Professional Documents
Culture Documents
Contents
Description Page Table 1 Motor Load Reference. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Table 2 Non-Motor Load Reference. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Table 3 Surge Capability. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Table 4 Fuel Pipe Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Table 5 LP Vapor (LPV) Tank Sizing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 UPS Generator Compatibility. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Onsite Estimating Sheet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 System Capacity Load Calculator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Worksheet NEC 2008, 220 Part IV. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Typical Generator/Transfer Switch Combinations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 NEC (700, 701, 702) Comparison.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Electrical Formulas.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Weights and Measures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Important Notice:
This booklet is designed to familiarize estimators and installers with proper sizing guidelines for residential and commercial generators. The information is not comprehensive, nor does it replace or supercede any material contained in any of the written documents shipped with the equipment. This booklet should only be used in conjunction with the Owners Manual, Installation Manual and other technical documents shipped with each product. Always read all accompanying documentation carefully before attempting to install any generator, transfer switch or related equipment.
Safety Information:
Proper sizing of the generator is crucial to the success of any installation and requires a good working knowledge of electricity and its characteristics, as well as the varying requirements of the electrical equipment comprising the load. When analyzing the electrical load, consult the manufacturers nameplate on each major appliance or piece of equipment to determine its starting and running requirements in terms of watts, amps and voltage. When choosing the generator output for commercial or industrial applications, select a rating that is approximately 20 to 25% higher than the peak load (for example, if the load is about 40 kilowatts, select a 50 kW genset). A higher rated generator will operate comfortably at approximately 80% of its full capacity and will provide a margin of flexibility if the load increases in the future. For safety reasons, Eaton recommends that the backup power system be installed, serviced and repaired by an Eaton Authorized Service Dealer or a competent, qualified electrician or installation technician who is familiar with applicable codes, standards and regulations. It is essential to comply with all regulations established by the Occupational Safety & Health Administration (OSHA) and strict adherence to all local, state and national codes is mandatory. Before selecting a generator, check for municipal ordinances that may dictate requirements regarding placement of the unit (setback from building and/or lot line), electrical wiring, gas piping, fuel storage (for liquid propane or diesel tanks), sound and exhaust emissions. If you have a technical question regarding sizing or installation, contact Eatons Technical Service Center toll free at 1-800-975-8331 during normal business hours (8 a.m. to 4 p.m. CST).
LR Amps @ 208V 3 22 44 67 78 97 146 97 167 146 250 167 333 416 250 500 333 666 416 833
LR Amps @ 240V 3 19 38 58 67 84 126 84 144 126 217 144 289 361 217 433 289 577 361 722
LR Amps @ 480V 3 10 19 29 34 42 63 42 72 63 108 72 144 180 108 217 144 289 180 361
General Residential Description Refrigerator pump, sump, furnace, garage opener Freezer, washer, septic grinder General 1 Hp Well & septic lift pump Hp 0.5 Running kW 0.5 Amps @ 120V 1 4.9 4.9 Amps @ 240V 1 2.5 LR Amps @ 240V 1 13 LR Amps @ 120V 1 25 kW 1.5
0.75
0.75
7.4
3.7
19
38
2.3
1 2
1 2
9.8 19.6
4.9 9.8
25 50
50 100
3 6
Caution: Do not size the generator based on starting kW alone. You must compare LR Amps to generator surge capability (table #3). Size the generator by following the sizing instructions.
EATON CORPORATION www.eaton.com
Amps @ 120V 1 N/A N/A N/A N/A N/A N/A 24.9 10.4 12.5 8.3 8.3 8.3 8.3 12.5 12.5
Amps @ 240V 1 50 29 23 50 30 19 N/A N/A N/A N/A N/A N/A N/A N/A N/A
Residential (LR Amps @ 30% Voltage Dip) 240V 1 134 138 153 205 225 225 254 292 321 550 550 738 1088 208V 1 92 92 137 137 150 151 169 195 214 330 366 441 724 240V 3 N/A 91 118 130 118 131 147 168 185 318 318 426 628 480V 3 N/A 59 64 87 87 87 97 112 112 190 212 255 419
Generators (Operating at 3600 RPM) 7 8 10 13 14 16 17 18 20 25 30 35 45 60 70 80 100 150 29 33 42 54 58 67 71 75 83 104 125 146 188 250 292 333 417 625 N/A N/A N/A N/A N/A N/A N/A N/A N/A 87 104 121 156 208 243 278 347 520 N/A N/A N/A N/A N/A N/A N/A N/A N/A 75 90 105 135 180 210 240 300 451 N/A N/A N/A N/A N/A N/A N/A N/A N/A 38 45 52 68 90 105 120 150 226 23 26 31 48 52 59 63 67 73 71 100 113 146 179 275 275 369 558 N/A N/A N/A N/A N/A N/A N/A N/A N/A 48 67 75 98 120 164 183 222 372 N/A N/A N/A N/A N/A N/A N/A N/A N/A 46 60 60 94 103 142 158 214 322 N/A N/A N/A N/A N/A N/A N/A N/A N/A 30 43 43 57 69 95 106 128 215 46 51 63 95 102 117 125 133 145 138 205 225 292 350 550 550 738 1121 N/A N/A N/A N/A N/A N/A N/A N/A N/A 92 137 150 195 234 330 366 441 747 N/A N/A N/A N/A N/A N/A N/A N/A N/A 91 130 118 168 204 286 318 426 647 N/A N/A N/A N/A N/A N/A N/A N/A N/A 60 87 87 112 136 190 212 255 431
Note: All nominal ratings based upon LP fuel. Refer to specification sheet for NG ratings and deration adjustments for ambient temperature and altitude.
EATON CORPORATION www.eaton.com
LPG: 8.55 ft 3/lb., 4.24 lbs./ 3 gal., 2500 btu/ft. LPG: 36.3 ft3 = 1 gal.
1 inch Water Column = 0.036 psi. 5-14 inches water column = 0.18 psi to 0.50 psi.
Note:
Pipe sizing is based on 0.5" H2O pressure drop. Sizing includes a nominal number of elbows and tees. Please verify adequate service and meter sizing.
Tank Capacity (btu/hr.) 246,240 164,160 82,080 293,760 195,840 97,920 507,600 338,400 169,200 642,600 428,400 214,200 792,540 528,360 264,180 1,217,700 811,800 405,900 1,416,960 944,640 472,320
Length
Diameter
Overall Ht.
120
72
57
24
33
150
90
68
24
33
250
150
94
30
39
325
195
119
30
39
500
300
119
37
46
850
510
165
41
50
1000
600
192
41
50
Load (kW) 5 10 15 20 25 30 35 40 50 60 70 80 90 100 110 120 130 140 150 200 300
BTU / Hr 110,000 176,400 231,800 267,100 352,800 418,300 467,400 550,000 675,000 836,600 1,035,700 1,170,000 1,200,000 1,280,000 1,550,000 1,675,000 1,800,000 1,925,000 2,050,000 2,800,000 4,100,000
LP Gal / Hr 1.2 2 2.5 2.8 3.8 4.5 5.1 6.1 7.5 9 11 12.7 13 13.8 17.1 18.5 19.5 21.3 22.7 30.9 45.3
NG Ft3 / Hr 110 156 220 262 316 417 485 550 675 862 1,020 1,154 1,200 1,260 1,550 1,675 1,786 1,925 2,050 2,800 4,100
NG Therms/ HR 1.1 1.6 2.2 2.6 3.2 4.2 4.8 5.5 6.7 8.6 10.2 11.5 12 12.6 15.5 16.7 17.8 19.2 20.5 28.0 49.0
Gas Required For Common Appliances Appliance Warm Air Furnace Single Family Multifamily, per unit Hydronic Boiler, Space Heating Single Family Multifamily, per unit Hydronic Boiler, Space and Water Heating Single Family Multifamily, per unit Range, Free Standing, Domestic Built-In Oven or Broiler Unit, Domestic Built-ln Top Unit, Domestic Water Heater, Automatic Storage, 30 to 40 gal. Tank Water Heater, Automatic Storage, 50 gal. Tank Water Healer, Automatic Storage, Instantaneous 2 GPM 4 GPM 6 GPM Water Heater, Domestic, Circulating or Side-Arm Refrigerator Clothes Dryer, Type 1 (Domestic) Gas Fireplace Direct Vent Gas log Barbecue Gas light Incinerator, Domestic Approxlmate Input (btu/hr.) 100,000 60,000 100,000 60,000 120,000 75,000 65,000 25,000 40,000 35,000 50,000 142,800 285,000 428,000 35,000 3,000 35,000 40,000 80,000 40,000 2,500 35,000
Note: Tank BTU capacity and generator run times based upon maintaining a minimum tank fuel level of 20%. Tanks are typically filled to 80% full. Typical fuel consumption based on a generator 100% loaded.
Single phase models: Limit the total UPS loading to 25% of the generator capacity. Single phase Minuteman UPS models: Limit the total UPS loading to 50% of the generator capacity. Three phase models without filters (current distortion > 30%): Limit the UPS loading to 35% of the generator capacity. Three phase models with filters (current distortion < 10%): Limit the UPS loading to 80% of the generator capacity.
Limit the total UPS loading to 15% - 20% of the generator capacity.
Passive (Standby) 3000 series Enspire Back-UPS Series PowerSure PST & PSP
Line-Interactive 5000 series Enterprise Plus Smart-UPS Series PowerSure PSA & PSI
Applications
Contractor______________________________________________ Email_________________________________________ Phone______________________________________________ Fax_____________________________________________ Job Name__________________________________________________________________________________________ Date__________________________________ Location__________________________________________________ VOLTAGE TYPE ELEC. SERVICE 120/240 1 Natural Gas 100 Amp 120/208 3 LP Vapor (LPV) 200 Amp 400 Amp 600 Amp Other____________ 120/240 3 277/480 3
The QT Series does not meet the necessary requirements for the following applications:
NEC 695 Fire Pumps NEC 700 Emergency Systems NFPA 20 Fire Pumps NFPA 99 Healthcare NFPA 110 Emergency Systems
Before installation contact local jurisdiction to confirm all requirements are met. Jurisdictions may vary. Eaton recommends contacting local authorities prior to installation. Loads: Look for heavy building loads such as refrigeration, air conditioning, pumps or UPS systems.
NEC 225 Branch Circuits and Feeders NEC 240 Overcurrent Protection NEC 250 Grounding NEC 445 Generators NEC 700 Emergency Systems NEC 701Legally Required Standby NEC 702 Optional Standby NFPA 37 Installation & Use of Stationary Engines NFPA 54 National Fuel Gas Code NFPA 58LP Gas Code
Motor Load Table (Refer to Table 1) Use the following for sizing and determining generator kW. Device HP RA LRA kW Rnning (= HP) Starting kW
Starting kW for HP < 7.5 starting kW = HP x 3 Starting kW for HP > 7.5 starting kW = HP x 2 Starting kW for loading with no listed HP, calculate HP based on running amps in the chart on the right
Non-Motor Load Table (Refer to Table 2) Use the following for sizing and determining generator kW. Device Amps kW
Transfer Switch Avalability Single Phase* Service Entrance Non-Service Entrance Three Phase Service Entrance Non-Service Entrance 100, 225, 300, 400, 600, 800 100, 200, 300, 400, 600, 800 Amps 100, 200, 400, 600, 800 50, 100, 200, 400, 600, 800
* Single Phase ATSs from 100-400 Amp have intelligent load management standard. To Calculate kW 120 V 1 240 V 1 208 V 3 240 V 3 Install notes:
Amps x 120/1000 = kW Amps x 240/1000 = kW (Amps x 208 x 1.732 x PF) /1000 = kW (Amps x 240 x 1.732 x PF) /1000 = kW (Amps x 480 x 1.732 x PF) /1000 = kW
480 V 3
Suggested concrete pad minimum thickness of 4 with 6 overhang on all sides. Composite pad included with air-cooled products. Consult manual for installation recommendations. Consult local authority having jurisdiction for local requirements.
Recommended Generator Size ___________ Refer to Generator Sizing Instructions on other side of this sheet.
Enter running kW for all motor loads (except the largest) expected to run during peak load levels into table 6. Refer to table 1 for typical motor load sizes and electrical requirements. Enter kW for all non-motor loads expected to run during peak load levels into table 7. Refer to table 2 for typical residential loads and rules of thumb. Add the running motor load kW, non-motor load kW, and the starting kW of the largest motor load. _______________ kW _______________ kW _______________ kW = _______________ kW
Motor load running total (minus largest motor): (ref. table 6) Non-motor load total: (ref. table 7) Starting load from largest cycling motor: (ref. table 6) Total electrical loads:
Select generator: Commercial (add 20 to 25% to total kW) Residential (add 10 to 20% to total kW)
Confirm that voltage dip is within acceptable limits by comparing motor LRA to generator surge capability (see table #3). Confirm UPS compatibility (see page 6).
System Capacity Load Calculation If the local municipality or state you are in has adopted the 2008 NEC Code, you may be required to use this step. Article 702 of the 2008 NEC includes a new requirement for sizing (702.5B). If no other method for sizing is acceptable, sizing of the generator shall be made in accordance with Article 220 of the NEC. The system capacity estimating sheet will guide you through this process.
Project Layout
Ball Park Estimates (Do not use for final sizing) Estimate based on 60% service size: (commercial) 240 Volts, 1 : __________ 208 Volts, 3 : __________ 240 Volts, 3 : __________ 480 Volts, 3 : __________ 240 Volts, 1 : __________ 208 Volts, 3 : __________ 240 Volts, 3 : __________ 480 Volts, 3 : __________ Amps x .15 = __________ kW Amps x .22 = __________ kW Amps x .25 = __________ kW Amps x .50 = __________ kW Amps x .10 = __________ kW Amps x .15 = __________ kW Amps x .17 = __________ kW Amps x .34 = __________ kW
Estimate based on square footage Fast food, convenience stores, kW = 50 kW + 10 watts/sq. ft. restaurants, grocery stores Other commercial applications kW = 30 kW + 5 watts/sq. ft. Square footage = __________ Estimated kW = __________
Amps to kW Rule of Thumb (assumes .8 pf) For 480 volt systems For 208 volt systems For 240 volt 3 systems For 240 volt 1 systems
10
EATON CORPORATION www.eaton.com
Served by a single feeder conductor (generator) 120/240 volt or 208Y/120 volt service Ampacity of 100 amps or greater 220.82 (B) 220.82 (C)
The calcultated load will be the result of adding 220.82 (B) General Loads, and
220.82 (C) Heating and Air-Conditioning Load Calculated neutral load determined by 220.61. (Additional 70% demand factor can be taken for cooking appliances and dryers when tables 220.54 and/or 220.55 are used)
General Loads General Lighting and General-Use Receptacles Calculate at 3 VA per square foot
Use exterior dimensions of the home to calculate square footage do not include open porches, garages, or unused or unfinished spaces not adaptable for future use. Add 20-amp small appliance & laundry circuits @ 1500 VA each 220.82 (B) (2) 220.82 (B) (3) 220.82 (B) (3) a 220.82 (B) (3) b 220.82 (B) (3) c 220.82 (B) (3) d 220.82 (B) (4) 220.82 (C) 220.82 (C) (1) 220.82 (C) (2) 220.82 (C) (3)
Calculate the following loads at 100% of nameplate rating Appliances fastened in place, permanently connected or located on a specific circuit
Ranges, wall-mounted ovens, counter-mounted cooking units (Tables 220.54 & 220.55) Clothes dryers not connected to the laundry branch circuit Water heaters Permanently connected motors not included in Heat & Air-Conditioning Load section
Heating & Air-Conditioning Loads Include the largest of the following six selections (kVA load) in calculation Air Conditioning and Cooling 100% of nameplate rating Heat Pumps Without Supplemental Electric Heating 100% of nameplate rating Heat Pumps With Supplemental Electric Heating 100% of nameplate rating of the heat pump compressor*
65% of nameplate rating of supplemental electric heating equipment If compressor & supplemental heat cannot run at the same time do not include the compressor 220.82 (C) (4) 220.82 (C) (5) 220.82 (C) (6)
Electric Space Heating Less than 4 separately controlled units @ 65% of nameplate rating
4 or more separately controlled units @ 40% of nameplate rating 40% of nameplate rating if 4 or more separately controlled units
Electric Thermal Storage (or system where the load is expected to be continuous at nameplate rating 100% of nameplate rating
Systems of this type cannot be calculated under any other section of 220.82 (C).
Load Calculations General Lighting Load Small Appliance & Laundry Circuits
3 VA x ft + 1500 VA per circuit + Total general appliances Total general load (VA) = 10,000 VA (Total VA - 10,000) x .40 = Calculated General Load (VA) Largest Heat or A-C Load (VA) = TOTAL CALCULATED LOAD
General Appliances & Motors (100% rated load) Sum of all General Loads = Total General Load (VA)
11
Worksheet NEC 2008, 220 Part IV Contractor Phone Job Name Date Voltage (Circle) Fuel Elec. Service NET SQUARE FOOTAGE General Loads General Lighting and General Use Receptacles Branch Circuits (1500 VA/ft) Small Appliance Circuits (20 Amp) Laundry Circuits Fixed Appliances Well Sump Pump Freezer Microwave (Not counter-top model) Disposal Dishwasher Range (See Table 220.55 for multiple cooking appliances) Wall-Mounted Oven Counter-Mounted Cooking Surface Water Heater Clothes Dryer Garage Door Opener Septic Grinder Other (list) 1500 1500 Full Current Rating 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% TOTAL GENERAL LOADS Heat / A-C Load A-C / Cooling Equipment Heat Pump Compressor (if not included as A-C) Supplemental Electric Heat Electric Space Heating Less than 4 separately controlled units 4 or more separately controlled units System With Continuous Nameplate Load Largest Heat / A-C Load (VA) VA kW General Loads 1st 10 kW of General Loads 100% kW Remaining General Loads (kW) 40% kW CALCULATED GENERAL LOAD (kW) kW LARGEST HEAT / A-C LOAD 100% kW kW TOTAL CALCULATED LOAD (Net General Loads + Heat/A-C Load) 100% 40% kw kw kw kw kw 100% 100% 65% 65% 40% 100% VA kW 100% 100% Email Fax Location 240V -1 100 Amp Qty NG 200 Amp Rating (Load) 3 VA/ft LPV 400 Amp Factor 100% Other Loads (VA) Loads (kW) (VA 1,000)
12
10
25
14
27
17
EGS100 EGS100SE EGS100L24R EGS200 EGS200SE EGS100 EGS100SE EGS100L24R EGS200 EGS200SE
30
20
36
45
48
60
70-150
13
14
Known Values Volts, Current, Power Factor Volts, Current kW, Volts, Power Factor Volts, Amps, Power Factor Frequency, RPM RPM, No. of Rotor Poles Frequency, No. of Rotor Poles Motor Horsepower, Efficiency Volts, Amperes Ohms, Amperes Ohms, Volts
1-Phase ExI 1000 ExI 1000 kW x 1000 E Volts x Amps 2 x 60 x Frequency RPM RPM x Poles 2 x 60 2 x 60 x Frequency Rotor Poles HP x 0.746 Efficiency E I IxR E R
3-Phase E x I x 1.73 x PF 1000 E x I x 1.73 1000 kW x 1000 E x 1.73 x PF E x I x 1.73 x PF 2 x 60 x frequency RPM RPM x Poles 2 x 60 2 x 60 x Frequency Rotor Poles HP x 0.746 Efficiency E I IxR E R
15
Metric System
Cube Measure (The unit is the meter = 39.37 Inches) 1 Cu. Centimeter 1 Cu. Decimeter 1 Cu. Meter = = = = = = = 1000 Cu. Millimeters 1000 Cu. Centimeters 1000 Cu. Decimeters 1 Steer 1 Gram 1 Liter 1 Metric ton = 1 Kilogram = = = = 0.06102 Cu. Inches 61.02374 Cu. Inches 35.31467 Cu. Feet 1.30795 Cu. Yards
Mile Measurements 1 Statute 1 Scots 1 Irish 1 Russian 1 Italian 1 Spanish = = = = = = 5,280 Feet 5,952 Feet 6,720 Feet 3,504 Feet 4,401 Feet 15,084 Feet
Measures of Weight (The unit is the gram = 0.035274 Ounces) 1 Milligram 1 Centigram 1 Decigram 1 Gram 1 Dekagram 1 Link 1 Fathom 1 Furlong 1 Cable = = = = 7.92 Inches 6 Feet 10 Chains 608 Feet 1 Hectogram 1 Kilogram 1 Myriagram 1 Quintal 1 Metric Ton 1 Gram 1 Dram 1 Metric Ton = = = = = = = = = = = = = 0.015432 Grains 10 Milligrams 10 Centigrams 10 Decigrams 10 Grains 10 Dekagrams 10 Hectograms 10 Kilograms 10 Myriagrams 10 Quintal .056438 Drams 1.77186 Grams 27.3438 Grains 2,204.6223 Pounds = = = = = = = = = 0.15432 Grains 1.5432 Grains 15.4323 Grains 5.6438 Drams 3.5274 Ounces 2.2046223 Pounds 22.046223 Pounds 1.986412 Cwt. 2,2045.622 Pounds
Square Measurements 144 Square inches 9 Square feet 30 1/4 Yards 40 Rods 4 Roods 640 Acres 1 Square mile 36 Sections Cubic or Solid Measure 1 Cu. foot 1 Cu. yard 1 Cu. foot 1 Gallon (Water) 1 Gallon (U.S.) 1 Gallon (Imperial) = = = = = = 1728 Cu. inches 27 Cu. feet 7.48 Gallons 8.34 Lbs. 231 Cu. inches of water 2771/4 Cu. inches or water = = = = = = = = 1 Square foot 1 Square yard 1 Square rod 1 Rood 1 Acre 1 Square mile 1 Section 1 Township
Measures of Capacity (The unit is the liter = 1.0567 Liquid quarts) 1 Centiliter 1 Deciliter 1 Liter 1 Dekaliter 1 Hectoliter 1 Kiloliter Note: Kilometers 8 = = = = = = 10 Milliliters 10 Centiliters 10 Deciliters 10 Liters 10 Dekaliters 10 Hectoliters = = = = = = Miles 5 0.338 Fluid ounces 3.38 Fluid ounces 33.8 Fluid ounces 0.284 Bushel 2.84 Bushels 264.2 Gallons
x 5 = Miles
or
x 8 = Kilometers
16
Linear Measurement (The unit is the meter = 39.37 Inches) 1 Centimeter 1 Decimeter 1 Meter 1 Dekameter 1 Hectometer 1 Kilometer 1 Myriameter = = = = = = = 10 Millimeters 10 Centimeters 10 Decimeters 10 Meters 10 Dekameters 10 Hectometers 10,000 Meters = = = = = = 0.3937011 Inches 3.9370113 Inches 1.0936143 Yards 3.2808429 Feet 10.936143 Yards 109.36143 Yards 0.62137 Mile
Ft.
.0833
Yd.
.0278
Mile
1.578 x 10-5
Mm
25.4
Cm
2.54
M
.0254
Km
2.54 x 10-5
1 Foot =
12
.333
1.894 x 10-4
304.8
30.48
.3048
3.048 x 10-4
1 Yard =
36
5.6818 x 10-4
914.4
91.44
.9144
9.144 x 10-4
1 Mile = 1 Mm =
63,360 .03937
5,280 .0032808
1,609,344 1
160,934.4 0.1
1,690.344 0.001
1.609344 0.000001
Square Measurement (The unit is the square meter = 1549.9969 Square Inches) 1 Sq. Centimeter 1 Sq. Decimeter 1 Sq. Meter 1 Sq. Dekameter 1 Sq. Hectometer 1 Sq. Kilometer = = = = = = 100 Sq. Millimeters 100 Sq. Centimeters 100 Sq. Decimeters 100 Sq. Meters 100 Sq. Dekameters 100 Sq. Hectometers = = = = 0.1550 Sq. Inches
1 Cm =
.3937
.0328084
.0109361
10
0.01
0.00001
1M=
39.37
3.28084
1.09361
6.2137 x 10-4
1000
100
0.001
0.62137
1,000,000
100,000
1,000
Scientific Notation: A way of expressing very large or very small numbers in a more compact format. Any number can be expressed as a number between 1 & 10, multiplied by a power of 10 (which indicates the correct position of the decimal point in the original number). Numbers greater than 10 have positive powers of 10, and numbers less than 1 have negative powers of 10.
(The unit is the Are = 100 Square Meters) 1 Centiare 1 Deciare 1 Are 1 Dekare 1 Hektare 1 Sq. Kilometer
Cubic Measure (The unit is the Stere = 61,025.38659 Cubic Inches) 1 Decistere 1 Stere 1 Dekastere = = = 10 Centisteres 10 Decisteres 10 Steres = = = 3.531562 Cubic Inches 1.307986 Cubic Yards 13.07986 Cubic Yards
17
Notes
18
19
Generator and transfer switch products are supported by an unparalleled service network and sales force. 24 hour support 7 days a week. For Pre-Sale support contact Eatons Technical Resource Center at 1-877-ETN-CARE. For installation and technical support contact Eatons Aftermarket Support team at 1-800-975-8331. Products are serviced by only factory certified contractors. Eaton generator and transfer switch products are backed by competitive warranties. For additional information or to place an order, contact your local Eaton representative or visit us at http://generators.eaton.com.
Eaton Corporation Electrical Group 1000 Cherrington Parkway Moon Township, PA 15108 United States 877-ETN-CARE (877-386-2273) Eaton.com 2009 Eaton Corporation All Rights Reserved Printed in USA Publication No. TD00405018E August 2009