Introduction
Introduction
This section lists the EMC CX-Series Fibre Channel devices that the
Telco Rail Self-Supporting Rack (Telco rack) supports and provides
an illustration of the rack.
Device Model
CX500-FD
CX400-FD
DCX300-FD
CX200-FD
CX700-FD
CX600-FD
CX-2GDAE-OSFD
FRAME-T-SPE
FRAME-T-DAE2/FRAME-T-2PDAE;
SPST-2GB
CX-2GDAE-FD
FRAME-T-DAE2
CX-2PDAE-FD
FRAME-T-2PDAE
DS-16M2-OD
DS-24M2-OD
DS-16B2-OD
DS2-RK1U-T
DS-32M2-OD
DS-32B2-OD
DS2-RK2U-T
a. CX600-FD and CX700-FD models require the CX-2GDAE-OSFD or CX-2PDAE-OSFD device model because
the SPE does not contain any disk drives.
Introduction
Flange edge to
flange edge:
450.85 mm
(17.75 inches)
Mounting hole to
mounting hole:
465.074 mm
(18.31 inches)
76.2 mm to 203.2 mm
(3 inches to 8 inches)
EMC2611
Figure 1
Position in Rack
Devices with internal cooling fans that move air from front to back
(or vice versa) and not from beneath or above have no special cooling
requirements that direct placement in the rack. All of the storage
systems and enclosures mentioned in this document have fans that
move air from front to back.
Requirements are as follows:
Device Dimensions
The table below lists the dimensions for the supported CX-Series
Fibre Channel devices. Device height requirements and rack
mounting measurements are based on NEMA units (U for short).
Device
Height
SPS
1U
40.132 mm
1.58 in
DPE2
3U
133.35 mm
5.25 in
DAE2/DAE2P
3U
133.35 mm
5.25 in
SPE
4U
177.8 mm
7.00 in
1U
43.18 mm
1.7 in
1.5 Ua
64.77 mm
2.55 in
Switches
DS-16M2, DS-24M2,
and DS-16B2
DS-32M2 and DS-32B2
a.Requires a 2U bezel.
DAE (3U)
DAE (3U)
36.5U
DAE (3U)
DAE (3U)
DAE (3U)
DAE (3U)
5.5U with
SPE/SPS
tray
SPE (4U)
1.5U with SPS tray
SPS (1U)
EMC2615
4 PDUs,
2 per side
DAE
DAE
DAE
DAE
DAE
DAE
DAE
SPE
SPS
SPS
EMC2614
Mounting Kits
Mounting Kits
This section describes the mounting kits that are available with the
Telco rack. These kits are for Telco racks only.
Quantity Use
Attaches to the DPE2 front support tray (3U) or the SPE front support tray
(4U). Then the combined front support trays are attached to the front of
the Telco rack.
Attaches to the DPE2 rear support tray (3U) or the SPE rear support tray
(4U). Then the combined front support trays are attached to the front of
the Telco rack.
Mounting bracket
Attaches to the ends of the rear SPS tray once the SPSs are installed.
For a single SPS, only one mounting bracket is used.
For a single SPS only. Covers the area in which a second SPS would be.
For dual SPSs only. Attaches the two SPSs together and to the SPS rear
tray.
Latch bracket
M5 x 12 SEMS screw
11
4 to hold the SPS front tray to the DPE2 or SPE front tray.
4 to hold the SPS rear tray to the DPE2 or SPE rear tray.
1 to hold the center mounting bracket to the SPS rear tray.
2 to hold the latch brackets to the front SPS tray.
Mounting Kits
Component
Quantity Use
18
Dual SPSs
8 to hold the SPS mounting brackets to the rear SPS tray.
4 to hold the center mounting bracket to the SPS.
4 to hold the SPS rail cover.
2 to hold the short SPS bracket.
Single SPS
4 to hold the SPS mounting brackets to the rear SPS tray.
4 to hold the SPS and filler panel.
4 to hold the SPS rail cover.
2 to hold the short SPS bracket.
Attaches to the front of the SPS by lining up the bezel with the latch
brackets.
Mounting Kits
10
Component
Quantity
Use
DPE2 - The DPE2 front support tray is attached on top of the SPS front
support tray. Then the combined front support trays are attached to the front of
the Telco rack.
DAE - The DAE2/DAE2P front support tray is attached to the front of the Telco
rack.
DPE2 - The DPE2 rear support tray is attached on top of the SPS rear support
tray. Then the combined rear support trays are attached to the rear of the
Telco rack.
DAE2 - The DAE2 rear support tray is attached to the rear of the Telco rack.
DAE2P -The DAE2P rear support tray is attached to the rear of the Telco rack.
Attaches to the rear corner of the DPE2 or DAE enclosure and DPE2 or DAE
rear tray. DAE2 fastening bracket shown - DAE2P slightly different)
M5 x 12 SEMS screw
12
M5 flat washer
Secures the rear fastening bracket to the rear corner of the DPE2 or DAE.
Secures the rear fastening bracket to the rear corner of the DPE2 or DAE.
M5 hex nut
Secures the rear fastening bracket to the rear corner of the DPE2 or DAE.
M5 x 12 flat-head
Secures the rear fastening bracket to the rear corner of the DPE2 or DAE.
Mounting Kits
Quantity
Use
The SPE front support tray is attached on top of the SPS front support
tray. Then the combined front support trays are attached to the front of
the Telco rack.
The SPE rear support tray is attached on top of the SPS rear support
tray. Then the combined rear support trays are attached to the rear of the
Telco rack.
Attaches to the rear corner of the SPE enclosure and SPE rear tray.
M5 x 12 SEMS screw
12
M5 flat washer
Secures the rear fastening bracket to the rear corners of the SPE.
Secures the rear fastening bracket to the rear corners of the SPE.
M5 hex nut
Secures the rear fastening bracket to the rear corners of the SPE.
M5 x 12 flat-head
Secures the rear fastening bracket to the rear corners of the SPE.
11
Mounting Kits
Use
4a
Latch bracket
M5 x 12 mm SEMS screw
Attaches the front and rear switch trays to the Telco rack.
12
Quantity
2 each
Attaches the mounting slide rail to the front and rear switch
trays.
10
Mounting Kits
Component
Quantity
Use
Used for the DS-16B2 switch only. Attaches the mounting slide
rails to the front and rear switch trays.
a.Four mounting slide rails are included in this kit; only two are required for installation. Make sure you use the appropriate
mounting slide rails for your switch.
13
Mounting Kits
Use
4a
14
Quantity
1 each
Attaches to the front left and right support tray to hold the bezel.
M5 x 12 mm SEMS screw
Attaches the front and rear switch trays to the Telco rack.
10
Used for the DS-32M2 switch only. Attaches the mounting slide
rails to the front and rear switch trays.
Note: Phillips flat-head TF screws #6 x .375 are also included in
this kit. You should use these screws only if you have an older
version of the DS-32M2 switch. Refer to the physical kit for
information on which screws you should use with your switch.
Used for the DS-32B2 switch only. Attaches the mounting slide rails
to the front and rear switch trays.
Mounting Kits
Component
M4 Washer and kep nut
Quantity
2 each
Use
Attaches the mounting slide rail to the rear switch tray.
Attaches the mounting slide rail to the front and rear switch trays.
Attaches to the front of the switch by lining up the bezel with the
latch brackets.
a.Four mounting slide rails are included in this kit; only two are required for installation. Make sure you use the appropriate
mounting slide rails for your switch.
15
Follow the steps below to assemble the SPS front tray to the DPE2 or
SPE front tray.
NOTE: The DPE2 front tray is part of the FRAME-T-DAE2 kit. The SPE front
tray is part of the FRAME-T-SPE kit.
1. Place the SPS front tray on a table so that the front of the tray is
facing you, as illustrated below.
SPS front tray
EMC2641
Front
16
2. Place the DPE2 or SPE front tray on a table, positioning the DPE2
or SPE tray rail screw holes to the rear, as illustrated below.
DPE2 or SPE
front tray
Rail screw
holes
EMC2569
Front
3. Place the DPE2 or SPE front tray on top of the SPS front tray, as
illustrated below.
NOTE: The SPSs must be located immediately below the DPE2 or SPE
whose power they will provide.
DPE2 or SPE
front tray
EMC2640
17
4. Slide the DPE2 or SPE tray toward the front of the SPS front tray.
Ensure that the screw holes on the bottom of the DPE2 or SPE tray
align with the holes on each side of the SPS front tray.
5. Using four M5 x 12 SEMS screws, secure the front DPE2 or SPE
tray to the front SPS tray, as illustrated below.
Screws
EMC2571
Follow the procedures below to install the front tray assembly (the
combined SPS front tray and DPE2 or SPE front tray) to the Telco
rack.
1. Determine where in the rack you intend to position the front tray
assembly (the combined SPS and DPE2 or SPE front trays).
2. Align the screw holes on the front tray assembly with the screw
holes on the Telco rack.
3. Secure the front tray assembly to the rack, with six M5 x 12
screws, three per side, for a DPE2 or SPE.
EMC2616
18
4. Attach two latch brackets to the ends of the front tray assembly, as
shown below, using two M5 x 12 screws, one per side.
Latch bracket
EMC2617
Assembling the
Rear Trays
Follow the steps below to assemble the SPS rear tray to the DPE2 or
SPE rear tray.
NOTE: The DPE2 front tray is part of the FRAME-T-DAE2 kit. The SPE front
tray is part of the FRAME-T-SPE kit.
1. Place the SPS rear tray on a table so that the rear flanges are facing
you, as shown below.
SPS rear tray
EMC2618
Rear flanges
19
2. Place the DPE2 or SPE front tray on a table, positioning the DPE2
or SPE tray rail screw holes to the rear, as illustrated below.
DPE2 or SPE
rear tray
3. Place the DPE2 or SPE rear tray on top of the SPS rear tray,
positioning the DPE2 tray rail screw holes to the rear, as shown
below.
DPE2 or SPE
rear tray
4. Pull the DPE2 or SPE rear tray toward the front of the SPS rear
tray. Ensure that the screw holes on the bottom of the DPE2 or
SPE rear tray align with the holes on each side of the SPS rear tray.
20
5. Secure the trays with four M5 x 12 screws, two per side, leaving
the screws loose for now.
EMC2620
Screws
Follow the procedures below to install the rear tray assembly (the
combined SPS rear tray and DPE2 or SPE rear tray) to the Telco rack.
1. Align the screw holes of the rear tray with the holes in the rack.
Ensure that the bottom of the tray lines up with the bottom of the
SPS/DPE2 or SPE front tray assembly.
2. Secure the tray to the rack with six M5 x 12 screws, three per side
for a DPE2 or SPE, as shown below.
DPE2 or SPE
rear tray secured
to rack.
EMC2576
21
loosen
EMC2576
b. Adjust the rear SPS tray so that the rear flange (with self-clinch
nuts) is 21.25 inches (539.75 mm) from the front flange (with
four clearance holes) of the SPS front tray.
c. Tighten the screws you loosened in step a in the DPE2 or SPE
rear tray.
22
Important: You must install the front DAE tray either directly above the front
DPE2 or SPE/SPS tray assembly or directly above another DAE.
1. Align the screw holes on the outer edges of the DAE front tray
with the holes on the rack.
2. Secure the tray to the rack with six M5 x 12 mm screws, three per
side. See the figure below.
If you are installing the unit in a NEBS-compliant environment, secure the tray
to the front channel with the shape thread rolling screw, supplied with your
installation hardware in part number 100-560-644.
EMC2582
EMC2581
1. Align the screw holes on the outer edges of the DAE rear tray
with the holes on the rack. Ensure that the bottom of the front and
rear trays line up with each other.
DAE2 and DAE2P rear trays are similar in design and function; the
DAE2P tray supports a chassis that is ten inches shorter than the DAE2.
23
2. Secure the tray to the rack with six M5 x 12 mm screws, three per
side, as shown below.
EMC2583
24
EMC2584
EMC2627
EMC2626
EMC2623
EMC2624
The switch trays are typically installed at the top of the Telco rack.
Note: The following procedure uses the 1.5U switch tray for illustration
purposes.
1. Align the screw holes on the outer edges of the switch front tray
with the holes on the rack (refer to the illustrations above).
25
EMC2639
3. Attach two latch brackets to the ends of the switch front tray, as
shown below, using four M5 x 16 mm screws, two per side. Be
sure to use the appropriate length latch bracket for your switch.
Note: The latch brackets for a 1.5U switch are marked with an L for the
left side and an R for the right side.
Latch bracket
EMC2628
26
1. Align the screw holes on the outer edges of the rear switch tray
with the holes on the rack (refer to the illustrations on page 25).
Ensure that the bottom of the front and rear switch trays line up
with each other.
2. Secure the rear tray to the rack with six M5 x 12 mm screws, three
per side, for a 1.5U tray or with four M5 x 12 mm screws, two per
side, for a 1U tray, as shown below.
EMC2625
27
Enclosure Installations
Enclosure Installations
This section describes how to install the SPS, DAE2, DAE2P, DPE2,
and SPE enclosures to the Telco rack.
Mounting bracket
EMC2621
3. If you are installing a second SPS on the left, repeat step 1 and 2
for the second SPS, as illustrated below.
EMC2577
Mounting
brackets
28
Enclosure Installations
If you are not installing a second SPS, you must install an SPS
filler panel, as follows:
Attach the SPS filler panel to the SPS and SPS rear tray as you
would an SPS. Note, however, that you need only four
M4 x .7 x 8 mm screws (two per side) to secure the SPS filler panel
to the tray, as illustrated below.
EMC2622
4. For dual SPSs, attach the center mounting bracket to the two SPSs
with four M4 x .7 x 8 mm screws. Secure the center mounting
bracket to the rear tray with one M5 x 12 mm screw, as illustrated
below.
EMC2578
29
Enclosure Installations
5. Secure the front of the SPSs to the front of the SPS tray with four
M4 x .7 x 8 mm screws, as illustrated below.
EMC2579
Latch
bracket
Screws
EMC2629
30
Enclosure Installations
WARNUNG
Das enclosure ist schwer und sollte nur von zwei Personen in einem
Gehuse installiert werden. Zur Vermeidung von krperlichen
Verletzungen und/oder der Beschdigung des Gertes, bitte die
enclosure nicht ohne die Hilfe einer zweiten Person anheben und
einbauen.
1. Attach the clip of the ESD strap to bare metal on the enclosure,
and put the wristband around your wrist with the metal button
against your skin.
2. With two people, lift the enclosure up and place it on the edge of
the enclosure front tray.
3. Push the enclosure in until the front flanges of the enclosure are
flush against the rack.
4. Attach the front of the unit to the front tray with four pan-head
M5 x12mm SEMS screws, two per side.
If you are installing the enclosure in a NEBS-compliant environment,
secure the unit to the front tray with the shape thread rolling screws
supplied with your installation hardware in part number 100-560-644.
31
Enclosure Installations
Top screw
Bottom screw
EMC2635
Attaches to
the bottom
rear notch of
the enclosure.
Bottom notch
Rear tray
enclosure
Secured to the rear
enclosure tray.
EMC2639
Please note that this procedure covers only the physical installation of
the enclosure into the rack. Refer to the hardware reference manual
that shipped with the enclosure that you are installing for further
detailed installation procedures.
32
Enclosure Installations
EMC2633
Screws
Note: Be sure to install the mounting slide rails so the flat side
of the rail is against the switch, as illustrated above.
33
Enclosure Installations
EMC2631
Screws
Once you have attached the mounting slide rails to the switch, you
can install the switch in the Telco rack as described below.
1. Place the switch on the rear switch tray. Slide it forward until the
rear end of the switch (the end without the ports) meets the back
end of the front switch tray.
2. Using one M4 x 14 mm pan-head SEMS screw, secure the switch
mounting slide rails to the front switch tray. Secure the screw
with one M4 washer and one M4 kep nut (in this order), as shown
below. Repeat this step for the other side.
DS-16B2 or DS-32B2 Switch - Front View
Screw
EMC2632
34
Enclosure Installations
EMC2636
EMC2634
EMC2637
35
Enclosure Installations
4. Snap the 2U bezel (for a 1.5U switch only) onto the latch brackets,
as illustrated below.
2U Bezel
EMC2631
If you have a 1U switch, snap the 1U bezel onto the latch brackets,
as illustrated below.
1U Bezel
EMC2629
Please note that this procedure covers only the physical installation of
the switches into the rack. Refer to the hardware reference manual
that shipped with the switch that you are installing for further
detailed installation procedures.
36