You are on page 1of 11

Power Systems Protection ­ subtransmission, distribution & industrial levels, Part III 

POWER SYSTEMS STUDIES: 
In order to be able to adequately select the protective relays in an electrical power system, certain 
studies and calculations have to be performed. The degree of complexity varies from one system to 
another. Despite this fact certain studies are common to any system, though using different approaches 
and mathematical models. Power systems can be classified, broadly, into radial and network 
configurations (designs). The essential studies to be done are: fault calculations (parallel and series 
faults), load flow, transients and reliability. Fault calculations can be performed using the traditional 
method of system impedance (reactance) reduction or using the system (network) impedance 
(reactance) model. The major outputs of studies are: the short circuit current levels after the first cycle 
(important in calculating the mechanical forces exerted on the system and in specifying momentary 
ratings), after 3 or 5 or 8 cycle (required to specify the breaking device interrupting ratings, and the 
thermal overloading of the system) and after 30 cycles (if applicable, important for time delay 
calculations). Load flow studies are performed using Newton Raphson method or fast decoupled and 
successive elimination method of solving simultaneous equations. It is possible to use other methods. 
The admittance (susceptance) network (system) model is used to calculate the equivalent elements for 
the system under study. The study can be performed for different configurations and system 
components. It can, also, include for the effects of starting a large motor on the system. The major 
outputs are: the voltage and phase angle of each bus included in the study, the active and reactive power 
flowing between the different buses (nodes) in the system. Transients analysis will vary from one 
system to the other and it will depend on the operation of the system, its location, its extent, the 
transients that have to be investigated in order to get a better understanding of transients in the subject 
system. Examples of calculations are: the overvoltages induced in the system due to direct lightning 
hits, indirect lightning hits, the operation of the breaking devices under fault conditions, ferroresonance, 
the effect of the L.A. leads on the overvoltages seen by the protected equipment. Reliability studies, in 
general, includes for the relays (plus the other elements) in the system their number, type, failure rate, 
and number of hours per failure. The reliability study is function of the degree of compexity of the 
system under study (or design). 
Subtransmission and/or distribution system protection: 
The electrical power distribution system components constituting the utility portion up to the service 
entrance in a plant will, typically, have the following major elements: 
­overhead high voltage transmission line (eg. 115kV or 230kV) 
­high voltage disconnect switches (eg. 115kV or 230kV) 
­lightning arresters (station, distribution and maybe riser pole types) 
­capacitive voltage transformers 
­power transformers (eg. 230kV/27.6kV, 100MVA) 
­M.V. circuit breakers (main, tie and feeders) 
­instrument transformers 
­relay/metering panels 
­overhead distribution lines and poles 
­fuses, insulators & switches 
­underground cables, terminations & splices 
­distribution transformers (single and three phase) 
­reclosers and/or sectionalizers 
­system control & data acquisition equipment 
­distribution transformers (single and three phase) 
­reclosers and/or sectionalizers 
­system control & data acquisition equipment 
For distribution of power from the service entrance boards downstream to the different loads and load 
centers, the major elements are: 
­M.V. service entrance board or gear complete with breakers or switches/fuses combination 
­main distribution transformers (dry or liquid filled eg. 27.6kV/600V) 
­600V distribution board complete with molded case breakers/switches and/or power breakers 
­secondary distribution transformers (600/120/208V) 
­600V motor control centres 
­M.V. motor starters complete with motor protective relays 
­distribution/lighting panels complete with molded case circuit breakers or fuses 
­interconnecting wires/cables and loads (motors, lighting, appliances, office equipment, heating 
equipment and others) 
Protection for transformer station: 
The power transformers can have any of the following connections: 
Y­delta, delta­YG, Y­D­YG, delta­YG­YG, Y­ZG, Y­ZG­ZG. 
The protection to the power transformers (example of rating 75/100/125MVA, 230kV/27.6kV) will be 
against internal faults and is provided through the use of gas relays (in the transformer tank and tap 
changer enclosure) and one differential relay. Another differential relay of a different type, redundant 
(for dependability reasons) may,also, be used. Other faults that may occur and do not warrant a trip but 
rather an alarm or the operation of a bank of fans are: overload and overheating of the transformer. For 
overvoltage protection, horn gap protectors, lightning arresters and transformer rod gaps may be used. 
Overexciting of the transformer may occur and an overvoltage relay may be used to indicate or alarm, 
rather than to trip. Other devices that are found on transformers in order to indicate or protect against a 
certain abnormality are: thermometers, winding temperature equipment (thermometers) and pressure 
relief devices. Thermometers indicate top liquid temperature (ambient plus temperature rise of 
transformer). Thermometers may have a bimetal spiral in the metal housing, temperature indicating 
pointer, drag pointer (resettable). The liquid tight well for the sensing element allows the removal of the 
thermometer with no further steps. Thermometers may have up to three micro switches, the first for the 
fans (close @ 70 C, open @ 65 C), the second for the alarm (close @ 85, open @ 80) and the third for 
the trip (close @ 85 , open @ 90 ). The winding temperature thermometers can be classified into direct 
type and C.T. type. The first type has a capillary tube equiped with porcelain insulator that isolates the 
sensing bulb from the thermometer. The bulb is usually placed in direct contact with the low voltage 
bus. The second type consists of thermometer bulb, a resistor or thermocouple inserted in resistance 
heating element which is energized from a current transformer. The heating element and temperature 
sensitive device are mounted in a dry well on the tank wall, the whole assembley is then immersed in 
the top liquid. Pressure relief devices are used in sealed transformers. The common types are the 
diaphragm and the mechanical automatic reseal. The diaphragm is designed to rupture before damaging 
pressure can build up. After operation the diaphram has to be replaced. The automatic reseal type will 
maintain its seal until the threshold pressure (eg. 8psi + 1) is reached, at which point the valve snaps 
open, the full operation takes about 2 milliseconds. The device automatically re­closes and reseals 
when the intermal pressure drops to 4 psi approx. Remote and local indicators to show that the device 
had operated are, usually, available but not necessarly as a standard part of the transformer. Restricted 
ground (earth) faults may occur when the transformer neutral is grounded through high impedance, 
special protection is applied. The protection for this application is provided through the use of 4 current 
transformers (sensors), one in each phase and the fourth in the neutral circuit (between the neutral and 
the first terminal of the grounding resistor). The overcurrent relay connected in a differential protection 
configuration is connected across the C.T. in the neutral circuit and the other three current transformers 
connected in parallel. For external faults the secondary currents will circulate in the current 
transformers windings and not through the operating coil (circuit) of the relay; while in case of internal 
faults it will flow through the relay (this approach is also used in generator protection under similar 
conditions). The differential protection is one that operates when the vectorial difference of two or more 
electrical quantities of the same type exceeds a pre­determined value. What makes a protection 
differential is the way the circuit is connected. The most extensively used current differential relay is 
the percentage. Such relay has operating and restraint coils or circuits. There are two types of 
percentage differential relays: the fixed and the variable. The fixed has the following property: the ratio 
of the differential operating current (the difference of the two secondary currents of the current 
transformers on the high and low voltage power transformer windings divided by 2) to the average 
restraining current (the sum of the two secondary currents of the current transformers on the high and 
low voltage power transformer windings divided by 2) is a fixed value. The variable has the following 
characteristics: the slope of the operating current to the restraint current increases with higher through 
currents. The current in the operating coil tends to operate the relay, the current in the restraint coil 
tends to prevent this operation. This design is necessary to restrain the relay from operation for any 
faults outside the protected zone or for any unbalanced conditions or for the discrepancies in the 
characteristics of the current transformers, avoiding nuisance tripping. Transformers draw a steady state 
magnetizing current under normal operation (exciting current). This current can vary between 1 and 5% 
(depending on the design and type of steel used in the core) of the rated full load current of the 
transformer. Subjecting transformers to overvoltage, increases the exciting current significantly and due 
to the non­linear magnetizing ch/cs of the core, harmonics (third and fifth) will be present. A pick­up 
setting above the steady state exciting current would seem good enough, however, the amount of 
unbalance and the limited restraint at high emergency through current loads, may dictate a higher 
setting. The choice of the percent slope value is a function of three factors. The unbalance in the 
secondary outputs of the differential zone C.T. may be caused by the tap changer of the power 
transformer. Secondly, there will be an error current due to the mismatch of the C.T. taps, it is based on 
the average of the restraint currents. Finally, the ratio errors of the current transformers themselves may 
affect the unbalance of the secondary outputs. All these factors have to be taken into consideration to 
get the maximum possible percent unbalance. When transformers are energized, a large inrush transient 
current will flow through the primary of the transformer (and not seen by the secondary windings). 
Thus, the operating coil of the differential relay will receive currents with high peak values, leading to 
greater tendency for the relay to operate. The magnitude and wave shape of the inrush current is 
function of: the magnitude (point) of the supply voltage, at which the transformer is energized, the 
residual flux and its relationship in polarity and magnitude with respect to the instantaneous value of 
the steady state flux (corresponding to the particular initial energization point), the ratio of saturation 
flux density to the operating flux density at rated voltage. The duration of the inrush is affected by the 
size of the transformer bank and the resistance in the power system from the source to the transformer. 
The magnitude will be affected by the size of the power system, type of steel used in the transformer 
core and its saturation density and the residual flux level. For three phase transformers, the electrical 
connections of the windings and the magnetic coupling between the phases, affect the inrush. The 
inrush current is rich in second harmonic components, it varies from 20% to 65%. There are another 
two types of inrush, other than the initial, the first is the recovery which is the inrush that occurs after a 
fault external to the bank has been cleared and the voltage rises from the fault condition to the normal 
level. The second is the sympathetic inrush which is the inrush to an already energized transformer 
while another one in parallel with the first is being energized. 
Differential relays may have a second harmonic restraint element to prevent the relay operation during 
transformer energization. A dedicated over­excitation protection is provided when it is desired to protect 
against overvoltage (for short times). Differential relays can have a fifth harmonic filter to restrain the 
relay from operation (when overexcited). This will prevent the relay (instantaneous) operation, due to 
overvoltage. The percentage of the fifth harmonic (due to overvoltage) is approximately 35% of the 
fundamental. The third harmonic is also present when over­exciting the transformer. The current 
transformers should be selected and connected to achieve the following: 
­ correct secondary currents of the current transformers to reflect the different voltages (and 
cosequently the full load and fault currents) of the secondary of the power transformer to its primary. 
­ if there is a phase shift angle between the secondary and primary, the C.T. connection on each side 
should compensate for such difference (eg. for a delta or a zig­zag connected power transformer 
windings, the current transformers have to be connected in wye; for a wye connected power transformer 
windings, The current transformers to be connected in delta). 
­ the secondary currents through the differential relay should not cause the relay to operate under 
external (through) faults or maximum emergency load and should operate the relay for internal faults 
(should be sufficiently higher than the restraint pick­up level). 
The C.T. ratio is chosen so that it will give a secondary current close to but less than the nominal rated 
current of the relay at maximum load condition. Two winding percentage differential relays can be used 
for three winding transformers, provided the current transformers on the secondary side of the 
transformer are connected in parallel. Its advantage is its cost saving. 
In a network where more than one station is fed from the same transmission line through power 
transformers, a fault in the protected zone of the transformer should trip the breaker or breakers (main) 
on the low voltage side, remote tripping of the breakers upstream of this transformer (at terminal 
stations) and all low voltage side breakers (main) of transformers connected to the same line. The load 
break switch on the high voltage side, connected to the transformer high voltage bushing, is also tripped 
open. When the switch opens, the remote trip signal will be terminated (because of the disconnect 
switch interlock used in the remote trip circuit), the terminal breakers and l.v. breakers connected to the 
other than the faulty transformer are reclosed. For gas protection, Buchholz (pressure type) relays 
connected between the tank and the conservator (in the piping) are used. One of the 2 elements of this 
relay is a gas collecting chamber. After a certain amount of gas is collected, a contact is closed to sound 
an alarm. The second element contains a vane which is operated by the rush of oil through the piping. 
The first to protect against slow breakdown of insulation, the second against severe faults occurring 
inside the transformer. 
The second type of subtransmission/distribution system protection is the overhead line (H.V. eg. 230kV 
or 115kV) carried on transmission towers. This type of protection is applicable to transformer stations 
with ungrounded wye or delta transformer high voltage windings. Assuming a system that has two lines 
feeding a station through a breaker and a half (H.V. bus configuration) and the secondary of the 
transformers have main breakers and a tie breaker between the 2 medium voltage buses, under a fault on 
a line, a remote trip from the terminal stations is sent to initiate a trip and the pertinent M.V. breaker, 
that will complete the fault isolation, is opened. In this case, the line protection at the transformer 
station will be considered as back­up. If the terminal station has no remote trip capability, this line 
protection at the transformer station is the first line of protection to trip the M.V. breaker. This 
protection is achieved through the use of directional phase distance relays (IEEE #21) and ground 
residual overvoltage relays (non­directional). 
The use of two independent differential protections on power transformers at transformer stations, make 
it necessary to use circuit breaker failure protection for the main M.V. breakers. This protection is 
controlled from one of the contacts of the breakers auxiliary switch. When this protection is to operate 
with a standard configuration of a dual secondary winding power transformer, a signal is sent to initiate 
tripping of all breakers necessary to isolate a fault. In the event of failure of one of the main M.V. 
breakers, the breaker failure protection will trip all feeder breakers, the tie breaker and two of the 
remaining closed main breakers. It also sends remote trip to the terminal station affected and opens the 
transformer disconnect switch (at the right moment while no current is flowing through the switch) to 
isolate the transformer with the faulty breaker, thus permitting a reclose of the terminal breaker. 
Circuit breaker re­closing schemes are used between the terminal and transformer stations. The purpose 
of having such schemes is to permit reclosing after transient faults on H.V. lines thus: 
­ re­establishing the interrupted interconnections 
­ terminating any low voltages on customer buses 
­ restoring the previous level of load security 
Automatic reclosing can be classified into delayed and high speed. The latter is defined as closing the 
circuit breaker after a time delay, just sufficient to allow for the de­ionization of the arc. This time = 6 
to 10.5 + (system KV/34.5) cycles and it varies from 12 to 17 cycles for 230kV lines. As long as 
maintaining stability of the system is not a function of reclosing, high speed reclosing is not a must. 
The delayed reclosing is in the range of 5­10 seconds, this allows the initial system oscillation to decay. 
Re­closing is only permitted if specific system conditions are to be satisfied. When reclosing occurs for 
more than one circuit element, a pre­determined sequence is to be set. The control logic to allow the 
reclosing can be any combination of the following: voltage presence, undervoltage, synchrocheck, long 
and short time. Two contacts from the voltage relay, one normally open, the other normally closed, 
provide the voltage presence and the undervoltage supervision, respectively. The relay picks up at 80% 
of the nominal and drops out at 30% of the nominal. The synchro­check relay provided, checks for the 
presence of the voltage on both sides of the opened C.B. and that they are within the limits, it checks, 
also, for the phase angle between the two voltages and that they are within a preset range for the period 
of time defined. The long and short­time time are usually used in conjunction with the voltage 
supervision relay (voltage presence using the U/V condition). Generally, any attempt to reclose 
(automatically) a circuit breaker following a trip is made only if there is a reasonable probability that 
the fault initiating the trip is transient in nature. A single shot reclose scheme (a practical approach), 
provides similar discrimination for line faults. A single close attempt, after the initial trip, is considered 
a test for the nature of the fault. If the breaker recloses and stays for a minimum period of 10 seconds, 
the fault is assumed to be of a transient nature and the scheme resets (getting ready for the next fault). 
Reclosure is cancelled, not initiated, if the fault is occurring in a zone where transients are unlikely like 
generators, transformers, bus ducts and switchgear bus assemblies. To achieve remote trips and reclose, 
communication channels are required. Signals can be transmitted through power line carriers, by 
microwave antenna or through a dedicated pair of telephone wires. The last has a d.c. voltage applied at 
the local end to energize voltage sensing relays, installed at the remote ends which trip/annunciate the 
appropriate circuit. Generally, two such channels are provided to improve reliability. The availability, 
routes, size and type of telephone wires vary greatly (eg. #22 to #26 or #19 AWG). The maximum loop 
resistance of the telephone circuit (for two ended circuits) has to be 9600 ohm if the voltage at the trip 
receive relay end is to be 55V d.c., when the sending end has 125V d.c. This resistance is equivalent to 
approximately 90 km of #22 AWG and 56 km of #24 AWG. When the sending end has 250V d.c., the 
loop resistance can be 10,600 ohms, which is equivalent to 100 km and 61 km of #22 & #24 AWG, 
respectively. Monitoring relays, located at one terminal only, are used to indicate or annunciate when a 
channel becomes defective. The operating time of such protection can be 25 MilliSec, when both 
channels operate (higher speed of operation is allowed as when both channels are operating the chance 
of having false signal from both channels simultaneously is quite remote) or when one channel operates 
(to allow for transients and to avoid nuissance tripping) is 85 MilliSec. 
The two remaining types of transformer station protection are: the medium voltage bus protection 
(differential, phase O/C and ground O/C relays), the feeder protection. In most cases, the M.V. bus is 
fed from the zig­zag secondary winding of the power transformer with the neutral reactor grounded or 
from the delta winding. Overcurrent relays connected in a differential configuration or percentage 
differential relays or high impedance bus differential relays are used to protect against permanent faults 
in the bus zone. The common neutral of the differentially connected C.T.s (from the main transformer 
low voltage breakers, tie breaker and feeder breakers) are grounded at one point only. All current 
transformers will have the same ratio and characteristics. All feeder breakers, transformer breakers and 
tie breakers on the faulted bus are tripped and automatic reclosure is inhibited when this relay operates. 
This differential protection relay (one per phase) will have an instantaneous and timed element. 
Overcurrent back up protection is provided using phase and ground inverse timed O/C relays. Reclosure 
is inhibited when this relay operates. This differential protection relay (one per phase) will have an 
instantaneous and timed element. Overcurrent back up protection is provided using phase and ground 
inverse timed O/C relays and is set to operate on the same breakers as the main protective relays if the 
bus differential scheme fails. Usually, the ground O/C relay requires a high current range to permit 
higher pick­up current settings. The back up protection will trip the breakers as mentioned above, the 
overcurrent relays are connected to current transformers installed in the switchgear on the main 
transformers secondary breaker or breakers connected to the subject bus. 
The feeders (breakers) are protected against overcurrent & short circuit and protection is provided 
through the use of different types of relays O/C timed, instantaneous, auxiliary and reclosing (if 
required). Other types of relays like the solid state/microprocessor, can provide the previously 
mentioned protection with more flexibility and by using only one relay, substituting for the O/C, 
reclosing and auxiliaries. Another advantage of the solid state relay is the amount of data that can be 
retrieved under S.C. conditions on the feeder, like the magnitude of the fault current, the phase or 
phases affected. This data is also important to indicate the cumulative currents, the breaker is subjected 
to when interrupting faults. Generally, these relays have built in ammeters to indicate the current levels 
in the different phases under normal operation. As only radial feeders are covered here, the relays used 
are non­directional. The timed element of O/C relays can have a few shapes such as definite time, 
inverse, very inverse and extremely inverse. The last provides fastest clearance at higher fault values. It 
closely approximates the fuse curves which the relay should co­ordinate with (downstream). The 
extremely inverse characteristics is preferred for cold load pick­up. Initial cold load inrush can reach 4 
times normal peak loads, for a few seconds (about 2 to 10), after which it will decay to approximately 1 
1/2 times. The two parameters that govern the relay operation are the pick­up current value and the 
duration the current has to stay above the pick­up value. High set instantaneous protection are used to 
protect that portion of the feeder that is close to the station. Under close­in S.C. conditions, fast 
clearance is a must. There is usually another setting in feeder protection called low set instantaneous. It 
is intended for transient faults and is used with a reclosing scheme. It is meant to reduce the mechanical 
and the thermal stress on the feeder (and the equipment or lines connected between the source and the 
faulty point) and to reduce voltage disturbances on the station bus and consequently, the other feeders. 
It is set low to cover the entire feeder. When this protection operates and reclosing is initiated, the low 
set instantaneous is blocked as a fault that persists after reclosing is probably permanent and requires 
co­ordinated (with downstream fuses and reclosers) isolation. The low setting protection is also blocked 
during line energization. When discrete relays are used to provide feeder protection, a number of 
measuring relay contacts are connected in parallel. When any of these relays operate, the trip relay is 
energized to trip the C.B., annunciate and initiate reclosing. Reclosing is only used with overhead 
feeder lines and most probably, will be a single­shot one. The reclose scheme is disabled through the 
use of an auxiliary breaker control switch or protective relay contacts (if the breaker was previously 
opened manually or tripped by another protection). Supervision for reclosing is provided through a 
timer. For single shot reclose, the breaker is locked out, under the following conditions: trip on the 
delayed portion of the current/time ch/cs curve, after the previous trip of same or low instantaneous, 
after first trip on the high instantaneous. Typical settings of these relays are the pick­up current is 
approximately twice the full load current of the feeder and less than the minimum feeder end fault (3 
phase). The minimum feeder end fault is to be isolated in 2 to 3 seconds (this is for phase timed O/C 
protection). For ground timed O/C protection, the feeder end ground fault is to be isolated in 1.5 to 2 
seconds. The pick­up level is function of the available ground fault current. It has to accommodate for 
the possible feeder unbalance loading. 
Distribution system protection: 
From the transformer station, the feeder breakers are connected to cables and out it goes to overhead 
lines into distribution transformers, unit substations or distribution stations. The feeders are assumed to 
be of the radial design (rather than the loop ­ network­ one). At the taps, from the overhead lines to, for 
example, underground residential areas or to an industrial plant service entrance board, a power fuse 
and a switching device are usually installed. For a tap into a distribution pole mounted transformer, a 
series of a fuse cutout, with fuse link plus current limiting fuse are installed ahead of the transformer. 
Other switching/protecting components that are found in overhead distribution systems are reclosers 
and sectionalizers. In underground systems, fuses and tripping devices are found. 
For Reclosers & Sectionalizers, refer to Part II. 
For Fuses for Distribution Transformers, refer to Part II. 
Industrial systems protection: 
In industrial systems the protection of equipment and systems uses a variety of breaking/protective 
devices. Certain protectiv/breaking devices are integral, others are separate from each other. The 
breaking devices can be: molded case circuit breakers, air magnetic circuit breakers, molded case 
switches, safety switches, contactors, medium voltage circuit breakers (breaking medium can be any of 
air, oil, SF6 or vaccum). Also, load break switches and disconnect switches are found in industrial 
systems. The majority of the load in such systems is squirrel cage induction motors (about 75 % in 
average of total connected load). 
In generators protective schemes, the following types of relays are found: overcurrent, o/c ground, 
differential, negative sequence o/c, reverse power, field failure and ground fault protection for the field. 
For motors, the following types of relays are usually applied: overcurrent, neutral or ground overcurrent, 
thermal overload, reverse (directional) power relay, phase sequence voltage and 
overvoltage/undervoltage relay. 
For transformer protection, transformer percentage differential, gas and overcurrent relays are found. 
For transmission lines, distance relays are used to protect against faults on lines. 
For bus protection, differential relays or overcurrent relays connected in differential configuration are 
used. Certain critical relays may be duplicated (redundancy) for reliability reasons. Back­up protection 
is also common for critical stations. If the primary protections are to fail, the back up will take over, 
interrupt the circuit or circuits minimizing the disturbances to other load centres. 
For low voltage direct acting tripping devices and fuses, refer to Part II. 
For relays refer to Part II. 
Factory testing: 
Static relays testing methods differ from those of electromagnetic relays, as they have lower burdens, 
are more susceptible to higher voltages and disturbances, are built from semiconductor components 
rather than coils and cores. 
For electromagnetic relays, the following tests are performed at the factory: operation, calibration, 
insulation withstandability and maybe impulse. 
For solid state/microprocessor based, the following tests are performed: operation, current circuit 
dielectric (insulation) withstandability tests (eg. 2.5 KV for 1 min. @ 50 or 60 c/s), other circuits 
dielectric (insulation) tests (eg. 2 KV for 1 min. @ 50 or 60 c/s), impulse voltsge tests (eg. 5 KV, .5 
Joule, shape 1.2/50),fast transient disturbances (eg. 4 KV for 2 min.) and burst tests (eg. 1 MHZ, 2 KV 
decaying to 50 % in 6 cycles and remaining for 2 sec.). 
Site testing: 
This type of testing can be classified into commissioning and routine maintenance. 
The following are typical testing for certain protective relays at the site and prior to start­up of the plant: 

Overcurrent (instantaneous or timed): insulation resistance, pick­up value, drop­out and timing. 
Over/undervoltage: same as overcurrent, above. 
Differential: insulation resistance, pick­up value, timing and slope characteristics. 
Directional: insulation resistance, pick­up, timing, polarity check, directional sensitivity and stray 
operation check. 
Reverse power: insulation resistance, polarity, directional sensitivity and stray operation check. 
Over/under frequency: insulation resistance, pick­up value, drop­out value and timing. 
Distance: insulation resistance, pick­up, timing, polarity check, directional sensitivity, stray operation 
check and flag/auxiliary contacts operation. 
Negative sequence: insulation resistance, pick­up and timing. 
Current balance: same as ­ve sequence, above plus slope characteristics. 
Periodic checks on relays to ensure that the setting (adjustment) has not been changed or drifted are 
important. At the setting the following is checked (whichever applicable to the relay type and 
application): operation of relay flags and/or visual indicators (local and remote), the tripping of the 
associated breaker, the operation of the annunciator panel or sound alarm. The frequency of such 
testing is function of the following factors: the environment in which the relay is installed and operated 
(eg. temperature, humidity, degree of pollution), whether the subject protective scheme is a back­up or 
the primary protection, size and importance of equipment being protected, the consequences of 
maloperation of the protective scheme. 
Adjustments (settings): 
As mentioned previously, in order to reach the stage of setting the protective relays, a good 
understanding of the system has to be achieved and the necessary calculations and studies on the system 
have been done. For typical relays, the necessary settings will be given hereafter: 
Overcurrent relays: time delayed setting (eg. .5 to 200% of relay rated current), instantaneous setting (5 
tp 30 times delayed relay setting or relay rated current ­ function of type) and time multiplier setting 
(eg. .05 to 1 in .025 steps). 
Over/undervoltage relays: pick­up setting (eg. 60 to 110 V), drop­out (eg. 70 to 99 %), time delay on 
pick­up and drop­out (eg. instantaneous or .1 to 1 sec.). 
Differential: pick­up slope (eg. 20 to 50 %), operating current setting (eg. 20 to 50 % of relay rated 
current ­ 1 or 5 amp.), unrestrained settable current (eg. 8,13,20 times relay rated current). 
Directional: maximum torque angle (eg. 0 to 90 deg.), sector width (30 to 180 deg.) 
Reverse power: operating time (eg. 1 to 30 sec or instantaneous), minimum pick­up values of current 
and voltage (eg. rated volt, .02 amp.). 
Over/under frequency: frequency setting (eg. 59 c/s), timer setting range (.15 to 5 sec.) 
Distance: relay reach (eg. .2 to 4.5 secondary ohms or 1.27 to 36.6), maximum torque angle (eg. 60 to 
75 deg.) 
Negative sequence: tap setting (eg. from 2.5 to 4.5 amp.), pick­up setting (eg. from 10 to 40 % of tap 
setting), time setting (eg. 5 to 20). 
Current balance: ­ve sequence current pick­up (eg. .3 to 1.2), time delay adjustment (eg. .5 to 4 sec.) 
Voltage phase unbalance: pick­up (eg. 1, 2 or 3 ­ve sequence volt), time delay (4, 8 or 128 cycles). 
Synchro­check: magnitude of vector difference voltage (eg. 20 to 60 V), time adjustment (eg. 1 to 15 
sec.), dead bus­dead line levels (eg. 0 to 120 V). 
Loss of field: impedance setting (eg. 2.08 to 56 ohm in 3% steps), undervoltage unit setting (eg. 65 to 
85 %), timer setting (.2 to 3 sec. in .2 sec.). 
Reclosing: number of reclosures (eg. 1 or 2 or 3), time between reclosures (eg. .5 to 5 sec. adjusted 
continuasly). 
Motor protection: full load current ­ FLC (1 to 6 amp. in .1 amp. steps), instantaneous pick­ip (1 to 10 
times full load current in 1 time ­x­ step), load jam current & delay (eg. 1 to 10 times FLC in .1 steps & 
.5 to 10 sec. in .1 sec.), load loss current & delay (eg. 0 to 1 FLC in .01 steps & 1 to 20 sec. in .1 sec 
steps), ground overcurrent pick­up adjustment (eg. 5 to 50 amp. in primary current and in 1 steps), 
ground overcurrent time delay (.04 to 1 sec. in .01 sec.), ­ve sequence pick­up adjustment (eg. .1 to .5 
FLC in .01 steps), ­ve sequence tripping delay (eg. .05 to 5 sec. in .01 sec. steps), RTD trip setting (eg. 
10 to 200 deg.), RTD alarm setting (eg. 2 to 20 deg. below trip setting). 
Feeder protection: low set starting current adjustment (eg. .5 to 2.5 times rated input current ­ 1 or 5 
amp.), time setting (.05 to 100 sec. or time multiplier = .05 to 1), high set starting current adjustment 
(eg. .5 to 20 times rated input current), operating time (.03 to 100 sec.), starting current of the low set 
ground (earth) fault (eg. .1 to .5 times rated input current), time setting (eg. .05 to 100 sec. or time 
multiplier = .05 to 10), starting current of the high set ground (earth) fault (eg. .1 to 4 times rated 
current), operating time setting (eg. .05 to 100 sec.), number of high speed reclosing (eg. 1), number of 
delayed reclosing (eg. 1 to 3 or 4), initiated by overcurrent starting delay preceding high speed or 
delayed reclosing (eg. .05 to 2.5 sec. or .05 to 5 sec.), initiated by ground fault starting delay preceding 
high speed or delayed reclosing ( similar to initiated by o/c), dead time of high speed or delayed 
reclosing (eg. .1 to 99 sec. or 2 to 999 sec.). 
Co­ordinaion studies: 
For the coordination study the following data are essential: the relays current­time characteristics 
curves, fuses total clearing time­current & minimum melting time­current characteristic curves, total 
available 3­phase short circuit current in the system, the 58% IEEE point for transformers connected in 
delta ­ wye, damage curves for cables & transformers, inrush currents to induction motors and their 
durations, inrush currents for transformers and duration, relays burden data, instrument transformers 
saturation, excitation, accuracy, ratio, taps number and ratios data. 
For a numerical example regarding power transformer protection, refer to EPDS, level 1, lesson 2, 
question 27 
For a numerical example regarding sizing of breakong devices, refer to EPDS, level 1, lesson 3, 
question 16 
For a numerical example regarding principle calculations of power systems analysis, refer to EPDS, 
level 1, lesson 5, question 12

You might also like