FBKU-R ( ROTATIVE ) ON / OFF CALIBRATION ...................................................3 FBKU-L ( LINEAR ) ON / OFF CALIBRATION.........................................................4 FBKU-R A ( ROTATIVE ) THROTTLING CALIBRATION ........................................5 REVISIONS HISTORY .................................................................................................7

Page 2 / 8

FBKU Calibration - Technical Manual r 00

1. FBKU-R ( Rotative ) On / Off Calibration


The valve is tested and calibrated by RIZZIO but if is needed a new calibration follow the instructions below with valve in CLOSE position: 1. Unscrew the bolt and remove the local position indicator; 2. Unscrew the socket-head-screws and remove the E-Act cover; 3. Unscrew the grub-screw and rotate the dimmer in clockwise direction until the calibration RED led is lit; 4. Screws the grub-screw, Open and Close the valve to see the correct indication on the position led; 5. If calibration are OK, close the E-Act cover and screw the socket-head-screws; 6. Install the local indicator and screw the bolt. If you replace the FBKU-R or the Dimmer be careful to install the dimmer in a correct way according the picture.

Calibration Led

Page 3 / 8

FBKU Calibration - Technical Manual r 00

2. FBKU-L ( Linear ) On / Off Calibration


The valve is tested and calibrated by RIZZIO but if is needed a new calibration follow the instructions below with valve in CLOSE position: 1. Unscrew the socket-head-screws and remove the Actuator cover; 2. Unscrew the grub-screw and move the dimmer in down direction until the calibration RED led is lit; 3. Screws the grub-screw, Open and Close the valve to see the correct indication on the position led; 4. If calibration are OK, close the Actuator cover and screws the socket-head-screws; If you replace the FBKU-L or the Dimmer be careful to install the dimmer in a correct way according the picture.

Calibration Led Actuator Stem

Dimmer

Dimmer in Close position

Page 4 / 8

FBKU Calibration - Technical Manual r 00

3. FBKU-R A ( Rotative ) Throttling Calibration


The valve is tested and calibrated by RIZZIO but if is needed a new calibration follow the instructions below with valve in CLOSE position: 1. 2. 3. 4. Unscrew the bolt and remove the local position indicator; Unscrew the socket-head-screws and remove the E-Act cover; Unscrew the grub-screw and puts the dimmer in the drawing position; Screws the grub-screw, Open and Close the valve to see the correct indication on the position led; 5. If calibration are OK, close the E-Act cover and screw the socket-head-screws; 6. Install the local indicator and screw the bolt. If you replace the FBKU-R A or the Dimmer be careful to install the dimmer in a correct way according the picture.

2th led Off S et Zo

3th led
ne

Calibration Tools / Service PC connection

Calibration Led

Page 5 / 8

FBKU Calibration - Technical Manual r 00

Dimmer in Close position

Page 6 / 8

FBKU Calibration - Technical Manual r 00

4. Revisions history
Author GM Date 05/11/2008 Revision 00 Word Format 04 Comments