MASTER DIGITAL CONTROL UNIT FOR LOCAL AND REMOTE MANAGEMENT OF HEATING PLANTS EXPANSION MODULES - SLAVES

SLAVE MASTER

EV91A

FANBUS

EV91C

EV90

2003/05

EV92

EV90 MASTER DIGITAL CONTROL


UNIT FOR HEATING AND TECHNOLOGICAL PLANTS
USE Remote control EV90 is used in particularly complex plants where several different devices are required to solve heat regulation problems. The system consists of a master device EV90, and one or more slave devices connected to the master through a communication bus called a FANBUS. OPERATION The device operates as a central control unit. Through its display and keyboard the user may display and modify parameters of slave control units connected to the FANBUS. A probe detects the value of the outside temperature which is sent by means of the FANBUS to all relevant control units thereby avoiding duplication. The hour and date, including standard time, may be set directly on the front of the device and used by all devices connected to the BUS. Just one modem (analogue or GSM) lets you remotely manage and modify the parameters of the Master EV90 and all other control units. When an alarm is triggered by a slave, it is first transmitted to the master EV90 and then to a remote station or to an enabled mobile phone. Another function of EV90 is boiler regulation (with 1 or 2 stages); it maintains a high enough boiler temperature to provide all connected users with heat. CHOICE OF LANGUAGE During installation it is possible to select the language used to view the Menus. With the control unit off press and hold the + key (see figure hereunder) 4-line, 16-character and switch on the power. When the alphanumeric display SCELTA LINGUA icon appears, reTwo Tx and Rx lease the + key and scroll the lansignalling LEDs i n d i c a t e guages using the + and keys. Upon communication reaching the language desired press TX to FANBUS the > key. The instrument will display RX the information in the chosen language. 1
SCELTA LINGUA: ENGLISH
Two LEDs indicate s ta t u s o f b o t h output relays
2

EV90

DESIGN CHARACTERISTICS DIN 144x144 container, rapid coupling control unit on base with FASTON connectors and see-through cover. Protruding, built-in or back-of-board mounting possibility. All parameters are displayed on a 4-line alphanumeric display with 16 characters per line. To facilitate reading in bad light, press any key to light the display; the light goes off after about 60 seconds of being idle (no key pressed).

Use the UP and DOWN keys to move over a page and to go from one parameter to another

+ -

Use the < and > keys to go from one page to another

Use the + and keys to modify parameters

FANBUSFANBUS You may connect 15 different types of control units to the FANBUS with at most 8 of the same type of control units (so 15x8 = max of 120 control units). You may connect the EV90 to the slave with a simple low voltage, polarity free bifilar duplex cable (both wires may be inverted with each other without causing malfunction). All slaves must be connected in parallel to the BUS. ADDRESS OF CONTROL UNITS Each control unit is identified by two digits that determine its address. The first digit represents the model and cannot be modified. The second one may be set through jumpers on each slave's terminal board: EV91A first digit: 1 EV91C first digit: 2 EV92 first digit: 3 If only one control unit per type is present on the BUS, no intervention is needed. Since the second digit is automatically set =0, the control units will have the addresses 10, 20 and 30 respectively. If 3 EV91A control units are needed on the same BUS, you'll have to set address 1 on the second control unit, and address 2 on

So, the result will be: 1 - EV91A address 10 (no bridge = address 0) 2 - EV91A address 11 (set address 1) 3 - EV91A address 12 (set address 2) 1 - EV91C address 20 (no bridge = address 0) 1 - EV92 address 30 (no bridge = address 0) This way every control unit will have an address that identifies it unambiguously. N.B. the two digits of the address must go in front of all remote management commands for faultless communication with the desired device. 1 - EV91C indirizzo 20 (nessun ponte = indirizzo 0) ADDRESS OF CONTROL UNIT EV90 The master control unit EV90D should be considered in the same way as a slave with a fixed address : 00. So, if you have to change the current time, for instance, you must send the change command preceded by 00. HOW TO SET THE ADDRESSES The purpose of connector A on each device is to supply power and to set its address through jumpers. This is convenient when the device must be replaced because, instead of losing the address, it is memorised in the terminal board and so the new device will automatically assume the address of the old one. Below we have indicated the jumpers to make to have all combinations

A 1 2 3 4 5 6 7 8 ADDRESS "0" A 1 2 3 4 5 6 7 8 ADDRESS "4"

A 1 2 3 4 5 6 7 8 ADDRESS "1" A 1 2 3 4 5 6 7 8 ADDRESS "5"

A 1 2 3 4 5 6 7 8 ADDRESS "2" A 1 2 3 4 5 6 7 8 ADDRESS "6"

A 1 2 3 4 5 6 7 8 ADDRESS "3" A 1 2 3 4 5 6 7 8 ADDRESS "7"

AUTOMATIC RECOGNITION When a new device is added to the BUS it is automatically recognised. After about 60 seconds master EV90 is able to display and communicate with it.

GENERAL DIAGRAM
EXTERNAL PROBE
BOILER PROBE

2-STAGE BURNER

BOILER

RETURN PROBE EV90 FANBUS

SLAVE 1

SLAVE 2

SLAVE 3

SLAVE 4

PLANT MANAGEMENT In normal conditions control unit EV90 shows a list of connected slaves. The first one on the list is EV90 itself, followed by a description of the devices and their address. This description may be modified as desired for every slave and it may be useful to easily identify the devices. Use the up and down keys to position the cursor on the desired slave. Press the > key to communicate with the slave and display and modify its parameters.

MAIN MENU
Device Type EV90 00 GYM 10 SOUTH BUILDING 11 SANITARY 40 BOILERS 1-2 20 BOILERS 3-4 21 INPUTS 50 OUTPUTS 30 .

MASTER control unit List of SLAVE control units + address

OPERATION AS CONTROL UNIT OF BOILER


OPERATION Besides performing the function as the master of a plant, the EV90 may be used as the control unit of a boiler with either fixed temperature or sliding temperature, by directly commanding a one- or two-stage burner. Through a measuring probe the device detects the temperature value of the boiler. If the temperature value falls below differential 1, the first stage is turned on, and if it falls below differential 2 and stays there for a certain length of time, the second stage is also turned on. The command of the relays is visible on the front of the device. The boiler may be turned on and off according to a weekly program that may be set on the same control unit.
BOILER T. 100 90 80 70 60 50 40 30 20 DIFF. 1 DIFF. 2 STAGE 1 ON STAGE 2 ON CALCULATED T.

CALCULATED BOILER TEMPERATURE The boiler temperature the control unit calculates may be fixed or sliding. When it is fixed, the value set will not be changed, but when it is sliding, the value set is added to the highest temperature value required by connected slaves. This way it is possible to regulate the boiler with a temperature that continually varies depending on the requirements of the entire plant. N.B. when you are setting the desired boiler temperature value, bear in mind that with fixed point regulation it is the value the control unit uses, and with sliding regulation, it represents an increase with respect to the highest value decided by the various control units of the plant. LIMITS You may set the highest and lowest boiler temperature limits within which the calculated temperature may vary. The control unit will ensure that these values are not exceeded. DIFFERENTIAL 1 Differential of the first stage. It indicates the temperature difference with the one calculated by the control unit below which the first stage of the burner is turned on. DIFFERENTIAL 2 Differential of the second stage. It indicates the temperature difference with the one calculated by the control unit below which the second stage of the burner is turned on. To avoid useless or ill-timed interventions, this situation should persist for a certain length of time (may be set on the control unit).

EXAMPLES OF PLANTS
Plant 1 -command of 2-stage boiler -two independent heating circuits
-remote management with GSM modem -the devices' addresses are in brackets

FANBUS

EV91A (10)

EV91A (11)

EXTERNAL PROBE

M BOILER PROBE

ANTENNA

2 - STAGE BURNER

BOILER

EXTERNAL PROBE MODEM EV90 (00)

Plant 2 -command of two cascaded boilers -two heating circuits -boiler regulation for sanitary hot water -Remote management with GSM modem

FANBUS

EXTERNAL PROBE

EV91A (10)

EV91A (11)

ANTENNA

SC

B1

BOILER

B2

BOILER

1
V1 V2

SANITARY WATER

MODEM

EV90 (00)

EV91C (20) FANBUS

EV91B (30)

INSTALLATION
INSTALLING THE CONTROL UNIT Fully loosen the tie rod to release the base of the control unit. Lever on the slots with a screwdriver to remove the base. After you have made the electric connections, press the FASTON connectors of the control unit into the couplings of the base until they are fully inserted. Tighten the tie rod.
DIMENSIONS OF CONTROL UNIT EV90 AND MOUNTING SYSTEMS BUILT-IN Fastening 93
screwlo

WALL MOUNTING 4,5


60

136

144

138

91 110

144

138

55 55 110

TEMPERATURE PROBE
BACK-OF-BOARD

EC81

EC82

EC83

138

138

EXTERNAL PROBE EC81 Install the external probe in a vertical position onto the north or north-west side of the building at least 2.5m from the ground. Apply the probe far from heat sources (windows, aerators, flues, etc.) to detect a meaningful temperature for the whole plant. N.B. It's always possible to install one of the external probes on control unit EV91A. The device will automatically use the value measured by its probe instead of the one transmitted by EV90 through the FANBUS. BOILER AND RETURN PROBE EC82-EC83 Contact probe EC82 must be applied onto the water pipe with a special clamp. Put some thermal compound between them to ensure good heat conductivity. For the same reason immersion probe EC83 must be inserted in the sheath filled with mineral oil or silicone grease.

Resistance values based on the temperature:


EXTERNAL PROBE TEMPERATURE C EC81 DELIVERY PROBE TEMPERATURE C EC82 EC83 RESISTANCE W RESISTANCE W

- 20 - 15 - 10 - 5 0 + 5 +10 +15 +20

5592 4499 3650 2979 2449 2024 1684 1408 1184

+ 20 + 30 + 40 + 50 + 60 + 70 + 80 + 90 +100

12090 8313 5828 4161 3021 2229 1669 1266 973

CONNECTION TO THE FANBUS Connect the control units to the Master EV90 through the FANBUS. Bear in mind that the bus has low voltage and is not polarised, so the terminals may be inverted with each other without causing malfunction ADDRESS OF CONTROL UNITS The control units must be addressed to work properly and to be questioned by remote management. Make sure that they are properly configured.

WIRING DIAGRAM
17 18
POWER SUPPLY 230V STAGE 1 COMMAND RS232 TX RS 232 RX RS232 0V FANBUS AL MODEM

20 21 9 10 11 12 13 22 14 15 16

1 2 3 4 5 19 6

RETURN PROBE

DELIVERY PROBE EXTERNAL PROBE

STAGE 2 COMMAND

7 8

N.B. RELAY CONTACTS ARE VOLTAGE FREE

CALIBRATION AND ADJUSTMENT


FACTORY SETTINGS The control unit leaves the factory with all parameters set for normal operation. If it is necessary to reset factory parameters, proceed as follows: turn off the power supply, then turn it on again while pressing the + key on the front. All data entered will be lost, while factory parameters will be reset. CALIBRATION AND ADJUSTMENT Every time power is supplied to control unit EV90, a configuration procedure starts for all devices connected to the bus. After about 60 seconds you may use the unit's keyboard and display to connect with these devices for modifications and readings since the device acts as if it were a display and remote keyboard for all

MENUS RELEVANT TO CONTROL UNIT EV90


COMMAND KEYS FOR MENU READING AND DATA MODIFICATION

+ Use the UP and DOWN keys to move over a page and to go from one parameter to another Use the < and > keys to go from one page to another Use the + and keys to modify parameters

MAIN MENU It contains a list of available submenus. To enter a submenu, press the -> key

Device Type ......................................... EV90 00 GYM 10 SOUTH BUILDING 11 SANITARY 40 BOILERS 1+2 20 BOILERS 3+4 21 INPUTS 50 OUTPUTS 30 .

MENU EV90 . >Information >Boiler Regulation >Programming Schedules >Set Current Time >Remote Management >Temperature Limit ..................................

List of submenus of ontrol unit EV90

INFORMATION SUBMENU:
01/APR/2003 MONDAY 14.35 Outside T.: -02.5 Boiler T.: 58.5 Plant Description: EV90 Control Unit Value of boiler temperature

The user may modify the plant description. This may be useful to identify the plant commanded by the control unit

FANTINI COSMI Via Dell'Osio, 6 Caleppio MILAN EV90 Rev.01

Device code and revision

BOILER REGULATION SUBMENU:


Boiler programming: Always on mode: On Desired Sliding Boiler Temp. DTC:13.5 Boiler Temp Limits: Highest :98.0 Lowest: 10.0 Sliding Regulation MaxT+DTC=Tcc 12.0 13.5 25.5 To set boiler operation to always on, always off or according to programming schedule

Desired temperature : fixed or sliding If fixed, the value set is the one used by the control unit (DBT). If sliding, it is higher (DBT) than the highest value required by the plant's control units.

Tcc represents the desired boiler temperature value. It takes account of the highest and lowest limits, the highest temperature of the plant, etc. Stage 1 Differential : 04.0 Stage 2 Differential: Setting of boiler differentials 0.8.5 Auxiliary Stage Command After Delay of : 02.00 Minutes The burner's second stage is turned off after this delay if the temperature falls below differential 2.

PROGRAMMING SCHEDULES SUBMENU:

MON. on-off Copy Weekly programming of the boiler 07.0 09.30 Use the keys to go to the desired TUE. 22.30 on-off Copy 17.0 value and change it. 07.0 09.30 Position the cursor on the word Copy WED. on-off Copy 17.0 22.30 and press the + key to copy a program 07.0 ------09.30 ------THU. on-off Copy to the next day 17.0 22.30 07.0 ------09.30 ------FRI. on-off 17.0 22.30 Copy 07.0 ------09.30 ------SAT. on-off 17.0 22.30 Copy 07.0 ------09.30 ------17.0 SUN. 22.30 on-off Copy ------07.0 ------09.30 17.0 22.30 -------------

SET CURRENT TIME MENU:


Set time Day: Sunday Time: 17.45 Date: 07/APR/2004

To set current time and date

Daylight Saving Time Start: 17/MAR End: 28/OCT

To set the starting and ending date of daylight saving time. The control unit automatically updates the time.

REMOTE MANAGEMENT SUBMENU:


Device Triggering Alarm No. Send Alarm In 00 Minutes Connection to Serial Bus with GSM Modem Operator No. 1 Phone Number 123456789 Operator No. 2 Phone Number 123456789 Operator No. 3 Phone Number 123456789

It indicates the address of slave device currently triggering alarm and the time lapse before the next alarm call.

To set modem type: GSM (for SMS management) or PSTN analog (for analog modem or GSM modem in data mode) To set the telephone numbers to send alarms to. Unused digits must be cancelled . N.B. an alarm is immediately sent to operator No. 1. and after 15 minutes to Nos. 1 and 2, and after another 15 minutes to Nos. 1, 2 and 3.

SOTTOMENU - TEMPERATURA LIMITE


Lowest Temperature Limit Set : 45.5 Measured: 56.0 If the temperature falls below the set limit, all the slaves connected to the FANBUS reduce their heat requirement. To exclude this function, do not connect the limit probe.

REMOTE MANAGEMENT
SMS CONNECTION
ANTENNA
VIA D CAL ELLOSI DAIA O IN BLO6 CCO
1 4 7 8 0 5 9 2 6 3

DATA CONNECTION

TELEPHONE LINE RS232 SERIAL CABLE RS232 SERIAL CABLE

+ SOFTWARE
SMS GMS MODEM ANALOG OR GSM DATA MODEM ANALOG OR GSM DATA MODEM RS232 SERIAL CABLE

DEDICATED

By connecting the EV90 controller to a GSM modem, the significant parameters of the control unit can be set or read (see SMS remote controls). To connect the controller to an analog or GSM modem follow the instructions relative to the wiring diagram to connect the modem or use the TC EV85 cable. N.B. The maximum length between controller and modem is 15 metres. If management takes place via a GSM modem a mobile phone can be used. If an analog or GSM modem in data mode is used, it is necessary to use a Personal Computer with dedicated control software available only in Italian provided by Fantini Cosmi or downloaded over the Internet. CONNECTING THE MODEM Follow the diagram below to connect the EV90 to the modem. It's necessary to connect pins 7-8 and 4-6 to each other for faultless communication.

20 21 9 10 11 12 13 22 EV90

TX RX 0V

5 4 3 2 1

9 8 7 6

N.B. this connection is available as an accessory with code TCEV80

MODEM CONNECTOR
MALE CONNECTOR DB9

PREPARING THE MODEM Both the GSM and the analogue modem supplied by Fantini-Cosmi will work properly. Another modem may be used provided that the communication speed is 2400bit/sec. To do this, use the command AT+IPR =2400 and save the new configuration with the command: AT&W. If a GSM modem is used, use and memorise the command AT+CMGF=1 to set the SMS message format to text mode. USING A SIM CARD The GSM modem works with any SIM card. Before using one, however, we recommend that you test it in a mobile phone to see if it's working. Particularly: -check that no PIN code has been set. If so, try to exclude it -Check the remaining credit -Send an SMS message and check if it arrives After these checks, install the SIM card in the modem connector OPERATION When a GSM or analogue modem is connected to the EV90, you may remotely read and change some of its data and data of all devices connected to the FANBUS. To properly communicate with the desired device, every command must be preceded by two digits representing the device's address. So, to address commands to unit EV90, you must first enter 00. All possible commands for each slave are described on the instruction sheets for each device. REMOTE MANAGEMENT SMS COMMANDS These commands may be used through a mobile phone by sending an SMS message containing the message to the unit's GSM modem. It answers with a reply SMS message to the phone number that requested the information. To facilitate message reading, the information is enclosed in a < and > sign. And every reply message is preceded by a description of control unit EV90, at times followed by a description of the slave control unit to easily identify the sender.

10

-???
It is used to know which SMS commands may be sent. -Reply: list of possible commands

-STATUS=?
-Reply: information about state of control unit such as temperatures read and set, current time and date

-TIME=12.33
It sets the current time -Reply: information about state of control unit such as temperatures read and set, current time and date

-BOILERT=82.5 It sets the desired boiler temperature without changing the fixed or sliding temperature selection -Reply: information about the state of the control unit -BOILERT=82.5F It sets the desired FIXED boiler temperature -Reply: information about the state of the control unit -BOILERT=82.5S It sets the desired SLIDING boiler temperature -Reply: information about the state of the control unit -PROGx=? -It programs the day x, where x represents the day of the week 1 = Monday, 2 = Tuesday, etc. -Reply: all 6 programming schedules for that day -PROGx=07.00-09.30 17.30-22.00 --.----.-It sets a program schedule for the day there are 3 on and 3 off periods by specifying hours and minutes. Unscheduled periods should be filled in with dashes. Leave a dash or a space between two periods. -Reply: all 6 programming schedules for that day -PAUT It sets the automatic programming schedules -Reply: information about the state of the control unit -PON It sets the always on program -Reply: information about the state of the control unit -POFF It sets the always off program RESET It deletes any alarms Reply: ALARMS DELETED TECHNICAL CHARACTERISTICS Power supply 230V 50Hz Power consumption 5 VA (4W) Contact rating 5A-230Vac (Ohmic charge) voltage free contacts Ambient temperature: 0 50C Weekly programming clock, 5-year battery life, automatic management of daylight saving time (DST) Compliant with norm EN60730-1 Measuring probes: - EC81 external probe - EC82 contact probe - EC83 immersion probe

11

EXPANSION MODULES (SLAVES)


- 1 FANBUS communication channel for connecting Slaves to Master EV90 - All parameters may be displayed and modified through the Master EV90 - Mounting on DIN rail, 6 modules - Power supply 230V 50Hz - Power consumption 7 VA - Removable terminal boards to facilitate wiring

TEMPERATURE REGULATION MODULE WITH EXTERNAL PROBE


TYPE CHARACTERISTICS Input and outputs relays 4 relays: 5A-250V ac (AC1) 1 analogic input for outside temperature (optional) 1 analogic input for delivery temperature - Regulation curve broken by 4 temperatures EV91A - Weekly programming with 6 on and off periods per day - Optimisation of switch-on time

FIXED SANITARY HOT WATER TEMPERATURE REGULATION MODULE


TYPE CHARACTERISTICS - Weekly programming with 6 on and off periods per day - Water temperature regulation: 0+100C Input and outputs relays 3 relays: 5A-250V ac (AC1) 1 analogic input for temperature measurement

EV91B

REGULATION MODULE FOR TWO CASCADED BOILERS


TYPE CHARACTERISTICS -Water temperature regulation: 0+100C Input and outputs relays - 4 relays: 5A-250V ac (AC1) 2 analogic inputs for temperature measurement

EV91C - High and low limits for boiler temperature


- At most 8 connected boilers

GENERIC OUTPUT MODULE


TYPE CHARACTERISTICS - Configuration of all 4 relays: Relay ON- Relay OFF Timed Relay Input and outputs relays 4 relays: 5A-250V ac (AC1)

EV91D - daily programming for all 8 outputs

DIGITAL INPUT MODULE


TYPE CHARACTERISTICS - Setting of active state for all 8 inputs: opening- closing - Configuration for all 8 inputs: Activated breakdown Desactivated breakdown Timed breakdown - Daily programming for each input Input and outputs relays

8 voltage free digital inputs

EV92

12

FANTINI COSMI S.p.A. VIA DELLOSIO, 6 20090 CALEPPIO DI SETTALA MI International calls Tel.++39 02 95682222 Fax.++39 02 95307006 E-mail: export@fantinicosmi.it http//www.fantinicosmi.com

17