You are on page 1of 65

DVR2000E+

DVR2000E+:

DVR2000E+

Topics
Specifications Operating Features Protection Features Installation HMI GUI Other Manual Sections

DVR2000E+ Specifications

Operating Power
PMG
Single phase Frequency Burden Terminals 180-240 Vac 250-300 Hz 350 VA 3 and 4

DVR2000E+ Specifications

Generator Voltage Sensing


Type Range Terminals Burden Single or three phase, 50 or 60 Hz 100-600 Vac E1, E2 and E3 < 1 VA per pahse

DVR2000E+ Specifications

Generator Current Sensing


Type Rating Burden Terminals Single or three phase, 50 or 60 Hz 5 Aac maximum continuous < 1 VA Single phase (B), CT1 and CT2 Three phase (A), J2-1 and J2-12 Three phase (B), J2-2 and J2-11 Three phase (C), J2-3 and J2-10

DVR2000E+ Specifications

Contact Inputs
Type Input pull-up voltage Terminals
UP DOWN DROOP_OFF EXCITATION_OFF

Dry contact 3.3 Vdc


J1-2 and J1-4 J1-3 and J1-4 J1-10 and J1-4 J1-11 and J1-4

DVR2000E+ Specifications

Contact Output
Type Rated load Break Operating voltage Maximum Terminals Form A 3 A Continuous 3 Aac or 0.1 Adc 240 Vac or 250 Vdc J1-6 and J1-7

DVR2000E+ Specifications

Field Output
Continuous rating 10 second forcing Field Resistance Terminals 75 Vdc, 3.0 Adc 150 Vdc, 7.5 Adc (assumes 200Vac input) 18 minimum F+ and F-

DVR2000E+ Specifications

Other Specifications
Voltage Regulation Shock Vibration 0.25% Up to 20 Gs 2.5 Gs 5-26 Hz 0.050 Peak 27-52 Hz 7 Gs 53-500 Hz

DVR2000E+ Specifications

Agency Approvals
UL Recognized CSA Certified CE

Related Industrial Standards


UL508 UL2200 CSA C22.2 No. 14-05 CISPR 11 IEC 6100-4-2 IEC 6100-4-4 ASTM E117-73

10

DVR2000E+ Operating Features

Communication Ports
RS232 for MODBUS
Allows PC communication via PC software
Set-up Generator monitoring

3 position Amp/Tyco Mate-N-Lock for CAN J1939


Allows for communication over a Controller Area Network
Greater system integration Generator system monitoring Generator system control Flexibility

11

DVR2000E+ Operating Features

True Three Phase Power Metering


CT inputs for all three phases Reported to PC software metering screen
CT secondary (direct) CT primary (scaled)

Reported on CAN bus

12

DVR2000E+ Operating Features

Excitation Disable
Allows for the communication with or programming of the regulator with the regulator output disabled Enabled and disabled through the EXCITATION_OFF contact input circuit (terminals J111 and J1-4)

13

DVR2000E+ Operating Features

Programmable Gain Values


Proportional Gain (Kp): Affects the rate of rise after a signal has been initiated into the control loop. Integral Gain (Ki): Affects the steady state stability by continuously changing in the direction to reduce the error, until the error signal is zero. Derivative Gain (Kd): Affects the voltage overshoot by measuring the speed of change in the measured output and causes an exponential decay in the measured parameter in the direction to reduce the error to zero. Preset by Marathon frame size Custom selection for user defined (5000 Frame over CAN)

14

DVR2000E+ Operating Features

Remote Set-point Adjust


Via switch or relay Connected to UP and DOWN contacts (terminals J1-2 (UP) or J1-3 (DOWN) and J1-4)

15

DVR2000E+ Operating Features

Regulation Modes
AVR1 Automatic Voltage Regulation Single-Phase AVR3 Automatic Voltage Regulation Three-Phase FCR Field Current Regulation

16

DVR2000E+ Operating Features

Configurable Auxiliary Input


Auxiliary Control
AVR Modes
3 Vdc signal applied results in a 30% offset to the set point

FCR Mode
0-3 Vdc signal applied results in a 0-3 A field current output

Auxiliary Meter
Voltage Mode
Accepts a 5 Vdc signal for customizable scaling

Current Mode (Short J1-5 and J1-8)


Accepts a 4-20 mA signal for customizable scaling

Configurable through the PC software


17

DVR2000E+ Operating Features

Load Sharing
When this feature is enabled, the regulator calculates the reactive portion of the generator load using the sensed generator output voltage and current quantities and then modifies the voltage regulation set point accordingly.

Enter desired amount of droop through HMI or GUI as a percentage of set point Droop active when DROOP_OFF terminal J1-10 is not shorted to J1-4

18

DVR2000E+ Operating Features

Generator Soft Start


Allows generator voltage to ramp to the regulation set point over a user defined period of time.

Enter a rate of 2 120 seconds through GUI Default is 3 seconds

19

DVR2000E+ Protection Features

Alarms and Faults Announced on the HMI via AXXX and FXXX codes Announced on the GUI via yellow alarm and red fault indicators Announced on CAN network

20

DVR2000E+ Protection Features

Field Over Excitation Shutdown


If the field current exceeds the Field Over Excitation Shutdown threshold (default 3.5 A), A008 will flash on the HMI display. If this condition continues for longer than the timer value (default 10 seconds), the regulator will stop producing excitation and F008 will flash on the HMI display. Alarms and faults are also announced in the GUI.

Current threshold adjustable from 0.5-4.0 Adc through GUI Timer threshold adjustable from 1.0-15.0 seconds through GUI
21

DVR2000E+ Protection Features

Field Current Limiting Shutdown


If load conditions dictate that the field current should exceed the Field Current Limiting Shutdown threshold (default 6.5 A), the field current will be limited and A010 will flash on the HMI display. If this condition continues for longer than the timer value (default 10 seconds), the regulator will stop producing excitation and F010 will flash on the HMI display. Alarms and faults are also announced in the GUI.

Field Current Limiting threshold adjustable from 0.500-7.500 A through GUI Timer threshold adjustable from 1.0-10.0 seconds through GUI
22

DVR2000E+ Protection Features

Instantaneous Field Over Current Shutdown


If load conditions dictate that the field current should exceed 11.0 Adc, the regulator will stop producing excitation and F009 will flash on the HMI display. Alarms and faults are also announced in the GUI.

The 11.0 Adc is a fixed threshold

23

DVR2000E+ Protection Features

Generator Over Voltage Shutdown


If the generator voltage exceeds the Generator Over Voltage Shutdown threshold (default 20% over set point), for longer than 0.75 seconds, the regulator will stop producing excitation and F013 will flash on the HMI display. Alarms and faults are also announced in the GUI.

Over voltage threshold adjustable from 5.0-20.0% through GUI Timer threshold fixed 0.75 seconds

24

DVR2000E+ Protection Features

Generator Under Voltage Shutdown


If the generator voltage dips below the Generator Under Voltage Shutdown threshold (default 20% under set point), A012 will flash on the HMI display. If this condition continues for longer than the timer value (default 10 seconds), the regulator will stop producing excitation and F012 will flash on the HMI display. Alarms and faults are also announced in the GUI.

Under voltage threshold adjustable from 5.0-50.0% through GUI Timer threshold adjustable from 1.0-15.0 seconds through GUI
25

DVR2000E+ Protection Features

Generator Voltage Imbalance Shutdown


If a generator voltage imbalance of more than 20% is detected, A016 will flash on the HMI display. If this condition continues for longer than the timer value (default 12 seconds), the regulator will stop producing excitation and F012 will flash on the HMI display. Alarms and faults are also announced in the GUI.

Voltage imbalance threshold is fixed at 20.0% through GUI Timer threshold adjustable from 1.0-15.0 seconds through GUI This feature is active in AVR3 regulation mode
26

DVR2000E+ Protection Features

Loss of Generator Sensing Shutdown


If generator sensing input continuity is lost, the regulator will stop producing excitation and F011 will flash on the HMI display. Alarms and faults are also announced in the GUI.

In AVR1 and AVR3 regulation modes, this feature is not active until after the soft start cycle is initiated

27

DVR2000E+ Protection Features

Processor Over Temperature Shutdown


If the regulator temperature exceeds the regulator over temperature alarm threshold (105 C), A007 will flash on the HMI display. If the regulator temperature exceeds the regulator over temperature fault threshold (120 C), the regulator will stop producing excitation and F012 will flash on the HMI display. Alarms and faults are also announced in the GUI.

Regulator temperature thresholds are fixed

28

DVR2000E+ Protection Features

Generator Under Frequency


When generator frequency drops below the selected knee frequency set point, the voltage set point is automatically adjusted so that generator voltage follows the selected PU (per unit) V/Hz curve. When operating in this condition, A015 will flash on the HMI display.

Enter under frequency knee through HMI or GUI V/Hz slope selectable through GUI

29

DVR2000E+ Protection Features

Generator Reverse Power Flow Alarm


If the regulator senses reverse power flow, A014 will flash on the HMI display. Alarms and faults are also announced in the GUI.

The reverse power flow threshold is fixed

30

DVR2000E+ Protection Features

Loss of CAN Communication Alarm


If the regulator does not receive a VR Heartbeat before the threshold timer expires, A006 will flash on the HMI display. Alarms and faults are also announced in the GUI.

Timer threshold adjustable from 0.0-45.0 seconds through GUI The default setting is 0.0 seconds which disables this feature

31

DVR2000E+ Installation

Regulator Connections

32

DVR2000E+ Installation

Quick Disconnect Connections

33

DVR2000E+ Installation

J1 and J2 Terminal Positions

34

DVR2000E+ Installation

J1 Terminal Assignments

35

DVR2000E+ Installation

J2 Terminal Assignments

36

DVR2000E+ Installation

MODBUS Port Terminal Positions

37

DVR2000E+ Installation

MODBUS Port Terminal Assignments

38

DVR2000E+ Installation

J3 Terminal Positions and Assignments

39

DVR2000E+ Operating Features

Rev 11
Configurable Auxiliary Input Scaling. Droop is now based on rated power of the machine. Simulation of Reactive Power. Field Under Excitation Fault has been added. A Startup Fault has been added. Power Limiting New easier to use manual

40

DVR2000E+ HMI

41

DVR2000E+ HMI

Button Functions and Descriptions

42

DVR2000E+ HMI

Status Mode Display Descriptions

43

Faults & Alarms: Set Points

44

DVR2000E+ HMI

Alarm Code Descriptions

The DVR displays an alarm signal on the HMI and in DVRPortal. An independent timer starts at the moment the alarm condition is triggered.

45

DVR2000E+ HMI

Fault Code Descriptions

If the timer threshold is exceeded before the alarm condition is removed, a fault is then triggered and the excitation current to the field is shutdown. A fault signal is displayed on the HMI and in DVRPortal. Table X shows the details of the timer-based protection features in the DVR.

46

DVR2000E+ HMI

Select

Enter

UP /

DOWN

47

MAKING SETTINGS CHANGES


1. The default state of the HMI display is SLEEP mode. The HMI will enter the SLEEP mode after 60 seconds of inactivity (no button presses). Any HMI button press will place the HMI into STATUS mode. In order to make changes to settings, the following procedure is used: 2. Repeatedly press the SELECT button, stepping through the main menu until the desired parameter is displayed (see Table 5-3). If no button is pressed within 60 seconds, the display will return to STATUS mode. 3. Press the ENTER button to place the HMI into EDIT mode. In EDIT mode, the HMI will display the current value of the selected parameter. 4. Press or hold the UP and DOWN buttons to modify the displayed parameter to its desired value. For parameters other than Stpt, pressing the SELECT button escapes EDIT mode without modifying the parameter. For Stpt, pressing the SELECT button escapes EDIT mode but preserves any modification. 5. To store the displayed parameter value to non-volatile memory, press the ENTER button. The stored parameter value will flash three times to confirm the entry. NOTE: While in STATUS mode, pressing either the UP or DOWN button places the regulator directly into Stpt EDIT mode. This feature allows a shortcut to set point adjustment.
48

DVR2000E+ GUI

49

50

51

52

DVR2000E+ Operating Features

Programmable Gain Values


Proportional Gain (Kp): Affects the rate of rise after a signal has been initiated into the control loop. Integral Gain (Ki): Affects the steady state stability by continuously changing in the direction to reduce the error, until the error signal is zero. Derivative Gain (Kd): Affects the voltage overshoot by measuring the speed of change in the measured output and causes an exponential decay in the measured parameter in the direction to reduce the error to zero. Preset by Marathon frame size Custom selection for user defined (5000 Frame over CAN)

53

54

DVR2000E+ Operating Features

Recovery

Voltage

P
Overshoot

D I

Time
55

56

57

DVR2000E+ TS

58

59

60

61

62

63

64

DVR2000E+

Questions?

65