DVR2000E+:
DVR2000E+
Topics
Specifications Operating Features Protection Features Installation HMI GUI Other Manual Sections
DVR2000E+ Specifications
Operating Power
PMG
Single phase Frequency Burden Terminals 180-240 Vac 250-300 Hz 350 VA 3 and 4
DVR2000E+ Specifications
DVR2000E+ Specifications
DVR2000E+ Specifications
Contact Inputs
Type Input pull-up voltage Terminals
UP DOWN DROOP_OFF EXCITATION_OFF
DVR2000E+ Specifications
Contact Output
Type Rated load Break Operating voltage Maximum Terminals Form A 3 A Continuous 3 Aac or 0.1 Adc 240 Vac or 250 Vdc J1-6 and J1-7
DVR2000E+ Specifications
Field Output
Continuous rating 10 second forcing Field Resistance Terminals 75 Vdc, 3.0 Adc 150 Vdc, 7.5 Adc (assumes 200Vac input) 18 minimum F+ and F-
DVR2000E+ Specifications
Other Specifications
Voltage Regulation Shock Vibration 0.25% Up to 20 Gs 2.5 Gs 5-26 Hz 0.050 Peak 27-52 Hz 7 Gs 53-500 Hz
DVR2000E+ Specifications
Agency Approvals
UL Recognized CSA Certified CE
10
Communication Ports
RS232 for MODBUS
Allows PC communication via PC software
Set-up Generator monitoring
11
12
Excitation Disable
Allows for the communication with or programming of the regulator with the regulator output disabled Enabled and disabled through the EXCITATION_OFF contact input circuit (terminals J111 and J1-4)
13
14
15
Regulation Modes
AVR1 Automatic Voltage Regulation Single-Phase AVR3 Automatic Voltage Regulation Three-Phase FCR Field Current Regulation
16
FCR Mode
0-3 Vdc signal applied results in a 0-3 A field current output
Auxiliary Meter
Voltage Mode
Accepts a 5 Vdc signal for customizable scaling
Load Sharing
When this feature is enabled, the regulator calculates the reactive portion of the generator load using the sensed generator output voltage and current quantities and then modifies the voltage regulation set point accordingly.
Enter desired amount of droop through HMI or GUI as a percentage of set point Droop active when DROOP_OFF terminal J1-10 is not shorted to J1-4
18
19
Alarms and Faults Announced on the HMI via AXXX and FXXX codes Announced on the GUI via yellow alarm and red fault indicators Announced on CAN network
20
Current threshold adjustable from 0.5-4.0 Adc through GUI Timer threshold adjustable from 1.0-15.0 seconds through GUI
21
Field Current Limiting threshold adjustable from 0.500-7.500 A through GUI Timer threshold adjustable from 1.0-10.0 seconds through GUI
22
23
Over voltage threshold adjustable from 5.0-20.0% through GUI Timer threshold fixed 0.75 seconds
24
Under voltage threshold adjustable from 5.0-50.0% through GUI Timer threshold adjustable from 1.0-15.0 seconds through GUI
25
Voltage imbalance threshold is fixed at 20.0% through GUI Timer threshold adjustable from 1.0-15.0 seconds through GUI This feature is active in AVR3 regulation mode
26
In AVR1 and AVR3 regulation modes, this feature is not active until after the soft start cycle is initiated
27
28
Enter under frequency knee through HMI or GUI V/Hz slope selectable through GUI
29
30
Timer threshold adjustable from 0.0-45.0 seconds through GUI The default setting is 0.0 seconds which disables this feature
31
DVR2000E+ Installation
Regulator Connections
32
DVR2000E+ Installation
33
DVR2000E+ Installation
34
DVR2000E+ Installation
J1 Terminal Assignments
35
DVR2000E+ Installation
J2 Terminal Assignments
36
DVR2000E+ Installation
37
DVR2000E+ Installation
38
DVR2000E+ Installation
39
Rev 11
Configurable Auxiliary Input Scaling. Droop is now based on rated power of the machine. Simulation of Reactive Power. Field Under Excitation Fault has been added. A Startup Fault has been added. Power Limiting New easier to use manual
40
DVR2000E+ HMI
41
DVR2000E+ HMI
42
DVR2000E+ HMI
43
44
DVR2000E+ HMI
The DVR displays an alarm signal on the HMI and in DVRPortal. An independent timer starts at the moment the alarm condition is triggered.
45
DVR2000E+ HMI
If the timer threshold is exceeded before the alarm condition is removed, a fault is then triggered and the excitation current to the field is shutdown. A fault signal is displayed on the HMI and in DVRPortal. Table X shows the details of the timer-based protection features in the DVR.
46
DVR2000E+ HMI
Select
Enter
UP /
DOWN
47
DVR2000E+ GUI
49
50
51
52
53
54
Recovery
Voltage
P
Overshoot
D I
Time
55
56
57
DVR2000E+ TS
58
59
60
61
62
63
64
DVR2000E+
Questions?
65