* Note : EIA RS-485 standard defines unit loads so that 32 of them can be operated on one line. For detailed information refer to EIA RS-485 standard.
2. Link layer
There are no choices for the link layer.
3. Application layer
3.1 Transmission mode for application data
Mode 1 (least significant octet first) as defined in 4.10 of IEC 60870-5-4, is used exclusively in this companion standard.
1/6
<245> End of general interrogation of generic data <249> Write entry with confirmation
3.6 Miscellaneous
Measurands are transmitted with ASDU 9. The maximum MVAL can 2.4 times the rated value.
Class 2
The measurement values are transported to the control system as a response to a class 2 request. And the class 2 data is always cyclically updated. The measurement values cyclic update period is 500 ms.
Explanations of Table
Code ST FUN INF TYPE COT Description
Status S : IEC 60870-5-103 standard P : private definition Function type Information Number ASDU(Application Service Data Unit) Type Cause of Transmission 1 : Spontaneous (Not in interrogation) 9 : Interrogated 2 : cyclic (Measurands)
System Functions
Description Power On Reset CU (Communication Unit) Reset FCB (Frame Count Bit) Synchronization Command ST S S S S FUN 255 255 255 255 INF 5 3 2 0 TYPE 5 5 5 6 COT 6 4 3 8
*) Type 5 (ASDU - Identification message) contain manufactures name and relay model name : P&C TECHE110 **) Class polling time out : 20 sec
Status Indications
Description System Error(Error LED) General pickup(pickup LED) General trip(trip LED) CB Status(Position) Trip Circuit Supervision 50_1 Pickup 50_1 Trip 50_2 Pickup ST P P P P P P P P FUN 242 242 242 242 242 162 162 162 INF 47 84 68 160 36 97 99 95 TYPE 1 1 1 1 1 2 2 2 COT 9 9 9 9 1,9 1 1 1
50_2 Trip 51 Pickup 51 Trip 50N_1 Pickup 50N_1 Trip 50N_2 Pickup 50N_2 Trip 51N Pickup 51N Trip 37 Pickup 37 Trip 49 Alarm 49 Trip 46 Pickup 46 Trip 50BF OP COLD LD Pickup COLD LD OP I2/I1 OP 79 Start 79 CB Trip Fail 79 CB Close Fail 79 CB Close #1 79 CB Close #2 79 CB Close #3 79 CB Close #4 79 Success 79 Failure Contact Input#1 Contact Input#2 Contact Input#3 Contact Input#4 Contact Output #1 Contact Output #2 Contact Output #3 Contact Output #4
S S S P P P S S S P P P P P P P P P P P P P P P P P P P P P P P P P P P
160 160 160 163 163 163 160 160 160 165 165 166 166 167 167 160 169 169 170 171 171 171 171 171 171 171 171 171 243 243 243 243 244 244 244 244
91 84 90 97 99 95 93 67 92 84 91 90 91 84 90 85 84 150 84 100 121 122 101 102 103 104 123 124 231 232 233 234 231 232 233 234
2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
General Commands
Description CB Open/Close Control Reset Annunciator (LED) ST P S FUN 242 242 INF 161 19 TYPE 20 20 COT 20, 21 20, 21
Measurands
Description Measurands II ST P FUN 160 INF 149 TYPE 9 COT 2
Set No 1 2 3 4 5 6 7 8 9 10
Description RMS IA RMS IB RMS IC RMS IN RMS I2fA RMS I2fB RMS I2fC RMS I1 RMS I2 Thermal state(%)
Phase A Current Magnitude Phase B Current Magnitude Phase C Current Magnitude Ground Current Magnitude Phase A 2nd harmonic Current Magnitude Phase B 2nd harmonic Current Magnitude Phase C 2nd harmonic Current Magnitude Positive Phase Sequence Current Negative Phase Sequence Current
Thermal state
Reference 4096 = 2.4*IN 4096 = 2.4*IN 4096 = 2.4*IN 4096 = 2.4*IN 4096 = 2.4*IN 4096 = 2.4*IN 4096 = 2.4*IN 4096 = 2.4*IN 4096 = 2.4*IN 4096 = 240% of Thermal state