Benefits
High-speed operation Interrupting time of 3 cycles or less Long life Hermetically sealed interrupters protect contacts from corroding elements and contamination. Ease of maintenance Interrupter assemblies and contact wear indicators accessible via a bolted panel. Reliability A minimum of moving parts on the motor-driven, spring-charged Type RI mechanism. Durability Robust design tested to the highest IBC-2000 seismic standard. Other seismic standards may be evaluated upon request. Flexibility Standard adjustable heights in 3 increments. Component Commonality Utilizes Type RI operating mechanism / coils / motor, which are commonly used among many Square D medium voltage circuit breakers.
Standard Features
Window for viewing status indicators and operation counter. Ground pads located on both sides of breaker. A #4 cable connects from the roof and HV/LV compartment to the ground pads to insure a solidly grounded enclosure. Painted adjustable legs with galvanized base channels. All external hardware is stainless steel. Optimized relay panel (32 5/8 W x 33 7/8 H) for instrumentation (model 1 only). 12 pole auxiliary switch (6 a & 6 b contacts), latch check switch and emergency cutout switch standard. All outer doors latch open at approximately 120 degrees. Type RI mechanism with integral manual charging handle.
Breaker Legend, EVR - Model # 0 and 1 1 - High Voltage Compartment (HV) 2 - Low Voltage (Relay) Compartment (LV) 3 - Adjustable Legs 4 - Cable Termination Bushing 5 - Current Transformers 6 - Vacuum Interrupter Bottle 7 - Mechanism 8 - Auxiliary Switch 9 - Control Mounting Panel 10 - Removable Filter Vent Covers 11 - Hinged Removable Door w/Padlockable Handles (HV) 12 - Hinged Removable Door w/Padlockable Handles (LV) 13 - Hinged Removable Door Fastened to Assembly 14 - Rear Access Panel Fastened to Assembly (HV) 15 - Vented Rear Access Panel Fastened to Assembly (LV) 16 - Galvanized Base Channel
The EVR is available with or without a relay compartment. Model 0 does not have a relay compartment, and is intended for applications in which the relay will be mounted remotely. Model 1 includes a relay compartment, and can be provided with the relay of your choice.
EVR 1 06 11 12 EVR 1 08 11 12 EVR 1 12 11 12 EVR 1 06 11 16 EVR 1 08 11 16 EVR 1 12 11 16 EVR 1 06 11 20 EVR 1 08 11 20 EVR 1 12 11 20 EVR 1 06 11 25
EVR 1 08 11 25 EVR 1 12 11 25
600 12.5 800 1200 600 16 15.5 20 800 1200 600 800 1200 600 25
800 1200
32
16 50 20 110 142 2
16
43
20
54
25
25
68
EVR
12
11
16
0
Model Interrupting Rating BIL Rating Continuous Current Rating
Adjustable leg has range of 24 inches. Cross brace must be installed during installation. All dimensions are typical. Diagrams are not for construction.
Control conduit entrance (3 x 8), customer installs cutouts in cover plates as needed
Notes:
Control panel with access terminal blocks is mounted on right wall of low voltage compartment. Approx. weight: 2000 lbs. All external hardware is stainless steel.
Breaker rear
Control conduit entrance (8 x 14), customer installs cutouts in cover plates as needed
All dimensions are in inches unless otherwise specified. Adjustable leg has range of 24 inches. All dimensions are typical. Diagrams are not for construction.
Control conduit entrance (8 x 14) Customer install cutouts in cover plates as needed