Professional Documents
Culture Documents
Brisbane 11 13 October
Tutorials OCP Configuration Tool Basic Protection Setting Activities Protection Features MODBUS Configuration MODBUS Implementation DNP3 Configuration DNP3 Implementation IEC 60870-5-101 Configuration
Nu-Lec Industries Pty Ltd ACN 085 972 425 35-37 South Street, Lytton, Queensland 4178 Australia Tel: (07) 3249 5444 Intl: +61 7 3249 5444 Fax: (07) 3249 5888 Intl: +61 7 3249 5888
Quality Endorsed Company ISO9001 Lic No 2477 Standards Australia
Page 2 of 2 Location:
21-09-2010
Step 1 Launch WSOS5 and manually create a new file for an N Series ACR and ADVC2 controller with a flexVUE panel.
Click on the New Switchgear icon on the tool bar or select New from the File menu. In the New Switchgear Device Wizard select Manual Creation and:
- Platform ADVC2 ACR - Product N Series - Display flexVUE
Give the new switchgear a name and click on the Next button.
Step 2a Check that the file you just created has flexVUE panel capabilities
Select Select Capabilities and Protocols in the Customise menu. Select the Capabilities tab on the Select Capabilities and Protocols dialogue and check that the flexVUE options is checked.
Step 2b Check that the file you just created has flexVUE panel capabilities
Select OCP Display in the Display menu. This will launch the OCP Display dialogue to allow an OCP mapping to be attached to this switchgear file.
Step 3 Open the OCP Configuration Tool from the Customise Menu
Select OCP Configuration Tool and Open in the Customise menu. This will launch the OCP Configuration dialogue. Select to open a new file suitable for
- All switchgear - Latest software.
Launch the Customise Global OCP Settings dialogue box by right clicking with the curson on the display. Configure the Global OCP Settings as follows: Beep Pattern
- Double Short Beep
Individually configured lamp colours Default font No Panel ON when Door is opened. Beep on Key/Button Press
Schneider Electric < AUTHOR > <DATE>
Press Apply or OK
Select Save As in the OCP Configuration Tool menu N.B. The OCP Configuration Tool menu is only available when the tool is open. Save the current file as Training OCP Configuration.ocp.
Select Properties in the Customise menu to launch the System Properties dialogue box. When the System Properties dialogue appears select the Directories tab. The location of the saved OCP file can be found under Configurable OCP Directory
Left click with the cursor over Status Lamp a1. This will launch the Customise Status Lamp dialogue box for a1. Launch the Logic Expression Builder by clicking on the fx button and search for the Lockout function. Left clicking on individual functions will display extra information on that function.
Schneider Electric < AUTHOR > <DATE> 10
Enter appropriate text in the Label Description and Comments fields. N.B. The comments entered will appear on the Operator Control Panel screen when the Lamp Data for this lamp is selected. Click on OK or Apply to save the configured settings for Status Lamp a1.
11
Open the Customise Status Lamp dialogue box for Status Lamp c6. Open the Logic Expression Builder, locate the Data Point for Auxiliary Supply Fail and check its details. Configure the lamp so that it is:
- Steady Green when the auxiliary supply is normal - Flashing Red when the Auxiliary supply has failed
Schneider Electric < AUTHOR > <DATE> 12
Open the Customise Status Lamp dialogue box for Status Lamp c8. Configure Status Lamp c8 to flash Red at all times (even if the panel is off) if any of the following conditions are present
- The Trip circuit is isolated. - The Close circuit is isolated. - The VI Contact Life is low. - The Gas Pressure is low or invalid.
13
Step 10a Configure Quick Action Key to toggle Auto Reclose On/Off
Configure QAK e1 to toggle Auto Reclose On/Off and display a steady Red LED when On providing:
- The panel is On - The Quick Action Keys are unlocked
Left click on QAK e1 to launch its Customise dialogue box. Use the Logic Expression Builders for Lamp and Key Action Logic.
Schneider Electric < AUTHOR > <DATE> 14
Step 10b Configure Quick Action Key to toggle Auto Reclose On/Off
Configure QAK e1 to toggle Auto Reclose On/Off and display a steady Red LED when On providing:
- The panel is On - The Quick Action Keys are unlocked
Left click on QAK e1 to launch its Customise dialogue box. Use the Logic Expression Builders for Lamp and Key Action Logic.
Schneider Electric < AUTHOR > <DATE> 15
Step 11 Configure Quick Action Keys to Select Remote and Local modes
Configure QAKs f1 and f2 to select Remote and Local modes respectively providing:
- The panel is On. - The Quick Action Keys are unlocked.
16
17
Select Save in the OCP Configuration Tool menu N.B. The OCP Configuration Tool menu is only available when the tool is open.
20
10
Step 14 Attach the file you just created to the Switchgear file
Select OCP Display in the Display menu. This will launch the OCP Display dialogue to allow an OCP mapping to be attached to this switchgear file.
21
11
Exercise No 5 Configure the Earth Fault protection such that for fault levels as shown, the tripping times are as follows: Trip No Trip 1 Trip 2 Trip 3 Trip 4 Protection Curve IEEE Moderately Inverse IEEE Very Inverse IEEE Extremely Inverse Trip not active. Fault Level 300 Amps <300 Amps >300 Amps <300 Amps >300 Amps Tripping Time 0.605s as per formulae 0.69s as per formulae 0.01s
Exercise No 6 Configure the reset curves for all active Phase and Earth trips to match the pickup curves. Exercise No 7 Configure the protection to start to reset when the current falls below 95% of the pickup level. Exercise No 8 Configure the protection settings such that if an Earth Fault pickup occurs when Auto Reclose is OFF, the recloser will trip instantaneously. Exercise No 9 Configure the protection settings such that although the Earth Trip Current Setting is 30 Amps, an Earth Fault protection trip will not occur when the earth current is less than 36 Amps.
Exercise No 10 Apply settings such that an SEF fault will always cause the ACR to trip in 10s when: Trips to Lockout = 3 SEF Trips to Lockout = 1 Exercise No 11 Apply the appropriate modifiers to the Phase protection curves such that an instantaneous trip should occur if there is a phase fault on the feeder between the recloser and the next protection device. N.B. The maximum short circuit current at the next protection device is 3000 Amps Exercise No 12 Go on-line to your controller and write the settings in your off-line file. Exercise No 13 Use Waveform Generation to simulate the faults described in exercises 4 and 5 and check the tripping times from events recorded in the Event Log. Exercise No 14 On successful completion of the previous exercise, read the switchgear settings from the controller and go off-line.
Tables for the times to trip for each of these curves are given below.
1.10 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00 6.50 7.00 7.50 8.00 8.50 9.00 9.50 10.00 10.50 11.00 11.50 12.00 12.50 13.00 13.50 14.00 14.50 15.00 15.50 16.00 16.50 17.00 17.50 18.00 18.50 19.00
73.37 17.19 10.03 7.57 6.30 5.52 4.98 4.58 4.28 4.04 3.84 3.67 3.53 3.40 3.30 3.20 3.12 3.04 2.97 2.91 2.85 2.80 2.75 2.70 2.66 2.62 2.58 2.55 2.52 2.48 2.46 2.43 2.40 2.38 2.35 2.33 2.31
Tables for the times to trip for each of these curves are given below.
1.10 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00 6.50 7.00 7.50 8.00 8.50 9.00 9.50 10.00 10.50 11.00 11.50 12.00 12.50 13.00 13.50 14.00 14.50 15.00 15.50 16.00 16.50 17.00 17.50
27.11 6.44 3.80 2.90 2.43 2.14 1.95 1.80 1.69 1.60 1.53 1.46 1.41 1.37 1.33 1.29 1.26 1.23 1.21 1.18 1.16 1.14 1.12 1.11 1.09 1.08 1.06 1.05 1.04 1.03 1.02 1.01 1.00 0.99
18.00 18.50 19.00 19.50 20.00 20.50 21.00 21.50 22.00 22.50 23.00 23.50 24.00 24.50 25.00 25.50 26.00 26.50 27.00 27.50 28.00 28.50 29.00 29.50 30.00
0.98 0.97 0.96 0.96 0.95 0.94 0.93 0.93 0.92 0.92 0.91 0.90 0.90 0.89 0.89 0.88 0.88 0.87 0.87 0.87 0.86 0.86 0.85 0.85 0.85
Live Load Blocking 1. 2. 3. 4. 5. Open the recloser and select Live Load Blocking ON. Run the Waveform Generator and simulate 3 phase voltages greater than the Live Line Threshold setting on the Source side. Check that the recloser can be closed and opened. Change the Power Direction to the alternate setting. Check that a panel close request is blocked and the appropriate events are logged.
1. 2. 3. 4. 5.
8. 9.
8.
8.
10. Check that the status of Binary Outputs are only reported in a Class 0 poll when Binary Outputs Status Reporting is On. .
8.