Air System Sizing Summary for WR Area

Project Name: Vantage-Harrisburg Prepared by: asdf 07/27/2012 08:38AM

Air System Information Air System Name: Air System Type:

WR Area VAV

Number of zones: Floor Area: Location:

5 5071.0 sqft Harrisburg, Pennsylvania

Sizing Calculation Information Calculation Months: Central Cooling Coil Sizing Data Total coil load: Total coil load: Sensible coil load: Coil airflow: Sensible heat ratio: Area per unit load: Load per unit area:

Jan to Dec

Calculation method:

Radiant Time Series

12.2 146.6 87.2 2109 0.595 415.0 28.9

Tons MBH MBH CFM sqft/Ton BTU/(hr-sqft)

Load occurs at: OA DB / WB: Entering DB / WB: Leaving DB / WB: Coil ADP: Bypass Factor: Resulting RH: Design supply temp:

Aug 1500 92.0/74.0 92.0/74.0 53.3/52.1 49.0 0.100 54 54.0

F F F F % F

Preheat Coil Sizing Data Max coil load: Coil airflow: Max coil airflow: Supply Fan Sizing Data Actual max airflow: Standard airflow: Actual max airflow per unit area: Outdoor Ventilation Air Data Design airflow: Airflow per unit floor area: Zone Sizing Data Zone Name

29.4 MBH 1508 CFM 3558 CFM

Load occurs at: Ent DB / Lvg DB:

Jan 600 33.8/52.0 F

3558 CFM 3519 CFM 0.70 CFM/sqft

Fan motor BHP: Fan motor kW: Fan static:

1.04 BHP 0.77 kW 1.00 in wg

3245 CFM 0.64 CFM/sqft

Airflow per person:

36.88 CFM/person

Rm. 009-Mens WR Rm. 010-Mens Locker Rm. 011-Womens WR Rm. 012-Womens Locker Rm. 001-Office Vestibule

Maximum Cooling Sensible MBH 4.8 14.3 4.8 13.8 9.9

Design Airflow CFM 560 1115 560 1010 439

Minimum Time of Peak Maximum Air Flow Load Heating Load CFM MBH 17 111 18 101 7 Jan 2100 Jan 2100 Jan 2100 Jan 2100 Sep 1400 0.0 0.0 0.0 0.0 5.7

Zone Floor Area sqft 340.0 2229.0 350.0 2020.0 132.0

Zone CFM/sqft

1.65 0.50 1.60 0.50 3.33

Reheat Coil Load MBH 0.3 1.9 0.3 1.7 5.8

Block Load 4.15

Page 1 of 9

System Design Load Summary for WR Area


Project Name: Vantage-Harrisburg Prepared by: asdf 07/27/2012 08:38AM

Zone Loads based on RTS Window and Skylight Solar Loads Wall Transmission Roof Transmission Window Transmission Skylight Transmission Door Loads Floor Transmission Partitions/Ceilings Overhead Lighting Electric Equipment People Infiltration Miscellaneous Safety Factor >>Total Zone Loads Thermostat and Pulldown Adjustment Plenum Wall Load Plenum Roof Load Plenum Lighting Load Ventilation Load Supply Fan Load >> Total System Loads Central Cooling Coil Preheat Coil Terminal Reheat Coils >> Total Coil Loads Key:

DESIGN COOLING Aug 1500 OA DB / WB 92 F / 74 F Details Sensible Latent BTU/hr BTU/hr 50 sqft 3316 339 sqft 420 132 sqft 80 50 sqft 403 0 sqft 0 42 sqft 3215 5071 sqft 0 0 sqft 0 5084 W 11378 0W 0 88 20525 18040 120 121 0 0 15% / 15% 5918 2724 45375 20885 2576 0 0% 0 70% 186 30% 5204 2109 CFM 32243 38576 2109 CFM 1595 87180 59460 87180 59461 0 0 87180 59461 Positive values are clg loads Negative values are htg loads

DESIGN HEATING Design Heating Day OA DB / WB 9 F / 6.7 F Details Sensible Latent BTU/hr BTU/hr 50 sqft 339 sqft 682 132 sqft 322 50 sqft 1793 0 sqft 0 42 sqft 1452 5071 sqft 276 0 sqft 0 0W 0 0W 0 0 0 0 430 0 0 0 15% 743 0 5699 0 -55 0 0 0 0 0 0 0 254 CFM 16388 0 254 CFM -667 21366 0 -125 0 11644 9846 21366 0 Positive values are htg loads Negative values are clg loads

Block Load 4.15

Page 2 of 9

Zone Design Load Summary for WR Area


Project Name: Vantage-Harrisburg Prepared by: asdf 07/27/2012 08:38AM

Rm. 009-Mens WR

Zone Loads based on RTS Window and Skylight Solar Loads Wall Transmission Roof Transmission Window Transmission Skylight Transmission Door Loads Floor Transmission Partitions/Ceilings Overhead Lighting Electric Equipment People Infiltration Miscellaneous Safety Factor >> Total Zone Loads

DESIGN COOLING Jan 2100 OA DB / WB 41.3 F / 39.5 F Thermostat Setpoint 75.0 F Details Sensible BTU/hr 0 sqft 0 0 sqft 0 0 sqft 0 0 sqft 0 0 sqft 0 0 sqft 0 340 sqft 0 0 sqft 0 340 W 797 0W 0 14 3381 0 0 15% / 15% 627 4804

Latent BTU/hr 2870 0 0 431 3301

DESIGN HEATING Design Heating Day OA DB / WB 9 F / 6.7 F Thermostat Setpoint 70.0 F Details Sensible BTU/hr 0 sqft 0 sqft 0 0 sqft 0 0 sqft 0 0 sqft 0 0 sqft 0 340 sqft 0 0 sqft 0 0W 0 0W 0 0 0 0 0 15% 0 0

Latent BTU/hr 0 0 0 0 0

Rm. 010-Mens Locker

Zone Loads based on RTS Window and Skylight Solar Loads Wall Transmission Roof Transmission Window Transmission Skylight Transmission Door Loads Floor Transmission Partitions/Ceilings Overhead Lighting Electric Equipment People Infiltration Miscellaneous Safety Factor >> Total Zone Loads

DESIGN COOLING Jan 2100 OA DB / WB 41.3 F / 39.5 F Thermostat Setpoint 75.0 F Details Sensible BTU/hr 0 sqft 0 0 sqft 0 0 sqft 0 0 sqft 0 0 sqft 0 0 sqft 0 2229 sqft 0 0 sqft 0 2229 W 5223 0W 0 30 7244 0 0 15% / 15% 1870 14337

Latent BTU/hr 6150 0 0 923 7073

DESIGN HEATING Design Heating Day OA DB / WB 9 F / 6.7 F Thermostat Setpoint 70.0 F Details Sensible BTU/hr 0 sqft 0 sqft 0 0 sqft 0 0 sqft 0 0 sqft 0 0 sqft 0 2229 sqft 0 0 sqft 0 0W 0 0W 0 0 0 0 0 15% 0 0

Latent BTU/hr 0 0 0 0 0

Block Load 4.15

Page 3 of 9

Zone Design Load Summary for WR Area


Project Name: Vantage-Harrisburg Prepared by: asdf 07/27/2012 08:38AM

Rm. 011-Womens WR

Zone Loads based on RTS Window and Skylight Solar Loads Wall Transmission Roof Transmission Window Transmission Skylight Transmission Door Loads Floor Transmission Partitions/Ceilings Overhead Lighting Electric Equipment People Infiltration Miscellaneous Safety Factor >> Total Zone Loads

DESIGN COOLING Jan 2100 OA DB / WB 41.3 F / 39.5 F Thermostat Setpoint 75.0 F Details Sensible BTU/hr 0 sqft 0 0 sqft 0 0 sqft 0 0 sqft 0 0 sqft 0 0 sqft 0 350 sqft 0 0 sqft 0 350 W 820 0W 0 14 3381 0 0 15% / 15% 630 4831

Latent BTU/hr 2870 0 0 431 3301

DESIGN HEATING Design Heating Day OA DB / WB 9 F / 6.7 F Thermostat Setpoint 70.0 F Details Sensible BTU/hr 0 sqft 0 sqft 0 0 sqft 0 0 sqft 0 0 sqft 0 0 sqft 0 350 sqft 0 0 sqft 0 0W 0 0W 0 0 0 0 0 15% 0 0

Latent BTU/hr 0 0 0 0 0

Rm. 012-Womens Locker

Zone Loads based on RTS Window and Skylight Solar Loads Wall Transmission Roof Transmission Window Transmission Skylight Transmission Door Loads Floor Transmission Partitions/Ceilings Overhead Lighting Electric Equipment People Infiltration Miscellaneous Safety Factor >> Total Zone Loads

DESIGN COOLING Jan 2100 OA DB / WB 41.3 F / 39.5 F Thermostat Setpoint 75.0 F Details Sensible BTU/hr 0 sqft 0 0 sqft 0 0 sqft 0 0 sqft 0 0 sqft 0 0 sqft 0 2020 sqft 0 0 sqft 0 2020 W 4733 0W 0 30 7244 0 0 15% / 15% 1797 13774

Latent BTU/hr 6150 0 0 923 7073

DESIGN HEATING Design Heating Day OA DB / WB 9 F / 6.7 F Thermostat Setpoint 70.0 F Details Sensible BTU/hr 0 sqft 0 sqft 0 0 sqft 0 0 sqft 0 0 sqft 0 0 sqft 0 2020 sqft 0 0 sqft 0 0W 0 0W 0 0 0 0 0 15% 0 0

Latent BTU/hr 0 0 0 0 0

Block Load 4.15

Page 4 of 9

Zone Design Load Summary for WR Area


Project Name: Vantage-Harrisburg Prepared by: asdf 07/27/2012 08:38AM

Rm. 001-Office Vestibule

Zone Loads based on RTS Window and Skylight Solar Loads Wall Transmission Roof Transmission Window Transmission Skylight Transmission Door Loads Floor Transmission Partitions/Ceilings Overhead Lighting Electric Equipment People Infiltration Miscellaneous Safety Factor >> Total Zone Loads

DESIGN COOLING Sep 1400 OA DB / WB 86.8 F / 71.2 F Thermostat Setpoint 75.0 F Details Sensible BTU/hr 50 sqft 2736 339 sqft 378 132 sqft 63 50 sqft 237 0 sqft 0 42 sqft 4747 132 sqft 0 0 sqft 0 145 W 323 0W 0 0 0 83 0 15% / 15% 1285 9853

Latent BTU/hr 0 87 0 13 100

DESIGN HEATING Design Heating Day OA DB / WB 9 F / 6.7 F Thermostat Setpoint 70.0 F Details Sensible BTU/hr 50 sqft 339 sqft 682 132 sqft 322 50 sqft 1793 0 sqft 0 42 sqft 1452 132 sqft 276 0 sqft 0 0W 0 0W 0 0 0 430 0 15% 743 5699

Latent BTU/hr 0 0 0 0 0

Block Load 4.15

Page 5 of 9

System PsychrometricsforWR Area


Project Name: Vantage-Harrisburg Prepared by: asdf 07/27/2012 08:38AM

Location: Harrisburg, Pennsylvania Altitude: 308.0 ft Data for: Aug DESIGN COOLING DAY, 1500
1. Outdoor Air 2.CentralCoolingCoilOutlet 3. Supply Fan Outlet 4. Room Air 5.ReturnPlenumOutlet

0.020 0.018 0.016


1

0.014 0.012

Specific Humidity ( lb/lb )

4 23

0.010 0.008 0.006 0.004 0.002 0.000 100

30

40

50

60

70 Temperature (F)

80

90

Block Load 4.15

Page 6 of 9

Ventilation Sizing Summary for WR Area


Project Name: Vantage-Harrisburg Prepared by: asdf 07/27/2012 08:38AM

Summary Ventilation Sizing Method: Design Ventilation Airflow Rate: Uncorrected Outdoor Airflow Rate: ASHRAE Std 62 Analysis Details Critical Space: Critical Space Outdoor Air Fraction (Z):

ASHRAE std 62-2001 3245 CFM 0 CFM

0.000

Uncorrected Outdoor Air Fraction (X): Corrected Outdoor Air Fraction (Y): Required System Ventilation Airflow:

0.000 0.000 0 CFM

Space Ventilation Analysis Table Zone Name Floor Area sqft 340.0 2229.0 350.0 2020.0 132.0 Totals Maximum Occupants 14.0 30.0 14.0 30.0 0.0 Maximum Supply Air CFM 560.0 1115.0 560.0 1010.0 439.3 3684.3 Required Outside Air CFM/person 0.00 0.00 0.00 0.00 0.00 Required Outside Air CFM/sqft 0.00 0.00 0.00 0.00 0.00 Required Required Uncorrected Uncorrected Outside Air Outside Air Outdoor Air Outdoor Air CFM (% of supply) CFM Ratio (Z) 0.0 0.0 0.0 0.000 0.0 0.0 0.0 0.000 0.0 0.0 0.0 0.000 0.0 0.0 0.0 0.000 0.0 0.0 0.0 0.000 0.0 0.000 Corrected Outdoor Air CFM 0.0 0.0 0.0 0.0 0.0 0.0

Rm. 009-Mens WR Rm. 010-Mens Locker Rm. 011-Womens WR Rm. 012-Womens Locker Rm. 001-Office Vestibule

Block Load 4.15

Page 7 of 9

System Psychrometrics Table for WR Area


Project Name: Vantage-Harrisburg Prepared by: asdf 07/27/2012 08:38AM

DESIGN COOLING DAY, Aug 1500


TABLE 1: SYSTEM DATA Component Location Dry-Bulb Temp F 92.0 92.0 92.0 53.3 54.0 75.5 87.9 Specific Airflow CFM Sensible Latent Heat Humidity Heat BTU/hr BTU/hr lb/lb 0.01410 2109 32243 38576 0.01410 2109 0.01410 2109 0 0.00809 2109 87180 59461 0.00809 2109 1595 0.01020 2109 47951 20885 0.01020 406 5390 -

Ventilation Air Vent - Return Mixing Preheat Coil Central Cooling Coil Supply Fan Zone Air Return Plenum

Inlet Outlet Outlet Outlet Outlet Outlet

Site Altitude = 308.0 ft Air Density x Heat Capacity x Conversion Factor = 1.0680 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor = 4694.0 BTU/(hr-CFM) TABLE 2: ZONE DATA Zone Name Zone Sensible Load BTU/hr 4630 13783 4656 13245 9060 T-stat Mode Zone Temp F Zone Airflow Reheat Coil CFM Load BTU/hr Cooling Cooling Cooling Cooling Cooling 75.2 75.3 75.2 75.3 75.5 217 646 218 620 406 0 0 0 0 0

Rm. 009-Mens WR Rm. 010-Mens Locker Rm. 011-Womens WR Rm. 012-Womens Locker Rm. 001-Office Vestibule

Block Load 4.15

Page 8 of 9

System Psychrometrics Table for WR Area


Project Name: Vantage-Harrisburg Prepared by: asdf 07/27/2012 08:38AM

WINTER DESIGN HEATING


TABLE 1: SYSTEM DATA Component Location Dry-Bulb Temp F 9.0 9.0 52.0 51.5 54.0 69.5 69.5 Specific Airflow CFM Sensible Latent Heat Humidity Heat BTU/hr BTU/hr lb/lb 0.00061 254 -16388 0 0.00061 254 0.00061 254 11644 0.00061 254 125 0 0.00061 254 667 0.00061 254 -5644 0 0.00061 7 0 -

Ventilation Air Vent - Return Mixing Preheat Coil Central Cooling Coil Supply Fan Zone Air Return Plenum

Inlet Outlet Outlet Outlet Outlet Outlet

Site Altitude = 308.0 ft Air Density x Heat Capacity x Conversion Factor = 1.0680 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor = 4694.0 BTU/(hr-CFM) TABLE 2: ZONE DATA Zone Name Zone Sensible Load BTU/hr 0 0 0 0 -5699 T-stat Mode Zone Temp F Zone Airflow Reheat Coil CFM Load BTU/hr Heating Heating Heating Heating Heating 69.5 69.5 69.5 69.5 69.5 17 111 18 101 7 0 0 0 0 0

Rm. 009-Mens WR Rm. 010-Mens Locker Rm. 011-Womens WR Rm. 012-Womens Locker Rm. 001-Office Vestibule

Block Load 4.15

Page 9 of 9