
74
38
+
84
103
+
+
+
58
+
74
+
+
+
84
+
103

121
129
177
121
+
129
288
+
+
325
177
+
444
544
+
+
+
288
+
325
+
+
+
444
+
544

1
2
2
2
3
3
3
3
3
3
4
4
4
4
4
4
4
4
6
6
6
6
6
6
8
8

3.6
1.9
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
2.7
2.7
2.7
3.6
3.6
3.6
3.6
3.6
2.7
3.6
3.6
3.6
3.6
3.6
2.7
3.6

16
7.9
16
16
16
16
16
16
16
16
13.1
13.1
13.1
16
16
16
16
16
13.1
16
16
16
16
16
13.1
16

1
1
1
1
1
1
1
1
1
1
1
1

1 22
1 22
1 29
1 22
1 29
1 42
1 42
1 64
1 64
1 81
1 64
1 91

29

20

42
42

20
27

64

20

81
64
81

27
38
38

81

58

91 58
91 74
113 58
113 84

27 121
38 121
38 129
58 121
74 129
58 177
74 177
74 288
84 288
84 325
103 288
103 444

129
177
177
288
325
288
325
325
444
444
544
544

Table 11
For Legend, please refer to page 20

Voltage imbalance between phases to be < 2 %

ACUX Series Condensing Units


Page 20

Electrical Data - 60 Hz

380V/3Ph/60Hz (Tolerance : 342V - 418V)

Unit Characteristic

Model
ACUX

MFA

MCA

6014
6018
6025
6027
6031
6035
6037
6038
6042
6044
6050
6051
6053
6061
6062
6063
6070
6075
6080
6085
6090
6095
6100
6105
6110
6120

63
80
125
125
125
160
200
160
200
250
200
250
250
315
315
315
315
315
315
315
315
400
400
400
400
500

37
48
69
66
82
90
104
98
106
128
118
127
142
177
165
154
178
178
203
232
228
247
257
259
286
321

Condenser Fan Motor

Compressor
ICF

DOL
173
153
240
202
203
211
365
274
282
417
284
378
544
416
468
440
483
522
641
660
728

PWS

Qty.

MOC

RLA

LRA

Qty.

FLA

LRA

1
1
1
2
+
2
1
+
+
1
2
+
1
1
+
+
+
2
+
2
+
+
+
2
+
2

26
35
50
26
+
35
76
+
+
97
50
+
109
135
+
+
+
76
+
97
+
+
+
109
+
135

24
32
45
24
+
32
69
+
+
88
45
+
100
123
+
+
+
69
+
88
+
+
+
100
+
123

142
138
209
142
+
138
324
+
+
376
209
+
514
601
+
+
+
324
+
376
+
+
+
514
+
601

1
2
2
2
3
3
3
3
3
3
4
4
4
4
4
4
4
4
6
6
6
6
6
6
8
8

5.4
3.2
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
3.8
3.8
3.8
5.4
5.4
5.4
5.4
5.4
3.8
5.4
5.4
5.4
5.4
5.4
3.8
5.4

27.5
12.2
27.5
27.5
27.5
27.5
27.5
27.5
27.5
27.5
16
16
16
27.5
27.5
27.5
27.5
27.5
16
27.5
27.5
27.5
27.5
27.5
16
27.5

193
1
284
200
208
323
244
285
428
520
339
313
352
381
377
450
490
509
555
565
584
664

1
1
1
1
1
1
1
1
1
1
1

1 26
1 26
1 35
1 26
1 35
1 50
1 50
1 76
1 76
1 97
1 76
1 109

35

24

50
50

24
32

76

24

97
76
97

32
45
45

97

69

109 69
109 88
135 69
135 100

32 142
45 142
45 138
69 142
88 138
69 209
88 209
88 324
100 324
100 376
123 324
123 514

138
209
209
324
376
324
376
376
514
514
601
601

Table 12

460V/3Ph/60Hz (Tolerance : 396V - 528V)

Unit Characteristic

Model
ACUX

MFA

MCA

6014
6018
6025
6027
6031
6035
6037
6038
6042
6044
6050
6051
6053
6061
6062
6063
6070
6075
6080
6085
6090
6095
6100
6105
6110
6120

63
80
100
100
125
160
160
160
160
200
200
200
250
250
250
250
250
250
315
315
315
315
315
315
315
400

32
41
59
57
70
77
89
84
91
109
102
109
121
150
141
132
152
152
174
198
195
211
218
221
244
273

Compressor
ICF

DOL
156
146
212
181
194
201
333
242
249
370
246
339
475
594
402
376
413
396
422
459
562
578
662
588
674
717

PWS

Qty.

MOC

RLA

LRA

Qty.

FLA

LRA

1
1
1
2
+
2
1
+
+
1
2
+
1
1
+
+
+
2
+
2
+
+
+
2
+
2

22
29
42
22
+
29
64
+
+
81
42
+
91
113
+
+
+
64
+
81
+
+
+
91
+
113

20
27
38
20
+
27
58
+
+
74
38
+
84
103
+
+
+
58
+
74
+
+
+
84
+
103

121
129
177
121
+
129
288
+
+
325
177
+
444
544
+
+
+
288
+
325
+
+
+
444
+
544

1
2
2
2
3
3
3
3
3
3
4
4
4
4
4
4
4
4
6
6
6
6
6
6
8
8

5
2.9
5
5
5
5
5
5
5
5
3.7
3.7
3.7
5
5
5
5
5
3.7
5
5
5
5
5
3.7
5

31.5
14.4
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
17.3
17.3
17.3
31.5
31.5
31.5
31.5
31.5
17.3
31.5
31.5
31.5
31.5
31.5
17.3
31.5

172
1
261
171
178
288
216
254
378
484
294
277
305
350
327
404
424
440
499
503
525
607

Condenser Fan Motor

1
1
1
1
1
1
1
1
1
1
1

1 22
1 22
1 29
1 22
1 29
1 42
1 42
1 64
1 64
1 81
1 64
1 91

29

20

42
42

20
27

64

20

81
64
81

27
38
38

81

58

91 58
91 74
113 58
113 84

27 121
38 121
38 129
58 121
74 129
58 177
74 177
74 288
84 288
84 325
103 288
103 444

129
177
177
288
325
288
325
325
444
444
544
544

Table 13
For Legend, please refer to page 20

Voltage imbalance between phases to be < 2 %

ACUX Series Condensing Units


Page 21

Electrical Data - 60 Hz
Unit Characteristic

Model
ACUX

MFA

MCA

6014
6018
6025
6027
6031
6035
6037
6038
6042
6044
6050
6051
6053
6061
6062
6063
6070
6075
6080
6085
6090
6095
6100
6105
6110
6120

100
125
200
200
200
250
315
315
315
315
315
315
400
500
400
400
500
500
500
630
630
630
630
630
800
800

65
86
124
117
146
162
188
176
192
232
215
230
257
320
301
281
325
325
371
422
414
449
466
470
519
583

DOL
325
287
475
377
375
391
536
552
558
716
847
784
871
-

220V/3Ph/60Hz (Tolerance : 187V - 253V)

Compressor

ICF
PWS
378
536
392
408
601
473
539
901
1058
631
590
655
711
702
830
1015
1050
1127
1148
1180
1320

1
1
1
1
1
1
1
1
1
1
1
1

Condenser Fan Motor

Qty.

MOC

RLA

LRA

Qty.

FLA

LRA

1
1
1
2
+
2
1
+
+
1
2
+
1
1
+
+
+
2
+
2
+
+
+
2
+
2

45
61
91
45
+
61
139
+
+
178
91
+
199
248
+
+
+
139
+
178
+
+
+
199
+
248

43
59
83
43
+
59
127
+
+
162
83
+
183
225
+
+
+
127
+
162
+
+
+
183
+
225

274
263
424
274
+
263
622
+
+
709
424
+
1105
1254
+
+
+
622
+
709
+
+
+
1105
+
1254

1
2
2
2
3
3
3
3
3
3
4
4
4
4
4
4
4
4
6
6
6
6
6
6
8
8

9.4
5.5
9.4
9.4
9.4
9.4
9.4
9.4
9.4
9.4
6.7
6.7
6.7
9.4
9.4
9.4
9.4
9.4
6.7
9.4
9.4
9.4
9.4
9.4
6.7
9.4

47.6
21.2
47.6
47.6
47.6
47.6
47.6
47.6
47.6
47.6
27.7
27.7
27.7
47.6
47.6
47.6
47.6
47.6
27.7
47.6
47.6
47.6
47.6
47.6
27.7
47.6

1 45
1 45
1 61
1 45
1 61
1 91
1 91
1 139
1 139
1 178
1 139
1 199

61

43

91
91

43
59

139

43

178
139
178

59
83
83

178 127
199 127
199 162
248 127
248 183

59 274
83 274
83 263
127 274
162 263
127 424
162 424
162 622
183 622
183 709
225 622
225 ###

Voltage imbalance between phases to be < 2 %


Legend
MFA : Maximum Fuse Amperes
ICF : Max. Instantaneous Current Flow
FLA : Full Load Amperes

PWS
LRA
MOC

263
424
424
622
709
622
709
709
###
###
###
###

Table 14
: Part Winding Start of Compressor
: Locked Rotor Amperes
: Maximum Operating Current

MCA
DOL
RLA

Typical Wiring Diagram

ACUX Series Condensing Units


Page 22

: Minimum Circuit Amps (for wire sizing)


: Direct On Line Starting of Compressor
: Rated Load Amperes at 45F(7.2C)
S.S.T and 115F (46C) ambient temp.

Dimensional Data

ACUX Series Condensing Units


Page 23

Dimensional Data

ACUX Series Condensing Units


Page 24

GUIDE SPECIFICATIONS
GENERAL

REFRIGERANT PIPING

Condensing units shall be composed of


compressor(s), coil(s) with fan(s), refrigerant piping,
electrical components & enclosing cabinet in one
piece. These units shall be factory assembled,
internally wired, refrigerant charged with R22, tested
under strict quality standards & are suitable for use
in systems with indoor units connected to remote
condensing units.

Refrigerant circuit piping shall be fabricated from


ACR grade copper including vibration eliminator &
hot gas discharge muffler. The piping connections
shall be terminated with sealed & soldered copper
pipe ends, which give much simplicity & ease to the
installation.

Units should be capable to operate from 50F (10C)


to 125F (52C) ambient temperature, and shall be
selected in accordance with project requirements
and installed as per Installation, Operation &
Maintenance Manual.

Unit casing shall be made of zinc coated galvanized


steel sheets conforming to JIS-G3302 and ASTMA653
which shall be phosphatized and then elctrostatically
dry powder coated of approximately 60 microns to
provide an extremely tough, scratch resistance,
excellent anti-corrosive protection that can pass 1000
Hrs in 5% salt spray testing at 95F (35C) and 95%
relative humidity as per ASTM B117-95.

COMPRESSOR(S)
Compressor(s) shall be of high energy efficiency
ratio, fully accessible, semi hermetic reciprocating
type with Discus valves, equipped with crankcase
heater, oil pump, refrigerant gas cooled electric
motor, preset internal relief valve, inherent thermistor
motor protection, suction and discharge service
valves, oil sight glass and shall be mounted on
spring anti vibration mounts to minimize vibration
transmissions. These compressors conform to DIN
standards.

COIL(S):
Coil(s) shall be air cooled with integral sub-cooling
circuit, constructed of seamless copper tubes 3/8
OD mechanically bonded to wavy Aluminum (Copper)
fins with maximum 12 FPI (2.1mm) spacing. Coil(s)
shall be tested against leakage by pressurizing air
at 450 psig (3100 Kpa) in coil, under water, cleaned
and dehydrated at the factory. Coil shall confirm to
ARI-410/91.

CASING

Unit casing shall be provided with access panels for


easy service and maintenance of all units parts.

CONTROL PANEL:
The panel shall be factory wired in accordance with
NEC 430 & 440, and conforms to IP54 requirements.
Control Panel shall contain individual electrical
components contactors, overload relays,
transformer, anti-recycling time delay relay, control
circuit disconnect switch, power & control circuit
terminal blocks, high / low pressure & oil failure
switch.
(Please refer to page 5 for detailed information of
Control Panel).

FANS(S)& MOTOR(S)
Unit shall be furnished with direct driven propeller
type, discharging air upward fan(s). These fans are
equipped with Aluminum blades, permanently
lubricated bearings, and inherent corrosion
resistance shaft. Each condenser fan shall be
balanced statically and dynamically at the factory.
Complete fan assembly is provided with suitable
acrylic coated fan guard.
Motor(s) shall be Totally Enclosed Air Over (TEAO),
6 poles, with class F insulation, minimum IP55
protection and factory wired to unit control panel.

GUIDE SPECIFICATIONS
ACUX Series Condensing Units